Networkable VAV Controller Specification and Installation Instructions. Controller Model EVCB14NIT4X (4 TRIACS / independent / external motor)

Similar documents
Networkable Fan Coil Controller Specification and Installation Instructions

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

Networkable VAV Controller Specification and Installation Instructions

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

TDU Series LCD Thermostat For EFCB and EVCB Controllers. Models. Features. Functions. Onboard Sensors. Model # Temp RH CO2 Color.

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

Humidity Controller Specification and Installation Instructions. Model HRO20

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network

± 3% or better at 40%RH and 23ºC [73ºF] 0.8 mm 2 [18 AWG] minimum

Fan Coil Thermostat. Specification & Installation Instructions TFC54F3Y1. Technical Data

Humidity Controller Specification and Installation Instructions. Model HROB20

Pressurized Condensate Return System (PCR)

READ AND SAVE THESE INSTRUCTIONS

Direct Steam Injection Humidifier

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

T600MEP-2 Programmable Economizer Thermostat

Multi-Steam HDR* SKD-R Series Direct Steam Injection Humidifier with Integrated Re-Evaporator. Installation Instructions and User Manual

I/O ZONE 560/583 USERS GUIDE

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

Ramp It Up VAV Ramps and Controller Possiblities

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

Carbon Monoxide Transmitter

CONTENTS. Installation Guide. VT7200 Series

Installation and Maintenance Manual IM

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

Touch Screen Thermostat. MTSC/SUPER, MTSC24/SUPER Series. MTS/SUPER, MTS24/SUPER Series. Owner s manual and technician settings

Safety & Installation Instructions

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

CLEANROOM MONITOR CR3A Network - Installation Instructions

T-32-TS Touchscreen Thermostat. Installation Manual

Smart Temp. Model

TB7200 Series Communicating Zone Thermostats

T7984 A,B,C Electronic Modulating Control Thermostats

DAP III Zone Master User s Guide

Manual for the integration in BMS/GTC

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

TEC210x-2 Series Networked Thermostats

VT8300 Series Installation Guide 24 Vac Low Voltage

TB7300 Series Communicating Fan Coil Thermostats 24 VAC/FOR COMMERCIAL AND LODGING HVAC APPLICATIONS

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat

RCS Residential Control Systems Inc.

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.

T6984 A,D,E Electronic Floating Control Thermostats

RPM1600 Series Room Pressure Monitors

Product Manual SZ1009

Document # R01

INSTALLATION & USER MANUAL

Parts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins

Series Temperature Controller Instruction Sheet

Introduction. What is the W2W Open controller?

TEC2100 Series Networked Thermostats

Comfort System T-21-P Touchscreen Thermostat Installation Manual

Bacnet Room Setpoint & Temp Display. Descriptions. Specifications

REMOTE CONTROL FOR CHILLER MYCHILLER

Programmable Thermostat

Document # R00

Siemens RDY2000BN. Start Up Guide

User s Manual

ET10 Series Stand-alone LCD Fan Coil Thermostat

Two-Channel Gas Controller

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

RC-2000 Thermostat Installation Instructions

Table of Contents. WSHP Open v3

Programmable Thermostat

CLEVER CONTROL Version: V3

Control Sequence Number

INSTALLATION MANUAL. Need Help? This manual covers the following models: T915. Power Type. Thermostat Applications Guide. Page.

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

Please read this manual carefully before installation and use.

ETN-24-SUPER-PROG (US Program - Celsius)

PIR Ready VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications September 1, 2010

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page.

SC Installation, Operation & Application Guide

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

INSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page.

Product Manual SZ1022/SZ1031/SZ1035/

Commercial Touchscreen Thermostat

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

ETAF Series VDC Fan output LCD Fan Coil Thermostat

RC-122BZ Two Stage Heat/Cool 2 Stage Heat / 2 Stage Cool Thermostat Installation Instructions

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408

INSTALLATION MANUAL. Need Help? This manual covers TopTech models: TT-N-721 and T721. Power Type. Thermostat Applications Guide.

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

Safety & Installation Instructions

INSTALLATION MANUAL. Need Help? This manual covers the following models: T725. Power Type. Thermostat Applications Guide. Page.

Smart Temp. ApolloP/n Installation Manual. Version 1.0

Digital Programmable

Model: Edge-HC. 1 edge-hc

Temperature Controllers

Natural Ventilation Controller with 24vDC drive NVC-1204

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

T6590 Series FAN-COIL CONTROLLER FEATURES APPLICATIONS PRODUCT DATA

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

- Data Brochure tekmarnet 4 Thermostat 542e

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Transcription:

Controller Model EVCB14NIT4X (4 TRIACS / independent / external motor) For use with external floating or modulating actuators TRL Series Thermostat TRL24 (Thermostat 2x4) TRLH24 (Thermostat 2x4 with Humidity) TRLG24 (Thermostat 2x4 with CO 2) TRLGH24 (Thermostat 2x4 with CO 2 and Humidity) TDU Series Thermostat TDU10 TDU40 TDU70 (Grey LCD, white enclosure) (Black LCD, black enclosure) (Black LCD, white enclosure) Description The EVCB Series is a combination controller and thermostat with support for networked communications via the BACnet MS/TP or Modbus protocol. The EVCB Series controller is compatible with both TRL24 and TDU series thermostats. The Networkable VAV Controller is designed for simple and accurate control of any variable air volume box in a number of zone control configurations. Its field configurable algorithms enable versatile implementation of required control sequences. TRL24 Series EVCB Series TDU10 / TDU40 / TDU70 Series Features Field configured VAV algorithms, inputs and outputs Control external actuators using analog (0-10Vdc, adjustable) or floating signals with feedback On-board differential pressure sensor Select direction on analog outputs Simple air balancing and commissioning via thermostat Configurable PI (Proportional-Integral) function Independent, configurable proportional control band and dead band per ramp Activate output with CO 2 sensor from TRL/TDU or external input Selectable internal or external temperature sensor (10KΩ) Changeover by contact or external temperature sensor Internal and external temperature sensor calibration Freeze protection Removable, raising clamp, non-strip terminals Operational Features Backlit LCD with simple icon and text driven menus Select thermostat s default display Network service port via on-board mini USB connector Manual night setback or no occupancy override Multi level lockable access menu and setpoint Selectable Fahrenheit or Celsius scale 3-wire connection to controller and 4 push keys Network Communication BACnet MS/TP or Modbus communication port Select MAC address via DIP switch or via network Automatic baud rate detection BACnet MS/TP Automatic device instance configuration Copy & broadcast configuration via thermostat menu or via BACnet to other controllers BACnet scheduler Firmware upgradeable via BACnet Support COV (change of value) Modbus Modbus @ 9600, 19200, 38400 or 57600 bps RTU Slave, 8 bits (configurable parity and stop bits) Connects to any Modbus master EVCB14NIT4X-TRL24-TDU-V500-180928-ESA EVCB14NIT4X Page 1

