KFTC Series 18,000 to 48,000 Btu/h Cooling Only & Heat Pump INSTALLATION MANUAL

Similar documents
INSTALLATION INSTRUCTION

FDT11 FDT15 FDT18. DUCTED TYPE SPLIT SYSTEMS (3 Phase, Fixed Speed)

INVERTER SPLIT - TYPE

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

DAIKIN AIR CONDITIONER

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump

Installation manual for room air conditioner

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO

MXZ-4B80VA MXZ-5B100VA INSTALLATION MANUAL

SPLIT WALL-MOUNTED AIR CONDITIONER

INSTALLATION MANUAL SPLIT TYPE ROOM AIR CONDITIONER (PART NO )

OWNER S MANUAL BD/BC DUCTED TYPE SPLIT SYSTEMS CAPACITY RANGE: 8-25kW

SINGLE - ZONE Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual

Installation Manual PMV Kit RBM-PMV0363E RBM-PMV0903E

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3B54VA MXZ-4B71VA. English

Service Manual. Air Conditional

Choosing the installation site. Installation. 07 Choosing the installation site

INSTALLATION INSTRUCTIONS

0RGHOV,QGRRU 8QLW MWM36Y3J 2XWGRRU 8QLW MRM36Y3J 11

Installation and Operation Manual. CMA12SB-0 Series. Horizontal/Side Discharge Condensing Units

Split Air Conditioner

ROOM AIR CONDITIONER INSTALLATION MANUAL

INSTALLATION MANUAL Duct Type Series MH FECA

[FLARE CONNECTION TYPE] ATTENTION

Mini-Split Air Conditioner

OWNER S AND INSTALLATION MANUAL RAV-480FS2B/RAV-480AS2B RAV-600FS8B/RAV-600AS8B

FLOOR-STANDING SPLIT TYPE ROOM AIR CONDITIONER

AIR CONDITIONER CASSETTE

Indoor Unit Operation & Installation Manual

Safety Precautions (1)

Installation Manual Super-Slim Four-Way Cassette

Split-type Air-Conditioner

Ductless Split Air Conditioner

KTIM. Four-way Cassette Type

Installation. All about the. of your. Split Type Room Air Conditioner. Refer to Page 2 for table of contents.

TCB-DP22CUL. Drain Pump Kit. Model name : AIR CONDITIONER (SPLIT TYPE) Installation Manual. Installation Manual 2 Air Conditioner (Split type) English

CONTENTS INSTALLATION MANUAL HFC FOR INSTALLER R410A. utilized 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2

Split-type Air-Conditioner

INSTALLATION MANUAL. R410A Split Series. Model RXS24LVJU. Installation manual R410A Split series. Manual de instalación Serie Split R410A.

Installation Manual. Ceiling & Floor Type CEILING & FLOOR TYPE AIR CONDITIONER

FLOOR-STANDING TYPE AIR CONDITIONER INSTALLATION MANUAL

Safety Precautions WARNING INSTALLING THE UNIT POWER SUPPLY LINE, FUSE OR CIRCUIT BREAKER

INSTALLATION MANUAL. System Air Conditioner (Cooling and Heating) Cassette Type Series CH070CAV1 CH105CAV CH140CAV DB A(1) ENGLISH ESPAÑOL

Split-type Air-Conditioner

SPLIT-TYPE ROOM AIR CONDITIONER

MULTI HEAT PUMP PANEL CONSOLE TYPE DUCTLESS INVERTER INDOOR UNIT INSTALLATION MANUAL. Models: CH09MCU230VI CH12MCU230VI CH18MCU230VI

1. BEFORE INSTALLATION

MULTI TYPE ROOM AIR CONDITIONERS INSTALLATION INSTRUCTIONS

R32 INSTALLATION MANUAL ENGLISH AIR CONDITIONER (SPLIT TYPE) Indoor unit RAS-10PKVPG-E RAS-13PKVPG-E RAS-16PKVPG-E

INSTALLATION MANUAL. R410A Split Series. Models RXS15LVJU RXS18LVJU. Installation manual R410A Split series. Manuel dinstallation Série split R410A

High Wall Split Air Conditioners 53QHCT KHCT

DUCTED CONCEALED (CEILING RECESSED) MINI SPLIT SYSTEM AIR CONDITIONER/HEAT PUMP MEDIUM EXTERNAL STATIC PRESSURE TYPE

DUCTLESS MINI-SPLIT INSTALLATION MANUAL COMFORT...BUILT TO LAST

Split Air Conditioner. Model: WMI09MH16S WMI12MH16S WMI18MH16S

Saunier Duval Clima, S.A.

