INSTALLATION MANUAL SINGLE PIECE, 4 POSITION ECM AIR HANDLERS MODELS: AHV SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

Similar documents
INSTALLATION MANUAL SINGLE PIECE, 3 POSITION ECM AIR HANDLERS MODELS: AHV SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE VARIABLE SPEED AIR HANDLERS MODELS: AV*(C) SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL SINGLE PIECE, 4 POSITION AIR HANDLERS MODELS: AHR SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR / AHE SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHP SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214

INSTALLATION MANUAL SINGLE PIECE VARIABLE SPEED AIR HANDLERS MODELS: AV*(C) SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHE SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL WARNING WARNING MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: MA LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION INSTRUCTION

INSTALLATION MANUAL SINGLE PIECE AIR HANDLERS MODELS: F6FP018** - 060** TABLE OF CONTENTS LIST OF FIGURES LIST OF TABLES SAFETY UIM-B-0409

INSTALLATION MANUAL SINGLE PIECE AIR HANDLERS MODELS: F*FP LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SAFETY UIM-B-0209

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

TECHNICAL GUIDE SINGLE PIECE VARIABLE SPEED AIR HANDLERS DESCRIPTION FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS FEATURE MODELS: AVG24 THRU 60*(C)

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

INSTALLATION INSTRUCTION

AHP SERIES INSTALLATION INSTRUCTIONS ELECTRIC FURNACES / AIR HANDLERS

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS DESCRIPTION FEATURES FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS

INSTALLATION MANUAL WARNING STANDARD PSC MODULAR MULTI-POSITION AIR HANDLERS MODELS: MP SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES

INSTALLATION INSTRUCTION

INSTALLATION MANUAL WARNING WARNING FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CF

INSTALLATION MANUAL MODULAR VARIABLE SPEED AIR HANDLERS MODELS: MV LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Apartment Fan Coil

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: F6FP DESCRIPTION FEATURES UTG-B-0409

AHG**-0B Series Hydronic Air Handling Units

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Installation Instructions

INSTALLATION INSTRUCTIONS

INSTALLATION AND MAINTENANCE INSTRUCTIONS. MCE4 Series. Electric Cooling Package Unit. Save these instructions for future reference

Your safety and the safety of others are very important.

Installation Instructions

INSTALLATION INSTRUCTIONS Fan Coils FCM4X24-60

Installation Instructions

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

MODELS B1PA024, 030 AND 036

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Installation Instructions

TECHNICAL GUIDE VARIABLE SPEED AIR HANDLERS DESCRIPTION FEATURES Rev. A (0105)

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS R-410A Split System Air Conditioner

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Installation Instructions

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL LIST OF SECTIONS. 1 General 1 3 Louvered Door Frame Assembly Installation 3 2 Safety 2 4 Coil Cabinet Installation 5

INSTALLATION MANUAL SINGLE PACKAGE HEAT PUMP/ELECTRIC

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH

INSTALLATION INSTRUCTIONS

ASUF Series. Multi-Position, Multi-Speed ECM-Based Air Handler 1½ to 5 Tons. Contents. Product Features

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

Installation Instructions

INSTALLATION INSTRUCTIONS

LRP14HP/LRP14DF/LRP14AC/LRP14GE/LRP16GE/LRP16HP SERIES UNITS

Installation Instructions

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

INSTALLATION INSTRUCTIONS

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

INSTALLATION INSTRUCTIONS

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor

PL Series Premier Indoor Plenum Coils

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Low Ambient Kit NASA201LA, NASA401LA

GAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT)

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH

Installation Instructions

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

EarthLinked AFN Series Air Handlers Installation Manual

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

C7 Series Split System Uncased Indoor Coils

Installation Instructions

AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax

INSTALLATION INSTRUCTIONS

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

USERS INFORMATION MANUAL

EarthLinked AVN Series Air Handlers Installation Manual

INSTALLATION INSTRUCTIONS

Installation Instructions

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2

INSTALLATION INSTRUCTIONS

installation and start-up instructions HUMIDIFIERS AND HUMIDISTAT

TECHNICAL GUIDE MODELS: MV MODULAR VARIABLE SPEED AIR HANDLERS FOR USE WITH SPLIT SYSTEM COOLING & HEAT PUMP DESCRIPTION FEATURES

Installation Instructions

INSTALLATION INSTRUCTION

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

Installation Instructions

Transcription:

INSTALLATION MANUAL SINGLE PIEE, POSITION EM AIR ANDLERS MODE: AV SERIES ISO 900 ertified Quality Management System GENERAL.............................................. SAFETY................................................ UNIT INSTALLATION..................................... DUTWORK AND ONNETIONS.......................... ELETRI EATER INSTALLATION........................7 LINE POWER ONNETIONS..............................7 Return Duct Attachment & omponent Location................. Dimensions & Duct onnection Dimensions.................... Typical Installation........................................ ondensate Deflector on Vertical Drain Pan.................... ondensate Deflector on orizontal Drain Pan Edge............. S-lip Installation......................................... orizontal Suspension..................................... Duct Attachment.......................................... Ductwork Transition....................................... TXV................................................... Dimensions............................................. Low Voltage onnections..................................9 Fault odes............................................ eat Relays............................................ omfort Setting Selection................................. Unit Data.............................................. Electrical Data - ooling Only............................... LIST OF SETIONS LIST OF FIGURES LIST OF TABLES LOW VOLTAGE ONTROL ONNETIONS.................. 8 REQUI ONTROL SET-UP........................... AIROW AND OMFORT SETTING SELETION............ UNIT DATA........................................... MAINTENANE........................................ START UP SEET...................................... Proper Bulb Location..................................... Line Power onnections................................... 8 ontrol Board........................................... 9 ooling Models with and without Electric eat Wiring........... 0 Two-Stage eat Pump Wiring............................. 0 Air andler with ommunicating A or P................... Wiring Diagram - Single Phase eat Kits with AOS EM Motor... 7 Wiring Diagram - Single Phase eat Kits with EON EM Motor... 8 Wiring Diagram - Phase eat Kits......................... 9 Electrical eat:: Minimum Fan Speed........................ Electrical eat Performance Data: 08/0--0 & 08/0--0.. Electrical Data For Single Source Power Supply: 08/0--0.... Electrical Data For Multi-Source Power Supply: 08/0--0..... Electrical Data For Single Source Power Supply: 08/0--0.... Electrical Data For Multi-Source Power Supply: 08/0--0..... Air Flow Data (FM)..................................... SETION I: GENERAL The AV single piece air handler series provides the flexibility for installation in any position. This unit may be used for upflow, downflow, horizontal right, or horizontal left applications. These units may be located in a closet, utility room, attic, crawl space, or basement. These versatile models may be used for cooling or heat pump operation with or without electric heat. Top and side power wiring and control wiring, accessible screw terminals for control wiring, easy to install drain connections, and electric heaters all combine to make the installation easy and minimize installation cost. Electric heat kits are available as field installed accessories. Single phase and phase kits are available and range from nominal. kw to kw sizes. A Brand Label (available from Distribution) may be applied to the center of the blower access panel. SETION II: SAFETY This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury. Understand and pay particular attention to the signal words DANGER, WARNING, or AUTION. DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury. WARNING indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury. AUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property damage. Improper installation, adjustment, alteration, or maintenance may create a condition where the operation of the product could cause personal injury or property damage. Refer to this manual for assistance, or for additional information, consult a qualified contractor, installer, or service agency. This product must be installed in strict compliance with the installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes. FIRE OR ELETRIAL AZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. A fire or electrical hazard may result causing property damage, personal injury or loss of life. 00-UIM-B-0