Controller Specifications Description Power consumption Power supply Inputs Outputs Real Time Clock BACnet Modbus Communication connection Electrical connection Operating temperature Storage temperature Relative Humidity Weight 10 VA max 22 to 26 Vac 50/60 Hz EVCB14NIT4X 2 Universal inputs (Thermistor 10KΩ Type 3, digital 24Vac/dry contact, or 0-10Vdc) 2 digital inputs 2 analog outputs (0-10 Vdc or 2-10Vdc; selectable) 4 TRIAC outputs 24 Vac, 500mA max thermal fuse in series with each TRIAC output (on/off, pulse, or 2 floating outputs) Real-time clock (RTC) with super capacitor backup (approximately 3 days) BACnet MS/TP @ 9600, 19200, 38400 or 76800 bps (BAS-C) Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and stop bit configuration: No parity, 2 stop bit Even parity, 1 stop bit Odd parity, 1 stop bit 24 AWG twisted-shield cable (Belden 9841 or equivalent). Max 0ft (15m) between controller and thermostat 0.8 mm 2 [18 AWG] minimum 0ºC to 50ºC [32ºF to 122ºF] -30ºC to 50ºC [-22ºF to 122ºF] 5 to 95% non condensing 1.8 kg. [4 lb] E Dimensions A = 7.20 182.9mm B = 1.22 31.0mm C = 2.93 74.3mm D = 3.74 94.9mm E = 3.45 87.6mm C A D B Thermostat Specifications Description Temperature Sensor (TRL24 and TDU) Setpoint range Control accuracy Display resolution 10ºC to 40ºC [50ºF to 104ºF] Temperature: ±0.4ºC [0.8ºF] ±0.1ºC [0.2ºF] Humidity Sensor (TRLH24, TRLGH24 and TDU models with Humidity Sensors) Sensor range Display resolution 0.1% 5 to 95%RH CO 2 Sensor (TRLG24, TRLGH24 and TDU models with CO 2 Sensors) Other Operating principle Sensor Range Setpoint range Accuracy Self-calibrating, Non-Dispersive Infrared (NDIR) 0 to 2000 ppm 100 to 2000 ppm ±30 ppm ±3% of reading Response time 2 minutes by 90% Display resolution Electrical connection Network service port Power supply Power consumption Operating temperature Storage temperature Relative humidity 1 ppm TRL24 and TDU Series 3 wires to VAV controller and 2 wires to BACnet/Modbus network 0.8 mm 2 [18 AWG] minimum Mini USB connector 24Vac 1VA 0ºC to 50ºC [32ºF to 122ºF] -30ºC to 50ºC [-22ºF to 122ºF] 5 to 95 % non condensing Enclosure protection IP 30 (EN 60529) Weight 120 g. [0.25 lb] www.neptronic.com EVCB14NIT4X Page 2

C E D Dimensions A = 2.85 73mm B = 4.85 123mm C = 1.00 24mm D = 2.36 60mm E = 3.27 83mm B TRL24 E D A = 4.94 125mm B = 2.87 72.8mm C = 3.44 87mm D = 1.22 31mm E = 0.75 19 mm F = 2.00 51mm G = 2.18 55mm TDU R.095 TYP A B G A C F R6.542 TYP TDU Models Model # Temp RH CO 2 PIR Color TDU10-100 TDU10-101 TDU10-102 TDU10-103 TDU10-104 TDU10-105 TDU10-106 TDU10-107 grey LCD white enclosure TDU10 Series Model # Temp RH CO 2 PIR Color TDU40-100 TDU40-101 TDU40-102 TDU40-103 TDU40-104 TDU40-105 TDU40-106 black LCD black enclosure TDU40-107 TDU40 Series Model # Temp RH CO 2 PIR Color TDU70-100 TDU70-101 TDU70-102 TDU70-103 TDU70-104 TDU70-105 TDU70-106 TDU70-107 black LCD white enclosure TDU70 Series www.neptronic.com EVCB14NIT4X Page 3

Interface TRL24.. AM PM.. MO TU WE TH FR SA SU %RH C F Cooling ON A: Automatic Heating ON A: Automatic Fan ON A: Automatic Communication Status Menu Locked Programming mode (Technician setting) %RH Alarm status Energy saving mode (NSB or Occupancy) Percentage of humidity C or F ºC: Celsius scale ºF: Fahrenheit scale TDU %RH C F AM PM Network Communication Alarm Status User Lock Energy Saving Mode (NSB/OCC) Time ppm Parts Per Million 1 2 3 4 5 6 7 C F %RH Programming Mode (Technician Setting) Schedule ºC: Celsius Scale ºF: Fahrenheit Scale %RH: Humidity A Automatic Mode Cooling Heating Fan Mechanical Installation- Actuator 1. Manually close the damper blades and position the actuator to 0º or 90º. 2. Slide the actuator onto the shaft. 3. Tighten the nuts on the U bolt to the shaft with an 8mm wrench to a torque of 150 in.lb. [17 Nm]. 4. Slide the mounting bracket under the actuator. Ensure free movement of the slot at the base of the actuator. Place the bracket pin at mid distance of the slot. 5. Affix the bracket to the ductwork with #8 self-tapping screws. 6. Connect the cable from the EVC to the terminal in the actuator as shown. External 180 in. lb. Actuator Do not press the clutch when the actuator is powered. Terminals on the Actuator 1 2 3 4 5 MON (-) (black) SUPPLY (+) (red) FEEDBACK (green) CONTROL (white) Signal cable from EVC controller Use to connect the external motor on EVCB14NIT4X. Green: Feedback White: Control Red: 24Vac Black: Common www.neptronic.com EVCB14NIT4X Page 4

