Installation instructions. Pump Group. For wall hung gas-fired condensing boiler GB162-50/65/80/ TD UK/IE (2014/09)

Similar documents
CondenseSure Siphon INSTALLATION INSTRUCTIONS UK/IE GREENSTAR EXTERNAL 500ML SIPHON

INSTALLATION INSTRUCTIONS FOR FLUE KIT

Greenstar System Filter

Greenstar Xtra. Installation instructions. Passive flue gas heat recovery device. For use with Greenstar CDi Compact, Si Compact and i combi boilers

GB162 Concentric Horizontal Vent Kit

Back to back. Cascade Venting System for RTG 199HE. Basic Set for units 1 and Installation instructions

Side by side. Cascade Venting System for RTG 199HE. Extension Set for units 3 or Installation instructions

Operating instructions

RT 10 RT 10 INSTALLATION, USER INSTRUCTIONS & CUSTOMER CARE GUIDE. Order no

Installation instructions

Operating instructions

Ridge End. DA Cooks. Progressing Meeting No:2. Neptune Responses Mechanical. 2 nd November 2015

Room-temperature (economy/night) unit TR 212 E

Installation and maintenance instructions

GREENSTAR i SYSTEM USER MANUAL WALL HUNG RSF GAS FIRED CONDENSING SYSTEM BOILER FOR CENTRAL HEATING SYSTEMS UK/IE (2013/08)

Installation instructions Logamax plus. GB162-L.B. 80 kw GB162-L.B. 100 kw. Read carefully before carrying out installation and maintenance.

Intelligent cascading kit

WALL HUNG RSF GAS FIRED CONDENSING REGULAR BOILER

Vortex 15/21 Utility and Outdoor Module Vortex Combi 21 and Outdoor Vortex Combi 21

GREENSTAR Ri USER INSTRUCTIONS UK/IE WALL HUNG RSF GAS FIRED CONDENSING REGULAR BOILER FOR CENTRAL HEATING SYSTEMS a (2010/10)

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

24CDi, 28CDi & 35CDi II COMBI

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

Greenstar 12i/24i System

Greenstar 25Si/30Si USER INSTRUCTIONS & CUSTOMER CARE GUIDE

Installation instructions

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

Installation and maintenance instructions

Connecting cable. Installation instructions (2018/04) US

Worcester GB162 wall mounted gas-fired condensing boiler series

Operating Instructions

GREENSTAR i JUNIOR USER INSTRUCTIONS UK/IE WALL HUNG RSF GAS FIRED CONDENSING COMBINATION BOILER

User manual. Logano GC 124 II. Gas boiler

FR 10 INSTALLATION & USER INSTRUCTIONS INTELLIGENT ROOM THERMOSTAT

GREENSTAR CDi CLASSIC REGULAR ErP

Users manual. Buderus /29/43/60 and Buderus T25/29T25 H/V. Wall-mounted condensing gas boiler. For the user

WALL HUNG RSF GAS FIRED CONDENSING COMBINATION BOILER GREENSTAR 24i Junior/28i Junior

Vote for your Installer of the year at. 9/14, 14/19 & 19/24CBi. Worcester supports the Benchmark code of practice

GREENSTAR Ri ErP. User instructions UK/IE. Wall hung RSF gas fired condensing regular boiler. For central heating systems

Outdoor kit. Models: RTG 199HE / RTG 199ME. Installation Instructions

Gas Instantaneous Water Heater

Users Manual. Gas wall hung Boiler condensing Buderus /S. Please read thoroughly before operating the unit

Safety. Operating instructions Ionization pilot burners ZAI, ZMI, ZKIH DANGER. Contents WARNING CAUTION Edition 12.11

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Bosch 80% AFUE Gas Furnace BGS80 Model

Operating instructions

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5

GREENSTAR HEATSLAVE II ErP+ 12/18, 18/25 & 25/32

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

ecotec plus Installation and maintenance instructions Installation and maintenance instructions For the competent person GB, IE VU GB 656/4-5 A

INSTALLATION AND MANINTENANCE INSTRUCTIONS

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

USER'S INFORMATION MANUAL

Service Instructions. Logamax plus GB kw/100 kw. Condensing gas boiler. For the contractor

Installation Commissioning and Servicing manual Logano plus GB102/GB102S. Regular boiler 16, 30, 42 System boiler 16, 30

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

INTRODUCTION STORAGE PRIOR TO INSTALLATION. Expansion Vessel Hose. Part No High Flow Rate Inlet Control Set. Part No.

