SECTION (15820) - AIR DUCT ACCESSORIES

Similar documents
SECTION AIR DUCT ACCESSORIES

AIR DUCT ACCESSORIES

SECTION DUCTWORK

D. Fabrication: Steel or Aluminum with baked enamel off-white finish. B. Type: Square and rectangular, adjustable pattern, multi-louvered diffuser.

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

SECTION (15833) - HVAC POWER VENTILATORS

SECTION DUCTWORK

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SECTION (15900) - INSTRUMENTATION AND CONTROL FOR HVAC

SECTION AIR OUTLETS AND INLETS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

SECTION AIR HANDLING UNIT

SECTION (16140) - WIRING DEVICES

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

DUCT SYSTEMS CHAPTER 6

SAFETY AND INSTALLATION MANUAL MODEL 8100

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6

SECTION AIR COILS

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD

Contents INDEX. TDM Series Indirect Fired Heaters

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

FIRE & SMOKE DAMPERS. Meeting tomorrow's requirements for fire and smoke protection today.

A. This Section includes air-handling units with coils for indoor installations.

SECTION (15530) - REFRIGERANT PIPING

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

SECTION CONVECTION HEATING AND COOLING UNITS

Gravity and Pneumatic Waste and Linen Handling Systems NFPA 82 Inspection Form

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK

Smoke extraction duct of sheet steel

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

SECTION CONVECTION HEATING AND COOLING UNITS

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

FLANGED CORR/GUARD CORR/GUARD INSTALLATION INSTRUCTIONS

CHIMNEYS AND VENTS CHAPTER 8

Chilled Water DOAS Fan Powered Terminal Units

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

CHAPTER 8 CHIMNEYS AND VENTS

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

CHAPTER 8 CHIMNEYS AND VENTS

INSTALLATION INSTRUCTIONS

SECTION (15767) - UNIT HEATERS

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

Richmond Hill Primary Renovation SECTION STAGE CURTAINS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

Residential Fans & Air Purifiers

15900 HVAC INSTRUMENTATION AND CONTROLS

SECTION AIR COILS

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

SECTION ELECTRICAL IDENTIFICATION

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

VentZone Systems VentZone Zoned IAQ with Heat Recovery Kits

Life Safety Dampers Selection and Application Manual

REFLECTOR PANS FOR HINGED ELEMENTS CONNECTOR BLOCK KIT TRIM RINGS FOR ABOVE PANS CONNECTOR BLOCK RANGE CORD REFLECTOR PANS FOR PLUG-IN ELEMENTS

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

Part # Page Dampers Supported Directly From Structure 5. Dampers Supported From Ductwork Above 4

IMC Significant Changes Summary Tier I

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

A. Codes and Standards that are Standard at the University:

University of Delaware

Duct Leakage, Sealing & Testing

SECTION AIR DOORS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

HVAC Equipment Access Equipment Location

Linear Floor Heaters

Section (CSI ) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

VentZone Systems VentZone Zoned IAQ with Energy Recovery Kits

Installation Instructions for Heat Recovery Ventilators with 2 Speed RNC Electronics. RNC Series. Residential Heat Recovery Ventilators (HRV)

SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

Transcription:

PART 1 GENERAL 1.01 SUMMARY A. Section includes: SECTION 23 33 00 (15820) - AIR DUCT ACCESSORIES 1. Manual-Volume Dampers 2. Fire Dampers 3. Turning Vanes 4. Duct-Mounted Access Doors 5. Flexible Connectors 6. Flexible Ducts 7. Zone Control Exhaust Terminals 8. Accessories B. Related Sections: 1.02 REFERENCES 1. Section 08 31 00 (08310) - Access Doors and Panels: For wall- and ceiling-mounted access doors and panels. 2. Section 23 05 53 - Identification for HVAC Piping and Equipment. 3. Section 23 05 93 - Testing, Adjusting, and Balancing for HVAC. 4. Section 23 37 00 (15850) - Air Outlets and Inlets. 5. Section 25 51 00 Integrated Automation Control of Guestroom Equipment 6. Section 28 31 00 (13850) - Fire Alarm and Detection Systems: For duct-mounted fire and smoke detectors. A. North American Insulation Manufacturers Association (NAIMA) Publications: 1. AH124 "Fibrous Glass Duct Liner Standard." B. National Fire Protection Association (NFPA) Publications: 1. 90A Standard for the Installation of Air Conditioning and Ventilating Systems 2. 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems C. Sheet Metal and Air Conditioning Contractors' National Association (SMACNA) Publications: 1. Fire Damper and Heat Stop Guide for Air Handling Systems 2. HVAC Duct Construction Standards Metal and Flexible D. Underwriter's Laboratories, Inc. (UL) Standards: 1. 181 Standard for Factory-Made Air Ducts and Air Connectors 2. 181B Closure Systems for Use With Flexible Air Ducts and Air Connectors 3. 555 Fire Dampers 4. 555C Standard for Safety for Ceiling Dampers PAGE 1

