NFPA 96, 2017 REVIEW SUMMARY

Similar documents
Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

JOINT CODE INTERPRETATION

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Winnipeg Fire Department Fire Prevention Branch

IMC Significant Changes Summary Tier I

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

Report on First Revisions with Statement June 2014 NFPA 101

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection:

Florida Building Code 2010

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Comparative Matrix A Comparison of the NFPA 96 and ICC Standards and Codes with regard to Commercial Kitchen Systems

Types of Detection. Fusible Link Detection - Most Common

Second Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 6/23/ :34 AM

Jacqueline Wilmot Fire Protection Engineer NFPA. Road Map for Mobile Food Truck Regulation

Changes in NFPA

Safety Tips for the Office

SAF-BCF SECOND REVISIONS WITH STATEMENTS

CHAPTER 5: EXHAUST SYSTEMS

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

Chapter One Commercial Kitchen Fires

CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

CLEAN AGENTS Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition

UNIFORM MECHANICAL CODE SIGNIFICANT CHANGE COMPARISON STUDY

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

Report on First Revisions with Statement June 2014 NFPA 101

Hot Topics. Helping You Protect Lives And Property. New Editions of NFPA Standards. By Mark Conroy

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

2012 International Mechanical Code Significant Changes. About the Significant Changes

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

WHEA FSE inspections.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Level I Chapter 1 Worksheet

Public Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

FIRE PROTECTION SYSTEMS

MOBILE FOOD VENDING Food Trucks & Trailers

Wausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records

Ships and marine technology Fireextinguishing. of galley cooking equipment

Introduction to the Exhaust Fan Interceptor Commercial Exhaust Fans from a Service Perspective

780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS

Recommended Amendments to the 2003 International Fire Code North Central Texas Council of Governments region

System Test Report CLEAN AGENT

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

NFPA 101 Life Safety Code Culture change 2012

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SANDUSKY FIRE DEPARTMENT Fire Prevention Bureau. Dear Prospective Food Vendor:

NFPA 96. Standard for. Ventilation Control and Fire Protection of Commercial. Cooking Operations Edition

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

Minimum Information Required to Process your Special Occasion Application. Parking area Access to site

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

UMC 2012 ( ): Item # 38

Report on First Revisions with Statement June 2014 NFPA 101

El Reno Fire Department Fire Alarm Plan Review Worksheet

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

ISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment

CARBON MONOXIDE ALARM STANDARDS ACT - ENACTMENT Act of Dec. 18, 2013, P.L. 1229, No. 121 Cl. 35 An Act

HLS Checklist Explanation and Examples

New Facilities. Minimum Requirements

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

SEMICONDUCTOR FABRICATION FACILITIES

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

BUILDING/FIRE CODE REFERENCES 2006 EDITION

SEMICONDUCTOR FABRICATION FACILITIES

UNIFORM MECHANICAL CODE

Chapter 4: Fire Protection Systems

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street?

SECTION COMMERCIAL-KITCHEN HOODS

2012 ICC Commercial Kitchen Hoods

CORE Protection Fire System Specification

Analysis of Changes for the 6 th Edition (2017) Florida Codes

Agency for Health Care Administration

XRRS Specification Fire Ready Hood

CITY & COUNTY OF DENVER COMMUNITY PLANNING & DEVELOPMENT BUILDING PERMIT POLICY

EXCELSIOR FIRE DISTRICT

New Construction Fire Inspection Process

Note: The event coordinator is responsible for compliance of all regulations.