00-UIM-B-0 SAFETY REQUIREMENTS. This air handler should be installed in accordance with all national and local building/safety codes and requirements, local plumbing or wastewater codes, and other applicable codes.. Read and follow all instructions in this manual. Failure to do so can result in air handler malfunction, death, personal injury and/or property damage.. Install this air handler only in a location and position as specified in the Unit Installation section of these instructions.. The air handler is not to be used for temporary heating of buildings or structures under construction.. Always install the air handler to operate within the air handler s intended maximum outlet air temperature.. Provide clearances from combustible materials as listed in the learances section of this manual. 7. Provide clearances for servicing ensuring that service access is allowed for electric heaters and blower. 8. heck the unit's rating plate and power supply to be sure that the electrical characteristics match. 9. Air handler shall be installed so the electrical components are protected from water. 0. Installing and servicing heating/cooling equipment can be hazardous due to the electrical components. Only trained and qualified personnel should install, repair, or service heating/cooling equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating/cooling equipment, observe the precautions in the manuals and on the labels attached to the unit and other safety precautions that may apply.. These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-ud modular home construction practices. These instructions are required as a minimum for a safe installation. These air handlers should be transported & handled in an upright, upflow position. Failure to do so may result in unit damage and personal injury. onfiguration conversions should be done at site of installation. INSPETION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier s freight bill. A separate request for inspection by the carrier s agent should be made in writing. Also, before installation the unit should be checked for screws or bolts, which may have loosened in transit. There are no shipping or spacer brackets which need to be removed. Also check to be sure all accessories such as heater kits, suspension kits, and coils are available. Installation of these accessories or field conversion of the unit should be accomplished before setting the unit in place or connecting any wiring, electric heat, ducts or piping. FRONT VIEW BLOWER OMPARTMENT VERTIAL DRAIN PAN REFRIGERANT LINE ONNETIONS OIL OMPARTMENT (Access panel removed) ORIZONTAL DRAIN PAN ORIZONTAL SEONDARY DRAIN SIDE VIEW PRIMARY DRAIN UPOW / TREADED DUT WORK MAY BE FASTENED AUTIOUSLY WIT SREWS TO TE SIDES AND REAR OF UNIT SEONDARY DRAIN UPOW / TREADED ORIZONTAL PRIMARY DRAIN ALTERNATE DRAIN ONNETIONS UPOW FILTER DOOR RETURN AIR DUT WEN ATTAING DUT WORK WIT SREWS - KEEP SREWS WITIN /8 OF SIDES AND BAK OF AIR ANDLER FIGURE : Return Duct Attachment & omponent Location Johnson ontrols Unitary Products

00-UIM-B-0 J F K Blower ompartment Refrigerant onnections D Drain onnections for Upflow Applications A Service Disconnect Panel Top Outlet Dimensions -/ 7-/ Filter Access B 0-/ Drain Pan onnections for orizontal Applications E Bottom Inlet Dimensions A0-00 FIGURE : Dimensions & Duct onnection Dimensions TABLE : Dimensions Dimensions Wiring Knockouts Refrigerant onnections Models A B D E F J K Line Size eight Width Depth Power ontrol Liquid Vapor AV8BX 7-/ -/ -9/ -/ AVBX 7-/ -/ -9/ -/ AV0BX 7-/ -/ -9/ -/ 7/8 (/ ) / AVX -/ -/ 7-/ 0 -/8 ( ) 7/8 (/ ) /8 AVDX 7 -/ 0-9/ -/ -/ (-/ ) AV8DX 7 -/ 0-9/ -/ 7/8 AV0DX 7 -/ 0-9/ -/. All dimensions are in inches and referenced in Figure.. Actual size (conduit size). SETION III: UNIT INSTALLATION UNIT SIZING. The size of the unit should be based on an acceptable heat loss or gain calculation for the structure. AA, Manual J or other approved methods may be used.. Only connect the air handler to a duct system which has an external static pressure within the allowable range.. Airflow must be within the minimum and maximum limits approved for electric heat and evaporator coils.. When an air handler is installed so that supply ducts carry air circulated by the air handler to areas outside the space containing the air handler, the return air shall also be handled by duct(s) sealed to the air handler casing and terminating in the space to be cooled/ heated.. Refer to the unit rating plate for the air handler model number, and then see the dimensions page of this instruction for supply air plenum dimensions. The plenum must be installed according to the instructions.. The installer must check available supply power and verify that it is within the normal operating voltage range for the unit. The acceptable voltage range for these units is as follows: Air andler Voltage Normal Operating Voltage Range 08/0--0 87- LEARANES learances must be taken into consideration, and provided for as follows:. Refrigerant piping and connections - minimum recommended.. Maintenance and servicing access - minimum from front of unit recommended for blower motor / coil replacement.. ondensate drain lines routed to clear filter and panel access.. Filter removal - minimum recommended.. The ductwork and plenum connected to this unit are designed for zero clearance to combustible materials.. A combustible floor base accessory is available for downflow applications of this unit, if required by local code. LOATION Location is usually predetermined. heck with owner s or dealer s installation plans. If location has not been decided, consider the following in choosing a suitable location:. Select a location with adequate structural support, space for service access, clearance for air return and supply duct connections.. Using hanging brackets to wall mount this single piece air handler unit is not recommended.. Normal operating sound levels may be objectionable if the air handler is placed directly over some rooms such as bedrooms, study, etc.. Rated in accordance with ARI Standard 0, utilization range A. Johnson ontrols Unitary Products

