Analysis of a Refrigerant Compressor Load Stand Incorporating Hot Gas Bypass and a Single Full Condensation Heat Exchanger

Similar documents
Experimental Analysis of Performance of Heat Exchanger with Plate Fins and Parallel Flow of Working Fluids

The Development and Calculation of an Energy-saving Plant for Obtaining Water from Atmospheric Air

for an improved energy efficiency

Solids circulation in a recirculating fluidized bed under sticky conditions

Characteristics of Air Flow through Windows Heiselberg, Per Kvols; Dam, Henrik; Sørensen, Lars C. ; Nielsen, Peter Vilhelm; Svidt, Kjeld

A Case Study: How the Maximum Spacing of Heat Detectors Should Be Determined

Technical Data Manual Model Nos. and pricing: see Price List. VITOCELL r 300-W, 300-V CAUTION. Vitocell 300-W, EVIA

A New Type of Dehumidifier for Enclosed High-voltage Switchgear Cabinet

PR. Termodinamika 2 B # 4

Ultra Thin Heat Pipe and its Application

Concentration analysis of extinguishing agents and toxic gases in small cabin aircraft

Heat and Mass Transfer Drying Cotton in Drum Drier

PERFORMANCE EVALUATION OF HYBRID SOLAR AIR- WATER HEATER WITH VARIOUS INLET AIR TEMPERATURE DURING HEATING PROCESS

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Alternative technologies for refrigeration and air conditioning applications

Effect of Variable-Drainage Freeze-Thaw Tests on Post-Thaw Shear Strength

Shear Headed Anchors with Large Diameter and Deep Embedment in Concrete

PERFORMANCE STUDIES FOR AN EXPERIMENTAL SOLAR OPEN-CYCLE LIQUID DESICCANT AIR DEHUMIDIFICATION SYSTEM

Control Equipment PTC PTC. modulating wall thermostat. NEP04/

A CALCULATION METHOD OF FULLY DEVELOPED FIRE TEMPERATURE FOR MULTI-ROOM FIRE SPREAD SCENARIOS

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Design and Development of a Heat Pump Rough Rice Dryer: A Study of Energy and Quality

(Refer Slide Time: 00:00:40 min)

Application of Water Mist to Extinguish Large Oil Pool Fires for Industrial Oil Cooker Protection

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Essence. Fryer HD6180

ELECTRICAL CONTRACTOR REQUIREMENT ITEM CONNECTION IN PANEL CONNECTION IN DEVICE VOLTAGE AMPERAGE COMMENTS

ACTIVA Rooftop. YKN2open. SlYORK* ARC-ARG-ARH-ARD A complete range from 17 kw up to 40 kw. A R C 032 A B Nomenclature. Features

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Indiana Mechanical Code Edition Title 675 IAC

System Modeling of Gas Engine Driven Heat Pump

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Low GWP Refrigerants for Air Conditioning Applications

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Dynamic Simulation of Liquid Chillers

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Subwoofer OWNER'S MANUAL CO104D CO104S CO124S CO124D CO154S CO154D MODEL

Air Distribution Fan and Outside Air Damper Recycling Control (DIV)

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Sub-Critical Operation of the CO2 Expander/ Compressor

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

A COMPARISON OF FIELD AND LABORATORY MEASUREMENTS OF RESIDENTlAL REFRIGERATOR ENERGY USE

Study of R161 Refrigerant for Residential Airconditioning

The KEYMARK. Your key to the European market. Robert Biedermann/Shutterstock.com

Breathe Fresh & Clean Air

tc/ Tengine STARK SLE PREMIUM Technical Design-in Guide

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

SCREENING FOR IRON CHLOROSIS TOLERANCE OF IN VITRO PYRUS ROOTSTOCK GERMPLASM

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

SIMULTANEOUS HEAT AND MASS TRANSFER IN AGITATED DRY- ER

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

FIRE RESEARCH STATION

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Air-Cooled Heat Exchanger Performance for R410A

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Compressor Capacity Control: A New Direction

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Scroll Compressor for Mobile HVAC/R Application

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Simulation of the Working Process of an Oil Flooded Helical Screw Compressor with Liquid Refrigerant Injection

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Air-Conditioners SUZ- KA25, KA35, KA50, KA60, KA71VA

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Pressure Enthalpy Charts

RESEARCH. A comparison of three visual assessments for riparian and stream health