Residential-based Care Facility R-4 Guideline

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

Agency for Health Care Administration

Transcription:

NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile and temporary cooking operations. The normative annex is written in mandatory language but is not intended to be enforced unless specifically adopted by a jurisdiction or is applied on a voluntary basis. This annex includes requirements not limited to clearance, hoods, ducts, terminations, fire extinguishing systems, carbon monoxide detectors, location, training, generators, LP-gas, as well as procedures for the use, inspection, testing, and maintenance of equipment. The language in the body of the standard clarifies that fixed and mobile cooking equipment is covered by NFPA 96. The term solid fuel is used in lieu of charcoal to cover the different types of solid fuel, not just one type. A device installed in a duct, such as a pollution control device, now must be protected by its own fire extinguishing system. 2) NOTED CHANGES OF SIGNIFICANCE 2014 Edition 2017 Edition Chapter 1 (pg 6) Administration Chapter 2 (pg 6) Referenced Publications Chapter 3 (pg 7) Definitions 3.2.7 Standard. A document, the main text of which contains only mandatory provisions using the word shall to indicate requirements and which is in a form generally suitable for mandatory reference by another standard or code or for adoption into law. Nonmandatory provisions are not to be considered a part of the requirements of a standard and shall be located in an appendix, annex, footnote, informational note, or other means as permitted in the Manual of Style for NFPA Technical Committee Documents. 3.2.7 Standard. An NFPA Standard, the main text of which contains only mandatory provisions using the word shall to indicate requirements and that is in a form generally suitable for mandatory reference by another standard or code or for adoption into law. Nonmandatory provisions are not to be considered a part of the requirements of a standard and shall be located in an appendix, annex, footnote, informational note, or other means as permitted in the NFPA Manuals of Style. When used in a generic sense, such as in the phrase standards development process or standards development activities, the term standards includes all NFPA Standards, including Codes, Standards, Recommended Practices, and Guides.

3.3.33.1 Fixed Baffle Hood. A listed unitary exhaust hood design where the grease removal device is a nonremovable assembly that contains an integral fire-activated waterwash fire-extinguishing system listed for this purpose. Chapter 4 (pg 10) 4.1.5 The responsibility for inspection, testing, maintenance, and cleanliness of the ventilation control and fire protection of the commercial cooking operations shall ultimately be that of the owner of the system, provided that this responsibility has not been transferred in written form to a management company, tenant, or other party. 4.1.9* Cooking equipment used in fixed, mobile, or temporary concessions, such as trucks, buses, trailers, pavilions, tents, or any form of roofed enclosure, shall comply with this standard unless otherwise exempted by the authority having jurisdiction in accordance with 1.3.2 of this standard. Chapter 5 (pg 12) Chapter 6 (pg 13) 6.1.2 Listed grease filters and grease removal devices that are removable but not an integral component of a specific listed exhaust hood shall be listed in accordance with ANSI/UL 3.3.52 Water-Wash Fire-Extinguishing System. A water-wash system that is listed as a re-extinguishing system. 3.3.53 Water-Wash System. A system that employs a water spray to clean grease from the plenum of an exhaust hood and portions of the ductwork on an intermittent or continuous basis. General Requirements 4.1.5 The responsibility for inspection, testing, maintenance, and cleanliness of the ventilation control and fire protection of the commercial cooking operations, including cooking appliances, shall ultimately be that of the owner of the system, provided that this responsibility has not been transferred in written form to a management company, tenant, or other party. 4.1.9* Cooking equipment used in fixed, mobile, or temporary concessions, such as trucks, buses, trailers, pavilions, tents, or any form of roofed enclosure, shall comply with this standard. 4.3.3.2 Listed single wall factory-built grease ducts shall be permitted to be enclosed with field-applied grease duct enclosure material where the material and the assembly of duct and material are listed for that application and installed in accordance with the grease duct manufacturer s listing and their installation instructions. Hoods Grease Removal Devices in Hoods 6.1.2 Listed grease filters and grease removal devices that are removable but not an integral component of a specific listed exhaust hood shall be listed in accordance with ANSI/UL

