RESISTRON. Replacing RES-102/RES-420. Replacement Instructions. Comparison of RES-102 / RES-420. Dimensions. Temperature indication (actual value)

Similar documents
RES-210 (-211, -220, -221) / RES-420

RESISTRON RES-408. Operating Instructions. Important features

RESISTRON RESM-5. Operating Instructions. Important features

TS400. Operating Manual. Test Station for Microtector II Series (G450/G460)

SCHMIDT LED Measured Value Display MD Instructions for Use

Operating Manual UV Monitor UVT 18

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

FlameGard 5 MSIR HART

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

FlameGard 5 UV/IR HART

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

1.7. Insulation fault evaluators EDS460/490 EDS461/491

RPM1600 Series Room Pressure Monitors

ELECTRONIC HUMIDISTAT: H270

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

1.7. Insulation fault evaluators EDS460/490 EDS461/491

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

BSR Addressable Fire Detection control panel. Installation operation manual

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

MultiFix Central unit

CIRUS. Heating elements for sealing plastic films. Heating elements for sealing plastic films. advanced heater technology. ULTRA-PULSE sealing bars

ELECTRONIC HUMIDISTAT: H200

CONTROL DEVICE SLIDETRONIC HD

AFMS Audible Flow Monitoring System TECHNICAL SPECIFICATION

TECHNICAL MANUAL CVM 3000 C 5030 CV/04-99 GB

S F IT 6" / 8"HES. Quick Installation Guide. franklinwater.eu

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

WIO 200B and WIOI200B Water in oil sensor

Remote alarm indicator and test combination MK2430

INSTALLATION & USER MANUAL

- Data Brochure Addendum

Telemetry Communications Device. Installation Guide. Interface for the Emizon managed network. Issue 1: February 2008

Line Isolation Monitor (LIM) LIM2000plus

BWAC Steuerung. Kochendwasser- Energiesparreinigung. Art.-Nr Version 1.0

Greentrol Automation, Inc.

ETO 2 - Controller for ice and snow melting

SD2. Differential Controller. Operating and Installation Instructions F2 72.3

Instructions for the fan motor control system, SILVER C

- Data Brochure Addendum

Insulation fault evaluator EDS460-DG

OilSET-1000 (12 VDC)

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

Mark 25 Ultrapure Water Conductivity Analyzer

Flostop TS D7E and A8E. Operation Manual

ADOS Biogas 905. Multi-channel Gas Analyser. A D O S GmbH Instrumentation and Control Trierer Str FRG

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Operating Manual TR600

MO n : 12JMC rév A

EC2-5x2 Series Condensing Unit Controllers

M15051) INSTRUCTION MANUAL

Deltapilot S FMB70. Functional Safety Manual. Level and Pressure Measurement with Output Signal ma

SCAN200E USER S MANUAL

PolyGard 2-channel Gas Controller MGC-03

SET-2000 Hi Level/Oil

Stand Alone DYNAGARD SP Operation Manual

5, SE GÅNGHESTER,

Control box FSTronic DES-FS

INSTALLATION INSTRUCTIONS

FIL-SPL Flow-through heater for central heating USER MANUAL

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

Sierra Model 951 Digital Flo-Box. Instruction Manual Part Number IM-951 Revision A 09-05

PRODUCT BULLETIN. Rev. A Monitoring Station offering PN Rev. B as a direct replacement. OVERVIEW / DESCRIPTION

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

OMC Ex interface unit. Manual. Version 1.2 August Author: Observator Instruments

Reciprocating Chiller

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Danfoss gas detection unit Type GD Heavy Duty

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

IMR 5000 IMR 400. CEMS Operating Manual IMR USA S/N: Sample IMR Sensors Inside IMR 400. Gas Dryer Inside. IMR Environmental Equipment Inc.