00-UIM-B-0. Select a location that will permit installation of condensate line to an open drain or outdoors allowing condensate to drain away from structure. The primary and secondary drain line must be trapped to allow proper drainage of condensate water. The secondary drain line should be piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secondary drain line is not used, it must be capped.. When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the air handler as is specified by most local building codes.. Proper electrical supply must be available. 7. If unit is located in an area of high humidity (i.e. an unconditioned garage or attic), nuisance sweating of casing may occur. On these installations, unit duct connections and other openings should be properly sealed, and a wrap of fiberglass insulation with vinyl vapor barrier should be used. UPOW EAT DOWNOW NOTIE EAT ORIZONTAL LEFT ONVERSION. With air handler in vertical position remove all access panels and the tubing connection panel.. Slide the coil assembly out of the air handler.. It would be easiest to remove and reposition the condensate deflector now, while you have the coil assembly removed from the unit.. Rotate air handler 80 so the blower outlet is facing down.. Reinstall the coil assembly on the coil support brackets.. Reattach tubing connection panel. 7. Reposition the air handler into the left hand horizontal application. 8. Remove the drain pan plugs from the horizontal drain pan and screw them into the vertical, A-coil drain pan. 9. Reattach access panels. DOWNOW ONVERSION A downflow floor base is available for this air handler. Refer to instructions supplied with the kit for installation.. With air handler in vertical position remove all access panels and the tubing connection panel.. Slide the coil assembly out of the air handler.. Rotate air handler 80 so the blower outlet is facing down.. Reinstall the coil assembly on the coil support brackets.. Reattach tubing connection panel.. Reattach access panels. ORIZONTAL RIGT EAT EAT ORIZONTAL LEFT FIGURE : Typical Installation ONDENSATE DEETOR The condensate deflector comes attached to the vertical, A-coil drain pan. If installing the unit in the upflow or downflow position, no modification is necessary. For units to be installed in the horizontal position, the condensate deflector needs to be removed from the vertical drain pan and placed on the horizontal drain pan. Remove the condensate deflector and the S-clips that attach it to the vertical drain pan. Relocate the deflector and S-clips onto the horizontal drain pan. Line up with the coil support bracket. See Figure for details. This positions the deflector below the feeder tubes to channel the condensate into the drain pan. AIR ANDLER ONFIGURATION These air handler units are supplied ready to be installed in an upflow and right horizontal position. If the unit requires either downflow or left airflow configurations, the unit must have the coil assembly repositioned. NOTIE For both right and left horizontal applications, the condensate deflector needs to be removed from the vertical drain pan and placed on the horizontal drain pan. See ondensate Deflector section for details. NOTIE onversion must be made before brazing the refrigerant connections to the coil. S-LIPS () VERTIAL DRAIN PAN ONDENSATE DEETOR FIGURE : ondensate Deflector on Vertical Drain Pan NOTIE The condensate deflector should be installed in the s-clip section which is inside the drain pan edge. See Figure. FEEDER TUBES ONDENSATE S-LIPS ON ORIZONTAL PAN DEETOR FIGURE : ondensate Deflector on orizontal Drain Pan Edge Johnson ontrols Unitary Products

00-UIM-B-0 S-LIP ONDENSATE DEETOR DRAIN PAN WALL SUSPENSION SUPPORT LOATIONS FOR ORIZONTAL APPLIATIONS Min. /8 Threaded Rod MIN. -/ x -/ Angle Recommended length minimum with clearance on both sides of Air andler FIGURE : S-lip Installation SETION IV: DUTWORK AND ONNETIONS The vast majority of problems encountered with heating and cooling systems can be linked to improperly designed or installed duct systems. It is therefore highly important to the success of an installation that the duct system be properly designed and installed. When installing a central air return grille in or near the living space, it is advisable to design the ductwork so that the grille is not in direct line with the opening in the unit. One or two elbows and acoustical duct liner will also assure a quieter installation and system. Where return air duct is short, or where sound may be a problem, sound absorbing glass fiber should be used inside the duct. Do not bring in return air from a location which could introduce hazardous substances into the airflow. Insulation of duct work is a must where it runs through an unheated space during the heating season or through an uncooled space during the cooling season. The use of a vapor barrier is recommended to prevent absorption of moisture from the surrounding air into the insulation. Duct work should be fabricated and installed in accordance with local and/or national codes. This includes the standards of the National Fire Protection Association for Installation of Air-onditioning and Ventilating Systems, NFPA No. 90B. They should be sized in accordance with National Environmental System ontractors Association Manual K, or whichever is applicable. -/ X -/ Air andler Dimension abinet Size X B 0 D 8 7 FIGURE 7: orizontal Suspension DUT ANGES Four flanges are provided to assist in positioning and attaching ductwork to the air handler. These flanges are rotated down for shipment. In order to use the flanges, remove the screw holding an individual flange, rotate the flange so it is in the upward position, and reinstall the screw. Repeat this for all flanges. If the flanges are not used, they must remain in the down position as shipped. FOR DUT ATTAMENT, IF NEEDED Min. /8 Threaded Rod MIN. -/ x -/ Angle Recommended length minimum with clearance on both sides of Air andler X FATORY INSTALLED This unit is not designed for non-ducted (freeblow) applications. Do not operate without ductwork attached to unit. Use flexible duct collars to minimize the transmission of vibration/noise into the conditioned space. If electric heat is used, non-flammable material must be used. All ducts should be suspended using flexible hangers and never fastened directly to the structure. ORIZONTAL SUSPENSION These air handlers may be suspended in horizontal applications. It is recommended to use angle steel support brackets with minimum /8 threaded rods, supporting the unit from the bottom. Attach the threaded rods at the locations shown in the Figure 7. NOTIE When assembling the support structure, make sure to size to provide clearance for access door removal. FIGURE 8: Duct Attachment REOMMENDED TRANSITION SUGGESTED LOATION OF BLOK OFF PLATE FIGURE 9: Ductwork Transition Johnson ontrols Unitary Products