Mounting Instructions TRL24 CAUTION: Remove power to avoid a risk of malfunction. A. Remove the captive screw that s holding the base and the front cover of the unit together. B. Lift the front cover of the unit to separate it from the base. C. Pull all wires through the holes in the base. D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections. E. Mount the control module on the base and secure using the screw. A B C D E TDU CAUTION: Remove power to avoid a risk of malfunction. A. Remove the wall mounting plate (highlighted) from the back of the thermostat. B. Install the mounting plate on the gang box. C. Pull the wires through the base hole and make the appropriate connections. D. Mount the thermostat onto the wall plate. To mount the thermostat correctly, place the top of the thermostat on the mounting plate first and push it into the grooves to snap it into place. E. Secure the thermostat using the screw (supplied). A B C D E BACnet or Modbus Address DIP Switch (DS1) MAC address for communication, are selectable by DIP switch using binary logic. If you do not change device instance in program mode, it will be automatically modified according to the MAC address. Note: Avoid using addresses above 246 when selecting Modbus MAC address. MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 Default Device Instance 0 OFF OFF OFF OFF OFF OFF OFF OFF 153000 1 ON OFF OFF OFF OFF OFF OFF OFF 153001 2 OFF ON OFF OFF OFF OFF OFF OFF 153002 3 ON ON OFF OFF OFF OFF OFF OFF 153003 4 OFF OFF ON OFF OFF OFF OFF OFF 153004 126 OFF ON ON ON ON ON ON OFF 153126 127 ON ON ON ON ON ON ON OFF 153127 * Slave addresses available by setting DS.8 to ON www.neptronic.com EVCB14NIT4X Page 5

INT EXT JP1 INT EXT JP2 TB1 TB2 TB3 TB4 TB5 TB6 ON 1 2 3 4 5 6 7 8 DS1 TB7 3 2 1 5 4 3 2 1 3 2 1 3 2 1 3 2 1 8 7 6 5 4 3 2 1 4 3 2 1 Wiring We strongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. TRL24 and TDU TB1 1 2 3 4 5 6 7 Pwr Data Optional: connect to enable service port High Total Pressure Low Static Pressure Data Pwr JP3 (End of line) None = No end of line 120 Ohms = Last node on network TXD RXD JP3 EOL B- (out) A+ (out) To other BACnet devices RXD Flash receiving data via network B- (in) A+ (in) TXD Flash transmitting data via network Status Flash communicating via thermostat Power On 24Vac applied to TB1 Power Status DS1 DIP Switch The 8 DIP switches represent a binary logic to calculate the MAC address. Default = all OFF AI2 AI1 2 analog inputs (config.) External temp, changeover, normally cool/ heat, setpoint air flow, CO 2,air supply temp AO2 AO1 DI2 DI1 2 analog outputs (config.) Cool ramp 1 or 2, heat ramp 1 or 2, CO 2, setpoint airflow 2 digital inputs (config.) DI2: Override, normally cool/heat DI1: OCC open/close, NSB open /close TO4 JP2 (TO3 / TO4 input voltage) INT = 24Vac supplied internally by TB1 EXT = Apply 24Vac to pin 5 of TB2 JP1 (TO1 / TO2 input voltage) INT = 24Vac supplied internally by TB1 EXT = Apply 24Vac to pin 1 of TB2 TO3 24Vac input (TO3/TO4) TO2 TO1 24Vac input (TO2/TO1) 24Vac 4 TRIAC outputs (config.) Cool 1 or 2, heat 1 or 2, CO 2 On/Off (config close/open percent) Floating (config float time) Pulse (heat only) Direct or reverse 24Vac Power Input/Output 24Vac www.neptronic.com EVCB14NIT4X Page 6

PGM RUN DATA PWR PCB Drawings TRL24 Thermostat 3 wire cable (TB1 #1, 2 & 3) Connect TB1 #6 (A+) & #7 (B-) to EVCB to enable the BACnet service port. Mode Selector Jumper RUN = Operation Mode PGM = Programming Mode JP1 A B C 1 2 3 4 5 6 7 TB1 PWR DATA A+ B- Connect to VAV controller Optional: connect to BACnet network to enable service port Mode Selection (JP1) JP1 JP1 RUN PGM RUN PGM RUN: Thermostat is in Operation Mode. Thermostat must be set in this mode for normal system operation. If not locked, setpoint and control mode can be changed by the end user. PGM: Thermostat is set in Programming Mode. Refer to the following sections for more details. CO2 sensor (TRLG24 and TRLGH24 only) Avoid touching the CO2 sensor as this may cause incorrect readings Temperature sensor (all models) Humidity sensor (TRLH24 and TRLGH24 only) BACnet service port TDU Thermostat 3 wire cable (TB1 #1, 2 & 3) Connect TB1 #6 (A+) & #7 (B-) to EVCB to enable the BACnet service port. Mode Selector Jumper RUN = Operation Mode PGM = Programming Mode JP1 RUN PGM TB1 1 2 3 4 5 6 7 A+ B- Mode Selection (JP1) JP1 RUN PGM RUN: Thermostat is in Operation Mode. Thermostat must be set in this mode for normal system operation. If not locked, setpoint and control mode can be changed by the end user. CO2 sensor (models with CO2 sensors) Connect to EVCB Optional: connect to BACnet network to enable service port JP1 RUN PGM PGM: Thermostat is set in Programming Mode. Refer to the following sections for more details. Avoid touching the CO2 sensor as this may cause incorrect readings BACnet service port Temperature sensor (all models) Humidity sensors (models with humidity sensors) Access to Menus The menu overviews and options are the same for both TRL24 and TDU thermostats. However, the action key or the key used to access the menus and save changes is different in the thermostats. Use the following menu overviews with the appropriate action key as per your thermostat. Action Keys on Thermostat Action Key TRL24 TDU Task Press to access the programming menus and save any changes. Press to return to the previous step without saving. www.neptronic.com EVCB14NIT4X Page 7

Pressure & Applications Menu (1 of 7) For a description of the default settings for each application refer to Annex A: Control Apps on page 19. Main Menu Sub Menu Configuration Main Menu *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** PrSs (Pressure) Pressur Mode Ind (independent) dep (dependent) BV.50 "APPS" Motor Minimum Pos Cooling 10% (0-100) AV.90 Motor Minimum Pos Heating 10% (0-100) AV.91 "APPS" APPS (Applications) InPt (Inputs) OutP (Outputs) Control Apps Cl (cool only) ClHt (cool & heat) CHrh (cool, heat, & reheat) CO2 (carbon dioxide) itos (ITOS) FPbo (fan powered box ON) FPbA (fan powered box Auto) Confirm Control apps NO (cancel) YES (confirm) "InPt" The APPS represent pre-defined default settings for selected applications. If you select Yes, the settings in Annex A will be applied and override any values already configured. We recommend selecting the `Control Apps` before changing any other configurations. Once selected, certain configurations, such as NSB, proportional bands, and deadbands, will be erased and reset to factory default values. tmp (Temperature) Mot (Motor) Setc (Settings) rmp (Ramps) NET (Network) HrS (Time & Date) OPt (Options) Only available with CO 2 sensor models www.neptronic.com EVCB14NIT4X Page 8

