ARTEMIS Series of Low Occupancy LED Ceiling Mounted Fixtures (Including Stairwells) Installation & Operation Guide

Similar documents
INSTALLATION INSTRUCTIONS

Caliber Series LED Edgelit Exit Sign EXPORT AC Only or Emergency Operation READ AND FOLLOW ALL SAFETY INSTRUCTIONS

THINLINE TL2 SERIES INSTALLATION AND OPERATING INSTRUCTIONS

LED Emergency Battery Backup Installation Instructions Ordering Code: EB23UQ

RAZOR RZR SERIES DIE CAST ALUMINUM LED EXIT SIGNS INSTALLATION AND OPERATING INSTRUCTIONS IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS

INSTRUCTION MANUAL IMPORTANT SAFEGUARDS. When using electrical equipment, basic safety precautions should always be followed, including the following:

INSTALLATION INSTRUCTIONS - PS1055LCP & PS1555LCP LED EMERGENCY DRIVER PS1055LCP & PS1555LCP

INSTALLATION INSTRUCTIONS - POWER SENTRY CONTROL POWER SENTRY CONTROL UNIT PSBCEB2 INSTALLATION INSTRUCTIONS

SERVICE BY QUALIFIED PERSONNEL ONLY

ILB-CP TBTS A MOUNTING DESIGN EMERGENCY LIGHTING EQUIPMENT FOR LED

ILB-CP TBTS A MOUNTING DESIGN EMERGENCY LIGHTING EQUIPMENT FOR LED

ILB-CP TBTS B MOUNTING DESIGN EMERGENCY LIGHTING EQUIPMENT FOR LED Patented. See iotaengineering.com/patents for more details

Model: EF34. Owner's Guide & Installation Manual

LED Emergency Battery Backup

Installation Instructions

INSTANT HOT WATER DISPENSER

Installation Instructions

GTD20A Installation Instructions BRANCH CIRCUIT TRANSFER SWITCH/LIGHTING CONTROL DEVICE

CXB Series SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. LED Luminaire TO INSTALL: INSTALLATION INSTRUCTIONS INSTRUCTIONS D INSTALLATION

LED CEILING LIGHT WITH MOTION SENSOR AND REMOTE. ITM. / ART Model: LM56123 CARE & USE INSTRUCTIONS

SAVE THESE INSTRUCTIONS INSTALLATION INSTRUCTIONS EMERGENCY FLUORESCENT BATTERY PACK MODEL PS300, PS600, PS1400

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

DS9370-BEL. Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector

5WF42XX Series Fan UL Model No. : AC-542OD. Owner s Guide and Installation Manual

5CO52XX Series Fan UL Model No. : 5CO52. Owner s Guide and Installation Manual. Attach sales receipt to this card and retain as your proof of purchase

BACKUP BATTERY INSTALLATION INSTRUCTIONS

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. NXM Series - Survive-All. Emergency Light Unit

1 x4 Dimmable LED RetroFits

Installation Instructions

3MNLR72XXD Series Fan. Owner s Guide and Installation Manual. UL Model NO. : 3MNLR72

Ceiling Fan Installation Instructions

5DI52XXD/5DI52XXD-L Series Fan UL Model No. : 5DI52. Owner s Guide and Installation Manual

Ceiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions

TOCR02 2 PART MICRO MOTION SENSOR W/IR REMOTE CONTROLLER

DATE OF PURCHASE: RETAILER NAME: MODEL NUMBER: RETAILER ADDRESS:

Ceiling Fan Installation Instructions

QCM979D-38AGO ELECTRIC FIREPLACE HEATER NDF-65NB-3 INSTRUCTION MANUAL

CEILING FAN OWNER'S MANUAL

Install Guide 8046 ENGLISH. Customer Support: or: visit our website Printed in China ON.

Step 1: Identify the parts of your shade (parts shown are not to scale)

WARNING. Tighten strain relief screws to secure cable. Make sure screw heads are facing up when tightening conduit nut.