1046. 1046 and shall be designated on the filter. 6.2.1.2 Where grease removal devices are 6.2.1.2 Where grease removal devices are used in conjunction with charcoal or used in conjunction with solid fuel or solid charcoal-type broilers, including gas or fuel-type broilers, including gas or electrically electrically heated charbroilers, a minimum heated charbroilers, a minimum vertical vertical distance of 1.22 m (4 ft) shall be distance of 1.22 m (4 ft) shall be maintained maintained between the lower edge of the between the lower edge of the grease removal grease removal device and the cooking device and the cooking surface. surface. 6.2.5 Grease Filter Orientation. Grease filters that require a specific orientation to drain grease shall be clearly so designated, or the hood shall be constructed so that filters cannot be installed in the wrong orientation. Chapter 7 (pg 14) 7.1.4.1 Factory-built grease ducts shall be permitted to be installed in accordance with the listing and the manufacturer s instructions. 7.1.4.3.1 Where provided, drains shall be continuously welded to the exhaust duct or listed grease duct drains, in accordance with the terms of the listing and the manufacturer s installation manual Chapter 8 (pg 19) 8.2.3.2 The hood exhaust fan shall not be required to start upon activation of the extinguishing system if the exhaust fan and all cooking equipment served by the fan have been shut down. 8.2.3.3 The exhaust fan shall be provided with a means so that the fan is activated when any appliance under the hood is turned on. Chapter 9 (pg 21) 9.3.1.1 Fume incinerators, thermal recovery units, air pollution control devices, and/or other devices installed in ducts or hoods shall comply with the following: (1) The clearance requirements of Section 4.2 (2) Hood construction requirements in 6.2.5 Grease Filter Orientation. Grease filters that require a specific orientation to drain grease shall be clearly so designated on the face of the filter as to be visible with the filter installed, or the hood or filter shall be constructed so that filters cannot be installed in the wrong orientation. Exhaust Duct Systems 7.1.4.1 Factory-built grease ducts shall be permitted to be installed at a lesser slope in accordance with the listing and the manufacturer's instructions. 7.1.4.3.1 Where provided, drains shall be continuously welded to the exhaust duct in accordance with the terms of the listing and the manufacturer's installation manual Air Movement 8.2.3.2 The hood exhaust fan shall start upon activation of the extinguishing system if the exhaust fan and all cooking equipment served by the fan have been shut down, unless fan shutdown is required by a listed component of the ventilation system or by the listing of the extinguishing system. 8.2.3.3 The exhaust fan shall be provided with a means so that the fan is activated when any heat-producing cooking appliance under the hood is turned on. Auxiliary Equipment 9.3.1.1 Fume incinerators, thermal recovery units, air pollution control devices, and/or other devices installed in ducts or hoods shall comply with the following: (1) The clearance requirements of Section 4.2. (2) Hood construction requirements in Section 5.1.

