The Clark-Reliance Corporation TWIP System Installation and Maintenance Instructions - Form E112 -

Similar documents
TWIP Level Switches. Water Detection for Alarms, Trips, Drain Pot, Heaters, Deaerators, and Condensate Tank Applications

OPERATING AND MAINTENANCE MANUAL FOR VERTICAL IMMERSION HEATED STEAM BOILERS. Technical Control Systems Limited MODELS "VIHS"

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

Low Water Cutoff (LWCO) IQ Option Card p/n , for Hot Water Boilers

Electronic Flow Switches

High Pressure Conductivity Monitor

Page. 1-2 Sepra-Lite Integral Optic Level Switches. 3-5 Electro Optic Level Systems: Probe and Controller

Ultrasonic Point Level Switches

Powers Controls Low Temperature Detection Thermostat

! WARNING. Before using product, read and understand instructions.

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Instruction Manual HWR MODEL RESISTO-FLO ELECTRIC BOILER

AlarmLine Addressable Linear Heat Detector

Motogard. Over Temperature Protection System. Installation Instructions

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

Electric Duct Heaters

Addendum for STI-6406 with Dual Access Control

STEAMPRO. Steam Generator Troubleshooting and Service Guide

Ultrasonic Switches. Features & Benefits

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

SECTION LOW VOLTAGE LIGHTING CONTROLS

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

Dual Input Toroidal Analyzer

Dual Input ph/orp Analyzer

OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D

TABLE OF CONTENTS Flow Detect 1000 Specifications 3 Description 4 Principle of Operation 4 Detection Through Walls 4 Sensing Beam Shape 4 Installation

Introduction to Flow Switch

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Dual Input ph/conductivity Analyzer

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

SECTION DOMESTIC WATER HEATERS

ANCHOR BOLT DETAIL. Non-Shrink Grout. Poured In Place, After Equipment Setting. "L" Type Anchor Bolt Carbon Steel AISI 304 S.S.

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

Model Q45P/R. ph/orp Monitor...

Line Isolation Monitor (LIM) LIM2000plus

Operating Instructions

Process Protection. MFA 4P Motion Failure Alarm

! WARNING. Before using product, read and understand instructions.

Instruction Manual April sitrans AS 100

Centro-Matic Automated Lubrication Systems System Controls

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

! WARNING. Before using product, read and understand instructions.

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

Model Q45P/R. ph/orp Monitor...

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

FX5 Series Explosion-Proof Electric Air Heaters

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Public Safety DAS Annunciator Panel

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

LC3000 Level Controller Installation and Maintenance Instructions

ROYCE SUSPENDED SOLIDS SYSTEM MODEL 7011A AND SENSORS MODELS 72A, 72P, 73B, 74A, 75A & 76A

Instruction Sheet LTR - Low Water Cutoff for Hot Water Boilers

ISIS SAFETY SYSTEM Installation guide

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

Installation Guide for models:

Instruction Manual. Princo Model L3522. Point Level Controllers with LEVEL SENTRY. Rev 2, June 2013

TABLE 1. Specifications: Dimensions: 6¼ x 9 5/8 x 2 ¾

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

INSTALLATION AND SERVICE MANUAL

TABLE 1 Electrical Specifications

MODEL B2 INSTALLATION MANUAL

Sensall Sapphire. Thermo MeasureTech ULTRASONIC POINT LEVEL SYSTEM

Boiler Instrumentation

1022 R/T Remote Monitor

SAVE THESE INSTRUCTIONS

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Basin Heater. user manual INSTALLATION OPERATION MAINTENANCE

SECTION ROTARY-SCREW WATER CHILLERS

Installation Guide for models:

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

FRP HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL FRP.IOM.R1

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

TABLE 1 Electrical Specifications. Phase

Instruction Manual STR MODEL RESISTO-FLO ELECTRIC BOILER

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Sapphire ULTRASONIC POINT LEVEL SYSTEM

B-40/B-41 Modulating Temperature Controller

Process Water Heater For Industrial Applications All Voltages, Single or Three Phase Up To 88 KW

Series. Access Power Controllers. Installation Guide

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

Installation and Operation Manual

Power Supply Display Module PSDM. Installation and Operation Manual

Frost Heave Protection System Installation and Operation Manual

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

! WARNING. Before using product, read and understand instructions.

