BS FP600 achieves the maximum 120 minute rating under the BS test conditions, which is required for fire fighting applications.

Similar documents
STANDARDS INSTALLATION. Certificate No 077m

FIRE RESISTANT CABLES FP400

FIRE RESISTANT CABLES FP300

All Prysmian FP400 cables are manufactured under an ISO 9001 Quality System certified by BASEC and LPCB.

FIRE RESISTANT CABLES FP200 GOLD

FIRE RESISTANT CABLES FP PLUS. New Generation. Now with enhanced Insudite TM insulation

FIRE RESISTANT CABLES FP200 GOLD

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

AFUMEX LSX BASEC APPROVED LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

LSOH Flexible Cables

LSOH Wiring Cables. LSOH Conduit Wire (HO7Z-R) Low Voltage (450/750 V) Cable Approvals. Key Applications. Conductor. Insulation. Core Identification

CONTENTS. Introduction Customer Service BS codes of practice BS Fire Performance Cable Selection Guide... 7

Total Fire Solutions. Includes BS 8519 and the updated BS :

High Performance LSZH Fire Resistant Cable

600/1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables (Multicore)

600/1000V XLPE Insulated, LSZH Sheathed, Double steel tape Armoured Power Cables (3 Cores)

600/1000V SR Insulated Flexibles Control Cables (2-4 Cores & Multicores)

Introduction.

BS /1000V XLPE Insulation LSZH Sheath Cables

FIRE PERFORMANCE CABLE

Fire Resistant Cables

GUARDIANTM QUALITY APPROVED CABLES. Cables Limited MADE IN IRELAND SINCE 1934 IDH CABLES LIMITED MECHANICALLY PROTECTED CABLES

ENHANCED FIRE PERFORMANCE CABLE

Flame Retardant Overall Screened Instrumentation Cables (multicore)

Table of Contents. TELE-FONIKA KABLE SA (DMCC Branch). 4 TELE-FONIKA Kable Group 6 FLAME-X 950 SERIES 1 11 FLAME-X 950 SERIES 2

Firetuf Cables ZERO HALOGEN, LOW SMOKE (0HLS ) CABLE

Firetuf Cables ZERO HALOGEN, LOW SMOKE (0HLS ) CABLE

A guide. Part 1: Code of practice for system design, installation, commissioning and maintenance. by T.L. Journeaux

fire resistant cables

AFIREFENIX SZ1-K 0,6/1 kv PH120 (AS+)

LV FIRE RESISTANT CABLES

Author Owner Issue Authority Name: Gordon MacKenzie Title: Senior Engineer Engineering Design and Standards

Selecting the AFUMEX range guarantees quality and offers the widest choice and the greatest safety.

Catalogue Telecommunication Cables INTRODUCCIÓN

INTRODUCTION. Our diverse range of world-class Specialty Insulated Wires and Cablesinclude: LV Cables -

Photovoltaic Cables EN H1Z2Z2-K

The Quality Connection. BETAflam Fire Resistant Safety Cables

Multi-Core Fire Resistant Cable

Cable technology for highest safety requirements

Requirements for Electrical Installations

Telecommunication Cables

Caledonian Flame Retardant Coaxial Cables

Data Sheet. Self regulating heating tapes. RS stock numbers

Catalogue Power Cables

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

IEC ; EN ; DIN VDE ; CEI 20-37/2-1 ; BS * No Corrosive Gas Emission

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK


Power Cables. Introduction 3 RV 4 RVMV 5 RVSV 6 RVFV 7. ELECWIRES 2 Page

FIRE RESISTANT CABLES

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

Flexflame. Arctic Grade Cables for Extreme Conditions. Photo: Sakhalin Energy Investement Company Ltd.

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

Guide to the Specification and Installation of Pyro Mi Wiring Cables

Tratos Railway Cables

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Firetuf OFC-UT-CST Fire resistant Armoured Central Tube Cable, variant in red

Data Sheet. Self regulating process heating tapes RS stock numbers ,

POWER SHOWERS Models 4500M 5002M 4500T 5002T

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS - Item No. FIBRE OPTIC COMMUNICATION CABLES, IN DUCTS (TEMPORARY) - Item No.

Optical Fibre Cable Technical Specification. Duct Cable GYTA-72B1.3

Caledonian Fire resistant Coaxial Cables

THE TRUE FIRE SURVIVAL CABLE

Firetuf OFC-UT-CST Fire resistant Armoured Central Tube Cable, variant in red

For Heavy Duty Commercial and Industrial Environments

IEC UNE DESIGN. 1. Conductor. 2. Insulation. Cross-linked polyethylene (XLPE) 3. Outer sheath. Flexible PVC, black colour.