Ceiling Fan Installation Instructions

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. HZM-Series-Class I, Div 2 Battery Unit. Instalation instructions

3MAVR60XXD Series Fan. Owner s Guide and Installation Manual. CUL Model NO. : 3MAVR60XXD

Ceiling Fan Installation Instructions

FIELD-INSTALLED MOTION ACTIVATED LED DIMMER CONTROL

Installation Instructions

Installation Instructions

DATE OF PURCHASE: RETAILER NAME: MODEL NUMBER: RETAILER ADDRESS:

2 PREPARE THE OPENING

Install Guide Customer Support: or Visit our website

Service Manual. Model Number: DF2024. UL Part Number

5SLR52XXD-B Series Fan UL Model No. : 5SLR52. Owner s Guide and Installation Manual

Installation & Operations Manual

Service Manual. Model Number: DF2624L. UL Part Number

CEILING FAN OWNER S MANUAL

M650-38A-OAK ELECTRIC FIREPLACE HEATER NDF-65NB-1 INSTRUCTION MANUAL

Table of Contents What to Expect with Your Installation. Top Housing. Ceiling Plate. Tools Needed.

Ceiling Fan Installation Instructions

Albeo TM LED Luminaire Accessory (Emergency Battery Backup Module)

3MAVR60XX Series Fan. Owner s Guide and Installation Manual. UL Model NO. : 3MAVR60XX

Viking Installation Guide

Installation. 324 Series Built-In Dishwashers U L. Viking Range, LLC 111 Front Street Greenwood, Mississippi USA (662)

Service Manual. Model Number VCX1525 VCX1525-WH. UL Part Number

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

I-320 SERIES AC EMERGENCY LIGHTING EQUIPMENT

Service Manual. Model Number VCX1525 VCX1525-WH. UL Part Number

5COM52XXD Series Fan. Owner s Guide and Installation Manual. UL Model NO. : 5COM52XXD

Service Manual. Model Number: Compact Fireplace DF203A DF2006. UL Part Number to 800

WARNING Risk of fire and electrical shock. DISCONNECT POWER AT ELECTRICAL PANEL before installing or servicing this product.

3DIR52XXD Series Fan. Owner s Guide and Installation Manual. UL Model NO. : 3DIR52XXD

Please read and save these instructions. Should you have any questions or difficulty installing your fan, call us first!

Service Manual. Model Number: DF2524L DF2524G. UL Part Number

CEILING FAN OWNER'S MANUAL

CEILING FAN OWNER S MANUAL

KD-27A SERIES DISHWASHERS

Ceiling Fan Installation Instructions

3SA60 3SA60+LED. Vogue & Vogue Plus. Net weight. This instruction contains 11 pages:

DATE OF PURCHASE: RETAILER NAME: MODEL NUMBER: RETAILER ADDRESS:

Dryer. User manual DV22K6800** DV22K A-00_EN (US)_ indd :15:41

CEILING FAN OWNER'S MANUAL

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. 3LERHZ Series Class I, Div 2 Combo Unit. Installation instructions

Cooktop Chimney Ventilation Hoods

SP-1000X. Panic Device Power Controller Installation Guide. Rev

INSTALLATION INSTRUCTION for ceiling fan

TRUSTY PRODUCTS, INC.

CEILING FAN OWNER S MANUAL

MODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload

Nachi Series TM Z6957-XL

CEILING FAN OWNER'S MANUAL

Infrared Wall Mount Occupancy Sensor

INSTALLATION. Glass Panel Doors (select models) CAUTION

HPNLS-LO. Installation Manual

Installation Instructions

Tommy Bahama INDOOR/OUTDOOR 52 in. / 132 cm. CABRILLO COVE CEILING FAN

Service Manual 23 Compact Fireplace Model Number: DF2305

LIVMODERN LIVMODERN RPT. Elegant linear LED fixture PART NUMBER BUILDER 10VDIM 0-10VDIMMABLE 3000K 4000K 24IN 36IN 48IN 1800LM* 3000LM** 3500LM***

Ceiling Fan Installation Instructions

Electrical cable Water supply tube Fittings for tube Coupler Teflon tape. Hole saw min. 2½" bit

PARTS & ACCESSORIES INSTALLATION AND SAFETY INSTRCUTIONS ITEM NO.:60006PC SAFETY PRECAUTION. Canopy. Downrod. Housing. Blade. Transmitter CR2032/3V

Transcription:

Low Occupancy Fixture XL Stairwell Fixture XS 1

Please read these instructions carefully, and keep them for future reference. IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: a) READ AND FOLLOW ALL SAFETY INSTRUCTIONS. b) Do not use outdoors. c) Do not let power supply cords touch hot surfaces. d) Do not mount near gas or electric heaters.. e) Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel. f) The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. g) Do not use this equipment for other than intended use. SAVE THESE INSTRUCTIONS 2

