"SXDDR" Series Steam Heat Exchanger Humidifiers

Similar documents
"ESDDR" Series Electric Humidifier

"ER" Series Electric Humidifier

Installation Instructions. Operation and Maintenance Manual

Installation Instructions. Operation and Maintenance Manual

ES Series Electric Humidifier

Insty-Pac Steam Humidifiers

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers.

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

INSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY

Installation Instructions. Operation and Maintenance Manual

INSTY-PAC EXTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY

DRI-STEEM Models and LTS-DI

STS Steam-to-Steam Humidifier

VAPORSTREAM. Electric-to-Steam Humidifier. With Vapor-logic controller Web-enabled access Interoperability via Modbus or optional BACnet or LonTalk

DRI-STEEM Models LTS and LTS-DI

HumidiPack,HumidiPackPlus and HumidiPackPlus CF Steam Humidifier Systems

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION STEAM HUMIDIFIERS

INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

LTS Liquid-to-Steam Humidifier. Installation, Operation and Maintenance Manual

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Humidifiers Dealer Parts List

Humidifiers. Model 400/400M Humidifiers NO. BLUE/GRAY UNITS - PART NAME QTY/CTN PART NO. PART NO.

HumidiClean Series HC-4000 Humidifier

LE Series. Electrode Steam Humidifiers

Humidifiers Dealer Parts List Model 400/400M Humidifiers

READ AND SAVE THESE INSTRUCTIONS STS. Steam-to-Steam Humidifier. Installation, Operation, and Maintenance Manual

Pressure Steam Humidifiers. Designed to deliver reliable humidity from facility steam boilers. Live Steam

Pressure Steam Humidifiers LS SERIES. humidity.com

VAPORSTREAM Models VLC and VLDI

BuildingName The Description of the Project P DOCUMENTS

.03 ATMOSPHERIC DEAERATOR

DRI-STEEM CRU SERIES ELECTRIC STEAM HUMIDIFIERS

FOGGING & HUMIDIFICATION PAPER STORAGE TEXTILE MILLS LIQUID STORAGE TANKS AIR DUCTS PRODUCE STORAGE ROOMS GREENHOUSES HATCHERIES CONCRETE PIPE CURING

FOGGING & HUMIDIFICATION PAPER STORAGE TEXTILE MILLS LIQUID STORAGE TANKS AIR DUCTS PRODUCE STORAGE ROOMS GREENHOUSES HATCHERIES CONCRETE PIPE CURING

SAS Steadyair Make-Up Air Units Technical Guide

VIFB Coil Technical Guide

Modulating Controls. Principle of Operation

Ultra-sorb Steam Dispersion Panels

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

VIFB Coil Technical Guide

DIVISION 15 MECHANICAL

DEAERATORS .005 ATMOSPHERIC DEAERATOR

SAM-e - Short Absorption Manifold Submittal Drawings

Portable CNA-Series - Large Industrial Heaters Tankless Water Heating Solutions

Steam Injection. Humidification system

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

Packaged Semi-Instantaneous Steam Fired Water Heater

DRI-STEEM MODEL STS and STS- DI

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG

SE Series. Installation and Operation Manual

Installation and Maintenance

.005 ATMOSPHERIC DEAERATOR

OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D

INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

Scotsman Technical Training. CU50 Cube Ice Machine

Installation Instructions. Operation and Maintenance Manual

SE Series. Installation and Operation Manual

USG Series. Unfired Steam Generators Generate Clean Steam With Boiler Steam or High Temperature Hot Water as the Energy Source

SERVICE MANUAL FOR MODEL RM-49

MODEL SW-2. Sample specifications for SW-2 SPECIFICATIONS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SECTION STEAM AND STEAM CONDENSATE SPECIALTIES

Steam to Steam Humidifier

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

Sterilizer Model LS2020 Series Beta Star Life Science Products of R-V Industries

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

Steam to Steam Humidifier

Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment

Steam Humidification Light Commercial Applications. Better technology means better business.

Submittal. RBVR Vertical Concealed Floor Mount FCU RBVR

Operation & Maintenance Manual

SECTION PLUMBING EQUIPMENT

Vaporstream Electric Humidifier. Installation, Operation, and Maintenance Manual

DISTILLATION. The Best Distillation Times Two! 4 FI-STREEM Tap/Pretreated 30 Liter Storage Reservoir WP54 50 Liter Storage Reservoir

DRI-STEEM Models GTS and GTS-DI

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107

BASIL 6000 TUNNEL CAGE WASHER

HWD-2110 Hot Water Dispenser

SECTION HUMIDITY CONTROL EQUIPMENT

STEAM TO STEAM HUMIDIFIER

Portable C2N Series - Light Industrial Heaters Tankless Water Heating Solutions

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Installation and Operating Service Manual

Catalog. Self-operated Regulators Volume 2 Temperature Regulators

Steam Injection Humidifiers for use with steam boilers. Installation, Operation, and Maintenance Manual

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

HumidiClean. Series HC- 4100/4145/4300/4500 Humidifiers. Installation, Operation and Maintenance Instructions. Table of Contents.