1.03 QUALITY ASSURANCE A. NFPA Compliance: Comply with the following NFPA standards: 1. NFPA 90A, "Installation of Air Conditioning and Ventilating Systems." 2. NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems." B. Sheet Metal and Air Conditioning Contractors National Association, Inc. manuals (SMACNA) except where details or notes on drawings indicate otherwise. 1. HVAC Duct Construction Standards Metal and Flexible. 2. Fire Damper and Heat Stop Guide for Air Handling Systems. C. Underwriters Laboratories (UL) Standard for Safety UL 181, UL 555. 1.04 EXTRA MATERIALS A. Furnish extra materials described in Section 01 78 43 (01790) Spare Parts and Materials that match products installed, are packaged with protective covering for storage, and are identified with labels describing contents. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Approved Manufacturers: 1. Manual Volume Dampers. a. Ruskin Company (816-761-7476) b. Air Balance, Division of Mestek (419-865-5000) c. Prefco (Perfect Air Control, Inc.) (800-437-6653) 2. Fire Dampers. a. Ruskin Company (816-761-7476) b. Air Balance, Division of Mestek (419-865-5000) c. Prefco (Perfect Air Control, Inc.) (800-437-6653) 3. Ceiling Fire Dampers a. Ruskin Company (816-761-7476) b. Air Balance, Division of Mestek (419-865-5000) c. Prefco (Perfect Air Control, Inc.) (800-437-6653) 4. Flexible Connectors. a. Ventfabrics, Inc. (800-621-1207) b. Ward Industries, Inc. (630-595-7320) c. Vent Products Co. (800-368-8368) 5. Flexible Ducts a. Clevaflex. Ltd. (216-941-6505) b. Approved Substitution 6. Zone Control Exhaust Terminal REVISED: 05/01/13 PAGE 2 FILE: 23-233300-CFRST-Air Duct Accessories.doc CFRST SPECMSTR-NEW BUILD 2013, Marriott International, Inc.

a. American Aldes (941-351-3441) 2.02 MANUAL-VOLUME DAMPERS A. General: Factory fabricated with required hardware and accessories. Stiffen damper blades for stability. Include locking device to hold single-blade dampers in a fixed position without vibration. Close duct penetrations for damper components to seal duct consistent with pressure class. B. Standard Volume Dampers: Multiple- or single-blade, parallel- or opposed-blade design as indicated, standard leakage rating, with linkage outside airstream, and suitable for horizontal or vertical applications. 1. Steel Frames: Hat-shaped, galvanized, sheet steel channels, minimum of 0.064 inch thick, with mitered and welded corners; frames with flanges where indicated for attaching to walls; and flangeless frames where indicated for installing in ducts. 2. Roll-Formed Steel Blades: 0.064-inch- thick, galvanized, sheet steel. 3. Blade Axles: Nonferrous. 4. Tie Bars and Brackets: Galvanized steel. C. Damper Hardware: Zinc-plated, die-cast core with dial and handle made of 3/32-inch thick zinc-plated steel, and a 3/4-inch hexagon locking nut. Include center hole to suit damper operating-rod size. Include elevated platform for insulated duct mounting. 2.03 FIRE DAMPERS A. General: Labeled to UL 555. B. Fire Rating: One and one-half hour unless noted otherwise. C. Frame: SMACNA Type B with blades out of airstream; fabricated with roll-formed, 0.034-inchthick galvanized steel; with mitered and interlocking corners. D. Mounting Sleeve: Factory- or field-installed galvanized, sheet steel. 1. Minimum Thickness: 0.052 inch or 0.138 inch thick and length to suit application. 2. Exceptions: Omit sleeve where damper frame width permits direct attachment of perimeter mounting angles on each side of wall or floor, and thickness of damper frame complies with sleeve requirements. E. Mounting Orientation: Vertical or horizontal as indicated. F. Blades: Roll-formed, interlocking, 0.034 inch thick, galvanized, sheet steel. In place of interlocking blades, use full-length, 0.034 inch thick, galvanized steel blade connectors. G. Horizontal Dampers: Include a blade lock and stainless-steel negator closure spring. H. Fusible Link: Replaceable, 165 F rated as indicated. I. Provide access door in duct adjacent to each fire damper. 2.04 CEILING FIRE DAMPERS A. General: Labeled to UL 555C; comply with construction details for tested floor- and roofceiling assemblies as indicated in UL's "Fire Resistance Directory." B. Frame: 0.040 inch thick, galvanized, sheet steel; round or rectangular; style to suit ceiling construction. C. Blades: 0.034 inch thick, galvanized, sheet steel with nonasbestos refractory insulation. D. Fusible Link: Replaceable, 165 deg F rated. PAGE 3