ARTEMIS Series of Low Occupancy LED Ceiling Mounted Fixtures (Including Stairwells) Installation & Operation Guide PARTS & TOOLS REQUIRED: Artemis S tairwell F ixture Wire Nuts Drill and Masonry Drill B its ( Not provided) Flat B lade S crewdriver (Not Provided) Phillips S crewdriver ( Not Provided) Anchors & Mounting Hardware ( Not Provided) Note: Ensure compliance w ith local codes and ordinances. WARNING: Turn power off at circuit breaker or fuse box. Do not rely on a wall switch alone to turn off power. Failure to do so may cause a shock hazard and damage this electronic fixture! 3 Xeleum Lighting, LLC. 3 33 North Bedford Rd. M ount Kisco, NY 10549 * P hone 9 54-617- 8170 * Fax 9 54-571- 9777 * www.xeleum.com

ARTEMIS Series of Low Occupancy LED Ceiling Mounted Fixtures (Including Stairwells) Installation & Operation Guide Installation Step Description 1 Remove the fixture from the packaging and m ake sure it has arrived in good condition. Place the fixture on a flat surface and remove two screws w hich secure the back- box to the light engine (located on either side of the fixture in the m iddle and just behind the lens). 2 Use a straight slot screw driver and gently pry the sheet m etal away from the light engine. There is a notch designed into the back box for this purpose. This w ill release the primary light engine from the back box (white). 3 4 5 Image Carefully remove the primary light engine and set it next to the back box. There are two connectors that m ust be disconnected. The larger of the two connectors is for the m otion sensor array. The smaller connector powers the light engine. After removing the existing fixture from the ceiling, position the new back box w here you want it. Using the provided openings, secure the back box to the imbedded junction box (if power is coming in from the back of the fixture). Check the alignment of the back box and then secure the ends of the fixture using the provided holes. An anchor or Tapcon is recommended, ensuring that this is compliant w ith local codes and ordinances. Note: Use w ashers as spacers if the ceiling is not flat. Not doing so can result in a w arping of the back box, m aking it difficult to snap in the primary light engine. If installing an emergency back- up battery, us a Philips screwdriver to remove the battery holding fixture closest to the driver. 4 4 Xeleum Lighting, LLC. 3 33 North Bedford Rd. M ount Kisco, NY 10549 * P hone 9 54-617- 8170 * Fax 9 54-571- 9777 * www.xeleum.com

ARTEMIS Series of Low Occupancy LED Ceiling Mounted Fixtures (Including Stairwells) Installation & Operation Guide Installation (cont.) Step 6 7 8 Description Image Feed the battery connector through the opening in the battery holder you just removed. Place the other end of the battery in the corresponding holder. Use a Philips head screwdriver and re- install the battery holder. Plug the w hite connector coming out of the battery into the m atting connector inside the back box. If power is coming into the fixture via an electrical conduit (flex or rigid), use one of the knockouts at either end of the fixture. Make sure the proper strain reliefs are used to fully comply w ith local codes or ordinances. Hook up the three incoming power w ires to the three w ires within the back box. Use the provided wire nuts or similar products to ensure the safety of the installation. 9 Hold the light engine close to the back box mounted to the ceiling and plug in the two connectors (sensor array and power for the light engine). 10 Snap the light engine into the back box, being very careful not to pinch any w ires. You may need to pry back the m etal of the back box slightly to facilitate this step. Once the light engine is snapped into the back box re- install to the two screws into either side of the fixture. Note: 1: If a replacement battery is needed, the part number is as follows: XAP- 0039 Note 2: As emergency lights ( with batteries) these fixtures should not be m ounted above 31. 5 Xeleum Lighting, LLC. 3 33 North Bedford Rd. M ount Kisco, NY 10549 * P hone 9 54-617- 8170 * Fax 9 54-571- 9777 * www.xeleum.com