Transcription:

The Clark-Reliance Corporation TWIP System Installation and Maintenance Instructions - Form E112 - Table of Contents A. Installation Page 2 B. Interwiring Control Unit Options Page 3 C. Operation Page 4 D. Maintenance Page 5 E. Trouble Shooting Page 6 F. Electrical Specifications Page 6 The Clark-Reliance Corporation 16633 Foltz Industrial Parkway Strongsville, OH 44149 USA Telephone: (440) 572-1500 FAX: (440) 238-8828

2 CLARK-RELIANCE TWIP SYSTEM INSTALLATION AND MAINTENANCE INSTRUCTIONS A. Installation 1. The TWIP Column Assembly should be installed on any cold return line, heater, or other vessel to detect water level. The distance between the TWIP Column Assembly and the application connections should be kept to a minimum. Isolation (Shut-off) valves should be installed to permit maintenance while the vessel is pressurized. A drain valve should be installed on the TWIP Column Assembly. The standard drain connection on the TWIP Column Assembly is 1/2" female socket-weld. The standard vessel connections are 1" male pipe projections. Flanged, butt weld, or female socket weld connections may have been furnished, if specified. We suggest that all piping between the vessel and the TWIP Column be insulated. Insulation will reduce the effects of cooling and will provide added personnel protection from hot piping. The TWIP Column Assembly may be insulated by field personnel, or with a removable custom-fit Flexpak insulation jacket, when specified. The Flexpak insulation jacket can be specified with the original order, or ordered for an existing system. When ordering, specify the serial number of the existing TWIP Column Assembly. This information is located on the nameplates which are attached to the probe housing and the relay control unit. The serial number will enable Clark-Reliance personnel to assist with technical questions or to identify components. Flexpak jackets are designed for easy removal or installation with Velcro seams. 2. The Control Unit is typically furnished in a NEMA 1 (indoor) or NEMA 4 (outdoor) enclosure. Standard ECIL or R***L model Control Units may be mounted up to 1000 feet away from the TWIP Column. The Control Unit should be mounted in an area that is accessible for inspection and below 140º F. The size of the Control Unit enclosure may vary with customer-selected options. Control Unit dimensions are shown on the drawings provided with the system. 3. The optional Remote Indicator should be mounted in the control room. There is no practical distance limitation between the Control Unit and the Remote Indicator. Although all Remote Indicators are designed for panel mounting, wall mounting brackets are available. Weatherproof enclosures should be specified for outdoor installations. Indicators may be wired in parallel, for multiple indicator installations. 4. Field Wiring from the Control Unit to the Remote Indicator(s) and to the TWIP Column Assembly should be performed as illustrated on the field wiring diagrams. Wiring diagrams are furnished with each TWIP system. The TWIP Column Assembly has been furnished with 30" lengths of high temperature leads exiting from the conduit connection. Longer leads may have been furnished, if requested.

3 The specifications for the high temperature probe wires are as follows: Pressure Pressures up to 1000 PSIG Wire Specifications 18 GA. Stranded Teflon insulated conductors rated at 300 VAC and 200ºC (Belden #83029, Alpha #5857, or equal) Pressures between 18 GA. Stranded Teflon-treated glass 1001 to 3000 PSIG braided rated at 300 VAC and 400ºC, Nickel coated copper conductor U.L. #5182 (Radix #MGT-4503, or equal) The high temperature probe wires should be routed to a junction box (furnished by C-R, when specified). Low temperature multi-conductor cable may be routed from the junction box to the control unit. The number of required conductors is equal to the number of probes, plus one, for the common connection. For example a four probe TWIP Column Assembly would require 5 conductors. We suggest the following cable specifications: 18 GA. multi-conductor (Tinned Copper), PVC insulated, rated at 300 VAC and 60º C (Belden #8468 or equal). The same type of wire may be used between the Control Unit and the Remote Indicator(s). The number of conductors required for a Remote Indicator is equal to the total number lights, plus one, for a common conductor. For example, an MTI-4B Remote Bicolor Indicator has 4 red lights, 4 green lights, and one common. Therefore, 9 conductors are required. Refer to the remote indicator field wiring diagram furnished with the system for clarification. A. Interwiring Control Unit Options 1. Auxiliary Alarm Contacts: ECIL Control Units that are furnished with auxiliary alarm contacts will provide a dry Form C switch. This switch is rated at 5 Amp @ 120/240 V.A.C. or 1 Amp @ 120 V.D.C., 5 Amp @ 30 V.D.C. The switches have been provided for all levels, as standard. Refer to the Control Unit wiring diagram for additional details. 2. Test Switch Circuits:

Optional Test Switch Circuits are specified to enable operators / users to test indicator lights and all relay circuits. The push button is furnished in a weather resistant enclosure for convenient mounting. 18 Ga. wire is sufficient for test switch interwiring. Refer to actual wiring diagrams for more details. Note: During the test mode, all alarm circuits that are intended to detect water will energize. 4 3. Dual Power Supply: Systems furnished with model PSD-120 or PSD-240 Power Supply Diverter are designed to accept two independent power supplies. The primary supply (A) will power the entire system under normal operating conditions. In the event of a power failure, the PSD diverts the power to the secondary supply (B), and continues to power the system. When supply A is restored, the PSD automatically switches back to supply A. A typical installation is illustrated in Fig. 1. L2A L1A Fig. 1 - Power Supply Diverter Interwiring (PSD-120 shown) C. Operation 1. Initial operation of all installations: i. Verify all interwiring