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Optimization of Compressors used in Air Conditioning Units

A Study on Compression Characteristic of Wet Vapor Refrigerant

Title: Measurement of dryness fraction by Separating Calorimeter,

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

WAVERLY LIBRARY CHARRETTE REPORT

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Modelling of Screw Compressor Capacity Control

Assessing Energy Efficiency of Compression Heat Pumps in Drying Processes when Zeotropic Hydrocarbon Mixtures are Used as Working Agents

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

AGRICULTURAL URBANISM

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

High Efficiency Heat Pump for Domestic Hot Water Generation

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

AIR CONDITIONER PERFORMANCE RATING

Transcription:

Purdue University Purdue e-pubs International Compressor Engineering Conferene Shool of Mehanial Engineering 1984 Analysis of a Refrigerant Compressor Load Stand Inorporating Hot Gas Bypass and a Single Full Condensation Heat Exhanger J. A. MGovern Follow this and additional works at: http://dos.lib.purdue.edu/ie MGovern, J. A., "Analysis of a Refrigerant Compressor Load Stand Inorporating Hot Gas Bypass and a Single Full Condensation Heat Exhanger" (1984). International Compressor Engineering Conferene. Paper 491. http://dos.lib.purdue.edu/ie/491 This doument has been made available through Purdue e-pubs, a servie of the Purdue University Libraries. Please ontat epubs@purdue.edu for additional information. Complete proeedings may be aquired in print and on CD-ROM diretly from the Ray W. Herrik Laboratories at https://engineering.purdue.edu/ Herrik/Events/orderlit.html

ANALYSIS OF A REFRIGERANT COMPRESSOR LOAD STAND INCORPORATING ROT GAS BYPASS AND A SINGLE FULL CONDENSATION HEAT EXCHANGER J.A. MGovern, Leturer Department of Mehanial and Manufaturing Engineering Trinity College Dublin, Ireland ABSTRACT A refrigerant ompressor load stand is desribed and a theoretial analysis of its operation is presented. The purpose of the load stand is to establish and maintain pre-determined values of the sution pressure, the disharge pressure and the sution superheat. These are ontrolled by means of throttle valves. The power of ompression is rejeted to ooling water in a full ondensation heat exhanger whih normally operates lose to ambient temperature. The refrigerant flow is divided and the smaller part, generally less than one third, passes through the heat exhanger, while the greater part bypasses it as vapour. The two streams are re-ombined by adiabati mixing. Brief details are given of suh a load stand whih has been built reently, together with initial operating experienes. INTRODUCTION A researh programme with the title 'apaity Control of Reiproating Piston ompressors for Heat Pump or Refrigeration Appliations by Speed Variation' has been underway at Trinity College sine the Summer of 1983. The purpose of this work is to study the performane of reiproating ompressors when operated at different shaft speeds. As the programme will involve a great deal of performane testing of ompressors over a wide operating range of eah of four main parameters, the initial phase involves the onstrution and development of a suitable load stand. The four main parameters to be ontrolled are' mean sution pressure mean disharge pressure sution superheat temperature ompressor shaft speed. The first three are parameters of the load stand, while the fourth diretly influenes its apaity. In ontrolled parameters measure the following: ompressor shaft speed ompressor shaft torque (reation torque) refrigerant mass flow rate addition to the it is intended to (by means of an orifie plate) disharge vapour temperature. It is also pressure-volume measurements for onditions. intended to obtain diagrams and valve lift a full range of operating A load stand is proposed in whih the three main yle parameters are ontrolled by means of throttle valves and in whih part of the refrigerant is fully ondensed to the liquid state. Suh a system offers several potential advantages. As some exess liquid is always present it is not neessary to vary the system harge when the operating onditions are hanged. If the temperature of the ondensing heat exhanger is maintained onstant its thermal inertia and that of its ontents should be of small onsequene and a rapid system response to hanges in the operating onditions should be possible, Automati ontrol of the throttle valves should be feasible. The load stand is a variation on those desribed in referenes (1) and (2). In some respets the proposed system is analogous to a hydrauli dynamometer used in engine testing. The heat equivalent of the shaft power is rejeted to the ooling water and the onversion from work to heat is by means of totally irreversible proesses of fluid frition. A number of subroutines have for the analyses subroutines listed used for the alulations. omputer programs and been written in FORTRAN whih follow. The in referene (3) were refrigerant property 468