Installation and maintenance instructions for contractors

Gas 220 Ace Cascade Assembly Manual

KEY TO COMPONENTS. 1. Heat exchanger 2. Pilot gas pipe 3. Gas injector nozzle 4. Measuring point

AGS 2 SOLAR PUMP STATION FOR SOLAR DOMESTIC HOT WATER SYSTEMS UK/IE

Bosch Group. 15SBi / 24SBi. WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water

HX Field Replacement Kit

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES

USER'S INFORMATION MANUAL

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

/2010 US/CA

Compact HE. High efficiency combi boiler. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

GREENSTAR HIGHFLOW 440/550CDi

GREENSTAR Ri ErP + User instructions UK/IE. Wall hung RSF gas fired condensing regular appliance. For central heating systems

Installation, operating and servicing instructions

TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw /17 Subject to modification

Greenstar 12i system / 24i system

DIGISTAT PROGRAMMABLE 24 HOUR ROOM THERMOSTAT SYSTEM. Radio frequency controlled programmable room thermostat.

GEM TRAP FITTING & MAINTENANCE INSTRUCTIONS

GREENSTAR HEATSLAVE II EXTERNAL 12/18, 18/25 & 25/32

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

Alpha CombiMax 350 and 600

USER'S INFORMATION MANUAL

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

TEMPRA. Wall Mounted Fan Flue System boiler. Wall mounted fanned flue boiler INSTALLATION AND USE INSTRUCTIONS. Appr. nr. B A - CE 0063 AQ 2150

Utility and Utility System Floor Standing Condensing Oil Boiler Range ADDENDUM ATTENTION INSTALLERS - UPDATED INFORMATION!

The NEW Greenstar i. intuitive. innovative. improved performance. installation ease

CARVER CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

USER INSTRUCTIONS & CUSTOMER CARE GUIDE HIGHFLOW 400 ELECTRONIC SERIES

GREENSTAR HIGHFLOW 440/550CDi

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

Installation and maintenance instructions

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

Residential Gas Condensing Boiler Greenstar combi 100 p / 151 p ZWB28-3A... ZWB42-3A...

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model CLAS. R EN - Edition 01-01/02/2007

USER'S INFORMATION MANUAL

A/23 MFFI - A/27 MFFI

Installation and operation instructions Solar stations SolarBloC midi Premium DN 20 SolarBloC maxi Premium DN 25

Bosch Group. 24CDi OF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

DIGISTAT OPTIMISER PROGRAMMABLE 7 DAY ROOM THERMOSTAT SYSTEM. Radio frequency controlled programmable room thermostat

AGS 5/5E, AGS 10/10E INSTALLATION AND SERVICING INSTRUCTIONS SOLAR PUMP STATIONS FOR SEALED SOLAR HEATING SYSTEMS AND INDIRECT FED DOMESTIC HOT WATER

HEAT ONLY & COMBI BOILER

Transcription:

Installation instructions Pump Group For wall hung gas-fired condensing boiler GB6-50/65/80/00 6 70 648 7-000.TD UK/IE 6708374 (04/09)