00-UIM-B-0 UNIT ONNETIONS There are several ways to handle the supply and return air duct connections. The location and sizing of the connections depends on the situation and the method best suited to the installation. The supply air duct should be properly sized by use of a transition to match unit opening. Refer to Table for air handler unit inlet and outlet dimensions. SREW TXV BULB (over completely with insulation) Use / screws to connect ductwork to bottom of unit. Longer screws will pierce the drain pan and cause leakage. If pilot holes are drilled, drill only though field duct and unit bottom flange. LAMP NUT FIGURE : Proper Bulb Location SUTION LINE Ductwork that is not designed to match the supply air opening can cause turbulence inside the plenum. This turbulence can change the air flow patterns across the electric heater limit switches. If the factory suggested transition cannot be fabricated, it is recommended that a block off plate (approximately 8" high and running the full width of the plenum) be attached to the supply opening. Refer to Figure 9 as a visual aid. The use of this block off plate will enable better air circulation across the limit switches. AIR FILTERS Return air filters are required and must be field supplied. Filtration can be accomplished external to the unit or integral filter rack may be used. A " filter access rack has been built into the unit. Remove filter access cover shown. Install proper size filter. Standard " size permanent or throw away filter may be used, or, permanent washable filters are available using model numbers: PF00, 0 or 0BK. See Table for filter size. OIL UNDER PRESSURE. Relieve pressure by depressing schrader core. NOTIE The coil should be open to the air for no more than minutes to keep moisture and contaminates from entering the system. If the coil cannot be brazed into the refrigeration system in that time, the ends should be temporarily closed or plugged. For a short term delay, use masking tape over the ends of the copper tubing to close the tube to the air. For a longer term delay, use plugs or caps. There is no need to purge the coil if this procedure is followed. REFRIGERANT LINE ONNETION. Equipment should never be operated without filters. TXV OR ORIFIE METERING DEVIES All air handlers are shipped with flex coils, meaning that the evaporator coil does not have a factory installed metering device, in order to accommodate a variety of application choices. An R- or R-0A TXV or orifice needs to be installed in the field. Refer to the Outdoor Unit Technical Guide to verify to correct TXV for the A or P unit installed. It is recommended to install the TXV kit prior to brazing line sets. Refer to the instructions in the installation manuals provided with the TXV kit and outdoor unit for more information. Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation. NOTIE Route the refrigerant lines to the coil in a manner that will not obstruct service access to the coil, air handling system, or filter. VAPOR LINE TERMAL EXPANSION VALVE BULB (over completely with insulation provided) TXV EQUALIZER LINE FIGURE 0: TXV LIQUID LINE TERMAL EXPANSION VALVE DISTRIBUTOR BODY onnect lines as follows:. Suction and liquid line connections are made outside the cabinet. Leave the tubing connection panel attached to the cabinet with the tubes protruding through it. oil access panel should be removed for brazing. The lines are swedged to receive the field line set tubes.. Wrap a water soaked rag around the coil connection tubes inside the cabinet to avoid damaging the TXV bulb.. Remove grommets where tubes exit the cabinet to prevent burning them during brazing.. Purge refrigerant lines with dry nitrogen.. Braze the suction and liquid lines. Suction line must be insulated.. Re-attach the grommets to the lines carefully to prevent air leakage. 7. Attach the coil access panel to the cabinet. Johnson ontrols Unitary Products

00-UIM-B-0 NOTIE ALWAYS evacuate the coil and line. Set tubing to 00 microns before opening outdoor unit service valves. Refer to Outdoor unit Installation Manual for evacuation, leak check and charging instructions. Lines should be sound isolated by using appropriate hangers or strapping. All evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos- or equivalent. DO NOT use soft solder. DRAIN ONNETIONS All drain lines should be trapped a minimum of three inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection. Threaded drain connection should be hand-tightened, plus no more than / turn. Route the drain line so that it does not interfere with accessibility to the coil, air handling system or filter and will not be exposed to freezing temperatures. See Figure for drain connection locations. When the coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil if specified by local building codes. When this exterior secondary drain pan is used that drain should be piped to a location that will give the occupant a visual warning that the primary drain is clogged. oils should be installed level or pitched slightly toward the drain end. Suggested pitch should not exceed / inch per foot of coil. The drain pan connections are designed to ASTM Standard D Schedule 0. Use / PV or steel threaded pipe. Since the drains are not subject to any pressure it is not necessary to use Schedule 0 pipe for drain lines. SETION V: ELETRI EATER INSTALLATION If the air handler requires electric heat, install the electric heat kit according to the installation instructions included with the kit. After installing the kit, mark the air handler nameplate to designate the heater kit that was installed. If no heater is installed, mark the name plate appropriately to indicate that no heat kit is installed. Use only K heater kits, as listed on air handler name plate and in these instructions. Use data from Tables through 9 for information on required minimum motor speed tap to be used for heating operation, maximum over-current protection device required and minimum electrical supply wiring size required for listed combination of Air andler and eater Kit. SETION VI: LINE POWER ONNETIONS Power may be brought into the unit through the supply air end of the unit (top when unit is vertical) or the left side panel. Use the hole appropriate to the unit s orientation in each installation to bring conduit from the disconnect. The power lead conduit should be terminated at the electrical control box. Refer to Tables through 9 to determine proper wire sizing. To minimize air leakage, seal the wiring entry point at the outside of the unit. All electrical connections to air handlers must be made with copper conductors. Direct connection of aluminum wiring to air handlers is not approved. If aluminum conductors are present, all applicable local and national codes must be followed when converting from aluminum to copper conductors prior to connection to the air handler. If wire other than uncoated (non-plated), 7 ambient, copper wire is used, consult applicable tables of the National Electric ode (ANSI/ NFPA 70). The chosen conductor and connections all must meet or exceed the amperage rating of the overcurrent protector (circuit breaker or fuse) in the circuit. Additionally, existing aluminum wire within the structure must be sized correctly for the application according to National Electric ode and local codes. aution must be used when sizing aluminum rather than copper conductors, as aluminum conductors are rated for less current than copper conductors of the same size. NO ELETRI EAT. POWER SUPPLY N N OMPONENT ODES LUG B IRUIT BREAKER KT - IRUIT N WIRE ONNETOR/NUT FIELD POWER WIRING (08/0V) PASE ELETRI EAT OPTIONS: SINGLE SOURE POWER MULTI-SOURE POWER WIT JUMPER BAR MULTI-SOURE POWER POWER SUPPLY TERMINAL BLOK OR IRUIT BREAKER POWER SUPPLY JUMPER BAR B B B KT POWER KT SUPPLY KT B B B IRUITS ONKW-0KW IRUITS ON KW IRUITS ONKW-0KW IRUITS ON KW PASE ELETRI EAT POWER OPTIONS: SINGLE SOURE POWER MULTI-SOURE POWER POWER SUPPLY L TERMINAL BLOK OR IRUIT BREAKER KT POWER SUPPLY KT L L B B FIGURE : Line Power onnections Johnson ontrols Unitary Products 7

