Site Requirements ADVANTAGE PLUS

Similar documents
Site Requirements. MODEL 2.0 Australia

SITE REQUIREMENTS 1 USER MANUAL INSTALLATION PACKAGE SITE REQUIREMENTS

Customer Requirements Pre-Installation Instructions

Water Pre-Filtration System Installation Instructions Endoscope Reprocessing Systems

Plumbing fittings should be hand tightened followed by one complete turn with the appropriate wrench.

CER OPTIMA. Endoscope Reprocessing System CER-1 & CER-2 Site Requirements. Introduction. Space Requirements

CER-1 & CER-2 Site Requirements

SITE REQUIREMENTS & INSTALLATION DSD-201 & SSD-102

CER-1 & CER-2 Installation & Testing Instructions

RELIANCE 400 LABORATORY GLASSWARE WASHER

ARES-G2 Rheometer. Site Preparation Guide. Revision A Issued June 2016 Page 1

Attendance Sheet. (List each model reviewed during this session) Print Name Signature Title. Print Name Signature Title.

ON TRACK Reprocessing In-service / Competency for CF/PCF/GIF Endoscopes (EVIS, EXERA, EXERA II)

CER OPTIMA. Service Manual. Endoscope Reprocessing System. CER OPTIMA Service Manual

Refrigerated Compressed Air Dryers

Endoscope Reprocessor Installation Instructions Endoscope Reprocessing System

Refrigerated Compressed Air Dryers

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

Cool IR. Model C104 - Cooling System. Instruction Manual

Non-Cycling Refrigerated Air Dryers. HPRplus SERIES 100 to 3000 scfm (170 to 5097 nm 3 /h)

Gerber Innovations M Series Laser. Site Preparation & Installation Manual

PRE-INSTALLATION GUIDE

FUTURE AIR SOLUTIONS OIL FREE SCROLL COMPRESSORS

Portable Air Conditioner 6,000 BTU 8,000 BTU 10,000 BTU

Heat of Compression Desiccant Air Dryers. HOC SERIES scfm ( nm 3 /h)

CER-1 / CER-2 (MV-1 / MV-2) (CLM-5001X / CLM-5002VX)

Refrigerated Compressed Air Dryers

SCFM REFRIGERATED COMPRESSED AIR DRYERS. CRN Series

Frosty Factory of America, Inc.

NON-CYCLING REFRIGERATED AIR DRYERS. RNC Series

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

Refrigerated Compressed Air Dryers

RNC Series SCFM Global Air Treatment

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System

Atlas Copco. Refrigerant Air Dryers FX Hz

IQ/OQ Protocol Installation Qualification/ Operation Qualification

MCGUIRE AIR COMPRESSORS Compressed Air Dryers. CRN Series. Refrigerated. Leading Technology. MCGUIRE AIR COMPRESSORS

Non-Cycling Refrigerated Air Dryers. HPRplus SERIES 100 to 3000 scfm (170 to 5097 nm 3 /h)

IMPORTANT SAFETY INFORMATION READ ALL...

DRY-PAK INDUSTRIAL AIR DRYER Installation and Instruction Manual

Chemical Transfer Pump Tube Set and Adapter Instructions

Quest 105, Dry155, and 205 Dual

Refrigerated Compressed Air Dryers 5-6,000 scfm

Sullair Drains for Compressed Air Systems Zero Air Loss and Timed Solenoid

RDS SERIES REFRIGERATED COMPRESSED AIR DRYERS ENERGY SAVING REFRIGERATED COMPRESSED AIR DRYERS SCFM

Non-Cycling Refrigerated Air Dryers

Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC iers.com

RNC Series SCFM Global Air Treatment

CPC PRODUCT DESCRIPTION

HYDROGARD Refrigerated Air Dryers HGD and DES Series

5) Do not start or stop the unit by inserting or pulling out the power plug.

