AL602ULADA AL802ULADA AL1002ULADA

Similar documents
AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL800ULADA. NAC Power Extender. Installation Guide

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

AL600ULADA. NAC Power Extender. Installation Guide

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for models:

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

Installation Guide for models:

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

FireNET Plus Wiring Instructions

IFP-2000 F r a en e h n y h t y PH P D

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Rack Mount Series Installation Guide

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

TrueAlert Notification Appliances

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

SILENT KNIGHT Installation Manual. Distributed Power Module. Part Number G, 08/03

Series. Access Power Controllers. Installation Guide

LifeAlarm Fire Alarm Controls

Access Power Controllers with Power Supplies

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

MEA. SpectrAlert Series Horns, Strobes, and Horn/Strobes GENERAL

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

1. POWERPATH Operation

TrueAlert Addressable Notification Appliances

Addressable Fire Alarm Control Panel

TrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions

SELECT-A-HORN/STROBE SERIES

CSH24CH. Colored Light Strobe/Horn Series High Candela. Description. Features. Ceiling/Wall Mount Patent Pending. Ordering Information

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

TrueAlert Addressable Notification Appliances

MPC-6000 / MPC-7000 / RND-2

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

MODEL Distributed Power Module. Installation and Operations Manual. Part Number Rev L

Interface and EOL Modules 8

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN

SpectrAlert Advance. Field-Selectable Mass Notification Devices. Description. An ISO Company SIGNALING. MEA Approved E

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

AL600ULX Series. Power Supply/Charger. Installation Guide

Agent Release Control Panel

TrueAlert Addressable Notification Appliances

s Notification Appliances

PN: 51883:D ECN Field Charger/Power Supply FCPS-24FS6 FCPS-24FS8. Document # /14/05 Revision: D

TrueAlert Multi-Candela Notification Appliances

08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

TrueAlert Multi-Candela Notification Appliances

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

AL602ULADA. NAC Power Extender. Installation Guide (see 02 Application Guide for additional information) More than just power. TM. Rev.

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

I. Synchronized Strobes 2=PROGRAMMING PROGRAMMING ENTER PASSWORD *****

Honeywell Power Products

Appendix A Compatible Devices

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

Rev. B. TrueAlert Addressable Controller Application Manual

Release Control Fire Alarm Systems

Innovation that Endures

MR-2602 Two Zone Fire Alarm Control Panel

30.45 Electric Release PDRP-2001

L-Series, Indoor Strobes and Horn Strobes

LifeAlarm Fire Alarm Control Panels

Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet

Wheelock RSS & RSSP Series

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

Laptop / PC Programming Manual

L-Series, Indoor Strobes and Horn Strobes

PSN-1000 & PSN 1000(E) Installation Manual

HPFF8(E)/HPFF8CM(E) NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

AND ARCHITECT SPECIFICATIONS

Booster Power Supply Manual

PFC-4064 Conventional Fire Alarm Panel

Notification Appliance Circuit Module

Addressable NAC Output Module D327A

TrueAlert Addressable Notification Appliances

D7024 Fire Alarm Control Panel

advancedsolutions Advanced Design. We have engineered all SpectrAlert products to meet or exceed code today and tomorrow. We ve worked to standardize

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

/5121/5122 TrueAlert Power Supply Installation Instructions

L-Series, Emergency Communication Devices

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Intelligent Analog/Addressable Fire Alarm/Voice Integration Systems. IntelliKnight TM Series

MODEL Intelligent Power Module. Installation and Operations Manual. Document /12/10 Rev: E1 P/N :E1 ECN:

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

Transcription:

AL602ULADA AL802ULADA AL1002ULADA NAC Power Extenders Application Guide (See Installation Guide for additional information) Rev. 031703

