Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit

Similar documents
SBS-H2. Hydrogen Gas Detector Kit. For battery charging rooms and other areas where hydrogen gas may be present

SBS-H2 Hydrogen Gas Detector Kit

KDT00030, KDT00030A Phototransistor Photo Detector

Series: MBC1-TC Mini Benchtop Temperature Controller

Macurco HD-11 Hydrogen Gas Detector

Is Now Part of To learn more about ON Semiconductor, please visit our website at

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 110 Gas Monitor Operator s Manual

GAS MONITOR Model Model

Booster Power Supply Manual

Installation Guide for models:

RK Transmitter Technical Notice

Public Safety DAS Annunciator Panel

3 Macurco Carbon Monoxide Detector CM-16A

1022 R/T Remote Monitor

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

Beacon 800 Gas Monitor Operator s Manual

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Installation Guide for models:

KM300 Carbon Monoxide Detection System Installation Manual

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Crypto-Lock. Model CC-8521B Updated 7/17. Access Control System. MONITEQ, Inc. INSTRUCTION MANUAL

SP-1000X. Panic Device Power Controller Installation Guide. Rev

RK Combustible Gas Transmitter Operator s Manual

Beacon 410A Gas Monitor Operator s Manual

v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

MACURCO INC. CONTROLLERS & CARBON MONOXIDE DETECTORS SS103-3A, SS103-10A SS102H, SS102HC-1 INSTALLATION & OPERATING INSTRUCTIONS

QAS-101 SERIES SINGLE CHANNEL CONTROLLERS

Series. Access Power Controllers. Installation Guide

RK-05 Combustible Gas Transmitter Operator s Manual

Macurco Single-Gas XL Series Monitor, CM-1XL Carbon Monoxide (CO), HS-1XL Hydrogen Sulfide (H2S) User Instructions

Low-Power CMOS ALARM IC with Horn Driver

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

MBCE-110/230UV Flame Sensor Module

KT-100 Door Controller

SYSTEM CONTROL KIT Model: CK-41P

RK Carbon Monoxide Transmitter Operator s Manual

OPEARATING GUIDELINES FOR AERO-252 (Pages 1 to 3 contain general information on CO Guardian. Pages 4 to 6 contain information specific to Aero 252)

EVD-1 Installation, Operation, and Instruction Manual

MBCE-110/230FR Flame Sensor Module

Model OEM-2 INSTRUCTIONS FOR USE

TECHNICAL DATA OBSOLETE

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Model 4001 Series Single Channel Controller

Macurco CM-E1 Carbon Monoxide Detector

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

RMS/RPX Reader. User Manual

User s Guide HHAQ-109. Portable Multi-gas Detector. Shop online at omega.com SM

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

OWNERS MANUAL MODEL 451 (-101 & -201)

OPERATION & INSTALLATION MANUAL

GS100M Gas Detector. Technical Specification

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Operations Manual. Motion Detector Module Model ZS10

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

BEP Marine Gas Detector FD-2

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

ACL TC 200 TEMPERATURE CONTROLLER

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

OWNERS MANUAL. CARBON MONOXIDE DETECTOR MODELS Panel Mount & Remote Detectors (R) Guardian Avionics 1951 E. AIRPORT DRIVE TUCSON, AZ.

Installation Manual. Detector Bases: PAD100-IB, PAD100-RB & PAD100-SB

MODEL AC-SCC-5 INSTALLATION, OPERATION & MAINTENANCE MANUAL

Operation Manual. Rev. E GEM-II Self Contained Gas Detector.

