Gas Safety Products. Installation, operating and maintenance. Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System

Similar documents
Gas Safety Products. Installation, operating and maintenance. Merlin 1000BH Gas Proving/Gas Detection System

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance 23/08/2016. Merlin 1000BH Gas Proving/Gas Detection System

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016

Gas Safety Products. Installation, operating and maintenance 28/10/2015. Merlin CT1250 Gas Interlock System. S&S Northern Ltd 1

Product Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 4500PPM. Merlin CO2 Monitor. Rev: 11 Date:

Gas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Merlin Gas Detectors. Rev: 09 Date: Product Data Sheet

Troubleshooting Guide

Troubleshooting Guide

Gas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Read these instructions carefully before operating or servicing.

Gas Safety Products. Installation, operating and maintenance 11/26/2015. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance 10/12/2017. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 2800PPM. Merlin CO2 Monitor 2800ppm. American Gas Safety LLC 1

Please read this sheet as it contains important information

Boiler Room Control THE MERLIN RANGE GAS DETECTION EQUIPMENT ENGINEERED TO DELIVER EXCEPTIONAL LEVELS OF SAFETY

MERLIN RANGE KITCHEN EQUIPMENT CT1200S CT1250

MERLIN RANGE GAS DETECTION EQUIPMENT

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

Multi Function Control System for Boiler and Plant rooms SEC-B. The Home of Control & Automation in Ireland

Installation Instructions. The SEC-L is a gas pressure proving system with water and electric isolation, gas detection and ventilation interlock.

VGPS-evo V3.3. Installation Instructions. The VGPS-evo is a gas pressure proving system with ventilation interlock and optional CO2 detection.

GPPS-evo V3.3. Installation Instructions

Installation Instructions

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

BX444-Mc Gas Detector

ACCU-TEST SAFETY. Assured Gas Shut Off Protection

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

Four Channel Gas Detection System AGDS 4. The Home of Control & Automation in Ireland

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

Gas interlock system S & 100 CS

GS100M Gas Detector. Technical Specification

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

GS100M Gas Detection Controller

Reflective Optical Beam Smoke Detector User Guide

ESP TECHNOLOGIES LIMITED

GL-CO-RFG Channel Gas Leak Alarm System

Multi Channel Gas Detection System AGDS MC. The Home of Control & Automation in Ireland

OPERATION AND INSTALLATION MANUAL

FEC400 Series. Installation Manual

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

100 Series Gas Ventilation Interlock System

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Installation, Operating and Maintenance Manual

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

CaterSense 03 & ATSC-02-xx

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the BiWire / Conventional Repeater Panel

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

APM110 LOW AIR VELOCITY ALARM

Installation & Operation

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Intelligent Security & Fire Ltd

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

TECHNICAL MANUAL EDITION 1.0 VANDAL RESISTANT AUDIO AND VIDEO DOOR ENTRY SYSTEMS

B-40/B-41 Modulating Temperature Controller

Door Release Power Supply

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

A System That Utilizes the LD-2000 or LD-3000 Mechanical Line Leak Detector to Perform 3 10 PSI (catastrophic) Line Tests

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

intelligent solutions

AIR CURTAIN T SURFACE MOUNTED RANGE

Analog Room Pressure Monitor RPC Series

AquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

KM300 Carbon Monoxide Detection System Installation Manual

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

Carbon Monoxide Transmitter

OPERATION & MAINTENANCE MANUAL GUARDIAN SPACE PRESSURE MONITOR WITH REMOTE AUXILLARY ALARM

EXAMPLES OF HOW TO ORDER

AT-G-SENSE Gas Sensing System

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

EXAMPLES OF HOW TO ORDER

TMC Temperature Monitoring Control Temperature Range -30 to 250 F (-35 to 120 C)

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

Flopurge TS. Operation Manual

Conventional Releasing Control Panel

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

21-light Remote Annunciator. Owner s Manual

Dough Retarder Prover. Service Manual

Flostop TS D7E and A8E. Operation Manual

Cimco Series 21. Series 21 - Specifications INDEX. Description. Operational Specification 2