GLC/GW-100 MANUAL INSTALLATION SERVICE PARTS REV.1.01

BASIL 6000 TUNNEL CAGE WASHER

Installation. 324 Series Built-In Dishwashers U L. Viking Range, LLC 111 Front Street Greenwood, Mississippi USA (662)

hinge right B 1 85 cm + 6,5-7 cm max. height of the device feet B cm B 3 85 cm D 2 75 cm (with a maximum opening angle of 170 )

GASS Module. User Manual. Gas Analysis Sampling System PERMA PURE

G34M Bulletin #69/ August 2003

twin tower desiccant compressed air dryers flow capacity: 200-9,000 scfm (340-15,300 Nm3/hr)

Installation. 15 W. Undercounter/Freestanding Ice Machine FGIM515 / CFGIM515 FPIM515 / CFPIM515

AirStar Clinical Air Compressor AS60, AS90 and AS120. Installation & Operating Instructions

OWNE R S MA N UA L. Made in USA. September 2015

Heat of Compression Desiccant Air Dryers. NRG-LES SERIES scfm ( nm 3 /h)

OX100/OX102. Limiting-current type Oxygen Analyzer. Bulletin 11M10A01-03E

Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions

Symphony Plus Pressurized Water Sanitizing Kit P/N

ZPA Heatless Regeneration ZHA Heated Regeneration ZBA Heated Blower Regeneration

User manual Flushing device VAS 6337/1a

CRN Series MCGUIRE AIR COMPRESSORS INC MCGUIRE AIR COMPRESSORS INC Refrigerated Compressed Air Dryers

Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions

DHR Accessories Requirements. Site Preparation Guide

Portable Air Conditioner with Evaporative Technology PE6-10R-03 Operating Instructions. Model No. PE6-10R Soleus Air International

Advantage Series Bathing System Specifications

Optional Lift + Automatic Air Operated Sliding Cover

MODEL MW200 MODEL MW600 AIR DRYER

EVAPORATIVE COOLING AND HUMIDIFICATION. High-Pressure System Wetted Media System

Refrigerated Compressed Air Dryers

INSTALLER'S MANUAL CLEAN BURN TRANSPORT HEATER MODEL: 45 TH

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

CNC Series Refrigerated Air Dryer CFM

Model No.: PS08-01 PS10-01 Ref: KY80 KY100

LXGeR and LXGePR GLASSWASHER

CPVS PRODUCT DESCRIPTION

PRE-INSTALLATION GUIDE for MODELS

DEDPV-705, DEDPV-705 Hi Alt Dryer Exhaust Duct Power Ventilator (DEDPV)

Cooling Capacity CFM in. w.c. (125 Pa)

Heat of Compression Desiccant Air Dryers. HCD SERIES scfm ( nm 3 /h)

Atlas Copco Stationary Air Compressors. GA30-90C WorkPlace Air System TM 30-90kW/40-125HP oil-injected rotary screw compressors

PRE-INSTALLATION GUIDE for MODELS

MODEL CMA-180UC PARTS MANUAL Rev 1.16

Ingersoll Rand kw Single Stage Contact-cooled rotary screw air compressors

Quest Dry 105, 155, and 205 Dual

DRYPOINT AC ADSORPTION DRYERS EFFICIENT, COMPACT, POWERFUL m 3 /h

Installation Guide. 15 W. Undercounter/Freestanding Nugget Ice Machine U L. Viking Range, LLC. 111 Front Street

Owner s Manual GLC MANUAL INSTALLATION SERVICE PARTS REV.1.00

Model No. PE2-07R / PE2-09R / 9000 BTU Portable Air Conditioner with dehumidifier & Fan PE2-07R-62 / PE2-09R-32 Operating Instructions

NHR-25 Feed Hopper with Agitator

Portable Air Conditioner and Heater With Heat Pump Technology Operating Instructions. Model No.: PH3-12R-03 Reference No.: KY2-34

Models. Options. Standard Features. LoH 2 O

Adsorption Dryers. AD 7 to 1300

Transcription:

Site Requirements ADVANTAGE PLUS Reprocessing System MODEL 2.0 International 1

MEDIVATORS is a registered trademark. MEDIVATORS ADVANTAGE is a trademark of MEDIVATORS Inc. Windows and Windows XP are registered trademarks of Microsoft Corporation. 50098-039 Rev A 2013 MEDIVATORS Inc. All rights reserved. This publication is protected by copyright. Copying, disclosure to others, or the use of this publication is prohibited without the express written consent of MEDIVATORS. MEDIVATORS reserves the right to make changes in the specifications shown herein without notice or obligation. Contact your MEDIVATORS representative or MEDIVATORS customer service for more information. 2