Section 5.1 (3) Exhaust duct construction complying with Chapter 7 (4) Simultaneous operation requirements in 10.3.1 (5) Access panels or doors complying with Chapter 7 (6) In-line fans complying with 8.1.3.1 9.3.3 Any equipment, listed or otherwise, that provides secondary filtration or air pollution control and that is installed in the path of travel of exhaust products shall be provided with an approved automatic fireextinguishing system, installed in accordance with the fire-extinguishing system manufacturer s instructions, for the protection of the component sections of the equipment, and shall include protection of the ductwork downstream of the equipment, whether or not the equipment is provided with a damper. Chapter 10 (pg 22) 10.2.2* A placard shall be conspicuously placed near each extinguisher that states that the fire protection system shall be activated prior to using the fire extinguisher (3) Exhaust duct construction complying with Chapter 7. (4) Other equipment installed in a hood shall meet the simultaneous operation requirements in 10.3.1. (5) Other equipment installed in a duct complying with 10.1.3. (6) Access panels or doors complying with Chapter 7. (7) In-line fans complying with 8.1.3.1. 9.3.3 Any equipment installed in the path of exhaust products that provides secondary filtration or air pollution control shall be provided with an approved automatic fireextinguishing system, installed in accordance with the fire-extinguishing system manufacturer s instructions. 9.3.3.1 The fire-extinguishing system required by 9.3.3 shall provide protection for the component sections of the equipment, and ductwork downstream of the equipment. 9.3.7 If the heat source is non-electric and open flames are used, a carbon monoxide detector shall be installed in both the kitchen and dining areas. Fire-Extinguishing Equipment 10.1.3 Fume incinerators, thermal recovery units, air pollution control devices, or other devices installed in the exhaust duct, shall be protected by an automatic fire-extinguishing system. 10.2.2* A placard shall be conspicuously placed near each Class K extinguisher that states that the fire protection system shall be activated prior to using the fire extinguisher. 10.2.8 Fixed Baffle Hoods with Water Wash 10.2.8 Hoods with Water Wash 10.2.8.1 Grease removal devices, hood exhaust plenums, and exhaust ducts requiring protection in accordance with 10.1.1 shall be permitted to be protected by a listed fixed baffle hood containing a constant or fireactuated water-wash system that is listed and in compliance with ANSI/UL 300 or other equivalent standards and shall be installed in 10.2.8.1 Areas requiring protection in accordance with 10.1.1 shall be permitted to be protected by a water-wash system that is listed as a fire-extinguishing system in compliance with ANSI/UL 300 or other equivalent standards and installed in accordance with the requirements of its listing.

accordance with the requirements of their listing. 10.2.8.2 Each such area not provided with a listed water-wash extinguishing system shall be provided with a fire-extinguishing system listed for the purpose. 10.2.8.3 The water for listed fixed baffle hood assemblies shall be permitted to be supplied from the domestic water supply when the minimum water pressure and flow are provided in accordance with the terms of the listing. 10.2.8.4 The water supply shall be controlled by a supervised water supply control valve. 10.2.8.5 The water wash in a fixed baffle hood specifically listed to extinguish a fire shall be activated by the cooking equipment extinguishing system. 10.2.8.7 Where the fire-extinguishing system provides protection for the cooking equipment, hood, and duct, activation of the water wash shall not be required. 10.2.10 Water Valve Supervision. Valves controlling the water supply to listed fixed baffle hood assemblies, automatic fireextinguishing systems, or both shall be listed indicating type of valve and shall be supervised open by one of the following methods: (1) Central station, proprietary, or remote station alarm service (2) Local alarm service that will cause the sounding of an audible signal at a constantly attended point (3) Locking valves open (4)*Sealing of valves and approved weekly recorded inspection 10.3.1.1 Hoods installed end to end, back to back, or both, or sharing a common ductwork, and having a grease-producing 10.2.8.2 Each such area not provided with a listed water-wash fire-extinguishing system shall be provided with a fire-extinguishing system listed for the purpose. 10.2.8.3 The water supply for water-wash fire-extinguishing systems shall be permitted to be supplied from the domestic water supply when the minimum water pressure and flow are provided in accordance with the terms of the listing 10.2.8.4 The water supply for water-wash fire-extinguishing systems shall be controlled by a listed indicating valve. 10.2.8.5 Where a separate fire-extinguishing system is used for protection of cooking equipment only, a water-wash fireextinguishing system listed for protection of the grease removal device(s), hood exhaust plenum(s), exhaust duct(s), or combination thereof shall be provided with instructions and appropriate means for electrical interface for simultaneous activation. 10.2.10 Water Valve Supervision. Valves controlling the water supply to listed waterwash fire-extinguishing systems, automatic fire-extinguishing systems, or both shall be listed indicating type of valve and shall be supervised open by one of the following methods: (1) Central station, proprietary, or remote station alarm service (2) Local alarm service that will cause the sounding of an audible signal at a constantly attended point (3) Locking valves open (4)* Sealing of valves and approved weekly recorded inspection 10.3.1.1 Hoods installed end to end, back to back, or both, or sharing a common ductwork, not exceeding 22.9 m (75 ft) in distance from

