"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

Similar documents
THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

RELEASE DEVICE CONTROLS

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

MANUAL RESET ALARM RELEASE BOX

OWNER S MANUAL. Extended Performance Release Device. Models: Firefly III Plus, Firefly III Plus with Voiceboard

INSTRUCTION MANUAL. AlarmGard Chain Operator (Model FCA) AlarmGard Crank Operator (Model FKA)

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE

Hand Chain (Model FCF) &

AUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL

INSTALLATION & MAINTENANCE CORNELL FIREGARD CHAIN & ES ECO #1515 REVISION # 0000 FIREGARD CRANK OPERATORS BY: RICKM DATE: 3/23/2011

SP-1000X. Panic Device Power Controller Installation Guide. Rev

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

Installation Guide for models:

Installation Guide for models:

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Public Safety DAS Annunciator Panel

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

TECHNICAL DATA OBSOLETE

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Model 17A00 Expansion Enclosure

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Conventional Releasing Control Panel

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Multiple Input and Output Modules

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Series. Access Power Controllers. Installation Guide

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

AL600ULADA. NAC Power Extender. Installation Guide

Specification/ Data Sheet

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

AL800ULADA. NAC Power Extender. Installation Guide

30.45 Electric Release PDRP-2001

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Installation, Operating and Maintenance Manual

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC.

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL. FT-EPB Series. Single Motor

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

SECTION OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

Booster Power Supply Manual

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

SECTION OVERHEAD COILING FIRE DOORS FIREKING FIRE DOOR SERIES, MODEL 634

SECTION OVERHEAD COILING FIRE DOORS FIREKING FIRE DOOR SERIES, MODEL 635

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

MR-2602 Two Zone Fire Alarm Control Panel

Electric Release Panel Wiring Tips

Control/Communicator

Access Power Controllers with Power Supplies

FMR Installation Instructions. Addressable Fire System Controller

SECTION AUTOMATIC TRANSFER SWITCHES

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

Addressable NAC Output Module D327A

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

LifeAlarm Fire Alarm Controls

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

Notification Appliance Circuit Module

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

4100U City and Relay Cards Installation Instructions

Transcription:

S S S SS O L I D S S90 TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U L 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. "SS90" SERIES CONTROLS MADE IN THE U.S.A. MODEL C INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-48:00 The Solid State Securities "SS90" Model C Release Device/Control Panel is a U.L. Listed, Canadian Listed (C-UL) and California State Fire Marshal Listed (CSFM) normally energized Fail-Safe device incorporating state of the art electronic control circuitry. The SS90-C is designed to be used with motorized doors incorporating a reversing feature safety edge to create an automated door closing system. DO NOT install this unit without a safety edge. The SS90-C high performance control panel responds to emergency conditions generated by manual or automatic initiating devices. Upon activation from such a device, the unit can provide a voice warning (option) indicating that a closure is about to occur and will then close the door thru the motor. If the alarm is still present and power is available to the operator, the door can be opened by depressing the open switch of the operator, after which the door will close again. If the door meets an obstruction while in alarm, the door will reverse and make three attempts to close, after which the motor will be shut off and the release mechanism will release the door onto the obstruction. The unit can be factory ordered with cycle count from thru 0 (3 count standard), as well as continuous cycling capability. A safety timer within the unit will turn the motor off and perform a mechanical release if the lower limit is not detected within a predetermined time period. Verify factory installed options to desired features. The SS90-C features include time delay on alarm, remote test, motor voltage sensing, form-c output, lower limit detection, safety timer, battery support for release device logic, smoke detectors, multi-lingual voice (option), standard annunciators and trouble diagnostic capabilities (does not support motor). Check model label on unit to be installed to verify operating voltage. CAUTION: Review all installation instructions, procedures, referenced publications, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications and used with fuse link systems. DO NOT install this unit without a fuse link system. TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). TECHNICAL SUPPORT (570) 455-0577 997 SSSI, PATENTS PENDING ALL RIGHTS RESERVED HAZLETON, PENNA 820 P/N: REVC5 http://www.sssiusa.com - E-Mail: ss90@sssiusa.com