Installation & Maintenance Manual

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

Installation Instructions 4 Zone Fire Panel

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

ACCURATE ELECTRONICS INC

Water Detection Controllers

INSTALLATION AND OPERATING INSTRUCTIONS

Transcription:

Gas Safety Products Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System Installation, operating and maintenance Read these instructions carefully before operating or servicing Rev: 02 Date: 08-01-18 1

Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Mains Supply... 3 2.3 Gas solenoid valve.... 3 2.4 Electric Contactor.... 3 2.5 Water Valve... 3 2.6 BMS Connections.... 3 2.7 Gas Pressure Transducer.... 3 2.8 Remote emergency shut off buttons.... 3 2.9 Gas Detector.... 3 2.10 FS 123.... 3 2.11 Fan PD Switch.... 3 2.12 12v DC.... 3 2.13 Internal Buzzer.... 3 3 Operation Instructions... 4 3.1 How to turn the system on and off... 4 3.2 Explanation of LED status... 4 3.2.1 Gas on LED... 4 3.2.2 Electric on LED... 4 3.2.3 Water on LED... 4 3.2.4 Testing LED... 4 3.2.5 Test Fail LED... 4 3.2.6 Pressure Low LED... 4 3.2.7 Time Out... 5 3.2.8 EM Stop LED... 5 3.2.9 CO2/Gas Detected LED... 5 3.2.10 Fan Fault LED... 5 3.3 Using the emergency shut off... 5 3.4 BMS integration... 5 3.5 Fire alarm integration... 5 3.6 Fan switch integration... 6 3.7 Gas fill and prove time... 6 3.8 Auto reset... 6 1000VW+ Wiring Diagram... 7 Rev: 02 Date: 08-01-18 2

1 General information The Merlin 1000VW+ is an Electric and Water utilities isolation panel with gas proving and ventilation interlocking. The system comprises of a control panel and a gas pressure sensor. The Merlin 1000VW+ can receive connections from a remote air pressure differential switch or external current monitor, as well as remote emergency shut-off buttons, gas detectors and a CO2 monitors. It can also be integrated with a BMS and fire alarm. It is recommended that the user reads this guide before using the system. Please do NOT attempt to operate the unit until the contents of this document have been read and are thoroughly understood. 2 Installation 2.1 Panel Mounting The control panel is designed for surface mounting using 4 mounting screws. Removing the cover on the panel gives access to the circuit board. The PCB should be removed before drilling entry holes into the case. 2.2 Mains Supply A 230-volt electrical supply should be supplied to the panel. This should be externally fused at 3 Amps using a fused spur and should be connected to the terminals marked LNE Power IN 2.3 Gas solenoid valve The gas solenoid valve should be powered using the terminals on the Merlin 1000VW+ marked LNE to VALVE. 2.4 Electric Contactor An electrical output will be supplied to an electrical contactor. This will be internally fused at 3 Amps and should be connected to the terminals marked LNE Electric Contactor. 2.5 Water Valve The water solenoid valve should be powered using the terminals on the Merlin 1000VW+ marked LNE WATER VALVE. 2.6 BMS Connections Terminal connections are available on the circuit board for connections to Building Management systems etc. Detailed on the circuit board as BMS N/C, Com and N/O these are volt free connections. 2.7 Gas Pressure Transducer The terminals marked pressure sensor + - in.these wire to the gas pressure transducer which is screwed into the downstream port on the gas solenoid valve. Red + (positive), Black (negative) and Blue (IN). Please ensure this is wired as instructed. Minimum Operating Pressure = 12Mbar Maximum Operating Pressure = 100Mbar. 2.8 Remote emergency shut off buttons The terminal for remote emergency shut-off buttons is detailed on the circuit board as EM Remote. These connections are linked out as a factory setting. Remote emergency shut-off buttons should be volt free and wired to the Merlin 1000VW+ using twocore cable. 2.9 Gas Detector The terminals detailed on the circuit board as Gas Detector. These connections are +,- and these can be wired to a Merlin Carbon Dioxide, Natural gas, Carbon monoxide or LPG detector. If no detector is being used leave the link in between the. Other detector types are available. 2.10 FS 123 This terminal switches when the key is turned on and off. This can be linked to a fan switch (panel supplied separately) which can provide power to the fans when the control panel is switched on. 2.11 Fan PD Switch This terminal can be wired to a fan pd switch or current monitor to shut off the system in the event of a fan failure. If no fan interlock is required, leave the terminal link in. 2.12 12v DC This is a permanent 12v DC output when there is power at the panel. 2.13 Internal Buzzer Operates at 65dB measured 30cm from closed panel. Rev: 02 Date: 08-01-18 3