00-UIM-B-0 SETION VII: LOW VOLTAGE ONTROL ONNETIONS The volt power supply is provided by an internally wired low voltage transformer which is standard on all models, owever, if the unit is connected to a 08 volt power supply, the low voltage transformer must be rewired to the 08 volt tap. See the unit wiring label. Field supplied low voltage wiring can exit the unit on the top right hand corner or the right hand side panel. Refer to Figure. Remove desired knockout and pierce foil faced insulation to allow wiring to pass through. Use as small of a hole as possible to minimize air leakage. Install a 7/8 plastic bushing in the selected hole and keep low voltage wiring as short as possible inside the control box. To further minimize air leakage, seal the wiring entry point at the outside of the unit. The field wiring is to be connected at the pigtails supplied with the control board harness. Refer to SETIONS X and XI for system wiring. NOTIE All wiring must comply with local and national electrical code requirements. Read and heed all unit caution labels. NOTIE It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump. Standard wiring will only bring on the first stage of electric heat during defrost. See Table for additional information on heat during defrost cycle. OAT SWIT INPUT LEAVING AIR TEMP SENSOR TERMINA UMIDIFIER OUTPUT FM INDIATOR STATUS INDIATOR BLOWER SPEED JUMPERS UMIDISTAT JUMPER A/P JUMPER SERVIE TOOL PORT OMM PORT MODEL ID PLUG FUSE FIGURE : ontrol Board ONVENTIONAL LOW VOLTAGE ONTROL WIRING ( VA) The volt power supply is provided by an internally wired low voltage transformer which is standard on all models, owever, if the unit is connected to a 08 volt power supply, the low voltage transformer must be rewired to the 08 volt tap. See the unit wiring label. Remove desired knockout and pierce foil faced insulation to allow wiring to pass through. Use as small of a hole as possible to minimize air leakage. Install a 7/8 plastic bushing in the selected hole and keep low voltage wiring as short as possible. To further minimize air leakage, seal the wiring entry point at the outside of the unit. The field wiring is to be connected with wire nuts to the wires provided. Refer to Figure and. TABLE : Low Voltage onnections Wire olors Signal omment R Red VA power (fused) G Green ontinuous Fan operation Y/Y Yellow Second or full stage compressor operation Y Yellow & Black First stage compressor operation W Brown Second stage heat operation W White First stage heat operation O Orange Reversing valve operation UM Purple umidity switch input OM Blue VA common Not used with outdoor units having one stage compressors. VA will be present at this terminal when the MODE jumper is in the A position. This is normal. VA will be present at this terminal when the UM STAT jumper is in the NO position. This is normal. The field wiring is to be connected at the pigtails supplied with the control board harness. 8 Johnson ontrols Unitary Products

00-UIM-B-0 Air andler ontrol Wiring Typical A/ - ooling only Applications TERMOSTAT AIR ANDLER BOARD - STAGE AIR ONDITIONING R R Air andler ontrol Wiring Typical A/ with Electric eat Applications AIR ANDLER TERMOSTAT BOARD - STAGE AIR ONDITIONING R R G G G G Y Y/Y Y Y Y/Y Y W Y Y W W W W W UMIDISTAT W W UMIDISTAT O O UM UM OM OM FIGURE : ooling Models with and without Electric eat Wiring * Optional dehumidification humidistat switch contacts open on humidity rise. NOTES:. Y/Y Thermostat wire must be connected for full FM and applications requiring 0 second blower off delay for SEER enhancement.. Remove humidistat jumper on air handler control board.. For heat pump applications - set A/P jumper on air handler control board to the P position.. ONTROL WIRING - Air andler & UPG P Systems Two Stage /P with York Guard VI Board & opeland Ultra Tech onventional Application - Not ot eat Pump TERMOSTAT AIR ANDLER BOARD - STAGE SROLL EAT PUMP R R R G G Y Y Y/Y Y Y Y OUT Y E W W W W OUT W OUT W O O O UM UMIDISTAT * BS X / L X / L OM FIGURE : Two-Stage eat Pump Wiring * Optional dehumidification humidistat switch contacts open on humidity rise. NOTES:. Y/Y Thermostat wire must be connected for full FM and applications requiring 0 second blower off delay for SEER enhancement.. Remove humidistat jumper on air handler control board.. For heat pump applications - set A/P jumper on air handler control board to the P position. ONTROL WIRING USING OMMUNIATING ONTRO The ommunicating System consists of several intelligent communicating components including the ommunicating Thermostat ontrol (touch-screen wall thermostat), variable speed air handler, air conditioner ( and 8 SEER premium air conditioners) or heat pump (, and 8 SEER premium heat pumps), which continually communicate with each other via a four-wire connection called the A-R--B bus. ommands, operating conditions, and other data are passed continually between components over the A-R--B bus. See Figure. The result is a new level of comfort, versatility, and simplicity. In order to use this air handler in full communications (OMM) mode, it MUST be installed with the matching touch-screen ommunicating ontrol (wall thermostat) and an outdoor air conditioner or heat pump with a fully communicating control. This air handler may also be used along with the touch-screen ommunicating ontrol and a non-communicating outdoor air conditioner through the addition of a communicating A ontrol board to the outdoor unit. This system allows full communication between the air handler, outdoor unit, and touch-screen ommunication ontrol. Use the wiring diagram below to connect the air handler control, touchscreen ommunicating ontrol (wall thermostat) and communicating outdoor unit. Be sure that all of the A+ terminals are connected together, all of the B- terminals are connected together, all of the terminals are connected together and all of the R terminals are connected together. See Figure. When using a fully communicating system, removal of the low voltage signal connector at P is recommended (, G, R, etc.). The four small screw terminals in the terminal block on the end of the air handler control should be used. If any field-supplied wiring is to be connected to the control board, such as will be the case if the ommunicating ontrol is used or if a humidistat, float switch or leaving air temperature switch are used, the additional wires MUST be routed through the hole at the lower left of the control box. DO NOT add any additional holes to the control box. After attaching the additional wires to the board, the remaining hole around the wires must be plugged with the sealant putty supplied or with a suitable waterproof sealant. FAILURE TO SEAL TIS OLE MAY ALLOW WATER TO ENTER TE ONTROL BOX AND DAM- AGE TE ONTROL BOARD. Johnson ontrols Unitary Products 9