INSTALLATION INSTRUCTIONS -To be performed by factory authorized personnel only. The following installation procedures must be followed to assure performance of the "SS90" MODEL C Release Device/ Control Panel to factory standards. A. MOUNTING PROCEDURE (Figure ) - Typical installation configuration may not accurately depict door manufacturer s recommendations. See door manufacturer s recommendations for use of this product with specific door being utilized. All hardware required shall be supplied by the door installer or manufacturer. Use only hardware approved or recognized by the appropriate testing and listing agencies in conjunction with the installation of this product.. The release device shall be mounted on a vertical surface with chain end link exiting side of enclosure as illustrated in figure. 2. Release device enclosure shall be mounted with minimum #0 size fastening screws or bolts for securing to structures other than masonry. Masonry applications shall utilize /4" or greater anchors or studs as required to insure proper mounting strength. 3. Release device and associated hardware (sash chain or /6 cable, eyebolts, *fuse links, turnbuckles) shall be installed as per figure or door manufacturers recommendations. Note should be taken that the end link direction of pull is perpendicular to the enclosure side. An eyebolt installed at a minimum distance of 2 inches from the release device should adequately redirect sash chain pull as illustrated in Figure. *DO NOT use this device without fuse links. 4. Complete hardware installation by connecting fuse links, sash chain, S-hooks and turnbuckles where required. Push reset lever in direction of arrow on label to allow insertion of end link through release device side opening. Push end link completely in and release reset lever to latch end link. Remove sash chain or cable slack by adjusting turnbuckle. * DO NOT exceed maximum pull rating of 40 lbs. on releasing device. B. SMOKE DETECTORS. When installing smoke detectors with this unit refer to NFPA 72-993 and NFPA 80, paragraph 6-6, for instructions concerning proper placement and detection coverage. See Electrical Connections page 2A for wiring information. End of Line Devices shall be installed for supervision of electrical power to smoke detector. DO NOT interface this unit to smoke detectors if electrical supervision is not provided by means of an End-of-Line Device used in conjunction with the Model C! C. ELECTRICAL CONNECTIONS - Installation of all wiring and connections, including Class and Class 2 circuits, shall be performed in accordance with, but not limited to, the latest NFPA, U.L. and N.E.C. standards and codes. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material type, wiring gauge related to power capacity requirements and circuit length and wiring methods. This unit is designed to be used on motorized doors incorporating a reversing feature safety edge. DO NOT use this unit on a motorized door if a safety edge has not been installed. SEE Figure 2 - Verify wiring configuration with that recommended by door manufacturer for use of this product with specific door and accessories being utilized. All wiring beginning at step 4 is low voltage. 8 gauge wire is recommended.. Turn off power supply sources for Model C as well as motor before beginning. 2. Verify voltage rating of release device/control panel to power source being utilized. Model voltage is indicated on side of unit. 3. Connect power source inputs to TB5, screws & 2. On 24vdc units observe proper polarity by placing positive wire to screw. TB5 screw 3 shall be utilized for earth ground where applicable. (DO NOT connect battery) 4. (a) Normally closed initiating devices - remove jumper from TB screw 2 & 3. Connect wiring from N/C initiating device loop to TB screws 2 & 3. Auxiliary power (+2vdc) for smoke detectors may be obtained from TB2. Observe proper polarity, TB2-2, TB2-. 4 detector maximum. (b) Normally open initiating devices - (The N/C & N/O loops may be used simultaneously, but if the N/C loop IS NOT used, make sure the jumper is installed across TB screws 2 & 3) Connect wiring from N/O initiating device loop to TB screws 4 & 5 (do not share loop with other alarm circuits), making sure end of line supervisory resistor (5 K ohm @ /4 Watt) is installed at end of line as indicated. Auxiliary power (+2vdc) for smoke detectors may be obtained from TB2. Observe proper polarity, TB2-2,TB2-. 4 detector maximum. Note: TB initiating device loops are supervised and cannot be directly series or paralleled between multiple release devices or shared with other alarm equipment. For proper wiring configurations from multiple smoke detectors or signalling for simultaneous closure on multiple doors call tech support. Incorrect wiring between units may cause damage to the release control circuit and void warranty. 5. Connect motor control sensing voltage (24-30V ac or dc) from motor controller transformer secondary to TB3 screws & 2. This connection must be made or the unit will perform a mechanical release in all alarm conditions. Continued on page 2