THERMODYNAMIC PROCESSES A iruit diagram to implement the basi proesses of the load stand is shown in Fig. 1. It is assumed that ondensation to the saturated liquid state ours in the heat exhanger and that the saturation pressure an be maintained onstant. The sution and disharge pressures of the ompressor are established with respet to the heat exhanger pressure by the throttle valves D and A. By some, as yet unspeified means, part of the total refrigerant flow leaving valve A is aused to pass through the heat exhanger, while the balane is bypassed to valve D. A 3 2...--w-...------, D ' ' (..'~-- 4 adiabati mixing Figure 1. Load stand basi iruit By varying the proportion of refrigerant whih is bypassed the sution superheat may be ontrolled. The idealised thermodynami proesses are shown on a P-h diagram in Fig. 2. By applying the Steady Flow Energy Equation the flow rate of refrigerant through the heat exhanger an be expressed as a proportion of the total as followsb hi - h" 1 - (1) Table 1 is a set of results of this alulation for a wide range of operating onditions for refrigerant 12 when the saturation temperature in the heat exhanger is 20 deg. C. Similar tables have been produed for other values of the heat exhanger operating temperature. For example, at a saturation temperature of 30 deg. C the proportions of flow rate whih pass through the heat exhanger are higher by from 5% to 7%, depending on the pressure and superheat onditions. The main onlusion from Table 1 is that it is possible, in priniple, to produe any operating ondition of interest by varying the relative amounts of refrigerant whih are ondensed and bypassed. There are pratial diffiulties in implementing the yle as desribed thus far. There will be a pressure fall, however small, in any real heat exhanger and so a orresponding pressure fall will be required in the bypass line. These pressure losses will not upset the operation of the yle. A means of proportioning the flow is also neessary. This an be done by introduing throttle valves B and C as shown in Fig. 3. A 3 2.,.----4,..._------, e. al5 ~u Figure 2. Idealised thermodynami proesses h 2 0 6 B 7--' 5 I ',. Figure 3. Ciruit inluding bypass and liquid line throttle valves The effet these valves have on the thermodynami yle is shown on a P-h diagram in Fig. 4. The inlusion of these extra throttle valves does not alter the values presented in Table 1 for the proportion of the refrigerant flow whih passes through the heat exhanger. The pressure at whih adiabati mixing of the ondensed Iiquid and bypassed vapour ours may lie at any level between that of the 469

heat exhanger and that at sution, depending on the settings of 'valves B, C and D. ~is phx pmix- Ps" Figure 4. inluding throttling. Thermodynami liquid line The Ideal Load Stand and Compressor 2 A 3 B 6 h proesses, and bypass For the purposes of designing or sizing a load stand an ideal ompressor whih an be desribed in terms of its displaement rate and learane ratio is a suitable model. The volumetri effiieny of suh a ompressor is given by '1 ( 2) By using this equation in onjuntion with the displaement rate and the thermodynami relationships for the yle, the ideal mass flow rate, the proportions of refrigerant ondensed and bypassed, and the rate of heat rejetion in the heat exhanger an be alulated for any ombination of operating onditions. The results of suh alulations, assuming a displaement rate of 1 litre/se., a learane ratio of 3% and a heat exhanger saturation temperature of 20 deg. C are given in Tables 2 and 3. The values of heat rejetion rate, given in Table 3, apply regardless of the heat exhanger operating temperature. These figures an be used in seleting a suitable heat exhanger for the load stand. Effetive Valve Flow Areas The value hosen for the mixing pressure is a matter of ontrol strategy and, when this has been deided upon, the required flow areas for the four throttle valves an be alulated. The valves are modeled as orifies having a oeffiient of disharge of 1 and an thus be fully desribed by an effetive flow area. For valve, whih the refrigerant enters as a liquid, inompressible flow is assumed and the effetive flow area is given by my;-;;; ( 3) A.~ For valves A, B AND D the flow is ompressible and, depending on the pressure ratio in eah ase, may be hoked. In the alulations either the atual or the riti~l pressure ratio, whihever is the greater, is used. For the purposes of alulating the required orifie area isentropi flow is assumed, although, for the throttling proess as a whole, enthalpy is the property whih remains unhanged. The isentropi proess is modeled as being polytropi, i.e. one for whih onst. ( 4) While this assumption may be onsidered reasonably valid for refrigerant vapour, even within the saturation region, the ideal gas equation should not be assumed to apply, espeially when the refrigerant is saturated for part of the proess. The equation for the required flow area should therefore be in terms of the properties pressure and volume, rather than, for example, pressure and temperature. The following equation is used: A m [Pu ~ (rpfi - r~)~-.s ( 5) Vu n-1 J It should be noted that for some sution onditions point 7 in Fig. 4 lies within the saturation region on the P-h diagram. The speifi volume at this point an be found sine the speifi enthalpy is the same as at point l. Values of the required effetive flow areas for the valves are presented over a range of operating onditions in Table 4. It has been assumed in the table that one fifth of the pressure fall from the heat exhanger saturation pressure to the sution pressure ours aross the bypass and liquid line throttle valves B and C. It an be noted that any hange in the operating onditions requires a hange in the areas of all four valves. The required flow areas for valve, the liquid line throttle valve, are very muh smaller than for the other valves whih throttle vapour. HEAT EXCHANGER SELECTION, CHARACTERISTICS AND ANALYSIS The displaement rate of the ompressor to be tested was about 3.7 litres/seond and, using data from Table 3, the required maximum heat rejetion rate was found to be about?.2 kw, whih also oinided with the 470