Contents Contents Key to symbols and safety instructions.................... Key to symbols.................................. Safety instructions.............................. Regulations.......................................... 3. About these instructions.......................... 3. Intended use................................... 3.3 Regulations.................................... 3 Key to symbols and safety instructions. Key to symbols Warnings Warnings in this document are framed and identified by a warning triangle which is printed on a grey background. Electrical hazards are identified by a lightning symbol surrounded by a warning triangle. 3 Items supplied with pump group......................... 3 4 Dimensions........................................... 4 5 Installation........................................... 5 5. General installation instructions................... 5 5. Making the gas connection........................ 5 5.3 Removing the non-return valve (if necessary)......... 5 5.4 Installing the heating flow and return................ 6 5.5 Rotating the pressure relief valve................... 7 5.6 Installing the syphon............................. 8 5.7 Connecting the condensate drain pipe.............. 8 5.8 Connecting the expansion vessel (accessory)........ 9 5.9 Making the electrical connections to the pump........ 9 5.0 Installing the insulation cover.................... 0 6 Commissioning..................................... 0 7 Technical specifications.............................. Keywords indicate the seriousness of the hazard in terms of the consequences of not following the safety instructions. NOTICE indicates that material damage may occur. CAUTION indicates that minor to medium injury may occur. WARNING indicates that serious injury may occur. DANGER indicates possible risk to life. Important information Additional symbols Symbol Important information in cases where there is no risk of personal injury or material losses is identified by the symbol shown on the left. It is bordered by horizontal lines above and below the text. Meaning a step in an action sequence a reference to a related part in the document or to other related documents a list entry a list entry (second level) Table. Safety instructions Please observe these instructions for your own safety. You can find a detailed explanation of the format of these instructions in the Installation and Servicing Instructions of the GB6-50/65/80/00. Observe the following instructions when installing and operating the pump group: Repairs DANGER OF FATAL ACCIDENT by unprofessional repair. Do not repair parts with safety functions. DANGER OF FATAL ACCIDENT due to electric shock. Before opening the boiler: Switch off the power supply to the boiler by pulling the mains plug from the socket. IF YOU SMELL GAS: CALL NATIONAL GAS EMERGENCY SERVICE ON 0800 999 LPG BOILERS CALL THE SUPPLIER S NUMBER ON THE SIDE OF THE LPG TANK TURN OFF THE ECV (EMERGENCY CONTROL VALVE) AT THE METER/REGULATOR DO NOT TURN ELECTRICAL SWITCHES ON OR OFF DO NOT STRIKE MATCHES OR SMOKE PUT OUT NAKED FLAMES OPEN DOORS AND WINDOWS KEEP PEOPLE AWAY FROM THE AFFECTED AREA. 6708374 (04/09)

Regulations Regulations The country-specific standards and guidelines and the technical documents pertaining to the boiler must be observed for the installation and operation of the heating system! 3 Items supplied with pump group Check that the packaging is intact upon delivery. Check that all items have been supplied with the unit. Please contact your supplier if anything is damaged or missing.. About these instructions These installation instructions contain important information about the safe and proper installation of the GB6-50/65/80/00 pump group. These installation instructions are for competent heating engineers (e.g. Gas Safe registered) who, due to their professional training and experience, are experts at dealing with heating systems and gas installations. 3 4 7. Intended use The pump group must only be installed on the GB6-50/65/80/00 heating boiler. 5.3 Regulations Please ensure that you comply to all regulations at the time of installation. 6 6 70 648 7-00.TD Fig. Items supplied with GB6-50/65/80/00 pump group [] Insulation cover [] Isolating valve, red (CH boiler flow) with drain cock, pressure gauge, thermometer (for pump UPER 5-80) and 4-bar safety valve [3] Technical documents [4] Gas valve, yellow (GAS) [5] Isolating valve, blue (CH boiler return) with pump, drain cock and non-return valve (removable) [6] Connecting bracket [7] Flat rubber seal ½ (x) 6708374 (04/09) 3

Dimensions 4 Dimensions AIC FGC AIC FGC CHF/CHR Gas B CHF Gas B CHR PF/PR CDO Gas P PF Gas P CDO PR CS 6 70 648 7-00.TD Fig. Dimensions and connections [mm] ) DO NOT remove the cap CS (not used in UK) ) The pump group is accessory and can be ordered separately. This figure shows a pump group, that isn t ment for DHW supply, but ONLY for central heating hot water supply. There is also a pump group with 3-way valve (accessory) available, which is ment for DHW supply. [Shortcut] Descriprion [CS] Cap (DO NOT remove; not used in UK) [CDO] Condensate drain outlet Ø 4 mm O/D [CHF] CH (boiler) flow; G½" union nut with female thread [CHR] CH (boiler) return; G½" union nut with female thread [FGC/AIC] Flue gas/air intake connection: Ø 80/5 for GB6-50/65 and Ø 00/50 for GB6-80/00 [Gas B] Gas connection to boiler; G" female thread [Gas P] Gas connection to pump group; Rp" female thread [PF] Pump group flow; G½" male thread, flat seal [PR] Pump group return; G½" male thread, flat seal 4 6708374 (04/09)

