ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER

Similar documents
ADVANTAGE SERIES KXRP33 AIR-TO-AIR HEAT EXCHANGER

ADVANTAGE SERIES KXRP47 AIR-TO-AIR HEAT EXCHANGER

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

KNHX32 SERIES NEMA 4/4X AIR-TO-AIR HEAT EXCHANGERS

KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRADITIONAL SERIES P47 P52 P59

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRIMLINE WNP28 SERIES

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner INTEGRITY SERIES K_NA4C4P32L KNA6C4P32L

AIR CONDITIONER OPERATOR'S MANUAL

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner DP SERIES K2A3C14DP50L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner NPT SERIES K_A6C_NPT47L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES K2NA6C14DP50L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner WATER-COOLED RACK MOUNTED

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner DP SERIES K_A4C5DP33L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner ADVANTAGE RP55 SERIES

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner K2A3C8P36LFHN-1

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner INTREPID SERIES K2A6C30EP56TR-4

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRIMLINE KA6C4NP28L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner SLIMKOOL SERIES K_NA4C4SP28L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. GUARDIAN SERIES K3NA4C3DP24L 480 Volt 1-PHASE

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES K2NA6C14DP50L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C18DP53L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. DP SERIES KA4C3DP21L with Serial Numbers L18A3965 and above

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C26DP60L

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES KNA4C9DP47L-1

ProAir CR43 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

M52 3-Phase INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

AA-480-XX OUTDOOR THERMOELECTRIC COOLER ASSEMBLY USER S MANUAL

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. HAZARDOUS LOCATION SERIES K_A6C6HL40LV U.S. Pat. No.

ProAir CR23 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

Blade Series Heat Exchanger Operation and Installation

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C14DP50L

ProAir CR29 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

Panel Mounted Heat Exchangers by Dantherm, Inc.

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-Series Air Conditioner T53 Model

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Equipment Protection P/N

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL. Rev. F 2015 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T53 Model INSTRUCTION MANUAL nvent Rev. G P/N

GENESIS Air Conditioner. M52 3-Phase Model INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

INSTRUCTION MANUAL. T-SERIES Air Conditioner. T29 Model Pentair Equipment Protection P/N McLean Parts 5736 N. Michigan Rd.

PROAIR Air Conditioner

T-Series Air Conditioner T20 Model

T-SERIES Air Conditioner. T62 Model INSTRUCTION MANUAL nvent Rev. F P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

SPECTRACOOL Air Conditioner. N17 Model INSTRUCTION MANUAL. Rev. G 2015 Pentair Equipment Protection P/N

T-Series Air Conditioner

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL. Rev. D 2015 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL. Rev. B 2016 Pentair Equipment Protection P/N

T-Series Air Conditioner T15 Model

GENESIS Top-Mount Air Conditioner. HB16 Model INSTRUCTION MANUAL. Rev. J 2013 Pentair Equipment Protection P/N

T-Series Air Conditioner

SPECTRACOOL Air Conditioner

PROAIR Air Conditioner

RPI Industries, Inc.

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL

SPECTRACOOL Air Conditioner. N16 Model INSTRUCTION MANUAL. Rev. A 2016 Pentair Equipment Protection P/N

RPI Industries, Inc.

RPI Industries, Inc.

InstructIon Manual KrEs EQuIPMEnt stands

GENESIS AIR CONDITIONERS

Installation & Maintenance Instructions

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

Warnings 2. Installation Instructions 3. Wiring Instructions 3. Mounting Instructions 4. Replacement Element Installation 5. Replacement Parts 5

ClimaGuard Outdoor Heat Exchanger All Models

User s Manual and Operating Instructions

MODEL 925W FEATURES: ELECTRICAL DATA: DIMENSIONS: SHIPPING INFORMATION: FOOD WARMING/ MERCHANDISING CABINET

REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. I 2017 Pentair Equipment Protection P/N

Quality Refrigeration OWNER S MANUAL. Instructions for the installation, operation and maintenance of Traulsen: Heated Banquet & Transport Carts

Warnings 2. Installation Instructions 3. Wiring Instructions 3. Mounting Instructions 4-5. Replacement Element Installation 5. Replacement Parts 5-6