00-UIM-B-0 Touch Screen ommunicating ontrol Air andler ommunicating ontrol Air onditioner/eat Pump ommunicating ontrol SETION VIII: REQUI ONTROL SET-UP A+ A+ A+ R R R B- FIGURE : Air andler with ommunicating A or P Do not place more than one wire under any single communication terminal screw (there are four communication terminal screws). If more than one wire must be connected to a terminal screw, attach only the terminal end of a one wire pigtail no longer than, and use a wire connector to connect the other end of the pigtail to the other wires. Failure to do this will result in nuisance communication error faults. See Figure 7 WIRE ONNETOR A+ TERMOSTAT TERMINAL SREW AIR ANDLER OMMUNIATING ONTROL BOARD B- A+ FIGURE 7: Multi-wire Terminal onnection UMIDITY SWIT INPUT R B- INDOOR UNIT B- R G Y/Y Y W W O UM OM The air handler control is designed to work with a humidity control that closes when the humidity is below the set-point. The control is open when the humidity is above the set-point. This humidity control may be referred to as a humidistat or a dehumidistat. The humidity switch controls both humidification and de-humidification operation of the control. The control provides humidification using the UM OUT relay output and de-humidification by lowering the blower speed. This is accomplished using the de-humidification input of the motor for variable speed models. The humidity switch should be connected to UM terminals of the control. See Figure. OAT SWIT INPUT An optional switch may be connected to the T terminals on the control board. This feature is only functional when used with the ommunicating ontrol. It is intended for use with a water overflow switch. LEAVING AIR TEMP SENSOR INPUT A plenum air temperature sensor (thermistor) can be connected to the LAS terminals on the control board. The ommunicating ontrol can the monitor the temperature of the supply air in the plenum. B- NOTE ENSURE ONLY ONE WIRE UNDER TERMINAL SREW. TO ONNET MORE TAN ONE WIRE:. ONNET ONLY TERMINAL END OF WIRE PIGTAIL,. USE WIRE ONNETOR B- TO ONNET OTER END OF PIGTAIL TO OTER WIRES. OUTDOOR UNIT A07-00 The following steps must be taken at the time of installation to insure proper system operation.. onsult system wiring diagram to determine proper thermostat wiring for your system.. If a humidistat is installed, change UM STAT jumper from NO to YES.. Set the MODE jumper to A/ (Air onditioner) or P (eat Pump) position depending on the outdoor unit included with the system.. Set airflow and comfort setting jumper to proper positions. FUNTIONALITY AND OPERATION Jumper Positions um Stat Jumper The UM STAT jumper configures the control to monitor the humidity switch input. With the jumper in the NO position, the control will ignore the UM input. With the jumper in the YES position, the control will monitor the UM input to control the UM OUT output to control an external humidifier. If the jumper is not present, the control will operate as if the jumper is in the NO position. A/P Jumper The A/P jumper configures the control to operate properly with an air conditioner (A position) or heat pump (P position). With the jumper in the A position, the control will treat any Y call as a cooling call. With the jumper in the P position, the O input signal is received from the room thermostat. If the jumper is not present, the control will operate as if the jumper is in the P position. Airflow and omfort Setting Jumpers See separate section. Status and Fault odes The control includes an LED that displays status and fault codes. These codes are shown in Table. The control will display the fault codes until power is removed from the control or the fault condition is no longer present. TABLE : Fault odes Fault or Status ondition LED () Flash ode Status No power to control OFF Internal control fault ON sec on sec off heartbeat Normal 0. sec on, 0. sec off Test mode all for heat and cool at the same time 7 Model Plug Not inserted 8 Internal fault self-corrected, attempting normal operation 9 External Relay Output The control includes one output to drive external relays having VA coils. The output has a maximum rating of.0 Amp pilot duty at VA. UM OUT The UM OUT output can be used to drive an external relay or solenoid ( VA coil) to control a humidifier. The output is energized when the UM input is energized, the UM STAT is in the YES position, and the control has a thermostat call for heating (heat pump or electric heat). 0 Johnson ontrols Unitary Products