Model 3300 Technical Support and Installation Manual

Ammonia Leak Detector Manual

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

ENERVEX ADC100 DRAFT CONTROL

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL

Installation, Operation & Service Manual

ACCURATE ELECTRONICS INC

24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG

Document No

MODEL 834M1 ACCELEROMETER

E340 BOILER CONTROL INSTALLATION MANUAL

Installation Instructions

Rev Pulse Modulating Anti- Sweat Control (PMAC II) Installation and Operation Manual

SEC 2000 Millenium Infrared Gas Detector

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

BX444-Mc Gas Detector

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

PSN-1000 & PSN 1000(E) Installation Manual

CAUTION & SYMBOL DEFINITIONS:

Northwest RV Supply Manual Compliments of Printed From 900 & 9100 Series

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

Beacon 200 Gas Monitor Operator s Manual

Accessible Toilet Alarm

CabLite Luminous Auto Light Control Installation Manual

MODEL 4000A & 4001A ACCELEROMETER

RK-05 Carbon Monoxide Transmitter Operator s Manual

Transcription:

Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design N56 W16665 Ridgewood Drive Menomonee Falls, WI 53051 SBS-H2 Hydrogen Gas Detector Kit For battery charging rooms and other areas where hydrogen gas may be present INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS Protects Life, Property, and Profits Compliant with NFPA 70E and IEEE recommendations Hydrogen sensor is UL Class 1 Division 2 1-800-554-2243 www.sbsbattery.com TEST@sbsbattery.com 1

Table of Contents: Description Page Section Overview 3 1.0 Benefits 3 2.0 How It Works 3 3.0 Specifications 4 4.0 Sensor 4 5.0 Mounting Location 5 6.0 Installation 6 7.0 Operation 10 8.0 Electrical Testing 10 9.0 Calibration 10 10.0 LED Trouble Shooting Chart 11 11.0 Part Numbers & Options: Part No. SBS-H2 H2-JB H2-SENSOR H2-100FT-CABLE H2-CALKIT E190399 Description Hydrogen Gas Detector (Includes: Main Unit, (1) sensor & (1) 25ft cable) Junction Box, 4 11/16 X 4 11/16 Metal, with Knockouts Additional/Replacement Hydrogen Gas Sensor with 25ft Cable Custom 100 Ft Cable and ma Converter (no sensor) Field Calibration Kit for SBS-H2 110vac 3 Prong AC Cord, 10 Ft, 18AWG Warnings: This detector is added protection, not a substitute, for prudent safety measures where hydrogen gas is present. For large or highly sensitive areas, you may have to use two or more detectors with 1 or 2 sensors each for increased detection. The hydrogen sensor does not provide protection from fires or hydrogen explosions. The relay contacts are intended to be connected to a safety system, enabling audible alarms, system shutdown, ventilation, or other measures to ensure safe handling and use of hydrogen gas. Ensure that your installation complies completely with all relevant local, State, Federal, and OSHA safety and health regulations If sensor responds, there is a risk of combustion or explosion. To avoid injury leave area immediately. The hydrogen sensor is calibrated for operation in air. Tampering with the sensor or operation in other gas environments can lead to inaccurate readings and possible permanent damage if operating in a reducing atmosphere or 100% hydrogen. The hydrogen sensor is silicone resistant but uncured silicone compounds or extended exposure to silicone off gassing, or high concentrations of refrigerant gasses related to a leak, can give inaccurate readings in the sensor. 2