SUBMITTAL SCHEDULE & DATA

Armstrong Cool-Fog Systems

Condensate Return Feedwater Systems For Low and High Pressure Steam Boilers

VERTICAL TUBE HEATING COILS MV & VIFB MODELS

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

GORD COOKE. issues associated with humidification and dehumidification systems. In this article, humidification

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

Moss MOSS TRAY DEAERATOR ECONOMICAL INDUSTRIAL DEAERATOR SYSTEMS

SERVICE MANUAL FOR MODEL RM-26

Transcription:

SXDDR-1 Deionized, Demineralized, or Reverse Osmosis Water "SXDDR" Series Steam Humidifiers Looking for an alternative to electrically generated humidification? Concerned about using chemically treated boiler steam for direct humidification? PURE Humidifier s Steam Heat Exchanger humidifiers are exactly what you are looking for. Indoor air quality issues concerning the use of boiler steam for direct humidification have resulted in a growing apprehension for the use of steam injection type of humidifiers. The possible carryover of chemical additives and odor created within some boiler systems is being addressed in an effort to improve the indoor air quality for new and existing buildings. The alternative, electric humidifiers, can be prohibitive due to the higher energy costs associated with electrically generated steam versus the typically lower energy cost of boiler steam. For these reasons, PURE has developed the SXDDR Series Steam humidifier. The humidifiers utilize a stainless steel heat exchanger that allows boiler steam to be used as the heat source for producing steam from tap water. By isolating the boiler steam from the clean tap water, contamination from the boiler is completely eliminated. The steam produced by the humidifier is free from chemical or mineral carry-over, thus providing humidification to meet today's stringent indoor air quality requirements. PURE s highly efficient heat exchanger produces a greater capacity per unit size than competing designs due to the rectangular transfer tubes, as well as providing simplified maintenance. Since water mineral build-up does not occur with pure water, there is no need for an automatic drain system or cleaning. These units are practically maintenance-free. The water level is maintained with a special float valve (in lieu of the Tri-Probe electronic water controller which is used on the standard water SX Series) and a low water float switch is incorporated to provide a low water interlock with the steam control valve. Both floats are protected from water turbulence by an internal baffle. Modulation of the humidifier output is maintained by a high quality control valve, which modulates the steam flow into the heat exchanger. Each humidifier is supplied with a control system mounted in a NEMA-12 enclosure. The control system provides constant monitoring of the water level and safety systems. It also provides a control valve interlock which prevents operation should any of the safety circuits open. When it comes to installation, you have a choice with the Steam. The humidifier can be free-standing with a simple (optional) flexible hose connecting the unit to the stainless steel injection tube inserted through the duct wall. You can also mount the unit on the wall with wall brackets, or floor-mounted with support legs (both optional). For mounting under a duct you simply need hangers and support brackets. The versatility of the will allow you to design them into any system simply, efficiently, and reliably. The humidifier is designed to operate on absolutely pure water, such as deionized, demineralized, or reverse osmosis water. The PURE choice for humidification

Capacities & Piping SXDDR-2 Model Number SXDDR-1R SXDDR-2R SXDDR-3R SXDDR-4R Humidifier Capacity in Pounds per Hour (kg/hr) Steam Pressure in psig (Kpa) at the control valve 5 psig (34.5) 10 psig (69.0) 13 psig (89.6) 15 psig (103.4) 32.0 (14.5) 52.0 (23.6) 102.0 (46.3) 192.0 (87.1) 76.0 (34.5) 108.0 (48.9) 228.0 (103.4) 484.0 (219.5) 100.0 (45.3) 140.0 (63.5) 292.0 (132.5) 655.0 (297.1) 122.0 (55.3) 169.0 (76.7) 348.0 (157.8) 753.0 (341.7) Actual humidifier capacity may vary due to the heat loss from the humidifier reservoir. The ambient air temperature, air velocity, and injection tube system will affect the rate of heat loss from the reservoir. The capacities shown are based on a noninsulated humidifier reservoir tested in a 70 F environment. Humidifier Piping Control Valve Pneumatic Actuated Shown (by PURE) Wye Strainer (by PURE) Vacuum Breaker (by others) Water Supply Line Figure 1 Steam Supply Line Shut-Off Valve (by others) Condensate Steam Trap (by PURE) 3/4 SW Reservoir Non-Pressurized Condensate Return Line or PIPING NOTES: 1. Do not install piping across the front of the heat exchanger. 2. Dashed line piping is by others. 3. Do not use PVC or plastic for any of the piping connections to the humidifier. 4. A shut-off valve must be installed in the steam supply line prior to the wye strainer (valve by others). Reference Figure 1. 5. Allow a minimum side clearance equal to the unit width dimension for removal of the heat exchanger (see page SXDDR-3 for unit dimensions). Reference Figure 2 for illustration of heat exchanger removal. Figure 2