00-UIM-B-0 eat Output The control is connected to the heater relays using pins,, and of connector P. The relay outputs and the limit switch signal are VA. The control energizes the heat relays as shown in Table. TABLE : eat Relays Input eat Relay Output W T W T W and W T and T Depending on the heat kit installed in the air handler, the control provides the flexibility to configure the amount of heat delivered with the first stage heating call. As an example, when the control s W input is connected to the room thermostat s first stage heat signal, a call for first stage heat will energize one heating element (T). If the control s W input is connected to the room thermostat s first stage heat signal, a call for first stage heat will energize one heating element (T). With either configuration, the control will energize two heating elements (T, and T) when it receives a first and second stage heat input from the thermostat. Wiring Related Faults If the control receives a simultaneous call for heating and cooling (fault code 7), the control will perform both heating and cooling operations. SETION IX: AIROW AND OMFORT SETTING SELETION AIROW SELETION When not using communicating functionality, the airflow and comfort setting selection jumpers must be set properly at the time of installation for proper system operation. Place jumpers in the proper locations based on the information shown in Table or and Figure. Inputs to air handler control board are passed to the motor which determines the target FM to be delivered. The following inputs will produce the FM per the appropriate table and selected tap settings. NOTIE Incorrect airflow and comfort settings may result in decreased system efficiency and performance. These variable speed air handlers are designed to deliver constant airflow (FM) regardless of the external static pressure (ESP) in the ductwork. Therefore, if too many supply registers are closed, a filter becomes clogged, or there is a restriction in the ductwork, the motor will automatically operate at a higher speed to compensate for the higher ESP. This may result in a higher operating sound level. To Set ooling Airflow: Refer to the outdoor unit technical guide for the recommended airflow with the matching evaporator coil. Refer to Table or for the possible high speed cooling and heat pump airflow selections. Find the recommended system airflow in Table or for the installed air handler model. Select the OOL airflow you need from Table or. Set the OOL and ADJUST Jumpers on the control as indicated in Table or. To Set eat Pump Airflow: The heat pump airflow setting is the same as the cooling airflow setting. No additional airflow setting is required. owever, you must set the A/ P jumper to the P position for proper system operation (See Figure ). To Set Electric W eat Airflow: The blower speed required for st stage electric heat is different than cooling. Refer to Table or for the possible FM selections. Refer to Table0 for the minimum required airflow for the electric heater installed. Find the desired airflow in Table or for low heat. Set the EAT jumper on the control as indicated in Table or. To Set W Electric eat Airflow: Airflow for any W input, which is for Stages & of electric heat, is the indicated FM for high heat tap selection on Table or. DO NOT change the ADJUST tap position on the control as this will change your cooling airflow previously selected. Blower Ramp-Up /Ramp-Down: To minimize the sound made by the blower when it speeds up or slows down, the blower will slowly ramp up or down from one speed to another. hanges in blower speed during A/ or heat pump heating can take up to 0 seconds. hanges in blower speed during electric strip heating can take up to seconds. OMFORT SETTINGS TABLE : omfort Setting Selection DELAY TAP A B D OMFORT SETTING Normal umid Dry Temperate Normal The normal setting provides a ramp-up from zero airflow to full capacity and a ramp-down from full capacity back to zero airflow. umid The humid setting is best-suited for installations where the humidity is frequently very high during cooling season, such as in the southern part of the country. On a call for cooling, the blower will ramp up to 0% of full capacity and will stay there for two minutes, then will ramp up to 8% of full capacity and will stay there for five minutes, and then will ramp up to full capacity, where it will stay until the wall thermostat is satisfied. Dry The dry setting is best suited to parts of the country where excessive humidity is not generally a problem, where the summer months are usually dry. On a call for cooling the motor will ramp up to full capacity and will stay there until the thermostat is satisfied. At the end of the cooling cycle, the blower will ramp down to 0% of full capacity where it will stay for 0 seconds. Then it will ramp down to zero. Temperate The temperate setting is best suited for most of the country, where neither excessive humidity nor extremely dry conditions are the norm. On a call for cooling, the motor will ramp up to % of full capacity and will stay there for 90 seconds, then will ramp up to full capacity. At the end of the cooling cycle, the motor will ramp down to % of full capacity and will stay there for 0 seconds, then will ramp down to zero. Johnson ontrols Unitary Products

00-UIM-B-0 SETION X: UNIT DATA TABLE : Unit Data AV MODE Models 8B B 0B D 8D 0D Blower - Diameter x Width 0 x 8 0 x 8 0 x 8 x 0 x 0 x 0 x 0 Motor P / P / P / P / P / P / P / P Nominal RPM 00 00 00 00 00 00 00 Voltage 08/0 08/0 08/0 08/0 08/0 08/0 08/0 Full Load Amps @0V......9.9 Type DISPOSABLE OR PERMANENT Filter Size x 0 x x 0 x x 0 x 0 x 0 x x 0 x x 0 x x 0 x Permanent Type Kit PF00BK PF00BK PF00BK PF00BK PF00BK PF00BK PF00BK Shipping / Operating Weight (lbs.). Field supplied. TABLE 7: Electrical Data - ooling Only Models AV8B AVB AV0B AV AVD AV8D AV0D /0 /0 /0 /8 9/ 7/ 7/7 Motor A Minimum ircuit Ampacity 08V 0V 08V 0V AV MODE MOP Minimum Wire Size (AWG).7...9....0..9... A = Full Load Amps.. MOP = Maximum Overcurrent Protection device; must be AR type circuit breaker or time delay fuse.. 7, copper wire only. If wire other than non-plated, 7 ambient, copper wire is used, consult applicable tables of the NE and local codes. TABLE 8: Electrical eat: Minimum Fan Speed eater Kit Models, Nom. kw Air andler Models @0V AV8B AVB AV0B AV AVD AV8D AV0D K(0,)000.kW Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) K(0,)000.8kW Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) K(0,)0080 7.7kW Med-Low () Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) K(0,)000 K000 9.kW Med-Low () Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) K(,)00.kW - K(,)00 K00 K(,)080 K008 K(,)000 K00 K(,)00 K0.kW - Med-Low () Med-Low () Med-Low () Med-Low () 7.kW - - - Med-Low () 9.kW - - - Med-igh (B) Low (D) Low (D) Low (D) Low (D) Med-Low () Low (D) Low (D) Low (D) Med-Low () Med-igh (B) Low (D) Low (D) Low (D) Low (D) kw - - - - - - Low (D). (0,) - 0 = no circuit breaker OR = with circuit breaker.. (,) - = with circuit breaker, no breaker jumper bar OR = with circuit breaker & breaker jumper bar. Johnson ontrols Unitary Products