1. General Information (Use this in conjunction with respective Installation Guide): Altronix AL602ULADA, AL802ULADA and AL1002ULADA are very versatile devices. They can be used with or without specific synchronization modules provided by some manufacturers. Multiple units can be synchronized by using either the built-in sync mode or a external synchronization module. Please note, that only notification appliances with synchronization capabilities can be synchronized. Contact signal manufacturer for more detailed information. Units can operate with either one (1) or two (2) outputs from the FACP. Two (2) outputs from the NAC power extender can be paralleled to achieve up to 4 amp, for circuits requiring additional power. Note: Each output can be split into two (2) wire runs to achieve up to eight (8). 2. Paralleling Two (2) Outputs: To parallel two (2) outputs for maximum NAC capability of 4 amp, bridge (pos+) to (pos+) and (neg-) to (neg-) (ex. +OUT3 to +OUT4 and OUT3 - to OUT4 -, Fig. 2). Both of the corresponding output switches must be set the same way. Install two (2) ohm resistors in parallel across the last notification appliance. Please note: Paralleled output circuit configuration is not power limited and paralleling is not allowable for Class A configuration. Fig. 2 SW2 SW1 + OUT1 -- + OUT2 -- + OUT3 -- + OUT4 -- Class B single outputs Class B paralleled outputs 3. Class A and Class B Hookups: Units can be used with the outputs configured for: Two (2) Class A (Fig. 3A). Two (2) Class B and one (1) Class A NAC circuits (Fig. 3B). Up to Four (4) Class B (Fig. 3C). Fig. 3A Fig. 3B Fig. 3C SW2 SW1 + OUT1 -- + OUT2 -- + OUT3 -- + OUT4 -- SW2 SW1 + OUT1 -- + OUT2 -- + OUT3 -- + OUT4 -- SW2 SW1 + OUT1 -- + OUT2 -- + OUT3 -- + OUT4 -- 2 Class A Hookups NAC Loop 1 starts on Output 1 and terminates on Output 3. Switch SW1, when closed, provides proper termination for this loop. NAC Loop 2 starts on Output 2 and terminates on Output 4, SW2 must be closed for proper termination. Please make sure that all the dip switches for corresponding outputs are set the same way. One (1) Class A, two (2) Class B Hookups For combination of two (2) Class B and one (1) Class A circuit, only one (1) switch (SW1 or SW2) must be closed, terminating Class A circuit only. - 2 - Eight (8) wire runs Connect two (2) wire runs to one (1) output with a 4.7K, (Altronix Model # AL-47) used to terminate each wire runs. Note: Both wire runs will be supervised. A trouble condition on either wire run is reported on the common signaling circuit. However a short circuit on one wire run will affect the other wire run on the same signaling circuit. Keep wires on different sides of the screw. DO NOT USE one (1) continuous circuit around the terminal. This is available to facilitate more wire runs from the unit.

4. Non-synchronizable NAC Appliances: When using NAC appliances not designed to support synchronization feature, it is recommended to use separate output circuits for audible notification appliances (horns) and visual notification appliances (strobes). Set dip switches for the visual notification appliances to follow Input 1 [IN1] and for audible notification appliances to follow Input 2 [IN2]. This will allow, when using two (2) outputs from the FACP, to support silencing of audible notification appliances. When using only one (1) FACP output, set all dip switches to follow Input 1 [IN1]. The units outputs can each be set for the desired NAC drive signal, such as Code 3 or march time sequence (Output Programming Selection Table, pg. 6). Non-synchronizable Audible Appliances will follow the sequence, when feature is selected. 5. Synchronizing One (1) or More NAC Power Extenders from an FACP with Sync Capability or a Sync Module: AL602/802/1002ULADA units are designed to follow (replicate) the coded sequence, generated by a manufacturer s sync module. One (1) or more units can be synchronized. Please select Input to Output follower mode (Output Programming Selection Table, pg. 6). Connect the output of the sync module to Input 1 or Input 2, depending which input is selected to drive the outputs. Terminate the input circuit with the, connecting it to terminals marked [RET+ and RET-], or continue the input circuit, connecting to terminals marked [RET+ and RET- to INP+ and INP-] of the next unit, when multiple units need to be synchronized. Fig. 5 FACP with Sync Output NAC Power Extender: NAC Power Extender: FACP (Fire Alarm Control Panel with sync capabilities) Or Sync Module + NAC 1 --- + NAC 2 --- IN + IN --- IN + IN --- HORN CONTROL ZONE 1 ZONE 1 ZONE 2 OUT + OUT --- OUT + OUT --- To FACP or next NAC power extender - 3 -

