Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Similar documents
ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

R07. Answer any FIVE Questions All Questions carry equal marks *****

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

Mechanical Engineering Laboratory

Chapter 8 Balances on Nonreactive Processes PSYCHROMETRIC CHART

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

REFRIGERATION AND AIR CONDITIONING

2. CURRICULUM. Sl. No.

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Chapter 14, Problem 27.

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study

Department of Mechanical Engineering ME 322 Mechanical Engineering Thermodynamics

: REFRIGERATION & AIR CONDITIONING COURSE CODE : 6023 COURSE CATEGORY : A PERIODS/ WEEK : 6 PERIODS/ SEMESTER : 90 CREDIT : 6 TIME SCHEDULE

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

A/C Cooling Load calculation and measurement

Air Conditioning Clinic

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Evaporative Cooling. HEVAC Association. Humidity Group. an alternative and supplement to mechanical cooling

Desiccant Dehumidification in Air Conditioning for a Large Commercial Building

MODULE 6 HUMIDIFICATION AND AIR CONDITIONING

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Pharmaceutical Facility Design

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Prepared by: (415) With. High. Prepared for: Final Report June 27, Contributors: Tom. Me!

Basic Principals of Air conditioning By Dr. Esam Mejbil Abed

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

Designing Energy Efficient Outdoor Air Systems

INSTITUTE OF AERONAUTICAL ENGINEERING

PRINCIPLES OF HEATING, VENTILATION AND AIR CONDITIONING with Worked Examples

Capt. Tim s s Duct Design Mythbusters. The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!

Redesign of Bennett Hall HVAC System

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

MECHANICAL SERVICES 101. Ian White

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

When Duct Sealing Kills HVAC Equipment and Efficiency

TESTS OF ADSIL COATING

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

Armstrong Cool-Fog Systems

EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING


Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK

Humidity Control & Psychrometrics

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

SBS5311 HVACR II Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

HVAC (Heating, Ventilating, and Air Conditioning)

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Performance Rating of Commercial and Industrial Humidifiers

SECTION THIRTEEN HEATING, VENTILATION, AND AIR CONDITIONING

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

CE311 Fall 2016 Mid-Term Exam 1

Heat Pump Training Course 128 hours, 128 NATE CEHs, 12.8 CEUs Volume Pages, Volume Pages

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

MECCI Engineers. Institute of Engineering Design & Research

ω = (1) Kirby S. Chapman Ph.D.

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

Research and Development of Residential Heat Pump

Adding More Fan Power Can Be a Good Thing

Performance Optimization of the Evaporative Condenser Design

MEC E 466 Building Systems Design

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.

Duct Design and Installation

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

Preparing the Next Generation of Building Technicians

Use this Construction/HVAC Glossary to answer the questions below.

Short Questions with Answers APPLIED THERMODYNAMICS(5 TH MECHANICAL) Chapter No-1

LISTOF EXPERIMENTS. S. No. NAME OF EXPERIMENTS PAGE No.

Optimizing Electric Humidifier Operation with an Air Side Economizer

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Heating Ventilation and Air Conditioning Laboratory

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler

Problems Air and Water Distribution Systems

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

CE311 Fall 2016 Mid-Term Exam 1

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Bharathidasan University (Accredited by NAAC at A level) Tiruchirappalli

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Thermodynamics: Homework A Set 7 Jennifer West (2004)

Experienced Worker Assessment Blueprint HVAC - Heating, Ventilation and Air Conditioning

Saving Energy With Evaporative Media

Transcription:

Session 2633 Development of a Psychrometric Test Chamber Michael J. Swedish Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Acknowledgments The design of the Psychrometric Test Chamber was done as a Senior Design Project by undergraduate students Brent Losey and Joseph Stellbrink, under the supervision of Professor Swedish. Funds for the construction of the Psychrometric Test Chamber were provided through a grant from the A. O. Smith Foundation. I. Introduction The purpose of this paper is two-fold: - To illustrate the incorporation of the capstone design experience into the development of laboratory equipment. - To describe the capabilities and operation of the psychrometric test chamber. II. Engineering Design and the Energy Laboratory at the Milwaukee School of Engineering The Energy Laboratory at MSOE serves undergraduate students in the Mechanical Engineering, Mechanical Engineering Technology, and Architectural Engineering programs. The Lab is a collaborative arrangement between MSOE and Johnson Controls, Inc., which operates a large HVAC system for training purposes. The philosophy behind the continuing development of the Energy Lab is to allow the undergraduate students themselves to design and develop the equipment wherever possible. In this way, the Lab better fulfills its potential as a teaching facility. The primary vehicle for this work is the senior capstone design project. Several pieces of equipment have been designed in this way: a 14 ft/sec wind tunnel, a smoke tunnel for flow visualization, and most recently the psychrometric test chamber. A team of two students was given the chamber design project. The stated purpose for the chamber was to demonstrate the basic psychrometric processes of heating, cooling, humidification, dehumidification, and mixing. A number of criteria were defined, and a cost target specified. The design report was used as the basis for construction of the chamber, and is on file at the school. Page 4.191.1