Installation 5 Installation 5. General installation instructions Connect all pipes without forcing them into place. Make sure that the connections are tight and carry out a gas and water tightness test after completing the connection work ( boiler installation and servicing instructions). DANGER: Danger of fatal accident from explosive fumes. Only carry out work on gas pipes and fittings if you are properly certified (e.g. Gas Safe registered). 5. Making the gas connection DANGER: Danger of fatal accident due to gas escaping. Make sure that the factory-fitted flat rubber seal is located in the threaded connection (boiler side) ( fig. 3, detailed picture). 6 70 648 7-003.TD Fig. 3 Rubber seal Install the gas valve [] onto the gas pipe (GAS) in the boiler. Connect the main gas supply to the gas isolating valve [] free of strain. We advise you to integrate a gas filter in the gas line. Make the gas connection according to the countryspecific standards and regulations. Carry out gas leak test on gas connection using leak detection spray WARNING: Danger of fatal accident from explosive fumes. Pipes and screw connections may leak after commissioning and maintenance activities have been carried out. Carry out a leakage test. Only use approved detection products to locate leaks. 5.3 Removing the non-return valve (if necessary) If the system pressure is not sufficient according to table 4, page 7, you can remove the integrated non-return valve from single-boiler systems. Selecting the correct pump group Select the correct pump group using table 4. Multi-boiler system (cascade system) Single-boiler system with diverter valve Single-boiler system without diverter valve GB6-50 GB6-65 UPER 5-80/UPS 5-80 pump group with pump GB6-80 UPER 5-80/UPS 5-80 pump group with pump ) UPER 5-80/ UPS 5-80 pump group with pump GB6-00 Table Selecting the correct pump group ) Only remove the non-return valve from the pump group (beneath the pump) when installing single-boiler systems ) Do not use a pump group or switch, but select a separate pump using the installation and servicing instructions with the boiler. WARNING: Damage tot the unit in cascade systems or in single-boiler systems with a switch due to the heating medium flowing back. Only remove the non-return valve from the pump group of a single-boiler system if the residual head ( table 4, page 7) is not sufficient. ) Fig. 4 Making the gas connection [] Gas isolating valve [] Gas connection 6 70 648 7-004.TD GB6-50 GB6-65 GB6-80 Multi-boiler system (cascade system) not allowed Single-boiler system with diverter valve Single-boiler system without diverter Check the residual head valve Table 3 Removing the non-return valve GB6-00 not effective, use pump 6708374 (04/09) 5

Installation Removing the non-return valve Remove the non-return valve before installing the heating flow and return circuits otherwise it cannot be fully removed anymore! Remove the pump []. Remove the flat rubber seal []. Rotate and shake the pump group. 6 70 64 07-0.TD Fig. 5 Removing the pump Remove the non-return valve []. This will damage the non-return valve beyond repair. Fig. 7 Removing the rest of the non-return valve Then fit back the flat rubber seal [] and the pump []. 6 70 64 07-03.TD Fig. 8 Fitting the pump 6 70 64 07-04.TD Fig. 6 Removing the non-return valve 6 70 64 07-0.TD WARNING: Damage to the unit due to reduced flow or pipes becoming clogged up. Make sure that no fragments of the non-return valve stay behind in the pipe. 5.4 Installing the heating flow and return To prevent pollution in the heating system we advise you to integrate a dirt filter in the return circuit. When connecting the heating boiler to an existing heating system, this dirt filter must be installed. Install the blue and red isolating valve [ and 6] with the flat rubber seals in place on the CHR and CHF (boiler return and flow) connections. Connect the flow pipe to the red isolating valve [3] free of strain. If necessary, use the screw fitting (accessory, [4]). Connect the return pipe to the blue isolating valve [7] free of strain. If necessary, use the screw fitting (accessory, [4]). Calculate the flow and return pipe diameters taking into consideration the residual head downstream of the pump group with the minimum required volume flow ( table 4, fig. 4 and fig. 5 on page ). The minimum diameters of the flow and return pipes are ½ and Ø 35 mm. 6 6708374 (04/09)