SITE REQUIREMENTS The purpose of this section is to provide the customer with requirements that need to be met to ensure the ADVANTAGE Plus will be properly installed. Applicable Documents ADVANTAGE Plus Endoscope List and Operator ID Form (PN 50092-380) ADVANTAGE Plus User Manual (PN 50097-429) It is the responsibility of the customer to meet these requirements to ensure proper installation of the ADVANTAGE Plus. The ADVANTAGE Plus will be delivered on a pallet along with multiple boxes. It is important to keep all the boxes received with the ADVANTAGE Plus together. It is the responsibility of the customer to provide qualified personnel to provide the connections for the ADVANTAGE Plus to the building supply (Water, Electrical, Drain, Air and Network/Internet) during the installation process. Any deviation from these specifications may cause operational issues that would not be covered by the Warranty. Water Supply Potable water is the minimum standard. Disinfectant water temperature requirements: RAPICIDE PA 30o : 35oC ± 2ºC RAPICIDE PA 20o : 25oC ± 2ºC ADASPOR SS: 25oC ± 2ºC The water supply must be able to provide an on-demand water temperaure to meet the requirements for the disinfectant chemistry used (see below). A thermostatic mixing valve may be needed to supply the required water temperature. If a mixing valve is used it must be accessible and located near the prefilter to aid in adjustment. The mixing valve should include a thermometer followed by a bypass valve to a drain. One mixing valve per reprocessor is recommended. The incoming waterline must be a minimum of 15 mm ID providing a flow rate of 5 L/min and a water pressure of 2 to 6 bar. Water consumption is approximately 30 liters/cycle for a standard endoscope disinfection cycle, 49 liters/cycle for an endoscope disinfection cycle with a detergent wash, and 68 liters/cycle for an endoscope disinfection cycle with two detergent washes. Water consumption for the ADVANTAGE Plus will vary depending on the incoming water temperatures. The reprocessor will extend the initial flush to allow the water to come up to temperature to meet the minimum required temperature of the disinfectant. Ensure water hardness is less than 12 gpg (200 ppm) for optimal performance. The pre-filter assembly has the dimensions of 66 cm H x 97 cm W x 15 cm D, is wall mounted and needs to be within 1.5 meters of the ADVANTAGE Plus. The incoming water connection to the pre-filter assembly is 1/2 NPT on the right hand side. All fittings and hoses for the output of the pre-filter assembly are included. A shut-off valve must be installed before the pre-filtration system. It is important that the valve be mounted within reach of the operator. It is highly recommended that the facility water be analyzed to determine if the supplied pre-filter is adequate. The MEDIVATORS endoscope reprocessors do not require backflow protection for the incoming water supply, nor is a backflow protection device installed in the reprocessor. If building or plumbing codes require backflow protection, then please consult your local codes, standards and/or guidelines, for applicable requirements. Drain A drain system capable of draining 12 L/min, less than 46 cm from the floor and vented will ensure the proper operation of the ADVANTAGE Plus. The supplied drain line has a 2.5 cm ID, 3.5 cm OD. 3