Inputs Menu (2 of 7) AI1, AI2, DI1 and DI2 Main Menu Main Menu Sub Menu Configuration PrSs (Pressure) APPS (Applications) InPt (Inputs) OutP (Outputs) tmp (Temperature) Mot (Motor) Setc (Settings) rmp (Ramps) Config Input AI1 AI2 DI1 DI2 *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** AI1 Signal Type MSV.1 OFF (disabled) EtS (external temp sensor) SENs (sensor) NoCl (normally cool) NoHt (normally heat) StFl (setpnt airflow 0-10Vdc) CO2 (carbon dioxide) ASt (Air supply temp sensor) mor (Motor position) StFl*(setpnt airflow 0-10Vdc) CO2 (carbon dioxide) ASt (Air supply temp sensor) mor (Motor position) NSB-OCC Contact MSV.10 OFF OCCo (occupancy open) OCCc (occupancy closed) nsbo (night set back open) nsbc (night set back closed) AI1 AI2 Signal Type MSV.2 AI2 OFF (disabled) EtS (external temp sensor) SENs (sensor) NoCl (normally cool) NoHt (normally heat) DI1 "AI2" CH Over Setpnt 24 C "AI2" CO2 Maximum Range 2000 ppm "AI2" "DI1" CH Over Setpnt 24 C "DI1" CO2 Maximum Range 2000 ppm "DI1" "DI2" NSB Overide delay Min 120 min (0-180) AV.58 AV.140 AV.58 AV.140 OCC Minimum Time in Min 30 min (0-240) AV.62 AV.60 "AI2" CO2 Setpnt 800 ppm "DI1" CO2 Setpnt 800 ppm No OCC Overide Delay Min 120 min (0-180) AV.61 NSB Mode StP (setpoint) Off AV.141 To display CO2 without generating an alarm, use a setpoint higher than 2000ppm or the CO2 Maximum Range (highest of the 2). AV.141 To display CO2 without generating an alarm, use a setpoint higher than 2000ppm or the CO2 Maximum Range (highest of the 2). BV.20 Appears only if using thermostats with temperature and humidity sensors. For TRLG, TRLGH and TDU thermostats with CO2 sensors, go to "Opt" menu. CO2 DISPLAY NO YES No OCC Heating setpnt 16 C / 61 F BV.65 When set to YES, the unit will not display the time when in Operation Mode Appears only if using thermostats with temperature and humidity sensors. For TRLG, TRLGH and TDU thermostats with CO2 sensors, go to "Opt" menu. CO2 DISPLAY NO YES BV.65 When set to YES, the unit will not display the time when in Operation Mode AV.19 "AI2" "DI1" No OCC Cooling setpnt 28 C / 82 F AV.18 "DI2" NET (Network) HrS (Time & Date) OPt (Options) Only available with CO 2 sensor models DI2 Signal Type OFF Ovrd (override all) OVH1 (override heat 1) OVH2 (override heat 2) OVHt (override all heat) NoCl (normally cool) NoHt (normally heat) MSV.14 DI2 NSB Heating setpnt 16 C / 61 F "OutP" DI2 Contact NO (normally open) NC (normally closed) "OutP" AV.19 BV.36 NSB Cooling setpnt 28 C / 82 F DI2 Delay Seconds 120 (0-3600) AV.18 AV.64 NSB Motor Mode Auto OPEn "OutP" MSV.36 "OutP" www.neptronic.com EVCB14NIT4X Page 9

TRIAC Outputs Menu (3 of 7) TO1 and TO2 Main Menu Main Menu Sub Menu Configuration PrSs (Pressure) APPS (Applications) InPt (Inputs) OutP (Outputs) Output Config TO1 TO2 TO3 TO4 AO1 AO2 *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** TO1 Ramp MSV.25 TO1 OFF Cr1 (cooling ramp 1) Cr2 (cooling ramp 2) Hr1 (heating ramp 1) Hr2 (heating ramp 2) CO2 (carbon dioxide) StFl (setpnt airflow 0-10Vdc) Cor (changeover ramp) CH1 (cool/heat 1) ANLg (analog 0-10Vdc) "TO2" TO1 Signal Type MSV.26 OnOf (on/off) FLt (floating) PuLs (pulsed) * * = Only if Hr1 or Hr2 is selected TO1 Close Percent 40% (15-80%) TO1-TO2 Floating Time in Sec 100 sec (15 to 420 secs) If CO2 was selected AV.77 AV.75 TO1 Open Percent 0% [0-(TO1 cls pos-4)] AV.78 TO1 DIR-REV DIR (direct) REV (reverse) TO1-TO2 DIR-REV DIR (direct) REV (reverse) BV.32 BV.30 "TO2" "TO3" tmp (Temperature) Mot (Motor) Setc (Settings) TO2 Ramp MSV.27 OFF Cr1 (cooling ramp 1) Cr2 (cooling ramp 2) Hr1 (heating ramp 1) Hr2 (heating ramp 2) CO2 (carbon dioxide) StFl (setpnt airflow 0-10Vdc) Cor (changeover ramp) TO2 "TO3" TO2 Signal Type OnOf (on/off) PuLs (pulsed) MSV.28 TO2 Close Percent 40% (15-80%) AV.79 TO2 Open Percent 0% [0-(TO2 cls pos-4)] AV.80 TO2 DIR-REV DIR (direct) REV (reverse) BV.33 "TO3" rmp (Ramps) CH1 (cool/heat 1) ANLg (analog 0-10Vdc) "TO2 Close Percent" NET (Network) HrS (Time & Date) OPt (Options) Only available with CO 2 sensor models www.neptronic.com EVCB14NIT4X Page 10