Air Conditioner Service Manual KSWT SERIES INSTALLATION INSTRUCTION. Wall-mounted Split Type

Installation Manual. Floor-Standing Type FLOOR-STANDING TYPE AIR CONDITIONER

Air conditioner. Installation manual AM777KN4DCH

Inverter Air Conditioner Installation Manual GIN 090/GIN 091 GIN 120/GIN 121 GIN 180/GIN 181 GIN 240/GIN 241

Installation Manual. WAS / WYS Series. For 9,000-36,000 BTU/hr Systems. Inverter+ and Inverter++ Models

Split Air Conditioner

CENTRAL AIR CONDITIONER SPLIT SYSTEM

INVERTER SPLIT -TYPE ROOM AIR CONDITIONER

INSTALLATION INSTRUCTIONS

1. BEFORE INSTALLATION

UltraV Series Outdoor Units

Installation Manual. KS Series KS09 KS12 KS18 KS24 KS28. J3387_Kaden_Installer_Manual_ indd 1

R410A SPLIT SERIES DC INVERTER

1. BEFORE INSTALLATION

Installation Manual INVERTER ONE-TWO/ONE-THREE /ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER

AIR CONDITIONER SPLIT WALL MOUNTED

1. BEFORE INSTALLATION

AIR CONDITIONER (MULTI TYPE) Installation Manual. Indoor Unit. Model name:

Installation Instructions

1. BEFORE INSTALLATION

Saunier Duval Clima, S.A.

INSTALLATION MANUAL. R410A Split Series. Models ARX20GV1B ARX25GV1B ARX35GV1B ARX20JV1B ARX25JV1B ARX35JV1B. Installation manual R410A Split series

SUPER MODULAR MULTI SYSTEM AIR CONDITIONER

Installation Manual SPLIT-TYPE ROOM AIR CONDITIONER

INSTALLATION MANUAL. Four-Way Cassette. Model B-VMH09CU-1 B-VMH12CU-1 B-VMH18CU

Service Manual. Air Conditional

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER

AIR CONDITIONER CASSETTE

38VYX110/38VYX130 I S O INSTALLATION MANUAL

DVC/DVH Series. Inverter Single Zone Ductless Mini-Split A-DVC/DVH 09SF A-DVC/DVH 12SF A-DVC/DVH 18SF A-DVC/DVH 24SF

Installation Manual MMU-AP0154SH-E MMU-AP0184SH-E MMU-AP0244SH-E AIR CONDITIONER (MULTI TYPE) Indoor Unit. Model name: 1-Way Cassette Type.

Installation and Operation Manual. SVH Series. Inverter Single Zone Ductless Mini-Split SVH09SA-0 SVH09SA-1 SVH12SA-0 SVH12SA-1 SVH18SA-1 SVH24SA-1

Installation Manual. Middle Static Pressure Duct Type MIDDLE STATIC PRESSURE DUCT TYPE AIR CONDITIONER

InverterFlex Series Multi-Zone Ducted Indoor Unit B-VFH09DA-1 B-VFH12DA-1 B-VFH18DA-1 B-VFH24DA-1

FLEX MULTI SPLIT DUAL ZONE & TRI-ZONE INSTALLATION INSTRUCTIONS

Installation Instructions

FLOOR TYPE AIR CONDITIONERS

Table of Contents. Installation Manual. Accessories Safety Precautions Installation Overview Installation Diagram.

DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL

Please read this manual carefully before installation and keep it for future reference. Installation Manual. Olympus Series Cassette Air Handlers

INSTALLATION INSTRUCTIONS

42PHW / 42PHQ 42PHQ...K

Air conditioner. Installation manual AC777KN4DCH

1. BEFORE INSTALLATION

Transcription:

KFTC Series 18,000 to 48,000 Btu/h Cooling Only & Heat Pump INSTALLATION MANUAL

INSTALLATION INSTRUCTIONS CEILING CASSETTE TYPE INDOOR UNIT Read this installation instructions carefully before installing the unit MODEL KFTC018 / 024 SERIES KFTC036 / 048 SERIES COOLING ONLY OR HEAT PUMP SYSTEM

INSTALLATION DIAGRAM AND ACCESSORIES INDOOR UNIT High Pressure Copper Tube Low Pressure Copper Tube Drain Pipe Wire Low Pressure Piping Tape High Pressure Piping Tape OUTDOOR UNIT 2

