GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

Similar documents
GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

MGC Dock User s Manual

CO2 RESPONDER Portable Carbon Dioxide Detector QUICK REFERENCE GUIDE

OI-2400-DOCK Multi Gas Docking Station. Operation Manual trevision 2.2w

MGC Dock User s Manual

RK Carbon Monoxide Transmitter Operator s Manual

Single Gas Clip and SGC Plus User s Manual Rev 2.1 READ FIRST BEFORE OPERATION WARNING STATEMENTS / AVERTISSEMENT Activating tthe detector for the

RK-05 Combustible Gas Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

Single Gas Clip and SGC Plus User s Manual Rev 2.3

RK Carbon Monoxide Transmitter Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual

RK Transmitter Technical Notice

RK-03 Hydrogen Detector Operator s Manual

RK Combustible Gas Transmitter Operator s Manual

RK / RK Methane Detector Operator s Manual

RK Multi Point Detector Operator s Manual

RK CO 2 Transmitter Operator s Manual

RK/ RK Combustible Gas Detector Operator s Manual

CT-7 Series Toxic Gas Transmitter Operator s Manual

RK-05 Carbon Monoxide Transmitter Operator s Manual

NH 3 RESPONDER Portable Ammonia Leak Detector QUICK REFERENCE GUIDE

QUICK REFERENCE GUIDE

RK-02 Multi Point Detector Operator s Manual

GasAlertMicro 5. 1, 2, 3, 4, and 5 Gas Detectors. Quick Reference Guide

RK-05 Carbon Monoxide Detector Operator s Manual

RK/ RK Oxygen Detector Operator s Manual

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

RK-CH4-4 Combustible Gas Transmitter Operator s Manual

Operator s Manual. 1, 2, 3, and 4-Gas Detector

RK/ RK Oxygen Detector Operator s Manual

RK/ RK Carbon Monoxide Detector Operator s Manual

Combustible Gas Sample-Draw Detector Operator s Manual

Carbon Dioxide Sample-Draw Detector Operator s Manual

RK / RK CO 2 Detector Operator s Manual

CMF, CMX & CMA series

Single Gas Detector. Quick Reference Guide

Operator s Manual. 1, 2, 3, and 4-Gas Detector

GAS MONITOR Model Model

ANALOX 101 D2 PORTABLE OXYGEN MONITOR USER MANUAL

RK-OXY Oxygen Sample-Draw Detector Operator s Manual Part Number: RK Revision: P1 Released: 7/18/02

NH3 RESPONDER PORTABLE AMMONIA LEAK DETECTOR. Quick Reference Guide

GasAlertMicro 5 and GasAlertMicro 5 PID O 2, CO, H 2 S, PH 3, SO 2, Cl 2, NH 3, NO 2, HCN, ClO 2, O 3, VOC, and Combustibles

Controllers. Instruction Manual WARNING

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

MODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR

Macurco Single-Gas XL Series Monitor, CM-1XL Carbon Monoxide (CO), HS-1XL Hydrogen Sulfide (H2S) User Instructions

Combustible Gas/Hydrogen Sulfide Sample-Draw Detector Operator s Manual

! "! # Please read these installation and operating instructions completely and carefully before starting.

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

Instruction Manual WARNING

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

SEC 2000 Millenium Infrared Gas Detector

MACURCO INC. CONTROLLERS & CARBON MONOXIDE DETECTORS SS103-3A, SS103-10A SS102H, SS102HC-1 INSTALLATION & OPERATING INSTRUCTIONS

QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL

RKA-06 Sample-Draw Detector

LV-S-5. Instruction Manual DIRECT CONTACT STRAY VOLTAGE DETECTOR GENERAL DESCRIPTION HOW IT WORKS

User s Manual and Warranty Information for Counterweighted Chain Drive ThyssenKrupp Access

Combustible Gas/Carbon Monoxide Sample-Draw Detector Operator s Manual

Carbon Monoxide Sample-Draw Detector Operator s Manual

Operation and Maintenance Manual

Beacon 800 Gas Monitor Operator s Manual

VX SERIES Wireless Thermostat with Occupancy Sensor

This instruction manual explains the use of three models listed on the left.