S S S OLID S S S SS90 * PATENT PENDING TATE ECU RITIES, INC SOLID STATE FAIL-SAFE U NIT RESET LIST E D U L 99Y9 R E L E A S I N G D E V I C E * TYPICAL INSTALLATION FIGURE SS90-C RELEASE DEVICE/ CONTROL PANEL END LINK TURNBUCKLE FUSE LINK FUSE LINKS MOTOR REMOTE TEST PLATE ANNUNCIATOR * Actual configuration may differ. See door manufacturers recommendations and NFPA 80 for use of this device and fusible links with specific door. DO NOT install this unit without fusible links. DO NOT exceed 40lb. maximum pull rating on release mechanism. "SS90" MODEL C INSIDE VIEW FIGURE A TB TB2 TB3 TB4 DIAGNOSTIC LED's CLASS 2 WIRING *TRANSFORMER END LINK TROUBLE SOUNDER AUX. POWER RESET CLASS WIRING LOWER ENTRY CLASS 2 WIRING UPPER ENTRY TB5 BATTERY TEST SWITCH CLASS CLASS WIRING WIRING * TRANSFORMER FOUND IN 20VAC MODELS ONLY A

* 6. (a) Aux. Lower limit switch. Connect wiring from N/C electrical loop (switch closed when door is up) to TB screws &8 "or" N/O electrical loop (switch open with door up) to TB- & 6. This input precludes the door mechanism from releasing if a lower limit is detected (door is already closed). This circuit also turns off sounders in down limit. (b) Aux. Upper limit switch. Connect wiring from N/O electrical loop (switch closed when door is up) to TB-8 & 9 or N/C electrical loop (switch open with door up) to TB-8 & 3. Connection to an auxiliary up limit switch is required for 3 cycle obstruction count feature. Set aux. limit to toggle before operator limit when door is traveling toward open position. Improper adjustment will result in continuous cycling of door. * Note: Electrical loops must be provided as dry contacts and may not be used in conjunction with the simultaneous switching of a motor control or any other voltage through the same contacts. Connections of this type will result in immediate damage to the release device. Jumpers must remain installed on loops not being used. 7. Motor control relay (Delay relay) - Connect wiring from TB-4 & 7 across motor control down switch (For use with N/O down switch). This relay output latches to initiate a door closure thru the operator after a ten second delay. 8. Remote test station. - (option) This option disables the cycle counter to allow testing of the door without a mechanical release after 3 cycles. Connect remote test switch common to TB2-2, N/C to TB4- and N/O to TB4-3. Factory jumper should be removed between TB2-2 & TB4- when using test switch. Leave jumper in if test plate is not used. 9. Annunciator - (option) connect annunciator to TB-6 & 7. If Voice Module has been factory installed see SSVB Addendum. Note: Battery should not be connected until testing of unit is being performed. TESTING OF RELEASE DEVICE/CONTROL PANEL SHALL BE PERFORMED AND WITNESSED FOR NORMAL OPERATION AFTER INSTALLATION. REFER TO TEST PROCEDURES CONTAINED HEREIN, AS WELL AS ANY OTHER TESTING PROGRAMS RECOMMENDED BY DOOR MANUFACTURER. SS90 MODEL C RELEASE DEVICE/CONTROL PANEL POWER REQUIREMENTS & MECHANICAL SPECIFICATIONS VOLTAGE RATING SS90-C-24DC... 24VDC +0% / -5% SS90-C-24AC... 24VAC +0% / -5% SS90-C-20AC... 20VAC +0% / -5% CURRENT REQUIREMENTS () SUPERVISORY (non-alarm).00a / ALARM.500A MAX SUPERVISORY (non-alarm).00a / ALARM.500A MAX SUPERVISORY (non-alarm).00a / ALARM.500A MAX () Current max. with standard accessories including one Voice Module. Current of additional accessories shall not exceed fuse ratings. NOTE: Initial power up inrush current shall not exceed 3 times rated supervisory current on any model. MOTOR CONTROL SENSE - ALL MODELS Input Voltage: 24V ac/dc typical +5% / -0% Input Current: Not to exceed.004a FORM C OUTPUT (MAX. CONTACT RATING) 2A/30Vdc 60 Watt DC Resistive Load Only Combined Auxiliary Power: 2Vdc @.450a INITIATING/DOOR INPUTS CAUTION: All initiating devices shall be dry contact type only Maximum loop resistance: 00 Ohms Maximum current: Not to exceed.002a Maximum voltage: 5Vdc FUSES All fuses A @ 250V, 2AG Fast Acting Type MECHANICAL SPECIFICATIONS LOAD RATING(all models) PHYSICAL DIMENSIONS (all models) WEIGHT (includes battery) Support and Release : 40 LB. MAX. 5/8" x 0 x 5 w/flange (H x W x D) SS90-C-20vac approx. 3 lbs. 0 x 0 x 4 3/4 w/out SS90-C-24vac approx. 2 lbs. SS90-C-24vdc approx. 2 lbs. 2