1 INDOOR UNIT INSTALLATION WHERE TO INSTALL INDOOR UNIT : There should not be any heat source or steam near the unit. There should not be any obstacles to prevent the air circulation. A place where air circulation in the room will be good. A place where drainage can be easily obtained. A place where noise prevention is taken into consideration. Do not install the unit near the door way. 1.1 INDOOR UNIT DIMENSION. MODEL KFTC018 KFTC024 KFTC036 KFTC048 Height above ceiling (A) 235 mm. 235 mm. 285 mm. 285 mm. Height above suspension brackets (B) 180 mm. 180 mm. 230 mm. 230 mm. Height of condensate drain above ceiling (C) 230 mm. 230 mm. 280 mm. 280 mm. Pipe exit position (D) 165 mm. 165 mm. 215 mm. 215 mm. drainpipe outlet 830 refrigernt pipe 60 C B main cable entry D A FIG.1 22 3

INDOOR UNIT INSTALLATION THE CEILING HOLE 512 860~890 418 340 390 785 950 350 FIG.2 330 370 1.2 INDOOR UNIT INSTALLATION. Select the location where a space is more than 100 cm. as shown in fig.3 also ensure that the position does not interfere with light fitting, sprinkle head, etc. Determine the ceiling hole by using the paper pattern. Determine the mounting position on ceiling by using position A B C and D in the paper pattern. more than 100 cm FIG.3 more than 100 cm 4

INDOOR UNIT INSTALLATION Hang the four mounting rods to the positions marked as picture shown (using twelve nuts and eight washers to support the suspension brackets). Suspend the unit to the mounting rods. Lock the nuts, ensure for good drainsage, and check whether the unit is on horizontal level by using leveling guage. Lock Nut Washers Suspension Bracket Install the leveling metal plate to adjust the gap between the unit and a ceiling, fixing the screws following No. 1 2 3 and 4 in paper pattern. CROSS SECTION OF AIR OUTLET Remove four screws (M8). Fix the front panel with the units by tighten up four screws (M8). CAUTION : Overtightening the screws will distort the front panel. 5

2 OUTDOOR UNIT INSTALLATION WHERE TO INSTALL OUTDOOR UNIT : The foundation must be solid enough to bear the weight and vibration of the unit. The space around the unit is adequate for ventilation. The location is not close to any flamable gases. The location is sufficiently isolated so that the running noise and the hot exhaust air do not disturb the users or their neighbors. Easy access to check and to maintain. Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles. More than 10 cm. More than 10 cm. More than 10 cm. More than 70 cm. More than 35 cm. More than 10 cm. More than 30 cm. More than 30 cm. More than 35 cm. More than 120 cm. CAUTION Installation in the following places may cause problems. If it is unavoidable to use such places, consult with your distributor or dealer. A place with machine oil. A saline place such as a place very close to a seashore. A place with sulphur gas. A place where high-frequency waves are generated by radio equipment, welder and medical equipment. 6

3 PIPE PREPARATION PIPE & ELECTRICAL WIRE CUTTING Use cutting tools easily found in the market. Measure precisely both outer & inner pipe. Provide a little bit longer pipe than the measurement. Wire must be 1.5 m. longer than the refrigerant tube. Cutting Tool Right 90 Wrong Sloped Cut Rough Cut REAMING Clean inside of the inner refrigerant tube. While reaming, the tube end must be on the top of the reamer to prevent any dust going back into the tube. Refrigerant Tube Reamer Up side down position FLARING THE PIPE END Flare both ends of the pipe with flaring kit by fitting the flare nut on the pipe before flaring. Set the die on the pipe so that pipe end is 0.5 mm. above top of the die. Check if the pipe end is even and perfectly round. Refrigerant Tube 0.5 mm. Flare-Kit Uneven Slope Poor Skin Cracked Uneven Thickness WIRE CONNECTION AND TAPE COVERING (See the picture on the right hand side) 30-40 mm. Low Pressure Refrigerant Tube To Indoor Unit To Outdoor Unit 7

4 REFRIGERANT PIPING WORK 4.1 Select copper pipes for gas and liquid as informed in specific table (see the pipe table below) 4.2 For dust and moisture protection, before assembly of the pipe and its insulation, both ends of the pipe must be covered. 4.3 Avoid pipe bending as much as possible. If it is necessary, the bending radius must be more than 3 cm. or 4 cm. Gas pipe and liquid pipe insulation depends upon copper pipe size and the insulation thickness = 3/8" LIQUID PIPE TABLE MODEL PIPE SIZE THICKNESS (mm.) KFTC018 3/8" 0.8 KFTC024 3/8" 0.8 KFTC036 3/8" 0.8 KFTC048 1/2" 0.8 GAS PIPE TABLE MODEL PIPE SIZE THICKNESS (mm.) KFTC018 5/8" 1.0 KFTC024 5/8" 1.0 KFTC036 5/8" 1.0 KFTC048 3/4" 1.0 Gas Pipe Piping Tape Connecting Wire Liquid Pipe Dia. Drain Pipe 1/2" 4.4 The connection between an indoor unit and an outdoor unit. Unscrew the flare nut for releasing pressure gas in the indoor unit. If there is no high pressure gas blowing out, it is the signal of a leaking indoor unit. Fit the flare nut to the liquid pipe. Flare the pipe's end with flare tool. Tighten both flare nuts into gas pipe and liquid pipe at the indoor unit with two holding spanners. 8