Installation 3 CHF CDO Fig. 9 Installing the isolating valves [] Pressure relief valve [] Isolating valve, red [3] Flow connection [4] Screw fitting " female thread (accessory) [5] Pump [6] Isolating valve, blue [7] Return connection 4 CHR 5 6 7 6 70 648 7-005.TD Installing the differential pressure controller In situations where there is no low less header, installing a by-pass valve with a differential pressure controller would be required. If a low less header is present, it may be required -depending on the situation - to install a differential pressure controller to the secondary side of the open manifold. This serves to protect the secondary pump against overheating as a result of insufficient flow. Installing the drain cock Since the isolating valve for the return circuit already has an integrated filling and drain valve, fitting a drain valve is not necessary. Installing the non-return valve Since the isolating valve for the return circuit (blue) already has an integrated non-return valve, fitting a non-return valve in the return circuit is not necessary. 5.5 Rotating the pressure relief valve To prevent the pressure in the heating system from becoming excessively high, a pressure relief valve is required. A 4-bar pressure relief valve forms part of the pump group []. Remove the retaining pin from the pressure relief valve body (step ). Rotate the valve body (step ). boiler pump non return valve with residual head [mbar] ) with minimum required volume flow [l/h],00 GB6-50 UPS 5-80 without 550,00 with ),00 UPER 5-80 without 550,00 GB6-65 UPS 5-80 with ) 3,000 without 375 3,000 UPER 5-80 with ) 3,000 without 375 3,000 GB6-80 UPS 5-80 with 53 3,600 without 59 3,600 UPER 5-80 with ) 3,600 without 9 3,600 GB6-00 UPS 5-80 with ) 4,300 without ) 4,300 UPER 5-80 with ) 4,300 without ) 4,300 Table 4 Residual head downstream of pump group with a single-boiler system (ΔT = 0 K) Fig. 0 Removing the retaining pin 6 70 648 7-006.TD ) Switch required Install a shut-off valve for filter cleaning immediately upstream and downstream of the dirt filter. When using plastic pipework in the heating system, e.g. for underfloor heating, it has to be oxygen diffusion tight. If this pipework does not comply with the relevant standards, a heat exchanger must be integrated to separate the systems. 6708374 (04/09) 7

Installation Re-fit the retaining pin through the valve body. Connect the syphon [] to the condensate drain outlet (CDO). The trap is fitted with a bayonet connection. After pushing [.] the trap upwards into place, you have to turn it a ¼ turn anticlockwise [.] until it locks into position.. 6 70 648 7-007.TD Fig. Re-fitting the retaining pin Fit the compression elbow [] (supplied packed with the boiler) using thread sealant. Fit a mm metal discharge pipe [].. 774680008-3.TD Fig. 4 Installing the syphon [] Syphon Connect the syphon hose [3] and the rubber sleeve [] to the syphon []. Fig. Fitting the compression elbow with discharge pipe 5.6 Installing the syphon 6 70 648 7-008.TD DANGER: Danger of fatal accidentdue to poisoning. If the syphon is not filled with clean water, flue gas can escape and put people's lives at risk. Fill the syphon (supplied with the boiler) with clean water. Fig. 5 Installing the syphon hose [] Syphon [] Rubber sleeve [3] Syphon hose 3 774680008-4.TD 5.7 Connecting the condensate drain pipe Connect the condensate drain pipe to the syphon. Observe the following regulations: The waste water disposal regulations. Plastic pipework must be used to drain the condensate, at least until it is delivered to the sewage system. The condensate must be able to run into a funnel (or neutralisation tank) without restrictions. This prevents condensate from building up in the boiler. The syphon in the connection kit must no be permanently connected to the condensate drain pipe. The minimum distance between the syphon and the condensate drainage pipe is cm []. 6 70 64 07-06.TD Fig. 3 Filling the syphon with clean water 8 6708374 (04/09)