motor rating. A water ooled ondenser heat exhanger with some apaity to hold exess liquid was desired and a shell and tube type was seleted. Either a single pass or a two pass water piping arrangement was possible. The single pass arrangement was hosen in order to maximise the flow rate and to minimise the temperature hange of the water in passing through the heat exhanger. Heat Transfer Rate The manufaturer presented the heat transfer rate as a funtion of the water flow rate and the temperature differene defined in terms of the saturation temperature and the water inlet temperature. AT ( 6) Heat transfer orrelations suggest that the water side heat transfer oeffiient depends on the flow rate, raised to the power of 0.8 approximately. Hene, the following expression was derived for the rate of heat transfer Q [ a v 8 l 1 + b v ~ OT (7) By regression analysis of points taken from the manufaturer's graphs the following oeffiients were obtainedr a b 2. 009. l. 933 (8) ( 9) A graph of this expression is given in Fig. 5. Log Mean Temperature Differene The onstants given in equations 8 and 9 were re-evaluated for the ase where the log mean temperature differene is used in equation 7. The values are a b 3. 4 71 3.735 (11) ( 12) A similar fit to that shown in Fig. 5 was obtained using these onstants. RW/K.7.6 1-.4 '<I 3 I G.2.I 0 0. '.2..3 WATER f"low RAT Figure 5. Heat transfer rate temperature differene as a water flow rate. Water Pressure Loss.s. 6 1/s per degree funtion of It was found that the manufaturer's data ould be represented reasonably losely by the following expression: Care should be taken in applying equations 6 to 9 for flow rates lower than those quoted in the manufaturer's data (0.19 litres/se.), as no impliit aount is taken of the water exit temperature. 6P where and k = j 1.151 X 10 5 1. 833 (13) (14) (15) The temperature differenes were onverted to log mean values based on the refrigerant saturation temperature and the water inlet and outlet temperatures using the following equation (Ts - T,.,.,l - ('I's - Twi) In (~: - ~:~) ( 10) WATER CIRCUIT ANALYSIS The maximum available water supply rate was about 4 litres per minute and the maximum head between a onstant head tank installed in the laboratory and the drain was about 1.7 metres. The water iruit whih was adopted is shown diagramatially in Figure 6. Valve E ontrols the rate of water flow to drain and hene the saturation temperature within the heat exhanger. 471