Control Panel For Stairwell (XS) Fixtures Self- Diagnostic: Periodically it s a good idea for the operators to push the Self- Diagnostic button to run the built- in testing program. Results of the Self- Diagnostic test are reported on the DIAG LED Indicator. See the table on the next page for a detailed description of the indications. Stairwell Dial Switch: Some buildings have more than one stairwell. This switch helps to keep fixtures in one stairwell from talking to fixtures in another stairwell. If you have one stairwell, use a small straight slot screwdriver and set the dial to 1. For multiple stairwells within a building, set the dial accordingly. STAIRWELL Self- Diagnostic Status LED: This is a bi- colored LEDs (Red or Green). This LED provide the operator with the self- diagnostic test status and results. See the table on the next page for a detailed description of the indications. X10 FLOOR X1 X1 Status Indicator LED: This is a bi- colored LED (Red or Green). This LED provides the operator with the current system status. See the table on the next page for a detailed description of the various indications. DIM Setting controls the light level when the stairwell is un- occupied. DIM HI LOW POWER Setting controls the light level when the stairwell is occupied. POWER HI LOW Floor X10 Dial Switch: This dial is set to indicate the floor a particular fixture is being installed on. If the fixture is being installed on floors 1-9, this dial would be set to 0. If the fixture is being installed on floors 10 19, this dial would be set to 1. If it is being installed on floors 20 29, this dial would be set to 2, etc. Floor X1 Dial Switch: This dial is set to indicate the floor a particular fixture is being installed on. If the fixture is being installed on the 4 th floor, this dial would be set to 4. If the fixture is being installed on the 23 rd floor this dial would be set to 3, etc. Timer: Once the fixture sees motion within the stairwell it will immediately illuminate to full intensity. A small screwdriver is used to adjust the Timer. This Timer adjusts the length of time that the fixture remains on at full power prior to returning to the DIM setting. Turning the Timer all the way to the left (counter clockwise) will keep the fixture on at high power for only 10- seconds. Turning the Timer all the way to the right (clockwise) will keep the lights on at full power for 5- minutes after the sensor sees its last motion. The time can also be set anywhere between 10- seconds and 5- minutes by positioning the Timer accordingly. EXAMPLE #1: If a fixture is being installed in the second stairwell of a building on the 17 th floor, the dial indicators would be set like this: 2 1 7. EXAMPLE #2: If a fixture is being installed in a building with only one stairwell on the landing between floors 5 and 6, the dial indicators would be set like this: 1 0 5. NOTE: Landings between floors should have the same dial settings as the floor just below it i.e. A fixture installed on a landing between floors 2 and 3 should have the same dial settings as the fixture on floor 2. 6

Control Panel For Low Occupancy (XL) Fixtures Self- Diagnostic: Periodically it s a good idea for the operators to push the Self- Diagnostic button to run the built- in testing program. Results of the Self- Diagnostic test are reported on the DIAG LED Indicator. See the table on the next page for a detailed description of the indications. Zone Dial Switch: Some facilities have more than one building or areas to illuminate. This switch helps to keep fixtures in one building or area from talking to fixtures in adjoining buildings or areas. If you re only illuminating one area, use a small straight slot screwdriver and set the dial to 1. For multiple buildings or areas set the dial accordingly. Self- Diagnostic Status LED: This is a bi- colored LEDs (Red or Green). This LED provide the operator with the self- diagnostic test status and results. See the table on the next page for a detailed description of the indications. X10 AREA X1 Status Indicator LED: This is a bi- colored LED (Red or Green). This LED provides the operator with the current system status. See the table on the next page for a detailed description of the various indications. DIM Setting controls the light level when the stairwell is un- occupied. DIM HI LOW OFF POWER Setting controls the light level when the stairwell is occupied. POWER HI LOW XL Area X10 Dial Switch: This dial is set to indicate the floor or area a particular fixture is being installed on. If the fixtures are being installed on floors 1-9, this dial would be set to 0. If the fixture is being installed on floors 10 19, this dial would be set to 1. If it is being installed on floors 20 29, this dial would be set to 2, etc. Area X1 Dial Switch: This dial is set to indicate the floor or area a particular fixture is being installed on. If the fixture is being installed on the 4 th floor, this dial would be set to 4. If the fixture is being installed on the 23 rd floor this dial would be set to 3, etc. Timer: Once the fixture sees motion within an area it will immediately illuminate to full intensity. A small screwdriver is used to adjust the Timer. This Timer adjusts the length of time that the fixture remains on at full power prior to returning to the DIM setting. Turning the Timer all the way to the left (counter clockwise) will keep the fixture on at high power for only 10- seconds. Turning the Timer all the way to the right (clockwise) will keep the lights on at full power for 5- minutes after the sensor sees its last motion. The time can also be set anywhere between 5- seconds and 10- minutes by positioning the Timer accordingly. EXAMPLE #1: If a fixture is being installed in the second stairwell of a building on the 17 th floor, the dial indicators would be set like this: 2 1 7. EXAMPLE #2: If a fixture is being installed in a building with only one stairwell on the landing between floors 5 and 6, the dial indicators would be set like this: 1 0 5. NOTE: Landings between floors should have the same dial settings as the floor just below it i.e. A fixture installed on a landing between floors 2 and 3 should have the same dial settings as the fixture on floor 2. 7