DNVGL-CP-0401 Edition February 2016

KUTERLEX & KUTERLEX PLUS PLASTIC COATED COPPER TUBE

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

PRODUCT CATALOGUE Norröna

FLEXIBLE METAL - BENDING THE RULES OF PLUMBING CONNECT WITH CONFIDENCE SEE OUR NEW EXTENDED RANGE OF VALVES -

Carbon Film Installation Instructions

Self-Regulating Point Heating Performance Requirements

CORFLEX TYPE MC-HL POWER, CONTROL & INSTRUMENTATION CABLES

Duct Cable GYTS-144B1.3

CORFLEX. TYPE MC-HL & MV-105 or MC-HL OIL & GAS CABLES

Fire alarm cables. for highest safety requirements TRADITION INNOVATION PASSION

Compact Module. Category 6A FTP Cabling System 1.1

CHAPTER 7 MECHANICAL VENTILATION AND SMOKE CONTROL SYSTEMS 7.1 AIR CONDITIONING & MECHANICAL VENTILATION SYSTEMS

FUMEGUARD TM QUALITY APPROVED CABLES. Cables Limited MADE IN IRELAND SINCE 1934 IDH CABLES LIMITED LOW SMOKE HALOGEN FREE CABLES

DNVGL-CP-0402 Edition February 2016

Double insulated, electron-beam cross-linked, halogen free photovoltaic wire sunlight resistant. Single conductor, flame retardant insulation.

LINEAR HEAT DETECTION SENSOR CABLE ACCESSORIES

INTERNATIONAL STANDARD

Havells Fire Survival Cables

Method of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions.

DNVGL-CP-0399 Edition March 2016

WHHR Midi & Midi Lite

LSZH Zero Halogen Cables

F1202 TRACE HEATING. Road & Ramp

Assessment Schedule - TS.6

Thermocouple Cable TRANSMITTING, SENSING, MEASURING

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

OIL & GAS INDUSTRY OTHER INDUSTRIES

Catalogue. Instrumentation & Control Cables

LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions

Transcription:

FIRE RESISTANT CABLES FP600

FIRE RESISTANT CABLES FP600 BS7346-6 FP600 > Prysmian FP600 is a unique enhanced performance fire resistant power cable, designed specifically to meet the more onerous fire survival requirements now requested by regulators and specifiers for many fire fighting and life safety applications. Its superior mechanical protection provided by an interlocking steel tape armour is, unlike standard single wire armour designs, maintained to a high level under fire conditions. This armour design ensures that FP600 meets the new generation fire test requirement currently given in BS7346-6:2005 "Components for smoke and heat control systems - Part 6 Specification for cable systems" which involves direct mechanical impact and water jet application under fire conditions. FP600 achieves the maximum 120 minute rating under the BS7346-6 test conditions, which is required for fire fighting applications. standards > FP600 meets the 120 min survival time of BS7346-6. Note: At the time of publication of this document (August 2006), the complete cable fire test method is given in Annex B of BS7346-6:2005. However, it is understood that the test method will in the near future be published as a stand alone standard (BS8491). INSTALLATION > FP600 is an easy to install cable that requires no special tools or techniques. It is however important to follow the installation recommendations given in this document to ensure a trouble free installation and to ensure that the fire integrity of the installed system is not compromised. In accordance with BS7346-6 requirements, cables must be supported by a fixing that can withstand the same fire conditions as the cable. Any cable management system, joints and terminations should be similarly selected. It is recommended that joints are avoided wherever possible with FP600 in order to maintain the highest integrity of the installation. CABLE CHARTERISTICS Temperature Range -25 to +90 C Bending Radius Fixed r=8d Mechanical Impact Excellent Fire Performance BSEN60332-1-2 BSEN50266-2-4 Flexibilty Rigid Halogen Free BSEN50267-2-1 Low Smoke Emissions BSEN61034-2 Fire Resistant BS7346-6 120min