5 ii. Initial warm-up of the TWIP Column should be done gradually. To do this, keep the water valve closed, open the drain valve widely, and crack open the steam valve for a few minutes. Then, close the drain valve, and slowly open the steam and water valves fully. Check for any leakage near the probes. iii. Hot-torquing is recommended on all installations. After initial warm-up, the TWIP Column should be isolated and the drain valve opened. Then, retorque T, V, or ZG probes to 40 Ft - Lb., and FG probes to 90 Ft - Lb. The hot torquing procedure will extend the life of the sealing gasket. iv. Close drain valve, and open isolation valves to put the system into service v. Turn power on to the control unit. D. Maintenance 1. Blowdown of the TWIP Column should be performed only as needed, to minimize maintenance. We suggest blowdown to be conducted weekly or monthly, based upon water quality. Blow-down is performed correctly by closing the water valve and slowly opening the drain valve for approximately 15-30 seconds. A brief blowdown is sufficient. Excessive blow-down may shorten the life of the probes. 2. Probe Replacements: i. When replacing probes, lubricate threads with a high - temperature lubricant such as Molykote-G, Fel-Pro C or Never Seize. ii. iii. Torque T, V, & ZG probes to 40 Ft - Lb. Torque FG probes to 90 Ft - Lb. Always install a new sealing gasket, as indicated below, when replacing probes: Probe Gasket Part No. T WCM-13 V X175500 (Formerly E10-10) ZG E10-10S FG E10-10S Each replacement probe is supplied with 4 gaskets. iv. Control Units require no maintenance. However, test switches may be activated at any time. v. Indicators that are of the sub-miniature model contain integral L.E.D.'s, and require no replacement parts. Miniature models contain either red L.E.D. s (Part No. MI-52) or Red/Green L.E.D. s (Part No. MI-51)

E. Trouble - Shooting Guide 6 Symptom Probable Cause Corrective Action 1. Indicator Light illuminated above level, or remains on during blowdown 1. Failed/Short-circuited probe 1. Remove probe and clean if contaminated, or replace if leakage is detected. 2. Indicator light out at any level 2. B) On models with L.E.D. indicators, problem is either failed relay or wiring problem. B) Exchange relays and verify if problem moves with relay. Verify all wiring connections, at the probes, and at Control Unit terminal blocks. F. Electrical Specifications i.) RELAY - Standard ECIL and R***L model control units are furnished with Part No. ECID - 23R electronic control relays. Specifications Design: Contact Design: Contact Ratings: Solid State components enclosed in a clear Lexan, (or polycarbonate) plug-in style housing. DPDT (2 form C): two normally open (N.O.) and two normally closed (N.C.) One set is usually occupied by the 24 V.A.C. indicator circuitry. The other set is available for alarm use. 5A @ 120, 240 V.A.C., 5A. @ 30 V.D.C., and 1A. @ 120 V.D.C. Contact Life: Mechanical - 5 million operations. Electrical - 100,000 operations min. at full load. Supply Voltage: Supply Current: Standard units are designed for 120 V.A.C. supply. Some custom units are fabricated for 220 V.A.C. (Refer to wiring diagram provided for details). 4.4 VA Probe Circuit Current: Sensitivity: Temperature Rating: Listing: 1.5 ma @ 12 V.A.C. per probe. 50,000 Ohms -40 to +150ºF (-40 to +66º C.) Factory Mutual #2N2A4.AF, CSA # LR14001, and

U.L. listed 7 Direct Mode Operation: (Standard System) Direct Mode Operation: When the water rises in the TWIP Column Ass'y. to the probe, the control energizes (LED will be lit). The control remains energized until the water level recedes below the probe. Then, the relay will de-energize (LED will not be lit.). With no water level in the TWIP Column Assembly control will be energized (L.E.D. will be lit). As water level rises to contact each probe, the relay will de-energize (L.E.D. will go out). Inverse mode relays are often specified for applications that will detect a normal water level, and are located in geographic areas with frequent power interruptions. During momentary power interruptions, relays corresponding to probes immersed in water will remain de-energized, and no false alarm will occur. Consult the factory or your local Clark-Reliance Representative with any questions. Technical questions can be promptly answered, if the caller provides the system serial number (Example TD - ) or the drawing numbers. Clark-Reliance Corp. 16633 Foltz Industrial Parkway Strongsville, OH 44149 Tel: 440-572-1500 Fax: 440-238-8828