III. System Description A line drawing of the unit has been included as Figure 1. Figure 1. Psychrometric Chamber Layout Psychrometric State Points * Flow Rate Measurement Points : Water Supply Diffuser Strip Heaters Evaporator Coil Air Atomizing Spray Nozzles Outside of Chamber Fan Return Damper Psychrometric Chamber (8 x 4 x 9 ) 1 The apparatus has been designed to fit onto two 8-foot by 4-foot pallets so that it can be relocated within the lab, if necessary. The first pallet holds the chamber itself. The chamber is an 8-foot by 4-foot by 9-foot high room built to residential construction standards. The second pallet holds the entire HVAC system for the chamber. Filter, fan, evaporator coil, strip heaters, and sprayers are connected through ductwork to the chamber. Much of the front-facing wall of the ductwork has been constructed of plexiglas, so that the coil, heaters, and sprayers can be viewed from the Lab. IV. Components and Instrumentation Fan: The fan is an in-line centrifugal unit. A maximum air flow of 4 cfm (at about.3 wg of static pressure head) and minimum of 18 cfm have been achieved. Cooling unit: The size of the cooling unit was set at 1 ton capacity, because this was the smallest size split coil unit that was commercialy available. It is a standard vapor-compression refrigeration system, with Refrigerant-22 as the working fluid. Page 4.191.2

Heaters: Two commercially available electric resistance finned strip heaters are used. They were sized for a maximum power input of 12, BTU/hr, to match the size of the cooling unit. The power supplied to the heaters can be varied from zero to this maximum value. Sprayers: Humidification is accomplished with the use of 3 air-atomizing sprayers. Water is gravity-fed from a tank mounted on the chamber; compressed air is supplied at psig. Median droplet size is about microns diameter. Instrumentation: Dry-bulb temperature and relative humidity are measured at five locations within the system, and one location in the Lab. These locations are shown on Figure 1. Also shown in the Figure are two locations where flow velocity can be measured with a hot-wire anemometer, for determination of flow rate. Refrigeration system temperatures and pressures are measured, along with compressor power. Power supplied to the strip heaters is measured. Sprayer water flow rate can be estimated from air pressure and water static head. V. Unit Operation and Capability Proper damper adjustment allows for once-through flow through the chamber, complete recirculation, or any percent range of "ventilation" air. The following operations will be described separately. It is important to bear in mind that any combination of processes can also be used. Dry-bulb temperatures are repeatable to ± 1 o F, and relative humidities to ± 2%. Cooling and condensation: In complete recirculation mode, the cooling unit can be operated to obtain the change in psychrometric state of the air at any location over time. Beginning with relatively dry air, a characteristic constant-specific-humidity line should be traced on the psychrometric chart. This corresponds to cooling only. Page 4.191.3

Figure 2 shows an example of data obtained with the unit, starting with a dry-bulb temperature of 9 o F. The rise in specific humidity seen in the early stages of the cooling process is a characteristic of the unit, and calls for further investigation. Cooling Only Specific Humidity, gr/lbm 35 3 25 15 1 5 3 4 5 6 7 8 9 Figure 2. Beginning with humid air (obtained by operating the sprayers for a period of time), a typical cooling and condensation curve should be traced. That is, if the dry-bulb temperature is dropped low enough, water vapor should begin to condense out of the air mixture. Figure 3 shows data obtained with a starting dry-bulb temperature of 69 o F and 5% relative humidity. Cooling and Condensation 1 1 Specific Humidity 8 6 4 3 4 5 6 7 saturation line Figure 3. In complete recirculation, a minimum air temperature of 32 o F has been measured at the evaporator coil, corresponding to a chamber temperature of 5 o F. In the once-through mode, steady-state conditions across the coil, and in the chamber itself, have been observed. With minimal thermal load in the chamber, a steady-state temperature of 51 o F has been achieved there. This corresponds to a coil T of about 27 o F. Page 4.191.4