FP 600 FIRE RESISTANT CABLES Nominal cross sectional area mm 2 overall diameter mm cable weight kg/km Maximum conductor resistance at 20 C ohms/km Current rating DC or single phase Free Air Current rating DC or single phase Clipped direct Volt drop DC mv/a/m Volt drop single phase mv/a/m Recommended accessories Claw Cleat Brass gland Two core 10 24.3 900 1.83 90 85 4.7 4.7 370CG05 416FP55 16 25.5 1050 1.15 115 110 2.9 2.9 370CG06 416FP55 25 28.9 1375 0.727 152 146 1.85 1.9 370CG06 416FP56 35 32.7 1950 0.524 188 180 1.35 1.35 370CG07 416FP56 50* 33.4 2200 0.387 228 219 0.98 1.0 370CG07 416FP56 70* 36.6 2775 0.268 291 279 0.67 0.69 370CG07 416FP57 95* 38.3 3375 0.193 354 338 0.49 0.52 370CG08 416FP57 120* 41.9 4050 0.153 410 392 0.39 0.42 370CG08 416FP59 Nominal cross sectional area mm 2 overall diameter mm cable weight kg/km Maximum conductor resistance at 20 C ohms/km Short circuit rating (1 sec) of conductor KA Current rating Three phase Clipped direct Current rating Three phase Free Air Volt drop Three phase mv/a/m Recommended accessories Claw Cleat Brass gland Three core 10 24.9 1125 1.83 1.4 73 78 4.0 370CG05 416FP55 16 27.4 1350 1.15 2.2 94 99 2.5 370CG06 416FP55 25 32.4 1975 0.727 3.6 124 131 1.65 370CG07 416FP56 35 35.2 2375 0.524 5.0 154 162 1.15 370CG07 416FP57 50* 36.2 2775 0.387 7.1 187 187 0.87 370CG07 416FP57 70* 39.8 3550 0.268 10.0 238 251 0.60 370CG08 416FP57 95* 43.7 4500 0.193 13.6 289 304 0.45 370CG08 416FP59 120* 46.0 5400 0.153 17.2 335 353 0.37 370CG09 416FP59 Four core 10 26.5 1250 1.83 1.4 73 78 4.0 370CG06 416FP55 16 29.3 1500 1.15 2.2 94 99 2.5 370CG06 416FP55 25 33.6 2325 0.727 3.6 124 131 1.65 370CG07 416FP56 35 37.7 2825 0.524 5.0 154 162 1.15 370CG08 416FP57 50* 39.1 3400 0.387 7.1 187 197 0.87 370CG08 416FP57 70* 43.8 4450 0.268 10.0 238 251 0.60 370CG08 416FP59 95* 47.6 5625 0.193 13.6 289 304 0.45 370CG09 416FP59 120* 51.8 6900 0.153 17.2 335 353 0.37 370CG09 416FP59 Note* Shaped conductors Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations. The tabulated ratings are based upon a 30 C ambient temperature and 90 C operating temperature.

LOW VOLTAGE 600/1000V Key Applications Electrical supplies for fire fighting, life safety and property protection systems. Active fire safety systems which, as part of a Fire Safety Engineering solution, rely on an effective electrical supply remaining operational during a fire. Greater emphasis is now being given to the integrity of electrical circuits which maintain the functional safe working conditions of such equipment and systems. FP600 is the first of a new generation of fire resistant cables designed to meet the much more onerous fire survival requirement now considered appropriate for such applications. Examples of circuits which are required to remain operational under such conditions include: > Atrium, basement, underground car park and shopping mall smoke venting systems > Electrically operated fire shutters and smoke curtains > Fire fighting lifts > Pressurisation and depressurisation fans > Smoke dampers motor driven > Smoke relief dampers motor driven open > Sprinkler and wet-riser pumps The new requirements and test method for cables for use in such applications, which involves an integrated fire test with the application of radiation by flame, direct impact and water jet to a single sample of cable are given in BS7346-6 'Components for smoke and heat control systems - Part 6 Specification for Cable systems' FP600 has been extensively tested against these requirements and achieved the maximum120 minute rating. Cable Description CONDUCTOR Plain annealed copper stranded circular (10-35mm 2 ) or shaped (50-120 mm 2 ) conductor complying with BS EN 60228 Class 2. Insulation Primary Insulation: Mineral ceramic (Mica/Glass) fire resistant tape Secondary Insulation: 90 C cross - linked insulation Core identification: o o brown - blue o o o brown - black - grey o o o o blue - brown - black - grey Bedding Extruded LSOH bedding compound ARMOUR Single layer of interlocking steel tape. SHEATH Robust thermoplastic LSOH sheath. Colour - Black. Other colours to special order. Correction factors for Ambient temperatures Ambient Tempareture C 25 30 35 40 45 50 55 60 Correction Factor 1.02 1.0 0.96 0.91 0.87 0.82 0.76 0.71 Correction factors for grouping of cables Installation Method Single layer clipped to a non-metallic surface Single layer multicore on a perforated metal cable tray, vertical or horizontal Number of circuits or multi-core cables 2 3 4 5 6 7 8 9 Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 Spaced* 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 Spaced* 0.91 0.89 0.88 0.87 0.87 - - - * Spaced by a cleareance between adjacent surfaces of at least one cable diameter. Where the horizontal clearance between adjacent cables exceeds 2 cable diameters no correction factor need be applied Note. Standard conditions of grouping as stated in BS7671 (IEE Wiring Regs) apply