appliance(s) located under one or more of the hoods shall be considered a single hazard area requiring simultaneous automatic fire protection in all hoods and ducts. 10.3.1.2 Hoods installed end to end, back to back, or both that do not share a common exhaust and are separated by a wall(s) or other means to ensure that grease-laden vapors exhausted under one hood cannot propagate to the other hoods or exhaust systems shall not be required to comply with 10.3.1.1. 10.5.1 A readily accessible means for manual activation shall be located between 1067 mm and 1219 mm (42 in. and 48 in.) above the floor, be accessible in the event of a fire, be located in a path of egress, and clearly identify the hazard protected. 10.5.1.1 At least one manual actuation device shall be located a minimum of 3 m (10 ft) and a maximum of 6 m (20 ft) from the protected hood exhaust system(s) within a path of egress or at an alternative location acceptable to the AHJ. 10.5.1.2 Manual activation using a cableoperated pull station shall not require more the farthest hood, and having a greaseproducing appliance(s) located under one or more of the hoods, shall be considered a single hazard area requiring simultaneous automatic fire protection in all hoods and ducts. 10.3.1.1.1 In hoods that are installed end to end, back to back, or both, and that share a common ductwork, the duct work beyond 22.9 m (75 ft) from the farthest hood shall be protected by an independent fireextinguishing system with its own detection system or by a fire-extinguishing system that activates simultaneously with the fireextinguishing system(s) protecting the hoods. 10.3.1.2 Hoods installed end to end, back to back, or both that do not share a common exhaust duct and are separated by a wall(s) or other means to ensure that grease-laden vapors exhausted under one hood cannot propagate to the other hoods, the hoods fireextinguishing system(s) shall be independent and shall not be required to simultaneously discharge. 10.3.1.3 Fume incinerators, thermal recovery units, air pollution control devices, or other devices installed in the exhaust duct shall not be required to comply with 10.3.1.1. 10.4.5 Solid fuel cooking operations shall not be required to be shut down. 10.5.1 All systems shall have both automatic and manual methods of actuation. 10.5.1.2 The manual actuation device shall clearly identify the hazard protected. 10.5.1.1 At least one manual actuation device shall be located in a means of egress or at a location acceptable to the AHJ.

than 178 N (40 lb) of force, with a pull movement not to exceed 356 mm (14 in.) to activate the automatic fire-extinguishing equipment. 10.5.2 The automatic and manual means of system activation external to the control head or releasing device shall be separate and independent of each other so that failure of one will not impair the operation of the other except as permitted by 10.5.3. 10.5.3 The manual means of system activation shall be permitted to be common with the automatic means if the manual activation device is located between the control head or releasing device and the first fusible link. 10.5.5 The means for manual activation shall be mechanical or rely on electrical power for activation in accordance with 10.5.6. 10.5.6 Electrical power shall be permitted to be used for manual activation if a standby power supply is provided or if supervision is provided in accordance with Section 10.7. 10.5.7 Instruction shall be provided to employees regarding the proper use of portable fire extinguishers and the manual activation of fire-extinguishing equipment. 10.7.1 Where electrical power is required to operate the fixed automatic fireextinguishing system, the system shall be provided with a reserve power supply and be monitored by a supervisory alarm except as permitted in 10.7.2. 10.7.2 Where fixed automatic fireextinguishing systems include automatic mechanical detection and actuation as a backup detection system, electrical power monitoring and a reserve power supply shall not be required 10.7.3 System supervision shall not be required where a fire-extinguishing system(s) is interconnected or interlocked with the cooking equipment power source(s) so that if the fire-extinguishing system becomes 10.5.3 Instruction regarding the proper use of portable fire extinguishers and the manual activation of fire-extinguishing equipment shall be documented and shall be provided by the management to new employees on hiring and to all employees annually.