2-zone application 2X T6R SMART THERMOSTAT & 2-CHANNEL RECEIVER BOX FEATURES APPLICATION MANUAL

MC 31 Speed Controller Technical User Guide Code no GB

Instructions for the fan motor control system with integrated wiring terminals SILVER C

SET Installation and Operating Instructions. Level switch for one sensor

MultiFix Central unit

Dohse Aquaristik GmbH & Co. KG. T-Control Pro. Item no Status: 03/2013. Dohse Aquaristik GmbH & Co. KG

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

Operations Manual TS400. Test Station for G450/G460 Gas Detector

Analog Room Pressure Monitor RPC Series

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

7. ON/OFF Controller (CZ-ANC2)

DEIF A/S. Description of options. Option A4, Loss of mains protection package Automatic Gen-set Controller. Description of option

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

FIRERAY 5000 range USER GUIDE

Superdew 3. Hygrometer. Operating Instructions

Operations Manual TS400. Test Station for G450/G460 Gas Detector

CTT8 TEMPERATURE MONITOR DEVICE

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

Oxygen & Carbon Dioxide Analyser

Transcription:

RESISTRON GB Replacing / Replacement Instructions The RESISTRON temperature controller can be used as an alternative to the older controller type. The mechanical outlines are identical. The connection of the electrical terminals is different and must be changed acc. the described wiring diagram. The steps that are necessary to convert from -0-x (standard model without modifications) to are described below. These instructions only provide a brief overview of the two controllers. If in doubt, please refer to the latest version of the controller documentation, which is always binding. The convertion from controller types -1-x is not described here. Please contact ROPEX for further informations. Comparison of / Dimensions The front panel cutout dimensions of the RES-2xx and controllers are identical. The features a protective film to IP42 instead of the transparent hood. A transparent front cover featuring IP65 is available as a option. Temperature indication (actual value) Indication on a analog instrument (ATR-x). Indication on the 4-line display (dynamic bar and digital value). 23.1.04 Industrie-Elektronik GmbH Tel: +49/(0)7142/7776-0 E-Mail: info@ropex.de Gansäcker 21 Fax: +49/(0)7142/7776-19 Internet: www.ropex.de D-74321-Bietigheim-Bissingen (Germany) Data subject to change

Set point selection Selection by means of a 10-turn potentiometer with a fine control knob. Selection with step 1 in the software menu. If the controller is active, the set point is also indicated on the display. Zero calibration Zero calibration by means of a 10-turn potentiometer. The pointer of the indicating instrument must be set to Z. Automatic zero calibration (AUTOCAL) with step 3 in the software menu. Alarm output / reset Indicated by means of a red ALARM LED on the front panel. Reset by pressing the key. Indicated on the display. The error is identified by a numeric code ( documentation). Reset by pressing the key ( HAND ). Page 2 Replacing /

Manual mode Selected by pressing the HAND key. The red ON LED is lit continuously. RES-440 Selected by pressing the HAND key ( Home position is displayed. HAND ) while the Line frequency setting (50/60Hz) Configured with plug-in jumper. Detected automatically in the 47 63Hz range. Automatic detection Replacing / Page 3

Installation and setup Installation and startup may only be! performed by technically trained, skilled persons who are familiar with the associated risks and warranty provisions. The information provided here offers no more than a brief overview. If in doubt, please refer to the latest version of the controller documentation, which is always binding ( see also section Safety and warning notes of the documentation). Proceed as follows to replace the controller and install/start up the : 1. Switch off the line voltage and verify the safe isolation from the supply. 2. Remove the existing controller. 3. The supply voltage specified on the nameplate of the controller must be identical to the line voltage that is present in the plant or machine. The line frequency is automatically detected by the temperature controller in the range from 47 to 63Hz. 4. Set the DIP switches on the. The settings of the DIP switches on the! are NOT the same as on the. Please set these switches in accordance with the ROPEX Application Report in order to avoid malfunctions. New setting ranges on the : DIP-SWITCH The table below compares the two controllers. These settings can be taken as a guide (e.g. when the controller is started up for the first time): U 2 ON 12345 ON 1 2 3 4 5 OFF U 2 ( V ) 1-10 6-60 20-120 ON ON OFF OFF ON DIP switch ON 1 1 2 2 3 3 4 3 I 2 5 4 I 2 ( A ) 30-100 60-200 120-400 Old setting ranges on the : U2 ( V) Switch No. ON 12345 3-10 8-30 20-60 50-80 1 2 3 4 5 5. Install the controller in place of the. The connection of the electrical terminals is! different and must be changed acc. the described wiring diagram. 6. Switch on the line voltage. 7. A power-up message appears on the display when the controller is switched on to indicate that it has been started up correctly. Page 4 Replacing /