SS90-C ELECTRICAL CONNECTIONS FIGURE 2 (2) End of Line Relay As per U.L. 864 (4) (6) Do Not loop wires under terminals. Break wire run to provide system supervision. TB5 - CHASSIS MOUNT POWER SUPPLY INPUT BATTERY 3 GRD 2 2VDC 4AH RED BLACK Smoke detector (5) (2)(4) (7) 2VDC Annunciator (Option) (8) OR Use TB- for common AUX.UP LIMIT COMMON AUX.UP LIMIT N/O AUX.UP LIMIT N/C AUX.DOWN LIMIT N/ O OR AUX.DOWN LIMIT N/ C FROM MOTOR 24V AC/DC () BLACK YELLOW RED Test Plate Option TB- TB THRU TB4 PC MOUNT 2 3 4 5 6 7 8 9 0 2 3 4 5 6 7 8 2 TB3 - MOTOR SENSE 2 CIRCUIT BOARD () TB4 - REMOTE TEST 2 3 4 Trouble relay non-delayed 2A @ 30VDC Delayed relay 2A @ 30VDC () TB2- AUX. POWER () Note:All circuitry connected to/from circuit board terminal blocks TB thru TB4 is low voltage/low current (see electrical specs page 2). 8 gauge energy limited control cable is recommended for all connections between operator and circuit board. () DOTTED LINES INDICATE FACTORY INSTALLED JUMPERS: REMOVE WHEN CONNECTING TO N/C DEVICE. DO NOT REMOVE JUMPER IF LOOP IS UNUSED. (2) SUPERVISORY DEVICE MUST BE INSTALLED (3) ALL FUSES A @ 250V, 2AG FAST ACTING (4) MAXIMUM LOOP RESISTANCE 00 OHMS (5) SEE NFPA 80 AND NFPA 72-993 FOR PROPER PLACEMENT OF DETECTOR (6) CLASS WIRING (20VAC Models) MUST ENTER PROPER OPENING. SEE FIGURE A (7) IF UNIT CONTAINS FACTORY INSTALLED VOICE MODULE OPTION REFER TO SSVB ADDENDUM. DO NOT CONNECT A SPEAKER TO TB-6&7. DAMAGE MAY RESULT TO UNIT. (8) AUX. UP LIMIT SWITCH MUST BE SET TO TOGGLE OPEN (N/C) OR CLOSED (N/O) BEFORE THE UP LIMIT SWITCH OF THE OPERATOR WHEN THE DOOR IS TRAVELING TOWARD IT'S OPEN POSITION. IF THE SWITCH IS IMPROPERLY SET THE DOOR WILL CONTINUE TO CYCLE AND WILL NOT PERFORM THE THREE CYCLE FUNCTION. Installation of all wiring must be performed in accordance with, but not limited to, the latest NFPA, U.L. and NEC standards and codes, as well as the requirements of the final authority having jurisdiction. In addition, all installations subject to the Canadian standards, shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring type, wiring gauge related to power capacity requirements and circuit length and wiring methods. 2A