TRIAC Outputs Menu (4 of 7) TO3 and TO4 Main Menu Sub Menu Configuration Main Menu *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** PrSs (Pressure) APPS (Applications) InPt (Inputs) OutP (Outputs) tmp (Temperature) Output Config TO1 TO2 TO3 TO4 AO1 AO2 TO3 Ramp MSV.29 OFF Cr1 (cooling ramp 1) Cr2 (cooling ramp 2) Hr1 (heating ramp 1) Hr2 (heating ramp 2) CO2 (carbon dioxide) StFl (setpnt airflow 0-10Vdc) Cor (changeover ramp) TO3 "TO4" TO3 Signal Type OnOf (on/off) FLt (floating) PuLs (pulsed) * MSV.30 * = Only if Hr1 or Hr2 is selected TO3 Close Percent 40% (15-80%) AV.81 TO3-TO4 Floating Time in Sec 100 sec (15 to 420 secs) If CO2 was selected AV.76 TO3 Open Percent 0% [0-(TO3 cls pos-4)] AV.82 TO3 DIR-REV DIR (direct) REV (reverse) TO3-TO4 DIR-REV DIR (direct) REV (reverse) BV.34 BV.31 "TO4" "AO1" Mot (Motor) CH1 (cool/heat 1) ANLg (analog 0-10Vdc) Setc (Settings) rmp (Ramps) NET (Network) TO4 Ramp OFF Cr1 (cooling ramp 1) Cr2 (cooling ramp 2) Hr1 (heating ramp 1) Hr2 (heating ramp 2) CO2 (carbon dioxide) MSV.31 TO4 "AO1" TO4 Signal Type OnOf (on/off) PuLs (pulsed) MSV.32 TO4 Close Percent 40% (15-80%) AV.83 TO4 Open Percent 0% [0-(TO4 cls pos-4)] AV.84 TO4 DIR-REV DIR (direct) REV (reverse) BV.35 "AO1" StFl (setpnt airflow 0-10Vdc) Cor (changeover ramp) HrS (Time & Date) CH1 (cool/heat 1) ANLg (analog 0-10Vdc) "TO4 Close Percent" OPt (Options) Only available with CO 2 sensor models www.neptronic.com EVCB14NIT4X Page 11

Analog Outputs Menu (5 of 7) AO1 and AO2 Main Menu Sub Menu Configuration *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** Main Menu PrSs (Pressure) APPS (Applications) InPt (Inputs) OutP (Outputs) tmp (Temperature) Output Config TO1 TO2 TO3 TO4 AO1 AO2 AO1 Ramp MSV.20 AO1 OFF Cr1 (cooling ramp 1) Cr2 (cooling ramp 2) Hr1 (heating ramp 1) Hr2 (heating ramp 2) CO2 (carbon dioxide) StFl (stpnt airflow 0-10Vdc) AO2 Ramp MSV.22 OFF Cr1 (cooling ramp 1) Cr2 (cooling ramp 2) Hr1 (heating ramp 1) Hr2 (heating ramp 2) CO2 (carbon dioxide) AO2 "AO2" AO1 Minimum Voltage 0.0 Vdc "tmp" AO2 Minimum Voltage 0.0 Vdc AV.70 AV.72 AO1 Maximum Voltage 10.0 Vdc AO2 Maximum Voltage 10.0 Vdc AV.71 AV.73 AO1 DIR-REV DIR (direct) REV (reverse) AO2 DIR-REV DIR (direct) REV (reverse) BV.25 BV.26 "AO2" "tmp" Mot (Motor) StFl (stpnt airflow 0-10Vdc) Setc (Settings) rmp (Ramps) NET (Network) HrS (Time & Date) OPt (Options) Only available with CO 2 sensor models www.neptronic.com EVCB14NIT4X Page 12

Settings Menu (6 of 7) Temp, Motor, and Settings Main Menu Main Menu PrSs (Pressure) APPS (Applications) InPt (Inputs) OutP (Outputs) tmp (Temperature) Mot (Motor) Sub Menu Intern Temp Sensor Offset Actual temp C/ F AV.10 StFl* (stpnt airflow 0-10Vdc) Cor (changeover ramp) CH1 (cool/heat) ANLg (analog 0-10Vdc) Extern Temp Sensor Offset Actual temp C/ F AV.11 (± 5 C / ± 10 F) Appears only if AI1 or AI2 = EtS Configuration *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** (± 5 C / ± 10 F) Motor Signal Ramp OFF Cr1 (cooling ramp 1) Cr2 (cooling ramp 2) Hr1 (heating ramp 1) Hr2 (heating ramp 2) PRESSUR INDEPEN OUTPUT FLt1 (Floating1 using TO1/TO2) FLt2 (Floating2 using TO3/TO4) mot (Motor using control wires) MSV.35 MSV.40 Motor DIR-REV DIR (direct) REV (reverse) Motor minimum voltage 2 V (0 V-AV.96) AV.95 "SEtc" BV.40 User Minimum Setpnt 15.0 C / 59 F (10 C-AV.17 / 50 F-AV.17) User Setpnt 22.0 C / 72 F (Av.16 AV.17) AV.16 AV.15 Motor maximum voltage 10 V (AV.95-10 V) AV.96 User Maximum Setpnt 30.0 C / 86 F (AV.16-40 C / AV.16-104 F) Temp Control Sensor MSV.4 ItS (internal sensor) EtS (external sensor) NEt (network) EtS appears only if AI1 or AI2 is set to EtS AV.17 Motor feedback minimum voltage 2 V (0 V-AV.98) AV.97 User Setpnt Locked No (unlocked) Yes (locked) "mot" BV.2 Network timeout Minutes 5 min (0-60 min) AV.145 "mot" Motor feedback maximum voltage 10 V (AV.97-10 V) AV.98 "SEtc" Setc (Settings) rmp (Ramps) NET (Network) Temp Control Mode MSV.17 Auto (automatic all modes) HEAt (heat/off) COOl (cool/off) ON (manual heat/cool) CLHt (auto/off) BV.3 Enable onoff Control Mode No (Disabled) Yes (Enabled) Display Info MSV.95 t c (temp & demand) StP (setpoint & demand) t c (temp only) StP (setpoint) OFF (no display: blank) Freeze Protect No (Disabled) Yes (Enabled) BV.6 Cooling anti cycle minutes 2 min (0-15 min) AV.51 Cl Ht Switch Time in Minutes Airflow Intgral time in Min Heating Intgral time in Sec Cooling Intgral time in Sec HrS (Time & Date) 0 min (0-120 min) AV.170 0 min (0-60 min) AV.106 0 sec (0-250 sec) AV.30 0 sec (0-250 sec) AV.50 OPt (Options) Only available with CO 2 sensor models "rmp" www.neptronic.com EVCB14NIT4X Page 13