2.05 TURNING VANES A. Fabricate to comply with SMACNA's "HVAC Duct Construction Standards Metal and Flexible." B. Manufactured Turning Vanes: Fabricate of 1-1/2 inch wide, curved blades set 3/4 inch o.c.; support with bars perpendicular to blades set 2 inches o.c.; and set into side strips suitable for mounting in ducts. 2.06 DUCT-MOUNTED ACCESS DOORS A. General: Fabricate doors airtight and suitable for duct pressure class. B. Frame: Galvanized, sheet steel, with bend-over tabs and foam gaskets. C. Door: Double-wall, galvanized, sheet metal construction with insulation fill and thickness, and number of hinges and locks as indicated for duct pressure class. Include vision panel where indicated. Include 1-by-1-inch butt or piano hinge and cam latches. D. Seal around frame attachment to duct and door to frame with neoprene or foam rubber. E. Insulation: 1-inch thick, fibrous-glass. 2.07 FLEXIBLE CONNECTORS A. General: Flame-retarded or noncombustible fabrics, coatings, and adhesives complying with UL 181, Class 1. B. Standard Metal-Edged Connectors: Factory fabricated with a strip of fabric 3-1/2 inches wide attached to two strips of 2-3/4 inch wide, 0.028 inch thick, galvanized, sheet steel. Select metal compatible with connected ducts. C. Transverse Metal-Edged Connectors: Factory fabricated with a strip of fabric 3-1/2 inches wide attached to two strips of 4-3/8 inch wide, 0.028 inch thick, galvanized, sheet steel Select metal compatible with connected ducts. D. Conventional, Indoor System Flexible Connector Fabric: Glass fabric double coated with polychloroprene. 1. Minimum Weight: 26 oz./sq. yd. 2. Tensile Strength: 480 lbf/inch in the warp, and 360 lbf/inch in the filling. 3. Minimum Movement: 2 inches. E. Conventional, Outdoor System Flexible Connector Fabric: Glass fabric double coated with a synthetic-rubber, weatherproof coating resistant to the sun's ultraviolet rays and ozone environment. 1. Minimum Weight: 26 oz./sq. yd. 2. Tensile Strength: 530 lbf/inch in the warp, and 440 lbf/inch in the filling. 3. Minimum Movement: 2 inches. F. High-Corrosive-Environment System Flexible Connectors: Glass fabric coated with a chemical-resistant coating (For use in pool area equipment room). 1. Minimum Weight: 14 oz./sq. yd. 2. Tensile Strength: 450 lbf/inch in the warp, and 340 lbf/inch in the filling. 3. Minimum Movement: 2 inches. REVISED: 05/01/13 PAGE 4 FILE: 23-233300-CFRST-Air Duct Accessories.doc CFRST SPECMSTR-NEW BUILD 2013, Marriott International, Inc.

2.08 FLEXIBLE DUCTS A. General: Comply with UL 181, Class 1. B. Flexible Ducts, Uninsulated: Corrugated aluminum. For use on dryer vents only. C. Flexible Ducts, Insulated: Factory-fabricated, insulated, round duct, with an outer jacket enclosing 1-1/2-inch thick, glass-fiber insulation around a continuous inner liner. 1. Reinforcement: Steel-wire helix encapsulated in inner liner. 2. Outer Jacket: Glass-reinforced, silver Mylar with a continuous hanging tab, integral fibrous-glass tape, and nylon hanging cord. 3. Inner Liner: Polyethylene film. D. Pressure Rating: 6-inch wg positive, 1/2-inch wg negative. 2.09 ZONE CONTROL EXHAUST TERMINALS Note: Typical guestroom model is American Aldes ZRT-1-4-120. A. Zone exhaust terminals shall be of sizes and capacities scheduled on the Drawings. B. Terminal casing shall be minimum 24-guage 690 galvanized steel with integral duct collar. Include all necessary mounting brackets and hardware. C. All 120V terminals must be per UL standards. D. Primary air volume mechanism shall be a single blade damper on solid through blade shaft with disconnecting drive motor and spring-return enclosure. A perimeter gasket shall seal to prevent noise and leakage in closed position. 2.10 ACCESSORIES A. Louvers: 1. Provide blank off panels for unused portions of louvers. Panels shall be double wall construction with 0.032 inch aluminum, and 2 inch thick, internal glass fiber insulation in accordance with SMACNA HVAC Duct Construction Standards Metal and Flexible. B. Open ducts in suspended ceiling: No. 16 USSG, ¾ inch square mesh, screen over each opening; with 1 inch wide galvanized steel enclosing frame and flanged duct opening to receive frame. In lieu or screen and volume damper, provide register or grille plus opposed blade volume damper. C. Duct sleeves: Minimum 20 gauge USSG galvanized sheet steel unless otherwise indicated. 1. Clearances: a. Non-insulated duct: 1 inch between duct and sleeve on all sides. b. Insulated duct: 1 inch between insulation and sleeve on all sides. c. Grilles, registers and diffusers: Zero clearance. 2. Provide closure collars for exposed ducts on each side of wall or floor opening. Collars shall be galvanized sheet metal, minimum 4 inch wide, and fit tight against surface and around duct or insulation. Install with nails 6 inch on center. 3. Framed openings: Provide clearances and closure collars the same as for duct sleeves. 4. Duct-mounted automatic control devices: Mount on mechanical equipment all devices related to automatic controls such as automatic dampers. PAGE 5