8. One of the following states then appears: DISPLAY Home position Shows the SET and ACTUAL temperatures or the dynamic bar Shows error code 104, 106, 109 or 211 Shows error code 101 103, 201 203, 801 or 9xx Go to 9 Go to 9 ACTION Fault diagnosis ( documentation) 9. Select the language and reset the controller to the factory settings. Press the key for at least 2s (to open the Configuration menu). Step 20 is displayed. Select the desired language with the keys. Confirm your selection by pressing HAND. Press the key to display step 21 (factory settings). Press the HAND key to confirm the factory settings (an acknowledgment message appears). Step 22 is displayed next. 10.Set the temperature range to 500 C (Only if you have so far been using an -0-5 controller) Then set "Alloy 20, max 500 C" with the keys in step 22. Confirm your selection by pressing HAND. 11.Return to the Home position Press the key for at least 2s (to return to the Home position or Alarm menu). 12.Calibrate the zero point Activate the AUTOCAL function while the heatsealing band is still cold. Press the key repeatedly until step 3 is displayed. Then select the AUTOCAL funtion by pressing the HAND key. If this function is executed correctly, the Home position is displayed again automatically. If the zero has not been calibrated successfully, an error message appears on the display. In this case the controller configuration is incorrect ( see section Controller configuration of the documentation and the ROPEX Application Report). Configure the controller correctly and repeat the AUTOCAL function. 13.Set the heatsealing temperature (select the set point) Press the key briefly (to display step 1 in the Setting menu). Set the required temperature with the keys. Confirm your selection by pressing. Press the key for at least 2s (to HAND return to the Home position). The set heatsealing temperature is displayed in the Home position. Then activate the "START" signal (HEAT). The indication on the display (actual value and dynamic bar) permits the heating and control process to be observed: If an error code is displayed, please proceed as described in section Error messages of the documentation. The controller is now ready factory settings / as-delivered condition If you accept the factory settings (step 21 in the software menu, see step 9 above), the following defaults are restored: 23 Maximum temperature 300 C 24 Cycle counter 0 Menu step Function 1 Heatsealing temperature 0 C Value 25 Alarm relay Closed by alarm The selected language (step 20 in the software menu) remains set regardless of the factory settings. 2 Hold mode OFF 22 Alloy/range Alloy A20, max. 300 C As-delivered condition: The controller is delivered with the above factory settings and with the language set to "German". Replacing / Page 5

Wiring diagram of the (old) ALARM RELAY 11 12 13 14 15 16 17 18 19 20 N 5 6 L1 ALARM OUTPUT (max.50v/0,2a) I R CURRENT TRANSF. twisted U R START CONTACT START 24VDC + R HEATSEALING BAND IMPULSE TRANSFORMER U 1 PRIM. SEC. U 2 FILTER N L1 SL LINE Page 6 Replacing /

Wiring diagram of the (new) (also with MOD 01) N L1 14 15 Line filter LF-xx480 LINE 17 1 2 + 0V ALARM OUTPUT max. 50V/0.2A 6 5 11 12 Contact closed or opened by ALARM (see configuration) 5 6 13 12 Impulse transformer U1 prim. U2 sec. START (HEAT) with 24VDC signal 3 20 17 16 11 U R 10 twisted R Heatsealing band GND 4 19 14 9 8 IR Ground for 24VDC signals. Must be grounded externally to prevent electrostatic charging! 15 Current transformer PEX-W2 0V (Internal ground) Terminal 2 18 7 0V (Internnal ground) No external grounding allowed! START (HEAT) with contact X Terminal blocks Disconnect the ground wire connection (SL): The ground wire connection (SL) of the is not used for the. The has a plastic front cover. Replacing / Page 7

Menu structure of the Settings Configuration Power-up message Home position 1 Heatsealing temp. 20 Language 21 Factory settings The relevant menu steps are shown on a gray background. 2 Hold mode 22 Alloy/range 3 Autocal? 23 Max. temperature Autocal 24 Cycles 25 Alarm relay 26 Meas. imp. length MOD 1 only Fault Alarm 3 Autocal? Autocal Page 8 Replacing /