1 I. 7tn shut-off valves were used for throttling. Valves A, B and D were three quarter inh flare and valve C was quarter inh flare. It was found diffiult to ontrol the sution superheat temperature and this was attributed to the insensitivity of valve. This was replaed with a one eight inh needle valve and it was then found possible to ahieve and maintain desired operating onditions. However, the operating experiene to date is very limited. Figure 7 is a photograph of the load stand. A sight glass loated upstream of the liquid line throttle valve, C, is used to ensure that liquid is present. CONCLUSIONS PUMP Figure 6. Heat exhanger water iruit The equation representing the pressure loss through the heat exhanger has already been mentioned, The Dary equation was used to determine pressure losses in the pipes and approximate empirial loss oeffiients were used to take aount of the bends and tees. A standard domesti heating irulation pump, having three speeds, was used and its pressure versus flow rate harateristis were obtained from the suppliers. The maximum flow rate through the heat exhanger will our when there is no flow to drain and is limited by the available head between points X and Y in Figure 6. This flow rate was alulated to be about 20 litres per minute. At its lowest speed the pump would produe a flow rate of about 16 litres per minute and at the seond speed a flow rate of about 21 litres per minute. Thus the alulations indiated that a flow to drain was possible at the lowest pump speed, or at a higher speed with throttle valve F partially losed. The onlusion from the analysis was that a onsiderable inrease in the flow rate through the ondenser ould be produed by reirulation, but, that this was not essential to the operation of the system. One effet of a high reirulation rate is that subooling of the refrigerant in the heat exhanger is minimised. A straightforward analysis of the load stand has been presented and the results indiate that it is feasible in priniple. From the analysis and the limited operating experiene to date it is felt that purpose designed throttle valves of higher sensitivity will be required. NOTATION A a,b h j,k n p ~p Q r., rp T v 4T v '1 "' Subsripts effetive flow area of speified valve, sq. m onstants speifi enthalpy of refrigerant at speified state, J/kg onstants in pressure loss equation mass flow rate of refrigerant, kg/s polytropi index for a reversible adiabati proess of the refrigerant pressure, N/(sq. m) pressure differene, N/(sq. m) rate of heat transfer, kw learane ratio (= ompressor learane volume divided by ompressor swept volume) pressure ratio or ritial pressure ratio for a valve temperature, K temperature differene, K volume flow rate of water, litres per seond speifi volume at speified state, (u. ml/kg ompressor volumetri effiieny THE LOAD STAND AS BUILT A load stand has been built with the analyses presented. operated diaphragm-sealed in aordane Standard hand refrigeration dis hx mix s sue disharge heat exhanger mixing refrigerant saturation property sution 472

tot u wi wo 1-7 REFERENCES total upstream property water inlet property water outlet property refrigerant equilibrium states (Fig. 4) 1. sodel, w., "Introdution to Computer Simulation of Positive Displaement Compressors", Purdue University, 1972. 2. Marriott, L.W.; F.R. Lady; L.L. Evans, "Aelerated Test for Rating Positive Displaement Compressors Using Computer Control", Proeedings 6f the 1974 Purdue Compressor Tehnology Conferene. 3. Kartsounes, G.T.; R.A. Erth, (1971), "omputer Calulation of the Thermodynami Properties of Refrigerants 12, 22 and 502", ASHRAE Transations, vol. 77, part II, pages 88-l03. Figure 7. The refrigerant ompressor load stand 473

HEAT EXCHANGER MASS FLOW RATE AS A PROPORTION OF THE TOTAL REFRIGERANT NO.: 12 COMPRESSOR MASS FLOW RATE HEAT EXCHANGER OPERATING TEMP., DEG. C: 20.0 SUCTION SUPERHEAT, K: o.o DEG. 20.0 30.0 40.0 50.0 60.0-50.0. 2972.3204.3410.3594.3758-30.0.2017.2281.2517.2724.2907-10.0.1145.1437.1695.1923.2127 10.0.0363.0677.0956.1204.1424.3904.3071.2308.1620 ------------------------------------------------------------------------- SUCTION SUPERHEAT, K: 10.0 DEG. 20.0 30.0 40.0 50.0 60.0-50.0.2967.3200.3406.3590.3757.3906-30.0.2017.2281.2515.2723.2909.3076-10.0.1148.1439.1696.1929.2134.2318 10.0.0361.0680.0961.1211.1437.1635 SUCTION SUPERHEAT, K: 20.0 DEG. 20.0 30.0 40.0 50.0 60.0-5o.o.2959.3195.3402.3587.3753.3902-30.0.2013.2277.2512.2720.2910.3079-10.0.1146.1439.1699.1930.2137.2322 10.0.0362.0681.0963.1215.1439.1640 -------------------------------~----------------------------------------- DEG. 20.0 30.0 40.0 50.0 60.0-50.0.2954.3187.3394.3579.3745.3896-30.0.2007.2274.2509.2719.2908.3077-10.0.1.143.1436.1696.1931.2139.2327 10.0.0361.0680.0963.1215.1440.1646 Table 1 474