FIGURE 2A : SS90 MODEL C supplemental wiring diagram- Typical completed system. See installation manual, Section C, Electrical Connections, for complete wiring instructions. This illustration supplements and Does Not replace Figure 2. Electrical Supervision: Do not loop wires under terminals. Break wire run to provide proper supervision. End of line relay as per U.L. 864 TB-3 (5)(0) Smoke detector 2VDC SOUNDER/ STROBE (Voice module optional) OPERATOR Auxiliary Open Limit See Detail A (3)(8) Auxiliary Close Limit See Detail B (3)(7) Close Button L L2 (3) Secondary POWER SOURCE TB-2 TEST PLATE YELLOW & BLACK TB-4 TB-7 24-30vac/dc Common (4) SS90-C CONTROL BOARD 24V *F (0) *F3 () TB2 TB 8 *F2 TB3 TB5 3 2 2 3 6 7 8 9 4 7 2 2 TB4 (2) C O M (4) M O N TB-6 TB-7 B L A C K R E D BATTERY (6) SAFETY EDGE Recommended low voltage wiring (all except power source 20vac models) : 8 gauge, power limited fire protective signaling cable (type FPL). Detail A Operator Auxiliary Open Limit Switch Dry contact only. Auxiliary Close Limit Switch Dry contact only. Detail B C N/O TB-9 C N/C TB-8 TB-8 TB- * All fuses 2AG, amp fast acting () Transformer installed on 20vac unit only. Class one wiring must enter proper opening. (2) Supervisory resistor shall be installed at all times. When connecting normally open device, install resistor at end-of-line for proper supervision. (3) Maximum loop resistance 00hms. (4) Observe proper polarity on motor sense (control voltage sample). Common must connect to TB3-2. (5) See NFPA 80, National Fire Code and all other applicable standards and codes for proper placement of detector. (6) A reversing safety edge shall be installed for use with this unit. DO NOT install this unit on a motorized door without a reversing safety edge. (7) This unit is shipped standard with a safety timer. The auxiliary down limit must be installed to prevent safety timer release under normal operation.. (8) With door traveling toward it's open position, set auxiliary open limit to toggle before limit switch of operator. Improperly adjusted auxiliary switch will cause the door to continuosly cycle. A normally open switch (closes when actuated) must be used for this connection. If a normally closed switch was provided, call tech support for alternate connections. This unit can be configured to function with a normally closed switch. (9) Proximity switches may also be used. Call tech support for information. (0) TB2 auxiliary 2vdc may be used to power 2vdc, 4 wire smoke detectors (4 maximum). TB2-, TB2-2 Installation of all wiring must be performed in accordance with, but not limited to, the latest NFPA, U.L. and NEC standards and codes, as well as the requirements of the final authority having jurisdiction. In addition, all installations subject to the Canadian standards, shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring type, wiring gauge related to power capacity requirements and circuit length and wiring methods. 2B