Settings Menu (7 of 7) Ramps, Network, Time, and Options Main Menu Main Menu Sub Menu Configuration PrSs (Pressure) Ramp Setting COr (changeover) Cr1 (cooling ramp 1) Cr2 (cooling ramp 2) Hr1 (heating ramp 1) Hr2 (heating ramp 2) *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** CH Over Prop Band AV.56 2.0 C / 4.0 F (0.5-5 C / 1-9 F) CR1 Prop Band AV.41 2.0 C / 4.0 F (0.5-5 C / 1-9 F) CH Over Dead Band AV.57 0.3 C / 0.6 F (0-5 C / 0-9 F) CR1 Dead Band AV.42 0.3 C / 0.6 F (0-5 C / 0-9 F) "Cr1" "Cr2" APPS (Applications) CR2 Prop Band AV.46 2.0 C / 4.0 F (0.5-5 C / 1-9 F) CR2 Dead Band AV.47 0.3 C / 0.6 F (0-5 C / 0-9 F) "Hr1" InPt (Inputs) OutP (Outputs) Network Choice bac (BACnet) mod (Modbus) "BACnet Auto Baud Rate" "Modbus Auto Baud Rate" Hr1 Prop Band AV.21 2.0 C / 4.0 F (0.5-5 C / 1-9 F) Hr2 Prop Band AV.24 2.0 C / 4.0 F (0.5-5 C / 1-9 F) Hr1 Dead Band AV.22 0.3 C / 0.6 F (0-5 C / 0-9 F) Hr2 Dead Band AV.25 0.3 C / 0.6 F (0-5 C / 0-9 F) "Hr2" "NEt" tmp (Temperature) Mot (Motor) Setc (Settings) rmp (Ramps) Network Config type (Type) mod bac CPYc (copy config) If type = bac, menu contains "type", "bac" and "CPYc" If type = mod, menu contains "type" and "mod" Modbus Auto Baud Rate No (Manual) Yes (Automatic) BACnet Auto Baud Rate No (Manual) Yes (Automatic) Start Address 0 (0-254) AV.165 Modbus Baud Rate 57.6k (9.6k, 19.2k, 38.4, 57.6k) Modifiable only if Auto Baud Rate set to "No". Bacnet Baud Rate 1001 76.8k (9.6k, 19.2k, 38.4, 76.8k) Modifiable only if Auto Baud Rate set to "No". End Address 0 (0-254: max=start + 63) AV.166 Local Time Modbus Comport Config NP2s (no parity, 2 stop bits) EP1s (even parity, 1 stop bit) OP1s (odd parity, 1 stop bit) MSTP MAC Address 0 (0-254) Modifiable only if all DS1 DIP switches are set to OFF. Confirm Copy Config No (cancel) Yes (confirm) 1000 BV.90 Local Time Modbus Address 1 (1-246) Modifiable only if all DS1 DIP switches are set to OFF. 0153000 0 (device instance) "HrS" Copy Config in (in progress) Local Date "HrS" MSTP MAX Master 127 (1-127) Copy Config Result Succeed AV.167 Refer to Copy Config Annnex for a complete list of messages and error codes. "CPYc" "HrS" NET (Network) HrS (Time & Date) Set Time Display format 24 (24-hour format) 12 (AM/PM format) Appears only if using TRLG or TRLGH or TDU thermostats with CO2 sensors. Hours 12 (0-23 or 1-12 am/pm) Appears only if using TRLG or TRLGH or TDU thermostats with CO2 sensors. Minutes 00 (00-59) Month 1 (1-12) Local Date Year 15 (15-99) Day 1 (1-31) Local Date "OPt" OPt (Options) Only available with CO 2 sensor models For thermostats with temperature and humidity sensors, go to "InPt" menu. CO2 DISPLAY YES NO BV.65 When set to YES, the unit will not display the time when in Operation Mode For thermostats with temperature and humidity sensors, go to "InPt" menu. CO2 Setpnt 800 ppm AV.141 To display CO2 without generating an alarm, use a setpoint higher than 2000ppm or the CO2 Maximum Range (highest of the 2). Appears only if using thermostats with CO2 sensors. CO2 Control Source BV.66 trl ANLg Appears only if using thermostats with Humidity sensors. DISPLAY Humidty YES NO BV.60 "PrSs" www.neptronic.com EVCB14NIT4X Page 14

Operation Menus This menu is accessible through normal operation mode. The Mode Selector jumper (JP1) of the thermostat must be set to the RUN position (Operation Mode). Refer to Wiring on page 6. Note: Since the action keys are different on TRL and TDU thermostat series, both keys have been included in the instructions. Refer to the Action Keys on Thermostat section to know and use the key as available on your thermostat. 1. Press the [ / ] and keys simultaneously for 5 seconds. The Enter Password screen appears. 2. Enter the password within 1 minute by using the arrow keys to increase or decrease the value and the [ / ] and keys to toggle between the digits. a. Password 372 = Temperature Offset Menu b. Password 637 = Network Settings Menu c. Password 757 = Airflow Balance Mode 3. If you enter the wrong password, the thermostat displays Eror and returns to Operation Mode. The thermostat will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 minutes. The changed values will be saved automatically. Menu 372 Temperature Offset 1. Intern Temp Sensor Offset Range: 10 to 40ºC [50 to 104ºF] Offset: Increment: Max ± 5ºC 0.1ºC [0.2ºF] Compare the displayed temperature reading with a known value from a thermometer. To offset or calibrate the sensor, use the arrows key to set the desired temperature reading. This is useful for thermostats installed in areas where the temperature read is slightly different than the room s actual temperature. For example, a thermostat placed right under the air diffuser. If the thermostat is set to use an external temperature sensor (EtS), the thermostat displays OFF. 2. Extern Temper Sensor Offset Range: 0 to 50ºC [41 to 122ºF] Offset: Increment: Max ± 5ºC 0.1ºC [0.2ºF] This option appears if you ve set one of the analog inputs to EtS (External temperature sensor). When the thermostat is connected to the appropriate analog input, the display shows the temperature read by the external temperature sensor. Adjust the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, then the unit displays the sensor's limit. 3. Input3 Reading Range: 250mV (0") to 4000mV (1") Displays the voltage output value in mv of the pressure sensor. 4. Input3 Minimum Reading Range: Default: 10mV to 180mV 60mV This setting represents the deadband of the pressure sensor in mv. For advanced users or special applications only. We recommend that you use the default setting of 60mV. Menu 637 Network Settings If type = bac, menu contains "type", "bac" and "CPYc" If type = mod, menu contains "type" and "mod" Network Config type (Type) mod (Modbus) bac (BACnet) CPYc (copy config) End (exit menu) Network Choice bac (BACnet) mod (Modbus) Modbus Auto Baud Rate No (Manual) Yes (Automatic) BACnet Auto Baud Rate No (Manual) Yes (Automatic) "BACnet Auto Baud Rate" "Modbus Auto Baud Rate" Modbus Baud Rate 57.6k (9.6k, 19.2k, 38.4, 57.6k) Modifiable only if Auto Baud Rate set to "No". Bacnet Baud Rate 1001 76.8k (9.6k, 19.2k, 38.4, 76.8k) Modifiable only if Auto Baud Rate set to "No". Modbus Comport Config NP2s (no parity, 2 stop bits) EP1s (even parity, 1 stop bit) OP1s (odd parity, 1 stop bit) MSTP MAC Address 0 (0-254) Modifiable only if all DS1 DIP switches are set to OFF. 1000 Modbus Address 1 (1-246) Modifiable only if all DS1 DIP switches are set to OFF. 0153000 0 (device instance) Returns to run mode MSTP MAX Master 127 (1-127) "CPYc" Exit menu and return to normal operation Start Address 0 (0-254) AV.165 End Address 0 (0-254: max=start + 63) AV.166 Confirm Copy Config No (cancel) Yes (confirm) BV.90 Returns to run mode Copy Config in (in progress) Copy Config Result Succeed AV.167 Returns to run mode *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** www.neptronic.com EVCB14NIT4X Page 15