Heating: With a range of heating levels from to 12, BTU/hr available, the heating process can be examined in detail. Figure 4 shows data for complete recirculation, full heater power, with a starting dry-bulb temperature of 77 o F. Heating Only Specific Humidity, gr/lbm 35 3 25 15 1 5 74 76 78 8 82 84 Figure 4. For complete recirculation, duct air temperatures in excess of 14 o F can easily be achieved. A steady-state temperature of 11 o F has been achieved in the chamber. In once-through mode, a steady-state temperature of 92 o F has been achieved, at a minimum relative humidity of 3%. Humidification (Evaporative Cooling): With only the sprayers operating, in complete recirculation mode, the characteristic evaporative cooling process can be shown on the psychrometric chart by plotting the psychrometric state over time as measured at the point in the duct after the sprayers. If the humidification is adiabatic, the process should follow a constant enthalpy line on the psychrometric chart. Figure 5 shows an example of humidification data, starting at a dry-bulb temperature of 99 o F. A constant enthalpy line is included for comparison. In this case, the rise in enthalpy in the early stages of the process appears to be a characteristic of the unit. Humidification Constant h line shown for comparison Specific Humidity, gr/lbm 1 1 8 6 4 7 75 8 85 9 95 1 Page 4.191.5

Figure 5. From normal room conditions, in complete recirculation mode, it takes about 5 minutes to saturate the air. At this point, the formation of fog inside the duct at the sprayers can be clearly observed. Operation of the sprayers together with the heaters in complete recirculation mode should produce the most extreme condition of temperature and humidity in the chamber. In tests of the unit, a psychrometric state of 97 o F dry-bulb and 95% relative humidity has been achieved. Chamber Loading: The chamber can be set up to place a load on the cooling unit in a number of ways. A high intensity light bulb of known Wattage can be used. An electric resistance space heater can be placed in the chamber, and its power measured. A person can also be placed in the chamber, at rest or at various activity levels, to look at the effect of human loading on both sensible and latent energy. Energy Balances: With air flow rates known, energy balances can be performed for the cooling coil and heaters. In fact, energy balances can be performed between any two points in the air flow. For example, energy losses or gains through the uninsulated ductwork can be easily established. Chamber Environmental Control: By proper adjustment of dampers, fan speed, sprayers, heaters, and cooling unit, a wide range of psychrometric environments can be created and maintained in the chamber. Conditions of 97 o F dry bulb and 95% relative humidity, 97 o F dry bulb and 2% relative humidity, 4 o F dry bulb and 1% relative humidity, and 48 o F dry bulb and 5% relative humidity have been demonstrated. The chamber has been used to create high-humidity conditions for testing of the hygroscopic characteristics of hydraulic fluids, and used to mimic a Florida climate for small engine testing. Demonstrations: Because of the unique design of the unit, certain psychrometric phenomena can be demonstrated. Dehumidification can be shown by passing moist air over the cooling coil and observing droplet formation on the coil surfaces. Coil freeze-up can be shown by passing cold moist air over the coil, and observing the formation of frost. Mixture saturation can be manipulated in the sprayer section by heating or cooling the very moist air and observing the formation and disappearance of fog. VI. Conclusion Page 4.191.6

The Psychrometric Chamber as a Teaching Tool The psychrometric chamber is proving to be a reliable and versatile device for demonstration and experimentation in the fields of thermodynamics, heat transfer, and HVAC processes and design. Its versatility makes it an ideal teaching tool. The data already gathered make clear that there is much to learn about the functioning of this machine. The questions that have arisen from these first experiments will be explored in the future by students, as a part of their laboratory exposure. Development of the psychrometric test chamber will be an ongoing process. Bibliography Losey, B. and Stellbrink, J., Psychrometric Chamber Design, Design Project Report for Milwaukee School of Engineering, 1994. Moran, M. and Shapiro, H., Fundamentals of Engineering Thermodynamics, 3 rd Edition, Wiley, 1995. Pita, E., Air Conditioning Principles and Systems, 3 rd Edition, Prentice-Hall, 1998. MICHAEL SWEDISH Michael Swedish is Associate Professor of Mechanical Engineering at the Milwaukee School of Engineering. He also serves as Chair of the Energy Committee, and has responsibility for the Energy Laboratory at the university. He received B.S. and M.S. degrees from Marquette University in Milwaukee, WI, and is a registered Professional Engineer in Wisconsin. He has industrial experience in the field of electric power generation, and teaches in the thermal science and fluid mechanics areas. Page 4.191.7