Note: all low voltage connections should be made using a screened cable to avoid electrical interference should not be in the same conduit as per the low voltage directive. 3 Operation Instructions 3.1 How to turn the system on and off 1. Turn the fans on (only when interlocked with vent). 2. Turn the key switch to the on position. 3. Gas, electric and water will flash for 10 seconds. 4. Press relevant service button to turn required utility on. 5. Turn the key switch to the off position to turn the panel off. Please Note: All services can be turned on or off only within 10 seconds of the key switch being turned on. After 10 seconds, all utility buttons will be disabled. The user must turn the key off and back on to adjust any services. 3.2 Explanation of LED status 3.2.1 Gas on LED When the key switch is turned on, the Merlin 1000VW+ will check the installation for gas leaks. If gas proving is successful, the gas valve will open and the blue Gas LED will illuminate. BLUE = Gas On OFF = Gas Off 3.2.2 Electric on LED When Electric service is turned on, the Electric LED will illuminate BLUE. BLUE = Electric On FLASHING = Electric Off, Electric button enabled OFF = Electric Off, Electric button disabled 3.2.3 Water on LED When water service is turned on, the Water LED will illuminate BLUE. BLUE = Water On FLASHING = Water Off, Water button enabled OFF = Water Off, Water button disabled 3.2.4 Testing LED This LED will illuminate GREEN for approximately 30 seconds when the panel is checking the integrity of the gas installation upon start up. GREEN = proving the gas line, do NOT operate any appliances. 3.2.5 Test Fail LED Under normal working conditions this LED is off. When the panel detects a gas leak on start-up, the LED will illuminate AMBER. Gas valve will remain closed. AMBER = gas proving failed 3.2.6 Pressure Low LED Under normal working conditions the LED is off. The LED will illuminate AMBER when pressure of the gas supply drops below 12mBar for 10 seconds. The gas valve will close. AMBER = gas supply pressure low. Rev: 02 Date: 08-01-18 4

3.2.7 Time Out Under normal working conditions this LED is off. This LED will illuminate AMBER when auto-shut down has occurred. AMBER = auto-shut down 3.2.8 EM Stop LED If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate AMBER and the gas will be turned off. The EM Stop button must be re-set before restarting the system. AMBER = EM Stop button pressed 3.2.9 CO2/Gas Detected LED Under normal working conditions this LED is off. If the external Merlin detector connected detects gas this will show RED and the Gas valve will turn off. RED = Gas detected. 3.2.10 Fan Fault LED Under normal working conditions, this LED is off. If a fan fault is present for more than 20 seconds, the LED will illuminate RED. RED = the gas supply has been shut off due to a ventilation fault. WHEN A FAULT IS FOUND YOU WILL NEED TO CONTACT YOUR SERVICE/MAINTENANCE COMPANY. YOU SHOULD NOT ATTEMPT TO CARRY OUT A REPAIR OR RECTIFY THE FAULTS UNLESS YOU ARE QUALIFIED TO DO SO. 3.3 Using the Emergency Shut Off The Emergency shut off button is located on the front of the panel. There is also a facility for remote shut off buttons to be wired in series. The Emergency shut off button(s) will cut off the gas supply when activated. To reinstate the system, the Emergency shut off button(s) will need to be reset and the panel restarted. 3.4 BMS Integration The Merlin 1000VW+ can be integrated with a BMS to make or break a circuit on gas on/gas off, (valve open or valve closed). This will tell the BMS whether or not the room has use of the gas supply. There is a dip-switch located on the inside facia of the Merlin 1000VW+ labelled BMS Selection. This is factory set in the off position which signals the BMS on gas on/gas off. When switched to the on position, the 1000VW+ will only signal the BMS on a fault, i.e. CO2 high level detected, gas detected, EM Stop pressed, etc. 3.5 Fire Alarm Integration The Merlin 1000VW+ can be integrated with a fire alarm to close the gas supply automatically in the event of a fire. The volt free fire alarm signal can be wired in series with any remote emergency shut off buttons. If there is no remote emergency stop buttons installed wire this directly to the terminal marked EM REMOTE. Rev: 02 Date: 08-01-18 5