REFRIGERANT PIPING WORK DRAIN PIPE OUTLET A drain pipe and refrigerant pipes must be covered by insulation to prevent condensation. Caution on drain collecting piping. Use a larger diameter pipe as it comes near the end. Horizontal Not greater than 100 The size of pipes marked with *must be at least 40 mm (1-5/8), depending on the number of indoor units installed. Install the drain pipe at a lower level immediately after the unit. 9

5 AIR PURGING AND CHECK OF PIPE LEAKAGE AIR PURGING The purpose of air purging is to get rid of moisture and air in the system, otherwise moisture and air may cause ineffectiveness of the compressor which directly affects the cooling capacity. PURGING BY USING VACUUM. After tightening the flare nuts between the indoor and the outdoor units. Remove a blank cap of a three-way valve by using a torque wrench. Check if both high pressure and low pressure valves are in closed condition. Remove the nut of the service port. Connect a gauge into the service port and a vacuum pump. Vacuum until the gauge indicates at 30 inches mercury pressure. Remove gauge. Tighten up the nut of the service port. Use a hexagonal wrench to open both high pressure and low pressure valves to the end (counter clockwise). Tighten the blank cap of the three-way valve. Vacuum Pump OUTDOOR UNIT Point at 30 inches mercury pressure. Gauge Open Close GAS LEAKING CHECK Check leakage by apply soapsuds to every connection and inspect carefully. After checking, wipe them off completely. Cover indoor unit joint with pipe insulation and 4 plastic bands to prevent condensation at joints. 10

6 WIRING DIAGRAM Wiring is to be done as shown in the electrical wiring diagram (Do not change the internal wiring) Use copper conduction only. How to tighten screw on terminal block. 1. Bare the ends of electric wire. 2. After retaining the wire, check that all the terminal screws are firmly tightened. COOLING ONLY INDOOR UNIT KFTC018-C KFTC02-C KFTC036-C OUTDOOR UNIT KCHB018-C KCHB024-C KCHB036-C HEAT PUMP INDOOR UNIT KFTC018-H KFTC024-H KFTC036-H OUTDOOR UNIT KCHB018-H KCHB024-H KCHB036-H 11

WIRING DIAGRAM COOLING ONLY INDOOR UNIT KFTC036 / 048-C OUTDOOR UNIT KCVS036 / 048-C HEAT PUMP INDOOR UNIT KFTC036 / 048-H OUTDOOR UNIT KCVS036 / 048-H 12

7 LIQUID PIPE AND DRAIN PIPE IF THE OUTDOOR UNIT IS INSTALLED LOWER THAN THE INDOOR UNIT (picture 1) Sealed 1. A drain pipe should be above ground and the end of the pipe does not dip into water. All pipes must be restrained to the wall by saddles. 2. Taping of the pipes must be done from bottom to top. 3. All pipes are bound together by tape and restrained to the wall by saddles. Saddle Drain Pipe Picture 1 IF THE OUTDOOR UNIT IS INSTALLED HIGHER THAN THE INDOOR UNIT (picture 2) 1. Taping should done from lower to upper part. 2. All pipes are bound and taped together and trapped the pipes to prevent water returning to the room. (see picture) 3. Restrain all pipes to the wall with saddles. Tape Drain Pipe Refrigerant Pipe Wire Trap Picture 2 13

8 TEST RUNNING RUN TEST Check electrical main wire's voltage. Run the air conditioner for 15 minutes or more. Check the electrical current with ampmeter and compare with the specifications. Terminal Board Control Board Cover Electrical Wire Ampmeter EVALUATION OF THE PERFORMANCE Use a thermometer to measure cool air both in and out. The difference between in-air and out-air temperature should not be less than 8 c. Thermometer 14

Klimaire Products, Inc. 7909 N.W. 54th Street Miami, 33166 U.S.A. Tel : (305)593-8358 Fax : (305)593-8212 e-mail : klimaire@worldnet.att.net NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE I2TC2001