INSTALLATION AND OPERATING INSTRUCTIONS FOR THE VEHICLE-MOUNTED RADIATION DETECTION SYSTEM

Document No

OWNERS MANUAL. CARBON MONOXIDE DETECTOR MODELS Panel Mount & Remote Detectors (R) Guardian Avionics 1951 E. AIRPORT DRIVE TUCSON, AZ.

DESCRIPTION The HIH-4000 Series Humidity Sensors are designed specifically for high volume OEM (Original Equipment Manufacturer) users.

RKA-03 Sample-Draw Detector Head

DESCRIPTION The HIH-4000 Series Humidity Sensors are designed specifically for high volume OEM (Original Equipment Manufacturer) users.

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model COSTAR 24VC-e Single Relay

Hydrocarbon Gas Detector

AT-G-DETECT Gas Sensing System

COMBUSTIBLE GAS LEAK DETECTOR PEN

SEC 5000 IREvolution Gas Detector

TAG MR VOLTAGE DETECTORS AND ACCESSORIES. Instruction & Operation Manual

High-Velocity Floor Fan

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

RK-04 M2 Transmitter Operator s Manual

Transcription:

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

2

Table of Contents GasGuard H 2-1% General description. 4 Installation.. 4 Locating the sensor. 4 Installation guidelines 5 Wiring.. 6 Operation.. 7 Start-up... 7 Calibration.. 7 Maintenance. 9 Specifications.. 10 Warranty.. 11 Calibration Technologies 866-394-5861 3

General Description The GasGuard H2 1% sensor is a +24 VDC, three-wire, 4/20 ma sensor for hydrogen. It is designed to detect and monitor potentially explosive levels of hydrogen gas in air over the range of 0-10,000 ppm (25%LEL). It provides an industry standard linear 4/20 ma output signal compatible with most gas detection systems and PLCs. Typical sensor life is 5 years. The GasGuard H2 1% provides real-time continuous monitoring of high concentrations of hydrogen utilizing catalytic bead sensor technology. The transmitter circuit board is sealed in potting compound, protecting sensitive electronic components and copper tracing from corrosion. The specially vented enclosure is made of a highly impact and chemical resistant polycarbonate to protect the sensor. Installation Locating the sensor One of the most important considerations when installing the GasGuard H2 1% sensor is that it must be easily accessible for calibration and maintenance. Since hydrogen gas is lighter than air, careful consideration must be given where hydrogen pockets will be formed. The ceiling is where hydrogen gas will typically accumulate. This mounting location will usually provide the best personnel and property protection. As a general rule of thumb, try to mount sensors within 30 feet of potential leak sources. Hydrogen gas becomes explosive at 4% or 40,000 ppm. Calibration Technologies recommends an alarm setpoint at no higher than 1% (25% LEL). While the primary application for the GasGuard H2 1% sensor is exhaust fan activation for battery charging rooms, it can be used almost anywhere high concentrations of hydrogen vapors need to be detected or monitored. 4

Installation Guidelines: Always mount the sensor vertically. Must be easily accessible for calibration and maintenance. Mount the sensor close to the potential leak source. For optimum detection, mount sensor close to ceiling (1 3 below ceiling level). Take air movement and ventilation patterns into account. To prevent electrical interference, keep sensor and wire runs away from mercury vapor lights, variable speed drives, and radio repeaters. Protect sensor from physical damage(forklifts, etc.). If mounting sensor outdoors, consider prevailing wind direction and proximity to the most likely source of leaks. Protect the sensor from sun and rain as much as possible. Never mount the sensor in CA (controlled atmosphere) rooms because normal atmospheric levels of oxygen are required for operation. For highly critical locations more than one sensor should be installed in each room. Mount sensor enclosures through the mounting holes as shown in Figure 1. Use the supplied selftapping screws for mounting on sheet metal surfaces. Figure 1: Mounting Dimensions 5