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532

DH07, DH07A /DH08, DH08A CONVECTED AIR DISH HEATERS

User s Manual and Operating Instructions

M Series Fan Filter Units

Professional Warming Drawer and Warming Drawer Cabinet

Wax Base Heater & Dispenser

MODEL 620 ELECTRICAL DATA: FEATURES: DIMENSIONS: SHIPPING INFORMATION: AVAILABLE ACCESSORIES: CONVECTION OVEN 1/4 SIZE PAN

BX Series. Installation, Operation, Maintenance Instructions & Spare Parts

Quest Dry 105, 155, and 205 Dual

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

Warmer Cabinet Instruction Manual Model # 5581, 5581EX. Part No

ELECTRICAL DATA: FEATURES: SHIPPING INFORMATION: FOOD WARMING/ MERCHANDISING CABINET. 15 Width 7 Width

XT Series Thermostats

Transcription:

Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER OPERATOR'S MANUAL CAUTION BEFORE INSTALLING AND USING THIS HEAT EXCHANGER, IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC, INC. 30 Pennington-Hopewell Road Pennington, NJ 08534 609 466-3400 FAX: 609 466-1114 www.kooltronic.com 900-046-18

TABLE OF CONTENTS Page I. Introduction 2 II. Incoming Inspection 3 III. Product Handling 3 IV. Product Identification and Nameplate 3 V. Principles of Operation 4 VI. Specific Model Data 4-6 Mounting Drawings and Dimensions Technical Data Major Component Replacements Wiring Diagram VII. Maintenance 7 VIII. Packing Procedure 7 IX. Warranty 8 I. Introduction Kooltronic Advantage Heat Exchangers are designed for outdoor and indoor applications with ambient temperature from -20 F to 131 F and maximum allowable enclosure temperature of 160 F. These heat exchangers utilize a counterflow airstream, for maximum heat transfer efficiency in a closed-loop system, providing cooling within sealed electronic cabinets. This Manual provides you with the necessary general information for properly installing and operating Kooltronic Heat Exchangers. Unit specific technical data and mounting instructions are presented later in the Manual. 2

II. Incoming Inspection Kooltronic Heat Exchangers are designed, built, and packaged to withstand the shock and vibration normally associated with shipment by common carriers. Occasionally improper handling during shipping causes damage. Such handling could include unbanding of palletized shipments, failing to respect any carton handling instructions, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be done upon receipt of all shipments. Any carton tears, dents, scratches, or loose articles should be noted on the Freight Bill. Cartons should be opened promptly and the units inspected for CONCEALED DAMAGE. An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all packing materials. Kooltronic cannot assume responsibility for Consignee s failure to file a timely freight claim. III. Product Handling Do not attempt to operate your Kooltronic Heat Exchanger until you read and thoroughly understand this Manual. Before operating this unit, all electrical wiring must be checked to assure the proper connections. CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate. IV. Product Identification and Nameplate Each Kooltronic Heat Exchanger includes an identification nameplate. This nameplate provides: MODEL NO. ➀ Heat Exchanger SERIAL NO. MAX. CABINET VOLTS. FREQ. PH. AMPS TEMP. o F ➂ ➂ ➂ ➂ ➃ ➁ ➀ ➁ ➂ ➃ ➄ Model Number Serial Number Electrical power characteristics Maximum enclosure temperature Filter Part Number We recommend you copy this information from your unit. FILTER P/N ➄ MAX. FUSE SIZE UNAUTHORIZED SERVICE OR MODIFICATION VIOLATES WARRANTY ALL MOTORS ARE THERMALLY PROTECTED THIS PRODUCT IS PROTECTED BY ONE OR MORE OF THE FOLLOWING PATENTS: 3,019,965 3,120,166 3,211,360 3,559,728 3,807,493 AND OTHER PATENTS PENDING ➂ LISTED SPECIAL PURPOSE HEAT EXCHANGER MANUFACTURED BY: KOOLTRONIC, INC. PENNINGTON, NJ VENTURA, CA ➀➁➄ ➂ ➃ When ordering parts, specify the Model Number and Serial Number. Before operating, be sure that the power source matches these requirements. Make sure that these parameters are met. Failure to do so may result in permanent damage to the unit. 3