inoperable due to power failure, all sources of fuel or electrical power that produce heat to all cooking equipment serviced by that hood shall automatically shut off. 10.7.4 System supervision shall not be required where an automatic fireextinguishing system, including automatic mechanical detection and actuation, is electrically connected to a listed fire-actuated water-wash system for simultaneous operation of both systems. 10.8.1 Hoods containing automatic fireextinguishing systems are protected areas; therefore, these hoods are not considered obstructions to overhead sprinkler systems and shall not require floor coverage underneath. 10.8.2 A single detection device, listed with the extinguishing system, shall be permitted for more than one appliance where installed in accordance with the terms of the listing Chapter 11 (pg 24) 11.2.4* Fusible links of the metal alloy type and automatic sprinklers of the metal alloy type shall be replaced at least semiannually except as permitted by 11.2.6 and 11.2.7. 10.7.1 Hoods containing automatic fireextinguishing systems are protected areas; therefore, these hoods shall not be considered obstructions to overhead sprinkler systems and shall not require additional sprinkler coverage underneath. 10.9.4 Carbon dioxide-type extinguishers shall not be permitted. Procedures for the Use, Inspection, Testing, and Maintenance of Equipment 11.1.4* Instructions shall be provided to new employees on hiring and to all employees semiannually on the use of portable fire extinguishers and the manual actuation of the fire-extinguishing system. 11.1.4.1 Responsibility for compliance with 11.1.4 shall be that of management of the commercial cooking operation. 11.1.4.2 Records of compliance with 11.1.4 shall be maintained and shall be available to the authority having jurisdiction 11.2.4* Fusible links of the metal alloy type and automatic sprinklers of the metal alloy type shall be replaced at least semiannually. 11.2.8.1 Records, including certificates of inspection and maintenance, shall be permitted to be forwarded to or shared with the authority having jurisdiction either by hard copy or electronically. 11.6.1.1 A measurement system of deposition

Chapter 12 (pg 26) Chapter 13 (pg 26) Chapter 14 (pg 27) 14.3.4* Gas-operated equipment utilizing solid fuel for flavoring that meets all the following conditions shall not be required to have a separate exhaust system: (1)* The solid fuel holder (smoker box) shall be listed with the gas-operated equipment. (2) The solid fuel holder shall be located underneath the gas burners. (3) Spark arresters conforming with 14.1.6 shall be provided. (4)* The maximum quantity of solid fuel consumed shall not exceed 2 kg (4.5 lb) per hour per 29.3 kw (100,000 Btu/hr) of gas burner capacity. (5) The gas-operated equipment shall be protected by a fire suppression system listed for the equipment, including the solid fuel holder. (6) Gas-operated equipment with integral solid fuel holder(s) intended for flavoring, shall be established to trigger a need to clean when the exhaust system is inspected at the frequencies in Table 11.4. 11.6.1.1.1 Hoods, grease removal devices, fans, ducts, and other appurtenances shall be cleaned to remove combustible contaminants to a minimum of 50 μm (0.002 in.). 11.6.1.1.2 A grease depth gauge comb as shown in Figure 11.6.1.1.2 shall be placed upon the surface to measure grease depth. 11.6.1.1.3 Where a measured depth of 2000 μm (0.078 in.) is observed, the surfaces shall be cleaned in accordance with 11.6.1. 11.6.1.1.4 Where a measured depth of 3175 μm (0.125 in.) is observed in a fan housing, the surfaces shall be cleaned in accordance with 11.6.1. 11.6.16 Metal containers used to collect grease drippings shall be inspected or emptied at least weekly. Minimum Safety Requirements for Cooking Equipment Recirculating Systems Solid Fuel Cooking Operations 14.3.4* Gas-operated equipment utilizing solid fuel for flavoring that meets all the following conditions shall not be required to have a separate exhaust system: (1)* The solid fuel holder (smoker box) shall be listed with the gas-operated equipment. (2) The solid fuel holder shall be located underneath the gas burners. (3) Spark arresters conforming with 14.1.6 shall be provided (4)* The maximum quantity of solid fuel consumed shall not exceed 0.45 kg (1 lb) per hour per 29.3 kw (100,000 Btu/hr) of gas burner capacity. (5) The gas-operated equipment shall be protected by a fire suppression system listed for the equipment, including the solid fuel holder. (6) Gas-operated equipment with integral solid fuel holder(s) intended for flavoring,