D. Cleanout Doors (Kitchen and Laundry Dryer Exhaust): Horizontal ducts shall be mounted maximum 20 ft. apart and in change of direction. Cleanout doors on horizontal duct shall be mounted on side of duct. Bottom edge shall be not less than 2 inches above bottom of duct. Cleanout doors at veritical ducts shall be mounted at base. Door and frame shall be same gauge as duct. Hinges shall be Ventlock No. 260, extra heavy zinc plated. Latches shall be Ventlock No. 140, cast zinc. Gaskets shall be between door and frame. Gaskets shall be 1/8 inch double thickness rated 2,000 deg F for kitchen exhaust system. Cleanout door size shall be maximum 24 inch x 24 inch and minimum shall be 24 inch one side, and other side shall be 2 inch less than duct height. PART 3 EXECUTION 3.01 INSTALLATION A. Install duct accessories according to applicable details shown in SMACNA's "HVAC Duct Construction Standards Metal and Flexible" for metal ducts and NAIMA's "Fibrous Glass Duct Construction Standards" for fibrous-glass ducts. B. Install volume dampers in lined duct; avoid damage to and erosion of duct liner. C. Provide test holes at fan inlet and outlet and elsewhere as indicated. D. Install fire dampers according to manufacturer's UL-approved written instructions. REVISED: 05/01/13 1. Install fusible links in fire dampers. E. Install duct access panels for access to both sides of duct coils. Install duct access panels downstream from volume dampers, fire dampers, turning vanes, automatic dampers, smoke detectors, outside and exhaust air plenums equipment, and other locations as indicated. 1. Install duct access panels to allow access to interior of ducts for cleaning, inspecting, adjusting, and maintaining accessories and terminal units. 2. Install access panels on side of duct where adequate clearance is available. F. Label access doors according to Section 23 05 53 "Identification for HVAC Piping and Equipment." G. Provide flexible connections at fan and building joints. H. Install automatic dampers supplied by the automatic temperature control system manufacturer. Notch end of rod and label duct/casing to indicate open and closed blade position. I. Install zone control exhaust terminals and make required control and electrical connections. J. Provide volume dampers at following locations: 1. In all duct splits and branch connections of supply, return, and exhaust systems. 2. Ducts connecting to common plenums. 3. Ducts serving single outlet. 4. At open return duct in hung ceiling. 5. Other locations as indicated on drawings. K. Provide access doors in following locations and as indicated on the Drawings. 1. Automatic dampers: linkage side. 2. Main balancing dampers. 3. Fire dampers. PAGE 6 FILE: 23-233300-CFRST-Air Duct Accessories.doc CFRST SPECMSTR-NEW BUILD 2013, Marriott International, Inc.

4. Smoke detection heads. 5. On both sides of ducts where necessary to provide maintenance accessibility to equipment on the other side. 6. Outside air and exhaust air plenums. L. Flexible Duct Installation: 3.02 ADJUSTING 1. Installation shall be in accordance with SMACNA and local building code standards. 2. Flexible duct runs shall be a maximum of 5 feet, straight lengths, no bends. 3. Connections to beaded sheet metal fittings shall be with 3 wraps of approved tape and stainless steel draw band for tight seal. Seal the outer jacket with 3 wraps of approved UL 181B tape. 4. A 1 ½ minimum strap shall be used to support the flexible duct at a distance not greater than 5-0. Maximum permissible sag is ½ per foot of duct length. A. Adjust duct accessories for proper settings. B. Adjust fire dampers for proper action. C. Final positioning of manual-volume dampers is specified in Section 23 05 93 "Testing, Adjusting, and Balancing for HVAC. END OF SECTION PAGE 7