HEAT EXCHANGER Jl'iASS FLOW RA'I'E IN KG/S/1000 FOR AN IDEAL COMPRESSOR REFRIGERANT NO.: 12 OF GIVEN DISPLACEMENT RATE AND CLEARANCE RATIO HEAT EXCHANGER OPERATING TEMP., DEG. C: 20.0 COMPRESSOR DISPLACEMENT RATE, LITRES PER SECOND: 1.00 CLEARANCE RATIO:.030 SUC'l'ION SUPERHEAT, K: 0.0 SUCTION SAT. TEMP. f'isf'<ll\fgf' SPTVRrTI0N TEMP., f:p('. DEG. 20.0 30.0 40.0 50.0 60.C -50.0.540].5002.4259.3128.1559-30.0 1.1192 1. 2036 1.2452 1.2374 1.1788-10.0 1. 4308 1.7546 2.0107 2.2008 2.3243 10.0.8781 l. 6188 2.2537 2.7850 3.2183.oooo 1.0635 2.3786 3.5558 8UC'TI0N SUPERHF:AT, K; 10.0 SUCTION SAT. 'I'El-lP. Dl f.c'l-jllrgf: SP':'ORM'H!N TgMP. L'Jo:G. DEG. 20.0 30.0 40.0 50.0 60.0-50.0.5144.4769. 4071.3012.1554-30,0 1.0683 1.1498 1.1893 1.1849 1.1335-10.0 1.3678 1.6763 1. 9209 2.1083 2.2313 10.0.8316 1. 5455 2.1538 2.6652 3.0924.0000 1. 0306 2.2907 3.4205 SUC'l'ION SUPERHEAT, K: 20,0 SUC'l'ION Sl).T. TEMP. DISCHARGE SATURATION TEMP., DEG. DEG. 20.0 30.0 40.0. 50.0 60.0 -so.o.4903. 4556..3898.2903.1531-30.0 I. 0209 1.0995 1.1383 1.1359 1. 0911-10.0 1.3066 l. 6043 l. 8418 2.0209 2.1420 10.0.7948 ]. 4780 2. 06]3 2.5532 2,9593.oooo.9977 2.2038 3.2828 SUCTION SAT. TEMP. DISCHARGE SATURATION TEMP., DEG. DEG. 20.0 30.0 40.0 50.0 60.0-50.0.4689.4355.3732.2791.1497-30.0.9764 1. 0539 ]. 0923 1.0918 1.0502-10.0 l. 2504 1.5361 l. 7645 1.9415 2.0611 10.0.7594 1.4139 ]. 9736 2.4465 2.8381.oooo.9644 2.1254 3. 1 611 Table 2 475

HEAT EXCHANGER BEAT TRANSFER RATE IN KW FOR AN IDEAL COMPRESSOR OF GIVEN DISPLACEMENT RATE AND CLEARANCE RATIO REFRIGERANT NO.: 12 COMPRESSOR DISPLACEMENT RATE, LITRES PER SECOND: 1.00 CLEARANCE RATIO:.030 SUCTION SUPERHEAT, K: o.o DEG. 20.0 30.0 40.0 50.0 60.0-50.0.0846.0810 0711.0537.0275.oooo -30.0.]673.1861.1986.2029.1983.1831-10.0.2073.2629.3106.3496.3788.3968 10.0.1247.2376. 3411.4333.5136.5807 SUCTION SUPERHEAT, K: 10.0 DEG. 20.0 30.0 40.0 50.0 60,0-50.0.0844.0810. 0713.0543.0287.0000-30.0.1674.1863.1988.2037.2000.1862-10.0.2079.2634. 3112.351.4.3817.4012 10.0.1239.2381.3422.4355.5187.5872 SUCTION SUPERHEAT, K: 20.0 DEG. 20.0 30.0 40.0 50.0 60.0-50.0.0842.0810 0715.0547.0296.0000-30.0.1674.1864.1991.2043.2015.1888-10.0.2078.2639.3124,3526.3836.4041 10.0.1240.2384.3429.4369.5197,5903 SUCTION SAT. TE!YIP. DISCHARGE SATURATION TEMP., DEG. DEG. 20.0 30.0 40.0 50.0 60,0-50.0.0842.0809. 0715.0550.0303.0000-30.0.1672.1867.1996.2053.2027.1907-10.0.2077.2639.3126.3539.3857.4074 10.0.1237.2382.3429.4373.5207.5943 Table 3 476