such as radiant charbroiler(s), shall comply simultaneously with the requirements of ANSI/UL 300 that address that gas radiant charbroiler(s) and mesquite wood charbroiler(s). (7) A fire suppression system nozzle(s) shall be installed to protect the solid fuel holder. (8) The fire suppression system shall be designed and installed to protect the entire cooking operation. (9) Each solid fuel holder shall be limited to a size of 32.8 L (2000 in^3 ), with no dimension to exceed 51 cm (20 in.). (10) A maximum of one solid fuel holder for each 29.3 kw (100,000 Btu/hr), or portion thereof, of burner capacity shall be permitted. (11) The inspection frequency shall be the same as for solid fuel cooking operations in Table 11.4. Chapter 15 (pg 31) 15.2 Fire-Extinguishing Equipment. For fire-extinguishing equipment on downdraft appliance ventilation systems, the following shall apply: (1) Cooking surface, duct, and plenum protection shall be provided (2) At least one fusible link or heat detector shall be installed within each exhaust duct opening in accordance with the manufacturer s listing. (3) A fusible link or heat detector shall be provided above each protected cooking appliance and in accordance with the extinguishing system manufacturer s listing. (4) A manual activation device shall be provided as part of each appliance at a height acceptable to the authority having jurisdiction. (5) Portable fire extinguishers shall be provided in accordance with Section 10.10. such as radiant charbroiler(s), shall comply simultaneously with the requirements of ANSI/UL 300 that address the gas radiant charbroiler(s) and mesquite wood charbroiler(s). (7) A fire suppression system nozzle(s) shall be installed to protect the solid fuel holder. (8) The fire suppression system shall be designed and installed to protect the entire cooking operation. (9) Each solid fuel holder shall be limited to a size of 2.5 L (150 in^3 ), with no dimension to exceed 51 cm (20 in.). (10) A maximum of one solid fuel holder for each 29.3 kw (100,000 Btu/hr), or portion thereof, of burner capacity shall be permitted. (11) Solid fuel shall be immersed in water for a continuous period of at least 24 hours immediately prior to being placed in the cooking equipment. (12) The inspection frequency shall be the same as for solid fuel cooking operations in Table 11.4. Downdraft Appliance Ventilation Systems 15.2 Fire-Extinguishing Equipment. For fire-extinguishing equipment on downdraft appliance ventilation systems, the following shall apply: (1) Cooking surface, duct, and plenum protection shall be provided. (2) At least one fusible link or heat detector shall be installed within each exhaust duct opening in accordance with the manufacturer s listing. (3) A fusible link or heat detector shall be provided for each protected cooking appliance located in the plenum area of that appliance or in accordance with the extinguishing system manufacturer s listing. (4) A manual activation device shall be provided as part of each appliance at a height acceptable to the authority having jurisdiction. (5) Portable fire extinguishers shall be provided in accordance with Section 10.9.

3) RESULTS IN A FUNDING ISSUE (Do Not Adopt Until Resolved)? No. 4) FIRE PROTECTION PROGRAM CHANGE REQUIRED (Changes Required During Implementation After Adoption)? Yes, instructions on the use of portable fire extinguishers and the manual activation of fire-extinguishing equipment shall be provided to new employees on hiring and to all employees annually. 5) IMPORTANT INFORMATION FOR FIELD ENGINEERS? No. Reviewed By: Date: Caroline Yano May 23, 2017