1.0 Overview Hydrogen gas detectors act as monitors that provide alarms as well as control functions such as controlling exhaust fans, remote alarm and signaling, building management interfacing and more for the protection of your facility. Batteries on charge emit hydrogen gas after reaching 80% of the recharge point. Examples of typical hydrogen emissions per lead-acid battery are: Battery Size Hydrogen Gas 12 Volt / 500 Amp-Hour 3.5 Cubic Feet/hr. 24 Volt / 720 Amp-Hour 10.1 Cubic Feet/hr. 36 Volt / 935 Amp-Hour 19.8 Cubic Feet/hr. 48 Volt / 850 Amp-Hour 23.9 Cubic Feet/hr. Concentrations of 4.1% to 75% H2 mixed with air can be explosive. Sparks or hot surfaces can ignite them. A hydrogen gas detector in your battery room will provide a warning and facilitate dissipation of hydrogen concentrations before they reach the lower explosive limit (LEL) of 4.1%. 2.0 Benefits In addition to protecting your employees and your property, the detector may also reduce the following costs: Electricity - Heating - Air Conditioning Instead of continuously running an exhaust fan to prevent hydrogen gas accumulation, use the detector to activate the fan only if the concentration reaches 1%. Insurance Installation of a detector in areas where batteries are charged may result in a premium reduction. 3.0 How it Works Should the concentration of hydrogen gas in the air surrounding the sensor reach 1% by volume, the "1% Warning" yellow LED will light and the 1% internal relay will energize. Should the hydrogen gas concentration reach 2% by volume, the "2% Alarm" red LED will flash and an alarm will sound. Either relay can be used to activate a remote exhaust fan and/or alarm. Automatic operation, continuous monitoring, high sensitivity & stability,and solid state reliability. The unit is also intrinsically safe using 120/240 VAC 50/60 Hz or 12-48 VDC operating voltages, low in cost and easy and versatile to install. 3

4.0 Specifications Dimensions: 4.75"L x 5.25"W x 1.4"D (display only) Wall Mounting: Two 3/16" screws Junction Box Mounting: Requires 4 11/16 x 4 11/16 2-gang junction box (SBS Part# H2-JB) Power Requirements: 120/220 VAC, 50 / 60 Hz or 12VDC Isolated or 14 to 48 VDC *** An earth ground must be supplied to the GND terminal when using the 12VDC and Isolated (Gnd) inputs for 12 Volt supply to the unit. Relays: 1% Warning Relay, 1 Normally Open & 1 Normally Closed contact 2% Alarm Relay, 1 Normally Open and 1 Normally Closed contact 5.0 Sensor The sensor consists of a ceramic sensing element whose electrical conductivity increases when hydrogen is adsorbed on its surface. Conductivity of the sensor is proportional to the gas concentration which is continuously monitored by an electronic circuit. The sensor only monitors pure hydrogen gas (H2) and will not alarm due to Hydrogen Sulfide (H2S) which has an odor at very low concentrations. Hydrogen Sensor 25 Ft Cable extension 4

6.0 Mounting Location Hydrogen is colorless and odorless; the lightest of all gases and thus rises. The hydrogen sensor, therefore, should be installed at the highest, draft-free location in the battery compartment, cabinet, or room where hydrogen gas would accumulate. The Alarm Box can be mounted at eye level or wherever is convenient for the user. The size of the area one sensor will protect depends upon the battery compartment or room. The detector measures hydrogen gas concentration in the air immediately surrounding the sensor. Hydrogen gas may accumulate in several areas of the battery compartment or room therefore; individual detectors should be installed in each of these areas. Mounting and Power Options: Wall Mountable Integrated back mounting plate allows user to easily mount directly to any wall using qty.2 3/16 screws (not included). Wiring Power and Alarm Wires can be ran through the sides of the unit Alarm Wiring Input Power Junction Box Mountable Mounts to a standard, 4 11/16 x 4 11/16 2-gang junction box (SBS Part# H2-JB). Hardwire Run AC or DC power and alarm wires through back of the unit, into the gang box and out through conduit. 5