Air Supply The ADVANTAGE Plus system includes an air compressor that requires a dedicated circuit. If the ADVANTAGE Plus model purchased did not include the air compressor, the system may utilize house compressed air (dry, oil free) which must meet these required air pressure specifications:4 to 10 bar with a minimum flow volume of 0.71 L/s, maximum particle size is 5 microns, maximum dew point is 7 C, maximum oil concentration is 5 mg/m 3. Air usage is approximately 65 liters per cycle. A 6 mm ID flexible air hose (EPDM, braided, 10 bar minimum) is required to connect the ADVANTAGE Plus to the house air. This is not supplied with the ADVANTAGE Plus. The hose connects to a barbed fitting on the back of the ADVANTAGE Plus. Electrical Supply 100 to 240 VAC ± 10%, single phase, 50/60 Hz, 1000watts A GFI or RCD protected outlet should be located within the operator s reach. Power consumption 150 watts at idle, 400 watts during a cycle in one basin, 600 watts during a cycle in both basins, and a nominal peak of 1000 watts. The ADVANTAGE Plus can operate uninterrrupted with power losses up to 0.5 seconds. Power losses greater than 0.5 seconds without proper shutdown may produce system alarms and system shutdown. A UPS with a minimum rating of 1500 VA/865 watts is highly recommended. The role of the UPS is to solely protect the computer and will allow the Advantage Plus to operate for a short period of time without power allowing for an orderly shut down of the computer in the event of a power outage. Heat Load Idle: 500 BTU/hr Cycle (1 basin): 1400 BTU/hr Cycle (2 basins): 2000 BTU/hr Ventilation It is the Customer s Responsibility to ensure the room is in compliance with this requirement. This is not a requirement of the ADVANTAGE Plus but of the chemicals that are used for disinfection. It is a health and safety requirement to have a minimum of 10 air changes per hour in the room. During cycle operation and the chemical heating process, chemical vapor may be produced. The air exchange will minimize staff exposure to chemical vapors. A 10 cm flexible duct may be connected from the back of the ADVANTAGE Plus to the facility s exhaust system to aid in fume extraction. A minimum of 11.8 L/s at 62.25 Pa static pressure is required to properly vent the ADVANTAGE Plus. The ADVANTAGE Plus may also be supplied with an active vapor management system to aid in chemical vapor management. Please refer to the purchase order to determine the correct configuration of the ADVANTAGE Plus. Dimensions The ADVANTAGE Plus physical dimensions are 175 cm H x 124 cm W x 79 cm D, weight 180 kgs. If the optional air compressor is installed, the ADVANTAGE Plus will need an additional 28 cm at the back of the unit. Alternately, the compressor may be installed remotely (in an adjacent room, closet, wall space). Space is required on either side of the unit (approximately a combined 30 cm) for easy access to the internal components. If this is not available, the ADVANTAGE Plus contains a base with casters allowing the system to be moved. There should be adequate room for the ADVANTAGE Plus to be moved for access to accommodate maintenance. 4

124 cm 114 cm Figure 1. Front & Back Dimensions Air Compressor Figure 2. Side Dimensions & Clearance 5

Endoscope & User Information To ensure a smooth and trouble-free installation, the customer must supply a complete list of users and endoscopes that will be reprocessed in the ADVANTAGE Plus. Fill out the ADVANTAGE Plus Endoscope List & Operator ID form (PN 50092-380). Network/Remote Access The ADVANTAGE Plus is equipped with a PC based computer running Windows XP (SP3) which will allow full networking along with the capability of remote diagnostics. To allow for remote diagnostics an internet connection is required. This is highly recommended. This checklist should be utilized to ensure the installation site meets the required specifications. If all specifications are met, the site is suitable for the installation and use of the MEDIVATORS ADVANTAGE Plus Automated Endoscope Reprocessor. 6

SITE REQUIREMENTS Potable water is the minimum standard. Minimum flow rate 51pm with a pressure of 2-6 Bar Water Supply Water Temperature meets the requirements of the disinfectant chemistry used. The mixing valve must be accessible, if required. Hardness, less than 12 gpg (200 ppm) Pre-filter wall space 66 cm H x 97 cm W x 15 cm D Drain 12 L/min, less than 46 cm from the floor, vented Air Supply Electrical Supply Ventilation Unit Dimensions Included air compressor, adds 28 cm to depth of unit House compressed air requirements: (dry/oil free) 4 to 10 bar, minimum flow volume of 43 L/min, maximum particle size is 5 microns, maximum dew point is 7 C, maximum oil concentration is 5 mg/m 3 100 to 240 VAC ± 10%, single phase, 50/60 Hz, 1000 watts GFI or RCD protected outlet, accessible by user A minimum of 10 room air exchanges per hour Optional ventilation system available, adds 18 cm to the depth 175 cm H x 124 cm W x 79 cm D, 180 kgs. Add 30 cm of open space to the total width to aid with service access Endoscope List ADVANTAGE Endoscope List & Operator ID form (50092-380) completed Remote Access Internet connection (recommended) By signing below Customer acknowledges that (1) Customer reviewed these Site Requirements for the MEDIVATORS Reprocessor(s) listed on the face of this document; (2) Customer is solely responsible for meeting each of the specifications and requirements set forth in these Site Requirements to ensure proper installation and performance of the reprocessor(s); (3) Customer is able to meet each of these specifications and requirements; and (4) the failure of Customer to comply with these Site Requirements and any deviation from the specifications set forth herein may compromise the functionality of the reprocessor(s) and/or may cause operational issues, which will not be covered by the MEDIVATORS warranty and are hereby disclaimed by MEDIVATORS. Facility Representative Title Signature Date Email 7

8