V. Principles of Operation The main component of the heat exchanger is the counterflow aluminum element through which the heat transfer occurs. Ambient blower draws ambient air from the bottom inlet through an aluminum mesh air filter, and the element, and exhausts it through a discharge grill. Cabinet blower draws cabinet air from the top inlet, blows it through the element and exhausts it through the bottom discharge into the cabinet. BLOWER HEATED AIR IN AIR OUT BLOWER COOLED AIR OUT HEAT EXCHANGER ELEMENT ELECTRICAL HEATER AIR IN The heater option includes the electrical heater, ambient blower, bimetal thermostat, heater thermostat and limiter thermostat. All of the thermostats are installed in the discharged enclosure airstream. When the enclosure discharge air goes below 70 F, the ambient blower thermostat shuts off the ambient blower. When the enclosure discharge air goes above 85 F, the ambient blower thermostat turns on the ambient blower. When discharge enclosure air goes below 40 F, the heater thermostat turns on the heater. When the discharge enclosure air goes above 60 F, the heater thermostat shuts off the heater. See wiring diagram on page 6. VI. Specific Model Data Mounting Kooltronic Heat Exchangers have been engineered to be installed easily. To avoid damaging your Heat Exchanger, please read the following information before installation: 1. Attach the mounting bracket to the enclosure using the mounting hardware supplied by Kooltronic. 2. Route the power cord through the top cut out in your enclosure. Hang the unit on the mounting bracket. 3. Tighten the unit s bottom flange to the enclosure using the hardware supplied by Kooltronic. 4

Drawings and Dimensions KXRP28 Mounting Plan 10.00 [254.0] AIR IN 1.07 [27.1] 10.00 [254.0] 2.25 [57.1] CUSTOMER MOUNTING BRACKET AIR OUT 28.03 [711.9] 26.70 [678.1] 9.00 [228.6] TYP. 5.00 [127.0] 24.21 [614.9] AIR IN 7.99 [202.9] AIR OUT.50 [12.7] TYP. 3.94 [100.0] TYP..52 [13.2] 7.11 [180.6] (6).312 [7.9] DIA. HOLES Dimensions, inches [mm], are for reference only and are subject to change. Technical Data* Maximum Allowable Temperature F Approx. Power Enclosure Ambient Watts/ F Weight Model Volts Amps Watts Max Min/Max Air In (lbs.) KXRP28 115 1.2 135 160-20/131 24 31.5 K2XRP28 230 0.7 153 160-20/131 24 31.5 *60 Hz operation. For 50 Hz operation consult Kooltronic. Major Component Replacements Model Impeller Capacitor Filter KXRP28 0194-37 0452-72 5381F K2XRP28 0194-38 0452-73 5381F NOTE: Part Numbers shown are for 60Hz/1Ø. For 50Hz consult Kooltronic. 5

Wiring Diagram BLK WHT CAP. BLOWER T - STAT (OPTIONAL) CAP. BLOWER THERMAL CUT - OUT HEATER CONTROL T - STAT (OPTIONAL) HEATER WD-830 6

VII. Maintenance With Kooltronic Air-Cooled Heat Exchangers the use of a filter is optional. If you do choose to use a filter, and wish to remove it for cleaning or repair, follow the instructions below. CAUTION Disconnect electric power from the Heat Exchanger before proceeding. Optional Filter Removal and Service Kooltronic Heat Exchangers feature an easily removable optional inlet filter. 1. Move the filter up and toward you from the Filter Retainer. 2. After removal, the filter should be flushed under warm running water with the clean side up, driving contaminants out the dirty side of the filter. If the accumulated dirt is oily, washing in a detergent bath is recommended, followed by warm water rinse as above. 3. The filter may be sprayed with Kooltronic A-16 Filter Recoating Adhesive to trap fine airborne contaminants, or they can simply be dried and reinstalled as strainer type filters. Recoating is recommended for the best results. 4. Reinstall the filter in the Filter Retainer. VIII. Packing Procedure Keep Heat Exchanger in proper upright position. Pack Heat Exchanger in an appropriate carton (preferably original carton if possible), with adequate internal protective packaging, making sure carton is marked properly. For local controlled transportation, strap carton to a secure part of the vehicle to prevent falling or sliding, and to minimize vibration, etc. For common carrier shipment, band unit(s) securely to a pallet. Unpalletized shipment risks severe damage which voids the warranty. 7