Wiring Electrical wiring must comply with all applicable codes. Electrical Power: 24 VDC regulated, 250 ma. Output: Linear 4/20 ma output. Monitoring equipment may have a maximum input impedance of 700 ohms. Cable Recommendation: 20/3 shielded cable (General Cable C2525A or equivalent). Length of cable to sensor should be no greater than 1,500 feet. Monitoring: Monitoring equipment must be configured to indicate a fault if the signal is below 1 ma. All signals over 20 ma must be considered high gas concentrations. Alarm setpoints should not be lower than 10% of full-scale range. GASGUARD H2 1% RANGE 0-1 % (25% LEL) Wiring Guidelines: Always use three conductor, insulated, stranded, shielded copper cable. Do not pull sensor wiring with AC power cables. This can cause electrical interference. If cable runs cannot be made without a splice, all splice connections should be soldered. Ground the shield at the main control panel. Connect the shield wire in the sensor terminal block labeled SHLD. Use only the existing conduit hole for connections to the sensor. Figure 2: Wiring diagram 6

Operation Start-up Before applying power, make a final check of all wiring for continuity, shorts, grounds, etc. It is usually best to disconnect external alarms and other equipment from the sensor until the initial start-up procedures are completed. After power-up, allow at least 24 hours for the system to stabilize before testing the sensors. Because sensors are normally located at a distance from the main unit, the test time required and accuracy of the response checks will be improved if two people perform the startup procedures and use radio contact. Start-Up Test: 1) One person exposes each sensor to hydrogen calibration gas. 2) The second person stays at the control unit to determine that each sensor, when exposed to the gas, is connected to the proper input and responds, causing appropriate alarm functions. Calibration The GasGuard H2 1% Sensor comes factory calibrated and should require only minimal adjustments after installation. Calibration should be performed six months after installation. There are two pots on the preamp that are used for calibration. Note: Never measure sensor output in ma. Always use mvdc or VDC voltmeter settings. Calibration Mode: Cal mode is required for calibrating the sensor. It clears the deadband (factory set at 4.8 ma) and averaging. Pressing the CAL switch enables cal mode and the green LED will flash. To exit out of cal mode, press the CAL switch or after 4 minutes it will automatically time-out. Zero Calibration: After the unit is installed and has been powered up for a minimum of 24 hours, the unit can be zero calibrated by the following: Be sure the unit is in clean air, or use zero air gas. Press the CAL switch once to enter cal mode. Do not adjust the zero pot if the green LED is not flashing. Adjust the zero pot until the sensor outputs 40 mv from Test [-] to Test [+] (see Figure 3). Span Calibration: DO NOT ADJUST THE SPAN POT WITHOUT CERTIFIED CALIBRATION GAS! Do not remove sensor housing cap during calibration. If span adjustment is required, the following procedure will span the unit: Press the CAL switch once to enter cal mode. Apply span gas at 0.8 L/min (span gas must be in air, not nitrogen or other carrier). Sensor should react to gas within 15 seconds Once the output signal has peaked (or two minutes maximum) adjust the span pot until the correct output is achieved (see Figure 3). Calibration is now complete. 7

RANGE 0-1 % (25% LEL) GASGUARD H 2 1% Figure 3: Sensor board components and zero/span adjustments 8