AC Cord -not included (SBS Part# E190399) Unit shown with 3-prong grounded AC Cord (18+ AWG) 7.0 Installation Hydrogen gas has only 7% of the density of air, and thus rises. Your hydrogen gas detector should be installed at the highest, draft-free location in the battery room, cabinet, or compartment where hydrogen gas would accumulate. Carefully remove the cover by pulling it off the detector. Attach the detector to the wall, ceiling, or optional junction box using the mounting holes at the top and bottom of the detector mounting plate. For hard wiring using conduit, the detector box will fit onto the optional junction box. The detector has terminal blocks for connection to a single-phase 120 VAC 50/60 Hz power source, OR a +12 VDC Regulated Power Source or a +14-48 VDC power source. It also has two internal alarm relays. A 1% warning relay that is activated at 1% concentration of hydrogen gas and a 2% alarm relay that is energized at 2% concentration of hydrogen gas. The relays can be used to switch on a remote exhaust fan and/or to turn on an alarm. For 120 VAC power, use 18 gage stranded wire minimum (Belden 19348, equivalent or better). For relay wires, use stranded wire (Belden 8473, equivalent or better). Maximum wire size for connector terminations is 14 AWG stranded copper wire. Power Requirements: Current (A) Power (W) Voltage 1 Sensor 2 Sensors 1 Sensor 2 Sensors VDC 12 0.154 0.302 1.848 3.624 VDC 24 0.090 0.167 2.160 4.008 VDC 48 0.052 0.090 2.496 4.320 VAC 120 0.035 0.062 4.200 7.440 The detector's relay dry contacts are rated at 10A/250VAC, sufficient for most 1/3 HP exhaust fans. For higher current requirements, add an external relay. Locate the Sensor installation point within 25 feet of the detector and mount the sensor. Run the supplied cable from the sensor to the detector and connect to the Sensor 1 input labeled on the cover. 6

For installation of a second sensor One additional sensor may be added to each detector. Multiple detectors can be installed to meet the space coverage requirements of your particular installation. Locate the 2 nd sensor installation point within 25 feet of the detector and mount the sensor. Connect the cable from the second sensor to the Sensor 2 input labeled on the cover. On the detector printed circuit board, remove the jumper on P9 to enable the second sensor input. Either sensor is capable of triggering a warning or alarm condition. Switching from Voltage to Current Output- Required when using cable longer than 100 ft. When using cable exceeding the 100FT sensor cable (SBS Part# H2-100FT-CABLE), the Sensor jumper must be moved on the sensor input from the off condition to the on condition, so it covers both pins. 1. Removing the front snap on cover will reveal the inner electronics of the alarm box. 2. Locate the signal output select jumper(s) (P5 for Sensor 1 and P6 for Sensor 2). 3. Install the jumper across the two pins to enable the current output mode (see photos) Note: (Alarm will emit a chirp noise if sensors are not connected) Sensor Disabled (40mA Signal Output) Sensor Enabled (Voltage Signal Output) Wiring Diagram: 1. The detector has 2 internal relays. One relay energizes when the sensor detects a 1% concentration of hydrogen gas in the air surrounding it. The second relay contact energizes at a 2% concentration. The detector's internal relays are rated: 10 amps at 250 volts ac; 10 amps at 30 volts dc; 1/3 horsepower at 125 volts ac; 1/2 horsepower at 250 volts ac. 7

If the load you have is higher than these relay ratings, add an external relay (shaded item in the sketch above). Alarm System Electronics: Please refer to the photos below showing proper power and relay connection points in the detector. It is advisable to use a twisted pair of 14 gage wires for the relay contacts to help reduce any interference within the battery room that may cause false alarms. A. Multiple Sensor Jumper - Select between single or multiple sensor set-up. default jumper settings: single sensor (Jumper on P9 Only) Place a jumper on P8 to disable SENSOR 1 Place a jumper on P9 to disable SENSOR 2 B. Signal Output Select Jumper (Volts/Amps) (P5 for Sensor #1) (P6 for Sensor #2) Select between voltage or milliamp output. default setting: voltage output Enabled amp output by installing the jumper on these pins (lift jumper and slide over to short pins) C. Normally Open (NO) Relay for Warning Condition (1% H 2 ) D. Normally Open (NO) Relay for Alarm Condition (2% H 2 ) E. Test System Push Button F. Calibration Potentiometers (DO NOT ADJUST WILL VOID CALIBRATION) F C B B A D E 8