IX. Standard Warranty KOOLTRONIC products are warranted to be free of defects in workmanship, materials and components. The following warranty periods apply from date of shipment: Air moving devices/components and hermetic system components: One year Non-operating parts, except filters: 5 years The above warranty applies when the equipment is operated under the following conditions: Ambient temperature not in excess of 125 F (52 C) in normal atmosphere or as stated on product nameplate Voltage variation no greater than ± 10% from nameplate rating Frequency variation no greater than ± 3Hz from nameplate rating Maximum cooling load no higher than air conditioner nameplate rating Waiting five minutes before restarting air conditioner after intentional or accidental shutoff Compliance to all other installation, maintenance and operating instructions, as supplied The purchaser assumes the responsibility of grounding the unit and installing it in accordance with local electrical and safety codes, as well as the National Electric Code (NEC) and OSHA KOOLTRONIC cannot assume responsibility for mis-application of its products or the erroneous selection of an inappropriate product by a nonauthorized KOOLTRONIC representative. Our applications engineers will gladly assist in the selection of the proper product, provided all required details of the application are furnished. KOOLTRONIC assumes no liability beyond the repair or replacement of its own product. This Warranty does not cover: Labor or reimbursement of labor for evaluation, removal, installation, repair, or cost of any warranted part, unless authorized in writing by KOOLTRONIC Use of equipment for other than its designed purpose or operating conditions Operation in harsh, oily, corrosive or other abnormal environmental conditions, without the proper filtration, sealing, protective coatings and/or weather protection Damage to hermetic system resulting from continuous operation with dirty or clogged air filters or improper or negligent maintenance Use of refrigerant other than designated Customer modification or abuse Shipping damage or other accident (Claims for shipping damage are the responsibility of the customer. Timely claims must be filed by the customer with the freight carrier) Cracked or broken hermetic tubing, brazed joints or other internal damage caused by shipping or mishandling Damage caused by shipping units attached to an enclosure Any and all conditions resulting from noncompliance with the preceding operating conditions Returned freight must be paid by customer This standard warranty does not apply to custom products. Consult your KOOLTRONIC representative for limitations THIS WARRANTY CONSTITUTES THE ENTIRE WARRANTY WITH RESPECT TO THE PRODUCT AND IS IN LIEU OF ALL OTHERS, EXPRESSED OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY AND WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND IN NO EVENT IS KOOLTRONIC RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER. RETURN AUTHORIZATION (RA) PROCEDURE All returns require a Return Authorization number whether the return is for warranty or non-warranty repair, rotation of stock, damage or any other reason. Returns without an RA number will be refused. Customer must call KOOLTRONIC After Sale Kare (ASK), Pennington, New Jersey (609 466 3400) to obtain an RA number, or email ask@kooltronic.com. The following information is required when an RA is requested: - Original customer Purchase Order number and date - Date product was received by customer - Number of parts to be returned - Product description, model and serial number - Reason for return - Action requested - Contact name, telephone, FAX numbers and e-mail address Pack unit in a suitable container for shipment, preferably the 8 original packaging if available. All Heat Exchangers must be returned in an upright position properly secured to a pallet. Improper packaging may void warranty claim. If a Heat Exchanger is received laying down or shipped via UPS or similar small parcel service the warranty will be void. Mark carton prominently with KOOLTRONIC s Return Authorization Number. Enclose all pertinent documents. Freight charges on all products returned to KOOLTRONIC shall be paid by the customer. Unauthorized collect shipments will be refused. If a unit is repaired under Warranty, KOOLTRONIC will pay the freight charges both ways within the Continental USA at KOOLTRONIC s negotiated rates. Warranty repaired units will be returned to customer at KOOLTRONIC expense only within the Continental USA. All authorized returns are subject to a restocking fee.