EFFECTIVE FLOW AREAS OF VALVES ON THE TEST S'I'AND FOR AN IDEAL COMPRESSOR OF GIVEN DISPLACEMENT RATE AND CLEARANCE RATIO **** UNITS SQUARE MM **** SYMBOLS C - CHOKED FLOW, I - IMPOSSIBLE OPERATING CONDITION, 0 - VALVE FULLY OPEN Z - ZERO COMPRESSOR FLOW IT IS ASSUMED THAT THE ADIABATIC MIXING PRESSURE (=P7=P6=P5) LIES BETWEEN THE HEAT EXCHANGER PRESSURE (=P3=P4) AND THE SUCTION PRESSURE (=P1) AND THAT P7 = P3- (P3-P1)*(.20) REFRIGERANT NO.: 12 ADIABATIC INDEX (BASED ON P AND V): 1.180 HEAT EXCHANGER OPERATING TEMP. DEG. C: 20.0 COMPRESSOR DISPLACEMENT RATE, iitres PER SECOND: 1.00 CLEARANCE RATIO:.030 *** VALVE A *** SUCTION SUPERHEAT, K: 0.0 SUCTION SAT. TEMP. DISCHARGE SAT. TEMP., DEG. DEG. 20.0 30.0 40.0 50.0 60.0-30.0 99.999 0 1. 677 1.102 0.798 0.568 0.391-10.0 99.999 0 3.815 2.597 1.971 1. 501 1.139 10.0 99.999 0 7.386 5.094 3.933 3.060 2.390 SUCTION SAT. TEMP. DISCHARGE SAT. TEMP., DEG. DEG. 20.0 30.0 40.0 50.0 60.0-30.0 99.999 0 1. 581 1. 044 0.761 0.549 0.386-10.0 99.999 0 3.592 2.455 1. 874 l. 438 1.104 10.0 99.999 0 6.918 4.789 3.716 2.910 2.293 SUCTION SUPERHEAT, K: 0.0 *** VALVE B *** SUCTION SAT. TEMP. DISCHARGE SAT. TEMP., DEG. C DEG. C 20.0 30.0 40.0 50.0 60.0-30.0 2.082 1.949 1.799 1.630 1.435 1.212-10.0 5.741 5.525 5.290 5.033 4.746 4.422 10.0 17.705 17.231 16.733 16.205 15.636 15.012 ------~----------~~--------------------~--------------------------------------------- SUCTION SAT. TEMP. DEG. C -30.0-10.0 10.0 SUCTION SUPERHEAT, SUCTION SAT. TEMP. DEG. -30.0-10.0 10.0 SUCTION SUPERHEAT, SUCTION SAT. TEMP. DEG. -30.0-10.0 10.0 20.0 l. 958 5.391 16.539 K: 0.0 20.0 0.071 0.105 0.100 K: 30.0 20.0 0.062 0.092 0.087 SUCTION SUPERHEAT, K: 0.0 DISCHARGE SAT. TEMP., 30.0 40.0 1.832 1.693 5.183 4.961 16.069 15.588 *** VALVE C *** DISCHARGE SAT. TEMP., 30.0 40.0 0.076 0.079 0.129 0.148 0.185 0.258 DISCHARGE SAT. TEMP., 30.0 40.0 0.067 0.069 0.113 0.130 0.162 0.226 *** VALVE D *** DEG. C DEG. DEG. 50.0 1.538 4. 721 15.089 50.0 0.079 0.162 0.318 50.0 0.069 0.143 0.280 60.0 1. 364 4.461 14.563 60.0 0.075 0.171 0.368 60.0 0.067 0.151 0.324 1.168 4.175 13.999 0.068 0.175 0.406 0.061 0.156 0. 361. SUCTION SAT. TEMP. DISCHARGE SAT. TEMP., DEG. C DEG. C 20.0 30.0 40.0 50.0 60.0-30.0 2.234 2.125 1.991 1.829 1.632 1.394-10.0 4.945 4.834 4.697 4.530 4.326 4.079 10.0 10.467 10.342 10.188 10.000 9.770 9.489 --~~------~-----------~-------~~-----------~-------------~----------~---------------- SUCTION SAT. TEMP. DEG. C -30.0-10.0 10.0 DISCHARGE SAT. TEMP., DEG. C 20.0 30.0 40.0 50.0 2.089 1.989 1.869 1.724 4.633 4.531 4.408 4.260 9.773 9.659 9.520 9.353 60.0 1. 551 4.082 9.153 1.345 3.870 8.915 Table 4 477