Control Panel LED Indicator Message Interpretation Only For Fixtures (XS & XL) with Battery Back- Up Once the fixture has been properly secured to the ceiling and powered, two Indicator LEDs can be seen on the control panel on the side of the fixture. The one to the left (when looking at the control panel) is the Diagnostic LED Indicator. The one to the right is the Status LED Indicator. These LEDs are bi- colored, meaning they can be 2 different colors, in this case RED or GREEN. The table below explains what the Status LED Indicator means: STAIRW ELL X1 0 FLOOR X1 Status LED Function Status LED AC Power Good, Battery Charged GREEN: On X1 X1 0 AREA AREA X1 X1 or AC Power Good, Battery Charging AC Power Off, Battery Good GREEN: Flashing RED: On XL AC Power Off, Battery Low Battery FAULT RED: Flashing Alternate Flashing between RED and GREEN To be in compliance with NFPA Life Safety Code 101, end users must perform a 30- second monthly functional test and a 90- minute annual test. The 30- second monthly test is done by pressing the Diagnostic Test Button on the control panel. A 30- second self- diagnostic test is built into the programming of this unit. After 30- seconds the results will be displayed as indicated in the table below. To conduct the annual test, power should be secured to the stairwell fixtures externally (i.e. the circuit breaker). At the end of 90 minutes the fixtures should still be providing adequate illumination through the integrated battery back- up system within this fixture (if so equipped). The test itself and the results should be recorded and this record maintained by the end user. The table below explains what the Diagnostic LED Indicator (DIAG) means: STAIRW ELL X1 0 FLOOR X1 Diagnostic LED Function Diagnostic LED X1 0 AREA X1 or Diagnostic FAILED Diagnostic PASSED RED: On GREEN: On XL Diagnostic in PROGRESS Alternate Flashing between RED and GREEN Note: For full details related to periodic testing of stairwell fixtures, see NFPA 101(00), Sec 7.9.3. 8

DIM and POWER Settings For Artemis Fixtures There are very stringent illumination regulations governing fixtures intended for use in stairwells. Xeleum s XS Artemis fixtures are specifically design to surpass these requirements, and have been validated with 3 rd party testing and certification. As such, neither the POWER (occupied) and DIM (un- occupied) settings can be turned off. This ensures the proper illumination required to be compliant with regulatory requirements. POWER and DIM Settings: STAIRWELL X10 FLOOR X1 DIAG. STATUS For non- stairwell applications, Xeleum s Artemis XL series offers several different POWER and DIM settings allowing full customization for customer specific application. A small slide switch is provided in the window under the DIM and POWER labels on the control panel. These can be set with a finger or a small screwdriver. X10 AREA X1 DIAG. STATUS Slide Switch DIM Settings for the XL (non- stairwell version): The DIM setting controls the light level when the area being illuminated is unoccupied. There are three different options for this setting HI This setting provides about 50% of the fixtures full illumination capability when the area being illuminated is unoccupied. LOW This setting provides about 10% of the fixtures full illumination capability when the area being illuminated is unoccupied. OFF This setting turns the fixture completely off when the area being illuminated is unoccupied. Note: There may still be a slight glow coming from the fixture in this setting. This is related to the charging and memory features of this fixture. POWER Settings: The POWER setting controls the light level when the area is being illuminated after the fixture s PIR sensor has identified movement within the space (occupied) HI This setting provides 100% power or about 4200 lumens for maximum illumination within the space being illuminated. LOW - This setting provides about 75% power or about 3200 lumens within the space being illuminated. This setting provides an additional 25% energy savings as compared to the HI setting. 9