Menu 757 Airflow Balance Mode Pressur Filter Time In Sec Airflow Intgral time in Min Air Flow Scale MSV.41 Select Airflow KFactor "SEtc" 2 sec (1-10 sec) AV.100 0 min (0-60 min) AV.106 1 1200 AV.101 VAV Config COnf (configuration) SEtc (settings) bal (balancing) mot (motor) End (exit menu) Airflow Setting COOl HEAt AV.103 Maximum Cooling Airflow 1000 (Min cool airflow to Kfactor) AV.105 Maximum Heating Airflow 1000 (Min heat airflow to Kfactor) 10 100 Minimum Cooling Airflow 200 (0 to max cool airflow) Minimum Heating Airflow 200 (0 to max heat airflow) AV.102 AV.104 "HEAt" Range depends on air flow scale from previous step: (1) = 100-9995 (10) = 10.0-999.5 (100) = 1.0-99.9 "bal" Exit menu and return to normal operation Airflow Balance CLOs (close) Min (minimum flow) ma (maximum flow) OPEn (fully opened) MSV.47 Close Motor 130 (see note) Minimum Airflow AV.114 133 (same as Close Motor) Maximum Airflow 135 (see note) AV.114 AV.112 "mot" "mot" "mot" Adjusts the offset of the airflow reading. Offset range depends on selected air flow scale in Conf menu. (1) = +/-500 (10) = +/-50.0 (100) = +/-5.00 Displays the airflow based on the Kfactor. Range depends on air flow scale in Conf menu:. (1) = 100-9995 (10) = 10.0-999.5 (100) = 1.00-99.95 Motor Overide Auto (automatic) OPEn (open) CLOs (close) FLOl (airflow low) FLOh (airflow high) MSV.37 Open Motor AV.112 135 (same as Maximum Airflow) Returns to run mode Flow value depends on the actual mode of the system: Heating = heating airflow Cooling = cooling airflow "mot" *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** Note: Refer to EVCB-Airflow Balance Instructions on Neptronic website for further information on airflow balancing function. Reset to Factory Default Settings This will erase all actual configurations and replace them with the factory default settings. 1. The Mode Selector jumper (JP1) of the thermostat must be set to the RUN position (Operation Mode). Refer to Wiring on page 6. 2. During the power up sequence of the controller and thermostat (when the firmware versions are displayed), press and hold both the and keys. 3. The Enter Password screen appears. Enter 372 within 1 minute by using the arrow keys to increase or decrease the value and the [ / ] and keys to toggle between the digits. 4. Use the arrow keys to select YES and then press [ / ]. www.neptronic.com EVCB14NIT4X Page 16

Operation Mode The Mode Selector Jumper (JP1) of the thermostat must be set to the RUN position (Operation Mode). Refer to Wiring on page 6. TRL24 CO 2 reading in ppm (CO 2 display option must be enabled in programming mode ) Appears if in Night Setback (NSB) or Occupancy (OCC) mode. Flashes if overridden by user. C %RH Actual demand Room temperature Alternates between room temperature for 8 sec and then room humidity for 2 sec. (requires Humidity sensor thermostats ) Press for 5 sec. to display air flow (if using pressure sensors ) Press once to display control mode Press twice to display setpoint Press to toggle between C and F Press to change mode : - Auto - Off C Appears if setpoint adjustment is locked Setpoint value - Cool only - Heat only Exits after 5 sec. Exits after 5 sec. Exits after 3 sec. Change setpoint value Scroll through the following values : "Airflow" * "Airflow Setpoint" * "Actual Damper Pos Percent " "Air Supply Temp" * appears only in pressure independent mode appears only if "AST" is selected for the Analog Input Signal Type TDU CO2 reading in ppm (CO2 display option must be enabled in programming mode ) Appears if in Night Setback (NSB) or Occupancy (OCC) mode. Flashes if overridden by user. Press for 5 sec. to display air flow (if using pressure sensors ) Press once to display control mode Press to toggle between C and F C Press twice to display setpoint Actual demand Fan icon appears in fan -powered box applications only Appears if setpoint adjustment is locked Room temperature %RH C Change setpoint value Alternates between room temperature for 8 sec and then room humidity for 2 sec. (requires Humidity sensor thermostats) Exits after 5 sec. Exits after 5 sec. Exits after 3 sec. Setpoint value Scroll through the following values : "Airflow" * "Airflow Setpoint " * "Actual Damper Pos Percent " "Air Supply Temp " * appears only in pressure independent mode appears only if "AST" is selected for the Analog Input Signal Type Press to change mode : - Auto - Off - Cool only - Heat only www.neptronic.com EVCB14NIT4X Page 17