INSTALLATION RECOMMENDATIONS FP600 cables should be installed in accordance with BS7671/IEE Wiring Regulations and/or any other appropriate national legislation. They are primarily intended for use installed in air. INSTALLATION METHOD FP600 cables are primarily intended for use in buildings. They may be fixed directly to the building structure or be carried upon suitable cable management systems (e.g. tray, ladder). Due to its extremely robust nature, FP600 does not require additional mechanical protection. Minimum installation temperature The cable should not be installed at temperatures below 0ºC. Minimum Bending Radius The minimum recommended bending radius for FP600 cables during installation is 12x the cable overall diameter. Under controlled bending conditions the bending radius may be reduced to 8x the overall diameter. CABLE CLEAT SPING The maximum spacing of cleats should not exceed 1800mm when installed horizontally. When installed vertically the maximum spacing of the cleats should not exceed 900mm and alternate cleats should be offset about the vertical by a minimum of one cable diameter. Cable fixings When the cable is required to maintain circuit integrity during a fire, it is essential that the cleats or cable trays used to support the cable can also withstand the fire. Fixings and supports should be manufactured from a suitable metal and be suitable for fixing fire rated cable. The cable should not be fixed by plastic, nylon or similar fixings. The use of BICON 370CG series claw cleats is recommended. Cable pulling The construction of FP600 means that if the cable is not installed by a suitable technique, the outer armour/sheath combination may stretch, but the inner cores/bedding combination will not, thereby giving the appearance that the cores have shrunk back into the cable. It is recommended that the cable should be installed using a stocking pulling technique that locks the relative positions of the outer armour/ sheath and inner cores/bedding combinations: remove the armour/sheath combination for a length of 500mm, taking care to avoid injury from any sharp edges of the armour. Place a cable stocking of at least 1 metre in length over the inner bedding and outer sheath, ensuring that the stocking firmly grips both the outer sheath and the inner bedding. Pull the cable in the normal manner taking into account all limiting factors. If the cable is to be pulled where there is a possibility that water, mud, etc. may be present, then, before the cable stocking is placed into position, a self amalgamating tape should be applied to the cable to stop any ingress of water between the cable bedding and armour and within the inner cores. Once the cable has been pulled into position, the excess core/bedding shall be cut back to the armour/sheath and a heat shrink capping shall be applied. The maximum stocking pulling tension is 5 Kg per sq.mm of total conductor cross sectional area up to a maximum of 1000Kgs. The use of guide rollers or other friction reducing devices is recommended. Cable glanding FP600 may be easily glanded using BICON 416FP series glands. It is not necessary to use shrouds with these glands. Each gland includes a continuity clip which, when the gland is correctly fitted, provides adequate electrical connection of the cable armour to the gland. Reference should be made to the fitting instructions supplied with the gland for detailed advice. The sheath and armour should be removed by cutting back the oversheath to the length specified in the gland fitting instruction leaflet. Remove the armour by cutting one section of the steel strip at an angle of 45 degrees with a hacksaw. Rotate the tape armour anti clockwise and remove the cut section. Care should be taken to avoid injury from any sharp edges of the armour. Electrical Data Current ratings Current ratings are to BS7671, ( IEE wiring regs 16th edition) table 4E4A. Short circuit temperature The maximum short-circuit temperature of the conductor is 250ºC. Health and Safety Please refer to Prysmian Cables leaflet Statement to Cable Users on the Health & Safety at Work Act 1974 and to the Control of Substances Hazardous to Health Regulation (COSHH). Conductor cross - sectional area Maximum Resistance of conductor and armour and gross cross-sectional areas of armour tape Maximum Resistance of Conductor at 20 C Calculated maximum Resistance of Armour at 20 C Effective Cross Sectional Area of Tape Armour 2 Core 3 Core 4 Core 2 Core 3 Core 4 Core mm 2 ohms/km Ωohms/km Ωohms/km ohms/km mm 2 mm 2 mm 2 10 1.83 5.6 5.3 4.8 32 34 37 16 1.15 4.9 4.7 4.3 36 38 42 25 0.727 4.4 2.9 2.7 41 62 68 35 0.524 2.8 2.6 2.4 65 69 76 50 0.387 2.9 2.5 2.3 63 71 79 70 0.268 2.5 2.3 2.0 71 81 90 95 0.193 2.3 2.0 1.8 77 90 100 120 0.153 2.1 1.9 1.7 87 98 110

Sales enquiries Tel: +44 (0) 8457 678345 Fax: +44 (0) 23 8029 5465 Technical helpline Tel: +44 (0) 23 8029 5222 Fax: +44 (0) 23 8029 5002 Information hotline Tel: +44 (0) 23 8029 5029 Fax: +44 (0) 23 8029 5437 cables.marketing.uk@prysmian.com www.prysmian.co.uk Prysmian Cables & Systems Limited Chickenhall Lane Eastleigh Hampshire SO50 6YU United Kingdom Ref:FP600/PY/08/06