Terminal Connection Diagram: Pre-March 2016 Version 1% Warning Contacts COM N/O N/C AC Power Supply Terminals 120VAC LINE EARTH (GND) NEUTRAL DC Power Supply Terminals COM N/O N/C 2% Alarm Contacts EARTH(GND) GND (ISO) + 12 VDC +14-48VDC Earth GND Negative +12 VDC OR +14-48 VDC Using the Mechanical Relays: 1. Remove the front cover of the detector by pulling straight off the body. This will reveal the inner electronics of the alarm box. 2. Locate items C and D, and determine which condition you would like to use the relay to be related to. Use Relay C for the warning condition (1% H 2 ) and relay D for the alarm condition (2% H 2 ). 3. Restore the front covering of the alarm box and re-secure the two removed screws. 8.0 Operation Keep the detector on at all times. A Green LED indicates that the detector is powered on. 9

When power is first turned on, a warm up period of 4 hours will elapse before the detector will start to function. This delay is to prevent false activation of the internal relays and alarm. The GREEN LED will flash during the warm up period and then turn solid green once the warm up is complete. If the concentration of hydrogen gas in the air surrounding the sensor reaches 1% by volume, the yellow LED will light and the 1% internal relay will initiate(which can be used to activate a remote fan and/or alarm). Should the concentration reach 2%, the red LED will flash, the internal warning alarm will sound, and the 2% internal relay will energize. The 1% relay will remain energized & the yellow LED will remain on. When the concentration decreases below 2%, the red LED will turn off, the internal alarm will stop, and the 2% relay will de-energize. When the concentration falls below 1%, the 1% relay will de-energize and the Yellow LED will turn off. 9.0 Electrical Testing (after the input power is on for 4 hours) A "push-to-test" button is located on the front of the unit. Push and hold this button for approximately 10 seconds to test the unit's electronic circuitry. The caution and warning LEDs will light in sequence; the relays will activate whatever is connected to them and the internal warning alarm will sound. Note: The "push-to-test" button does NOT test the sensor itself. 10.0 Calibration The Sensor and display have been calibrated at the factory for hydrogen gas and should not need adjustment at the time of installation. The SBS-H2 Display can be *calibrated in the field using a calibration kit (SBS Part# H2- CALKIT) or the sensor and display can be sent to SBS for calibration. SBS Part# H2-CALKIT calibration kit** shown above *Sensor can accept up to 3 calibrations / **Sensor not included with calibration kit 10

11

The information in this sheet has been carefully reviewed and is believed to be accurate; however, no responsibility is assumed for inaccuracies. Storage Battery Systems, LLC. Reserves the right to make changes without further notice to any product, datasheet, technical data bulletin, or website. Storage Battery Systems, LLC. makes no warranty, representation of guarantee regarding the suitability of its product for any particular purpose, nor does Storage Battery Systems, LLC. assume any liability arising out of the application or use of any product and specifically disclaims any and all liability, including without limitation consequential or incidental damages. Typical parameters can and do vary in different applications. All operating parameters, including Typical must be validated for each customer application by customer s technical experts. Storage Battery Systems, LLC. products are not designed, intended, or authorized for use as components in systems intended for surgical implant into the body, or other application intended to support or sustain life, or for any application in which the failure of the SBS product could create a situation where personal injury or death may occur. Should buyer purchase or use SBS products for any such unintended or unauthorized application, Buyer shall indemnify and hold Storage Battery Systems, LLC. and its officers, employees, subsidiaries, affiliates, and distributors harmless against all claims, costs, damages, and expenses, and reasonable attorney fees arising out of, directly or indirectly, any claim of personal injury or death associated with such unintended or unauthorized use, even if claim alleges that Storage Battery Systems, LLC. was negligent regarding the design or manufacture of the part. In the case of a defect in the sensor, Storage Battery Systems, LLC. shall not be liable for any damages which may result, including, but not limited to, loss of revenue, property, or life. In any event, Storage Battery Systems, LLC. shall limit liability to replacement of the defective unit. Storage Battery Systems, LLC. does not convey any license under its patent rights nor the rights of others. N56 W16665 Ridgewood Drive Menomonee Falls, WI 53051 1-800-554-2243 www.sbsbattery.com TEST@sbsbattery.com 12