D. TEST PROCEDURES - TO BE PERFORMED BY FACTORY AUTHORIZED PERSONNEL ONLY! CLEAR FIRE DOOR OPENING AND PROHIBIT TRAFFIC THRU DOOR OPENING WHILE TESTING! Testing does not affect normal operation of alarm system when connected to release device/control panel. Testing of the SS90-C is independent of, and shall in no way be interpreted as an alternative method of, testing of a central fire alarm system, motorized operator and/or any other system component employed on the fire door or counter fire door installation. Complete testing and normal operation can only be accomplished with power applied to unit. This procedure describes testing of all options. Verify options ordered and installed with unit. All tests may not apply. POWER UP SEQUENCE: Follow proper sequence. Turning motor on before unit, or at the same time as unit, will result in a closure thru the motor. This is a normal condition when proper sequence is not followed. If a single electrical disconnect is provided for both motor and unit, have door if down limit when energizing. Turn on power to unit. When power is applied to unit under test the Power LED (red) will light on the bottom of the release device and the battery trouble sounder will begin to beep. Connect battery leads (observe polarity!) to silence battery trouble. Green LED will light indicating battery is connected and charging. Turn on power to motor. Motor Sense (Disable-amber) LED will light indicating power is present at motor control secondary. TEST PROCEDURES A). Enclosure mounted test switch: Depress and continue to hold test button on side of release device/control panel. Annunciator will turn on indicating a door closure is about to occur and after 0 second alarm verification (0 sec. delay), delay relay will turn on motor initiating a door closure. Optional annunciator will turn off when door makes lower limit. Release test button. Depress up button on door control to raise door to open position. 2 Remote test station: This test disables the internal counter circuit and allows the door to continuosly cycle if a suitable obstruction is utilized for such a test (See step 4). Insert key into remote test station and turn key in direction of test indicator. Annunciator will turn on and a door closure will occur immediately (no delay is provided). If no obstruction is placed in the path of the descending door, the door will fully close and the motor will turn off. If an obstruction is used, the door will continue to cycle until the key is returned to off. Return test switch to off position to silence test sounder, leaving the door closed. 3. Down limit detection: With door closed, depress and continue to hold enclosure mounted test switch. Annunciator will not turn on, indicating the door is already in the closed position. Release test button. Depress up button on door control to raise door to open position. 4. Three Cycle Obstruction test:warning! THIS EQUIPMENT IS DESIGNED TO BE USED IN CONJUNCTION WITH AN OPERATOR INCORPORATING A REVERSING FEATURE SAFETY EDGE. DO NOT EXECUTE THIS TEST WITHOUT A SAFETY EDGE INSTALLED! Place a chair or other suitable obstruction in the normal path of the door. Stand clear from opening. Depress and continue to hold down the enclosure mounted test button. The annunciator will turn on indicating that a door closure is about to occur. After factory adjusted 0 second delay, the device will turn on the motor initiating a closure. Upon contact with the suitable obstruction being utilized, the safety edge will reverse the motor raising the door to the open position. The SS90-C will make three (3) attempts to close through the motor, after which the SS90-C will turn off the motor when the door reaches the open position and release the door through the drop release mechanism. The door will drop onto the obstruction and will close fully when the obstruction is removed. The annunciator will continue to sound until the alarm condition has been cleared. Release test button. Reset fire door release mechanism, then reset Model C release mechanism by pushing reset knob in direction of arrow. Insert end link through enclosure opening and release reset knob latching the end link. Depress up button on motor control raising door to open position. B). Interrupt (turn off) power to motor operator. Make sure door is fully raised. 2. Note that Motor Sense/Lower Limit Disable LED (amber) is off on side of release device indicating power is off to motor and/or the door is not closed. Depress and continue to hold test button on side of release device. Annunciator will sound indicating a door closure is about to occur and after factory adjusted 0 second alarm verification (0 sec. delay) device will release door. Release test button. This test verifies a mechanical release in absence of power to the motor. 3. Reset fire door release mechanism, then reset Model C release mechanism by pushing reset lever in direction of arrow as indicated on device label. Fully insert end link through release device side opening and release reset lever to latch end link. 4. Restore power to the motor and raise door to its fully open position. 5. After completing all tests, verify that door is in its normal condition (open or closed) and that all power required for normal operation is restored to unit and operator. This equipment is designed to operate with its primary power source applied. 3

TROUBLE SHOOTING: SEE GUIDE AT REAR OF MANUAL IF PROBLEMS ARE ENCOUNTERED DURING TESTING OF UNIT. REMINDER: TESTING OF RELEASE DEVICE/CONTROL PANEL SHALL BE PERFORMED AND WITNESSED FOR NORMAL OPERATION AFTER INSTALLATION. Testing of the SS90-C release device/control panel is independent of, and shall in no way be interpreted as an alternative method of, testing of the fire alarm system, motorized operator and/or any other system component employed on the fire door or counter fire door installation. All system components shall be tested as per respective manufacturers procedures. MAINTENANCE REQUIREMENTS The "SS90" Model C release devices have been designed to require a minimum amount of system maintenance when installed and used in accordance with factory specifications. The unit has been designed and tested for use in indoor locations. Solid State Securities recommends weekly testing of the unit, but test intervals shall ultimately be subject to criteria established by the Final Authority Having Jurisdiction (AHJ). Serviceable fuses are provided for the following: See Figure 3 for fuse locations and the trouble shooting guide at the rear of this manual for further information.. Fuses F A @ 250V, 2AG Fast Acting, Input Power F2 A @ 250V, 2AG Fast Acting, Logic/Aux. Power F3 A @ 250V, 2AG Fast Acting, Battery F4 A @ 250V, 2AG Fast Acting, Motor Sense Replacement fuses shall be of equivalent rating and type may be ordered directly from the factory thru the technical support number provided below. Should servicing of fuses be required, personnel authorized to perform such maintenance shall ensure that; a) all traffic is prohibited through door opening, b) door is mechanically released and fully closed, c) all power is disconnected from unit including motor sense voltage on motorized doors. After servicing equipment as required, unit shall be tested and witnessed for proper operation as described in the TEST PROCEDURE contained herein. FIGURE 3 TB TB2 TB3 TB4 VR4 VR6 F4 VR VR2 F3 F2 F TECHNICAL SUPPORT 570-455-0577 4