Installation 5.9 Making the electrical connections to the pump Turn the vent key through a quarter rotation to undo the boiler door lock []. Push the fastener down [] and open the boiler door [3]. Remove the cover shield of the pump group [4]... Fig. 6 Condensate drain pipe [] Condensate drain pipe 774680008-6.TD 3. 5.8 Connecting the expansion vessel (accessory) WARNING: Damage tot the unit due to faulty pressure relief valve. The expansion vessel must be of sufficient capacity. Connecting the expansion vessel in a multi-boiler configuration (cascade configuration) In cascade systems only one expansion vessel is required for the heating system. Connect the expansion vessel to the secondary side of the header in the return circuit, so that every boiler is connected to the expansion vessel. Refer to the cascade system installation instructions for the installation details. 4. Fig. 8 Opening the boiler door Undo screw to release the cover over the electrical connections and pull the cover up... 6 70 648 7-00.TD CHF CHR CHF Gas Gas CHR 6 70 648 7-009.TD 774680008-9.TD Fig. 7 Connecting the expansion vessel in a multi-boiler configuration (cascade configuration) [] Expansion vessel [] Low loss header Fig. 9 Pulling the cover over the electrical connections up 6708374 (04/09) 9

Commissioning Lay the pump connection cable from the boiler through the hole under the electrical connection box downwards ( fig. 0, [] and fig., []). Connect the mains cable connector [] to the pump. Fig. 0 Laying the pump connection cable [] Pump connection cable 6 70 646 88-009.TD Fig. Connecting the pump [] Tacho cable connector [] Mains cable connector 6 70 646 88-0.TD 5.0 Installing the insulation cover Feed the insulation cover with its upper edge into the groove in the lower support. The door over the boiler control panel must be closed. 6 70 646 88-00.TD Fig. Laying the pump connection leads [] Pump connection cable Connect the tacho cable connector [] to the pump. 6 70 648 7-0.TD Fig. 3 Installing the insulation cover 6 Commissioning See the Installation and servicing instructions of the boiler assembly for commissioning instructions. Observe the safety instructions and take the relevant measures. 0 6708374 (04/09)

Technical specifications 7 Technical specifications 900 800 700 600 [mbar] 500 400 300 00 00 0 0 500 000 500 000 500 3000 3500 4000 4500 5000 Fig. 4 Residual head downstream of the pump group (UPS 5-80) - with and without a non-return valve [l/h] Volume flow [mbar] Residual head [] Residual head downstream of the pump group without a non-return valve (UPS 5-80) [] Residual head downstream of the pump group with a non-return valve (UPS 5-80) 900 [l/h] 6 70 65 676-05.TD 800 700 600 500 [mbar] 400 300 3 00 00 0 0 500 000 500 000 500 3000 3500 4000 4500 5000 [l/h] 6 70 648 7-03.TD Fig. 5 Residual head downstream of the pump group (UPER 5-80) - with and without a non-return valve [l/h] Volume flow [mbar] Residual head [] Residual head downstream of the pump group without a non-return valve (UPER 5-80) - full load [] Residual head downstream of the pump group with a non-return valve (UPER 5-80) - full load [3] Residual head downstream of the pump group with a non-return valve (UPER 5-80) - partial load 6708374 (04/09)

WORCESTER, BOSCH GROUP: TECHNICAL SUPPORT: 0330 3 3366 APPOINTMENTS: 0330 3 9339 SPARES: 0330 3 9779 LITERATURE: 0330 3 99 TRAINING: 0330 3 066 SALES: 0330 3 9669 Worcester, Bosch Group Cotswold Way, Warndon, Worcester WR4 9SW. Tel. 0330 3 9559 Worcester, Bosch Group is a brand name of Bosch Thermotechnology Ltd. worcester-bosch.co.uk 6708374