3.6 Fan Switch Integration There is the facility to connect a Fan Switch (FS1 or FS2 sold separately). The Fan Switch provides the facility to turn on the fan(s) when the key switch on the Merlin 1000VW+ is in the on position and turn the power off to the fan(s) when the key switch on the Merlin 1000VW+ is in the off position. There is a dip-switch located inside the facia of the Merlin 1000VW+ labelled EM Selection. This is factory set in the off position which instructs the system to shut down the fan(s) and gas supply on activation of the Emergency shut off button(s). On installation, this can be switched to the on position if required. This will instruct the system to leave the fans on and only shut off the gas supply on activation of the Emergency shut off button(s). Note: This option is not available if Fan Switch is not installed. 3.7 Gas Fill and Prove Time Gas fill and prove times are adjustable. There are two dip-switches located on the inside facia of the Merlin 1000VW+ labelled Fill Time and Prove Time. They are factory set in the off position. Fill and prove time can be changed by turning the relevant dip switch to on position. Fill time: Off 5 seconds, On 10 seconds Prove time: Off 30 seconds, On 50 seconds Once the settings have been changed please remove power from the fuse spur for seconds. 3.8 Auto Reset The Merlin 1000VW+ has a built-in auto reset feature. There is a dip-switch located on the inside facia of the Merlin 1000VW+ labelled Auto Reset. This is factory set in the off position. When the power is restored after the power cut, the panel has to be restarted manually. On installation, this can be switched to the on position if required. This will instruct the system to restart automatically when power is restored. Rev: 02 Date: 08-01-18 6

1000VW+ Wiring Diagram 1. Mains Input 230VAC Single Phase. 2. Gas Solenoid Valve Power Output, 230VAC, Max 3A. 3. Electric Contactor Power Output, 230VAC, Max 3A. 4. Water Valve Power Output, 230VAC, Max 3A. 5. BMS output contacts. Normally Closed, Common and Normally Open. Max.1A @ 230VAC. 6. Gas pressure transducer, Red + positive, Black negative and Blue IN. 7. Remote EM Stop buttons and Fire Alarm input wired in series (purchased separately). VOLT FREE INPUT 8. Natural Gas, CO or LPG Detector, power supply and volt free input (purchased separately). Carbon dioxide monitors can be wired in series. 9. Fan Switch output (purchased separately). For wiring instruction, see Fan Switch user manual. 10. Fan interlock input VOLT FREE INPUT 11. Permanent 12VDC output when there is power at the panel. Please note, Mains wires and low voltage wires should not be run in the same conduit as per the LOW VOLTAGE DIRECTIVE Rev: 02 Date: 08-01-18 7

INFORMATION ON WASTE DISPOSAL FOR CONSUMERS OF ELECTRICAL & ELECTRONIC EQUIPMENT When this product has reached the end of its life it must be treated as Waste Electrical & Electronics Equipment (WEEE). Any WEEE marked products must not be mixed with general household waste, but kept separate for the treatment, recovery and recycling of the materials used. Please contact your supplier or local authority for details of recycling schemes in your area. CONTACT US: S&S Northern Head Office Tel: +44(0) 1257 470 983 Fax: +44(0) 1257 471 937 www.snsnorthern.com info@snsnorthern.com South East Division Tel: +44(0) 1702 291 725 Fax: +44(0) 1702 299 148 south@snsnorthern.com S&S Northern is the owner of this document and reserves all rights of modification without prior notice. Rev: 02 Date: 08-01-18 8