ADDENDUM 09/25/95 MODEL SS90-C TROUBLESHOOTING GUIDE Verify that desired options are available on unit before troubleshooting. Refer to pages 2 & 2A for electrical connection information and the maintenance and service page of this manual for fuse locations. Troubleshooting shall be performed by factory authorized personnel only. Service and/or installation by unauthorized personnel shall void warranty. Review the following guide prior to requesting technical support. If technical support is required, unit serial number (found on front of manual and inside unit), as well as distributor who supplied unit must be supplied. SYMPTOM. Red Power LED does not light. 2. Green Battery LED does not light & trouble sounder stays on. 3. Amber Disable LED does not light 4. Unit goes into alarm as soon as power is applied 5. Annunciator does not shut off when door meets down limit. 6. Unit closes door before optional voice message is complete. 7. Unit does not respond to manual test button. 8. Unit does not shut off motor and mechanical release after 3 cycles. POSSIBLE TROUBLE A) Primary power source turned off. B) Loose connection on TB5 C) Incorrect polarity on D.C. unit D) Incorrect power source applied. Verify voltage and check fuse F. A) Battery leads not connected or leads may have bad connector. B) Battery connected using incorrect polarity. Red Black. Check fuse F3 C) Battery threshold circuit requires adjustment. Call Tech Support! D) Battery totally discharged. Replace battery. A) Motor control voltage not connected to TB3 B) Motor control is D.C.. Check polarity. C) Control voltage is above 30V. Check fuse F4. A) Alarm loop is not connected properly to TB. B) Alarm loop which is not being used must have jumper or resistor installed. If using N/C loop (TB-2&3), resistor must remain in TB-4&5, etc. A) Aux. down limit switch not connected properly. B) If using N/O down limit TB-&6, jumper must remain in TB-&8. A) Alarm delay must be lengthened to accommodate message. Call Tech Support! A) Unit is detecting down limit. Make sure Aux. down limit is connected properly. If N/O down limit is used, N/C loop (TB-&8) must have jumper installed. B) Possible defective switch. Call Tech Support! A) Aux. Up Limit not connected or connected improperly. Aux. limit switch must toggle before open limit of operator. Proper switch sequence is required for cycle count. Jumper must remain in 8&9 when using 8&3. B) Aux. Up Limit is not dry contact. Switching of voltage onto cycle count loop will result in immediate damage. 9. Green L.E.D. turns on and off as expected when battery is installed or removed, but trouble sounder stays on. A) Auxiliary power fuse F2 is blown. Measure TB2 for presence of 2VDC (3-4.8VDC). B) Damaged Aux. Power Reset switch. Measure across switch (0V normal). If 2VDC is present, switch is stuck open. C) Optional remote test plate is not connected properly or is not being used. If the test plate is not being used, the jumper must remain between TB2-2 & TB4-. UNIT SERIAL NUMBER DISTRIBUTOR TECHNICAL SUPPORT (570) 455-0577 9AM - 5PM EST MON-FRI 5

NOTES/TEST RECORDS Copy this sheet and attach to manual for additional test data as required. Maintain test records in a secure location for future reference. Serial Number TEST DATE PERFORMED BY WITNESSED BY COMMENTS 6