00-UIM-B-0 TABLE 9: Electric eat Performance Data: 08/0--0 & 08/0--0 P P eater Models, Nominal kw @0V Total eat kw Staging kw MB W Only W + W 08V 0V 08V 0V 08V 0V 08V 0V K(0,)000..8.. 7..8..8. K(0,)000.8....0.... K(0,)0080 7.7.8 7. 9.7..8 7..8 7. K(0,)000 9. 7. 8.8. 0. 7. 8.8 7. 8.8 K(,)00. 9...0 9...8 9.. K(,)00. 0.8..9... 0.8. K(,)080 7..0.9... 7.9.0.9 K(,)000 9.. 7. 9. 0. 7. 8.8. 7. K(,)00.0 8.0.0. 7. 7. 8.8 8.0.0 K000 9. 7. 8.8. 0. 7. 8.8 7. 8.8 K00. 0.8..9. 0.8. 0.8. K008 7..0.9...0.9.0.9 K00 9.. 7. 9. 0. 7. 8.8. 7. K0.0 8.0.0. 7. 9.0.0 8.0.0. (0,) - 0 = no circuit breaker OR = with circuit breaker.. (,) - = with circuit breaker, no breaker jumper bar OR = with circuit breaker & breaker jumper bar. TABLE 0: Electrical Data For Single Source Power Supply: 08/0--0 Air andler Models AV8B AVB AV0B AV AVD AV8D AV0D eater Models, eater Amps @0V Field Wiring Min. ircuit Ampacity MOP. Min Wire Size (AWG) 08V 0V 08V 0V 08V 0V K(0,)000 0.0.. 0 K(0,)000 0.0.0 7.9 0 0 0 0 K(0,)0080.0 8.0.9 0 8 8 K(0,)000 0.0.7.9 0 0 8 K(0,)000 0.0.. 0 K(0,)000 0.0.0 7.9 0 0 0 0 K(0,)0080.0 8.0.9 0 8 8 K(0,)000 0.0.7.9 0 0 8 K(,)00.0 9.7 7.9 0 70 K(,)00 0.0 8. 77.9 70 80 K(0,)000 0.0.. 0 0 K(0,)000 0.0. 9.0 0 0 0 0 K(0,)0080.0 9..0 0 8 8 K(0,)000 0.0 7.8.0 0 0 8 K(,)00.0 0.8 9.0 70 70 K(,)00 0.0 9. 79.0 70 80 K(,)080 7.0 8. 9.0 90 00 K(,)000 80.0 9. 0.0 00 0 K(0,)000 0.0 7. 8. 0 0 K(0,)000 0.0 8.. 0 0 8 K(0,)0080.0.. 0 8 8 K(0,)000 0.0 0.0. 0 0 8 K(,)00.0.0 7. 70 80 K(,)00 0.0 7. 8. 80 90 K(,)080 7.0 8. 9. 90 00 K(,)000 80.0 9. 0. 00 0 K(0,)000 0.0 7. 8. 0 0 K(0,)000 0.0 8.. 0 0 8 K(0,)0080.0.. 0 8 8 K(0,)000 0.0 0.0. 0 0 8 K(,)00.0.0 7. 70 80 K(,)00 0.0 7. 8. 80 90 K(,)080 7.0 8. 9. 90 00 K(,)000 80.0 9. 0. 00 0 K(,)00 00.0.0. 0 /0. (0,) - 0 = no circuit breaker OR = with circuit breaker.. (,) - = with circuit breaker, no breaker jumper bar OR = with circuit breaker & breaker jumper bar.. MOP = Maximum Overcurrent Protection device; must be AR type circuit breaker or time delay fuse.. Stated sizes are for 7, copper wire only. If wire other than non-plated, 7 ambient, copper wire is used, consult applicable tables of the NE and local codes. Johnson ontrols Unitary Products

00-UIM-B-0 TABLE : Electrical Data For Multi-Source Power Supply: 08/0--0 Air andlers Models AVB AV0B AV AVD AV8D AV0D eater Models Total eater Amps @0V Min. ircuit Ampacity MOP Min. Wire Size (AWG) 08V 0V 08V 0V 08V 0V ircuit ircuit ircuit st nd rd st nd rd st nd rd st nd rd st nd rd st nd rd K00.0. 7. -.. - 0 - - 0 8-0 8 - K00 0.0.. - 7.9 0.0-0 - 0 0-0 8-0 8 - K00.0. 7. -.7. - 0-0 - 0 8-0 8 - K00 0.0.. - 9.0 0.0-0 - 0 0-0 8-0 8 - K080 7.0. 9.0-9.0.0-0 - 0-8 8-8 8 - K000 80.0 7.8. -.0 0.0-0 - 0 0-8 8-8 - K00.0. 7. - 7.8. - 0 0-0 - 0 8-0 8 - K00 0.0 8.. -. 0.0-0 - 0-0 8-8 8 - K080 7.0. 9.0 -..0-0 0-0 - 8 8-8 - K000 80.0 9.9. -. 0.0-0 - 0 0-8 8-8 - K00.0. 7. - 7.8. - 0 0-0 - 0 8-0 8 - K00 0.0 8.. -. 0.0-0 - 0-0 8-8 8 - K080 7.0. 9.0 -..0-0 0-0 - 8 8-8 - K000 80.0 9.9. -. 0.0-0 - 0 0-8 8-8 - K00 00.0 9.9..7. 0.0.0 0 0 0 8 8 0 8 0. MOP = Maximum Overcurrent Protection device; must be AR type circuit breaker or time delay fuse.. Stated sizes are for 7, copper wire only. If wire other than non-plated, 7 ambient, copper wire is used, consult applicable tables of the NE and local codes.. st ircuit includes the blower motor amps. TABLE : Electrical Data For Single Source Power Supply: 08/0--0 Air andler Models eater Field Wiring eater Amps Min. ircuit Ampacity Models MOP Min. Wire Size (AWG) 0V 08V 0V 08V 0V 08V 0V AV8B K000. 8..8 0 0 8 AVB K000. 8..8 0 0 8 AV0B K00. 0.9. 0 8 8 K000. 9..9 0 0 8 AV K00..0 7. 0 8 8 AVD K008. 9..0 0 0 8 K00...8 0 70 K000..7.0 8 8 AV8D K00.. 9. 0 8 8 K008..7 8. 0 0 K00..7.9 0 70 K000..7.0 8 8 K00.. 9. 0 8 8 AV0D K008..7 8. 0 0 K00..7.9 0 70 K0 7.7 9. 78. 70 80. MOP = Maximum Overcurrent Protection device; must be AR type circuit breaker or time delay fuse.. Stated sizes are for 7, copper wire only. If wire other than non-plated, 7 ambient, copper wire is used, consult applicable tables of the NE and local codes.. The 0kW and kw heater models (K00 and K0) come with circuit breakers standard. Single source power MA and MOP requirements are given here only for reference if used with field installed single point power modification. TABLE : Electrical Data For Multi-Source Power Supply: 08/0--0 Air andler Models Min. ircuit Ampacity MOP Min. Wire Size (AWG) Total eater eater 08V 0V 08V 0V 08V 0V Amps Models ircuit ircuit ircuit 0V st nd st nd s t nd st nd st nd st nd AV AVD K00. 9..0.9 8.9 0 0 0 0 8 0 AV8D K00..7.0.0 8.9 0 8 0 8 0 AV0D K00..7.0.0 8.9 0 8 0 8 0 K0 7.7 7.9... 0 0 8 8 8 8. MOP = Maximum Overcurrent Protection device; must be AR type circuit breaker or time delay fuse.. Stated sizes are for 7, copper wire only. If wire other than non-plated, 7 ambient, copper wire is used, consult applicable tables of the NE and local codes.. st ircuit includes the fan motor. Johnson ontrols Unitary Products