6. Synchronizing One (1) or More NAC Power Extenders Using Built-in Sync Protocol: AL602/802/1002ULADA have built-in protocols to support Amseco, Faraday, Gentex and System Sensor twowire synchronizable devices, therefore an external sync module is not required (Output Programming Selection Table, pg. 6). In these modes, Input 1 is always used to activate visual notification appliances (strobes), and Input 2 is used to activate and silence audible notification appliances (strobes). Note: Input 1 has to be activated in all the configurations. Multiple NAC Power Extenders can be synchronized by one (1) of two (2) (Figs. 6A and 6B) methods described below: Set the master unit to generate the desired sync protocol, while the remaining NAC Power Extenders are set for Input/Output Follower Mode. Fig. 6A For continuous loop circuit use, (Altronix Model # AL-22). Dip Switches set for desired Sync Protocol (ex. Gentex, System Sensor, Faraday or Amseco). FACP (Fire Alarm Control Panel) Fig. 6B For split output circuit use 4.7K, (Altronix Model # AL-47). Dip Switches set for desired Sync Protocol (ex. Gentex, System Sensor, Faraday or Amseco). To 4.7K or next AL602ULADA, AL802ULADA, and AL1002ULADA. FACP (Fire Alarm Control Panel) When connecting, keep wires on different sides of the screws in order to maintain loop integrity supervision. DO NOT LOOP CONTINUOUS WIRE AROUND THE SCREW. - 4 -

7. Using a Single FACP Output: When only one FACP output is available, you may connect both Input1 and Input2 to it. Wire [RET1+ and RET1- to INP2+ and INP2-]. Both visual and audible notification appliances will be activated simultaneously (Fig. 7). Fig. 7A IN1+ IN1-- -- C "DRY1" NC RET1+ -- -- C "DRY2" NC UPPER TERMINALS LOWER TERMINALS FACP or Next Device - 5 -

Output Programming Selection Table: Outputs must be programmed independently (OUT1 - OUT4) Function Switch Positions Descriptions ON OFF Input to Output 1 2, 3 Output follows signal it receives from the corresponding input (i.e. FACP Follower Mode Sync module - maintains synchronization of notification appliance circuit. Temporal Code 3 3 1, 2 Enables Temporal Code 3 signal generation output. Mode This mode is activated by a steady or a pulsing input. Steady Mode 1, 2, 3 A steady output signal will be generated. This mode is activated by a steady or pulsing input. March Time Mode 2, 3 1 Enables a March Time output which will sound 60 beats (60 beats per minute) per minute. This mode is activated by a steady or pulsing input. For the above modes Dip Switch 4 determines which Input controls the corresponding output: Switch 4 in the ON position causes output(s) to be controlled by input 1. Switch 4 in the OFF position causes output(s) to be controlled by input 2. Gentex is a registered trademark of Gentex Corporation. (AL800LGK Board) Output Dip Switches Sync Mode Selection Table: Function Switch Positions Descriptions ON OFF Amseco 1, 3, 4 2 This mode is designed to work with the Amseco series of horns, strobes, Sync Mode* and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active. Faraday 2, 4 1, 3 This mode is designed to work with the Faraday series of horns, strobes, Sync Mode* and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active. Gentex 1, 2, This mode is designed to work with the Gentex Commander GOS Sync Mode* 3, 4 and ST/HS series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two (2)-wire circuit while leaving strobes active. System Sensor 1, 2, 4 3 This mode is designed to work with the SpectrAlert TM series of horns, Sync Mode* strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the one-second flash timing System Sensor is a registered trademark of Honeywell. of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active. Note: The AL602ULADA, AL802ULADA, and AL1002ULADA will only synchronize horns, horn strobes and strobes that contain synchronization capability. Contact signal manufacturer for more detailed info. The same synchronization mode must be selected for all outputs. * It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. 1 2 3 4 O N INPUT SELECT TEMPORAL STROBE SYNC IN>OUT SYNC - 6 -

Notes: - 7 -

Notes: 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIAL602,802,1002ULADA G29E - 8 -