Power Up Upon power up, the LCD illuminates and all segments appear for 2 seconds. The thermostat then displays its current version of the thermostat for 2 seconds followed by the current version of the controller for 2 seconds. Pressing any key on the thermostat illuminates the LCD for 4 seconds. CO 2 (Thermostats with CO 2 Sensors) If enabled via the configuration menu, the thermostat displays the CO 2 reading on the first line above the temperature reading. If CO 2 display is enabled, the time will not be displayed. Temperature Display and Setpoint If enabled in the "Display Info" menu (see Settings Menu (6 of 7) Temp, Motor, and Settings on page 13), the thermostat displays the temperature reading. If the sensor is disconnected or short circuited, then the unit displays the sensor's limit. To toggle the temperature scale between ºC and ºF, press the key. To display the setpoint, press the or key twice. The setpoint appears for 5 seconds. To adjust the setpoint, press the arrow keys while the temperature is displayed. If the setpoint adjustment has been locked Setpnt Locked, the lock symbol appears. Humidity If enabled in the "Options" menu (see Settings Menu (7 of 7) Ramps, Network, Time on page 14), the thermostat displays the temperature reading for 8 seconds and then displays the humidity reading for 2 seconds. If the sensor is disconnected or short circuited, then the unit displays the sensor's limit. Airflow and Air Supply Temperature Press and hold the [ / ] key for 5 seconds and use the arrow keys to view the airflow, airflow Setpnt", actual damper pos percent and air Supply Temp. After 5 seconds without any action, the thermostat returns to operation mode. The air supply temperature appears only if analog input AI1 or AI2 are configured with the AST option. Control Mode To access the Control Mode, press the [ / ] key. The Control Mode appears for 5 seconds. Press the [ / ] key to scroll through the following control modes. These options can vary depending on the options selected in "Temp Control Mode" and "Enable OnOff Control Mode". Auto (Automatic Cooling or Heating) OFF (if it is not disabled in Programming Mode) Cooling only (on, with cooling symbol) Heating only (on, with heating symbol) Night Setback (NSB) or Occupancy Mode This function is only available if you set DI1 to nsb (Night setback contact) or Occ (occupancy mode). If the DI1 contact is triggered, the thermostat enters NSB or No Occupancy Mode (the symbol appears) and uses the NSB or OCC heating and cooling setpoints. If not locked, you can override the night setback or no occupancy mode for a predetermined period by pressing any of the 4 keys. During the override period the symbol will flash. If the symbol does not flash, the override period is finished or the night setback or no occupancy override has been locked in programming mode. Set Time and Date 1. Ensure that JP1 on the thermostat is set to Run. 2. Press and hold the key for 5 seconds 3. Use the arrow keys to set the desired value. Press the [ / ] key to save and got to the next step. Press the key to go to the previous step without saving. Local Time Local Time Local Date Set Time Display format 24 (24-hour format) 12 (AM/PM format) Hours 12 (0-23 or 1-12 am/pm) Minutes 00 (00-59) Year 15 (15-99) Month 1 (1-12) Local Date Day 1 (1-31) Local Date Exits and returns to RUN mode. *** To save any changes, press on TRL and on TDU *** *** To the previous step without saving, press on TRL and TDU *** www.neptronic.com EVCB14NIT4X Page 18

Annex A: Control Apps Refer to Pressure & Applications Menu (1 of 7) on page 8 for more information. The available Control Apps vary according to the model. Description CL (cool only) CLHt (cool/heat) CHrH (cool/heat/reheat) CO 2 (CO2) ITOS (ITOS) FPbo (fan powered ON) FPbA (fan powered Auto) Min. Setpoint 20 C (68 F) 20 C (68 F) 20 C (68 F) 20 C (68 F) 15 C (59 F) 15 C (59 F) 15 C (59 F) Max. Setpoint 28 C (82 F) 28 C (82 F) 28 C (82 F) 28 C (82 F) 30 C (86 F) 30 C (86 F) 30 C (86 F) Changeover Setpnt 24 C (75 F) 20 C (68 F) 20 C (68 F) 20 C (68 F) 24 C (75 F) 24 C (75 F) 24 C (75 F) TO1 Ramp HR1 CR1 HR1 CR1 OFF HR1 HR1 TO1 Signal Type On/Off On/Off On/Off On/Off On/Off On/Off On/Off TO1 Close Pos. 40% 40% 40% 40% 40% 35% 35% TO1 Open Pos. 0% 0% 0% 0% 0% 0% 0% TO2 Ramp HR1 HR1 HR1 CO 2 OFF HR1 HR1 TO2 Signal Type Pulse On/Off Pulse On/Off On/Off On/Off On/Off TO2 Close Pos. 40% 40% 40% 40% 40% 70% 70% TO2 Open Pos. 0% 0% 0% 0% 0% 35% 35% TO3 Ramp HR2 CR2 HR2 HR1 OFF Fan ON Fan Auto TO3 Signal Type On/Off On/Off On/Off On/Off On/Off On/Off On/Off TO3 Close Pos. 40% 40% 40% 40% 40% 40% 40% TO3 Open Pos. 0% 0% 0% 0% 0% 0% 0% TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On/Off Pulse On/Off On/Off On/Off On/Off TO4 Close Pos. 40% 40% 40% 40% 40% 40% 40% TO4 Open Pos. 0% 0% 0% 0% 0% 0% 0% Motor Ramp CR1 COr COr COr CR1 CR1 COr AO1 ramp HR1 CR1 HR1 CR1 HR1 HR1 HR1 AO2 Ramp HR2 HR1 HR2 HR1 OFF HR2 Fan Auto AI1 Input OFF SENS SENS SENS OFF OFF SENS AI2 Input OFF OFF OFF CO 2 OFF OFF OFF DI1 Input nsb.o nsb.o nsb.o Occ.o Occ.o nsb.o nsb.o Heat Prop Band 2 2 C (4 F) 2 C (4 F) 2 C (4 F) 2 C (4 F) 2 C (4 F) 1 C (2 F) 1 C (2 F) Heat Deadband 2 1.3 C (2.6 F) 1.3 C (2.6 F) 1.3 C (2.6 F) 1.3 C (2.6 F) 0.3 C (0.6 F) 1.3 C (2.6 F) 1.3 C (2.6 F) Cool Deadband 2 1.3 C (2.6 F) 1.3 C (2.6 F) 1.3 C (2.6 F) 1.3 C (2.6 F) 0.3 C (0.6 F) 0.3 C (0.6 F) 0.3 C (0.6 F) Legend Grey Text = Standard default value Bold Text = Special default value for selected application HR = Heating ramp CR = Cooling ramp COr = Changeover ramp SENS = Changeover temperature sensor Fan ON = Fan powered box in continuous mode Fan Auto = Fan powered box in automatic mode (follows demand) nsb.o = Night Setback (normally open) Occ.o = Occupancy mode (normally open) TO AO AI DI = TRIAC output = Analog output = Analog input = Digital input www.neptronic.com EVCB14NIT4X Page 19

Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com. 400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com Toll free in North America: 1-800-361-2308 Tel.: (514) 333-1433 Fax: (514) 333-3163 Customer service fax: (514) 333-1091 Monday to Friday: 8:00am to 5:00pm (Eastern time)