4mA adjustment: Sometimes a fine adjustment of the 4mA signal may be desired to compensate for a slight positive or negative zero-signal reading on the control panel. Make sure the sensor is NOT in calibration mode. Adjust the 4mA pot until the control panel reads zero. Sensor replacement: If sensor replacement is required, follow the procedure below. Since any arcing could be an ignition source, ensure that the sensor location is clear of any explosive concentrations of hydrogen. Unscrew the sensor housing cap. Remove the sensor from the socket by pulling straight out with it. Discard old sensor. Notice orientation dot on backside of new sensor. The dot on the sensor needs to be facing upwards. Carefully plug in new sensor. Refer to calibration section on page 7 to calibrate new sensor. Note: Below are a few response characteristics which may be an indication that the gas sensor is at or near the end of its useful life. If any of these are observed, the sensor should be replaced: Slow response to / recovery from calibration gas. Failure of the output to reach 50% of the calibration gas value prior to span adjustment. Unable to achieve correct output during span adjustment. Maintenance The GasGuard H2 1% was designed for long life and minimal maintenance. For proper operation it is essential that the test and calibration schedule be adhered to. Calibration Technologies recommends the following maintenance schedule: Maintenance Guidelines: The sensor is shipped with a factory calibration. Sensor should be calibrated 6 months from purchase date. Calibrate the detector at least once every 6 months. Calibration should be performed with certified calibration gas. Calibration kits and replacement cylinders are available from Calibration Technologies. All tests and calibrations must be logged. 9

Sensor Life: This catalytic bead sensor exhibits long life and is very reliable. Typical sensor life is five years. As with all gas detectors, regular 6-month calibration intervals are essential to correct for sensor aging characteristics. Replacement sensors can be obtained from Calibration Technologies. Simply unplug the sensor from the transmitter, discard the old sensor and replace it with a new one. Refer to the sensor replacement section on page 9. The sensor can then be calibrated after a 24 hour warm-up period. Specifications Detection Principle: Catalytic Bead Detection Method: Diffusion Gases: Hydrogen (H2) Ranges: 0/1% (0/10,000 ppm)(0/25%lel) Output Signal: Linear 4/20 ma (max input impedance: 700 Ohms) Power Supply: +24 VDC, 250 ma Response Time: T 50 = less than 30 seconds T 90 = less than 60 seconds Accuracy: +/- 5% of value, but dependant on calibration gas accuracy and time since last calibration Zero Drift: Less than 0.1% of full-scale per month, noncumulative Span Drift: Application dependant, but generally less than 2% per month Linearity: +/- 0.5% of full-scale Repeatability: +/- 1% of full-scale Wiring Connections: 3 conductor, shielded, stranded, 20 AWG cable (General Cable C2525A or equivalent) up to 1500 ft. Enclosure: Injection-molded NEMA 4X polycarbonate sensor housing. Captive screw in hinged lid. For nonclassified areas. Temperature Range: -40 F to +120 F (-40 C to +49 C) Humidity Range: 5% to 100% condensing Dimensions: 7.5 high x 6.5 wide x 3.8 deep Weight: 2.0 lbs 10

Limited Warranty & Limitation of Liability Calibration Technologies, Inc. (CTI) warrants this product to be free from defects in material and workmanship under normal use and service for a period of one year (gas sensor also covered for one year), beginning on the date of shipment to the buyer. This warranty extends only to the sale of new and unused products to the original buyer. CTI s warranty obligation is limited, at CTI s option, to refund of the purchase price, repair, or replacement of a defective product that is returned to a CTI authorized service center within the warranty period. In no event shall CTI s liability hereunder exceed the purchase price actually paid by the buyer for the Product. This warranty does not include: a) routine replacement of parts due to the normal wear and tear of the product arising from use; b) any product which in CTI s opinion, has been misused, altered, neglected or damaged by accident or abnormal conditions of operation, handling or use; c) any damage or defects attributable to repair of the product by any person other than an authorized dealer or contractor, or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on: a) proper storage, installation, calibration, use, maintenance and compliance with the product manual instructions and any other applicable recommendations of CTI; b) the buyer promptly notifying CTI of any defect and, if required, promptly making the product available for correction. No goods shall be returned to CTI until receipt by the buyer of shipping instructions from CTI; and c) the right of CTI to require that the buyer provide proof of purchase such as the original invoice, bill of sale or packing slip to establish that the product is within the warranty period. THE BUYER AGREES THAT THIS WARRANTY IS THE BUYER S SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. CTI SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, INCLUDING LOSS OF DATA, WHETHER ARISING FROM BREACH OF WARRANTY OR BASED ON CONTRACT, TORT OR RELIANCE OR ANY OTHER THEORY. 11

GG-H2 1% 02/2013