Dimensions, Weights, & Layout SXDDR-3 NEMA-12 Humidifier Control Cabinet (reference control cabinet notes) Steam Outlet Connection (size and qty. will vary with application) 16.00 (40.6) B Cabinet Depth: 6.00 (15.2) 1) Door has been removed from the drawing for clarity 2) Control cabinet is shipped loose for field mounting unless optional factory mounting is specified 3) Control cabinet weight: 28 lbs (12.7 kg) (not supplied with optional control cabinet factory mounted) Top View Removal (allow a minimum side clearance equal to dimension B ) 3.625 (9.21) 1/4 - NPT Fill Inlet Connection Low Water Float Switch D Steam Supply Inlet Humidifier Cover C.75 (1.9) 3/4 NPT Overflow 3/4 NPT Condensate Outlet Drain Valve Side Entry A Front View Right Side View Unit Dimensions in Inches (cm) and Weight in Pounds (kg)* Model Number Dim. A Dim. B Dim. C Dim. D Shipping Operating SXDDR-1R SXDDR-2R SXDDR-3R SXDDR-4R 17.50 (44.5) 25.50 (64.8) 34.00 (86.4) 54.00 (137.2) 18.25 (46.4) 27.50 (69.9) 13.75 (34.9) 13.75 (34.9) 13.75 (34.9) 13.75 (34.9) 3/4 (NPT) 3/4 (NPT) 1-1/2 (NPT) 2 (NPT) 70 lbs (31.8) 95 lbs (43.1) 155 lbs (70.4) 285 lbs (129.4) 155 lbs (70.4) 210 lbs (95.3) 360 lbs (163.4) 700 lbs (318.7) *When calculating the total dry weight of the humidifier, the control cabinet weight must be added to the reservoir weight. Due to product improvement, catalog dimensions and specifications are subject to change without notice.

Capacities & Piping SXDDR-4 Humidifier Capacity in Pounds per Hour (kg/hr) Model Number Steam Pressure in psig (Kpa) at the valve 5 psig (34.5) 10 psig (69.0) 13 psig (89.6) 15 psig (103.4) SXDDR-8R 370 (167.8) 840 (381.0) 1200 (544.3) 1350 (612.4) Actual humidifier capacity may vary due to the heat loss from the humidifier reservoir. The ambient air temperature, air velocity, and injection tube system will affect the rate of heat loss from the reservoir. The capacities shown are based on a noninsulated humidifier reservoir tested in a 70 F environment. Control Valve Pneumatic Actuated Shown (by PURE, Typ. 2) Vacuum Breaker (by others, Typ. 2) Water Supply Line Wye Strainer (by PURE, Typ. 2) Shut-off Valve (by others, Typ. 2) Steam Supply Line (Typ. 2) Typ. 2 Condensate Steam Trap (By PURE, Typ. 2) 1 SW Reservoir Non-Pressurized Condensate Return Line or Figure 3 PIPING NOTES: 1. Do not install piping across the front of the heat exchanger. 2. Dashed line piping is by others. 3. Do not use PVC or plastic piping for any of the piping connections to the humidifier. 4. A shut-off valve must be installed in the steam supply line prior to the wye strainer (valve by others). Reference Figure 3. 5. Allow a minimum side clearance equal to the unit width dimension for removal of the heat exchanger (see page SXDDR-5 for unit dimensions).

Dimensions, Weights, and Layout SXDDR-5 NEMA-12 Humidifier Control Cabinet (reference control cabinet notes) Steam Outlet Connection (size and qty. will vary with application) 16.00 (40.6) B Cabinet Depth: 6.00 (15.2) 1) Door has been removed from the drawing for clarity 2) Control cabinet is shipped loose for field mounting unless optional factory mounting is specified 3) Control cabinet weight: 28 lbs (12.7 kg) (not supplied with optional control cabinet factory mounted) Top View Removal (allow a minimum side clearance equal to dimension B ) 3.625 (9.1) 1/4 - NPT Fill Inlet Connection Low Water Float Switch Humidifier Cover C D Steam Supply Inlet Typ. 2.75 (1.9) 1 NPT Overflow 3/4 NPT Condensate Outlet Typ. 2 Drain Valve Side Entry A Front View Right Side View Unit Dimensions in Inches (cm) and Weight in lbs (kg)* Model Number Dim. A Dim. B Dim. C Dim. D Shipping Operating Weight (kg) SXDDR-8R 54 (137.2) 27.25 (69.2) 32.5 (82.6) 2 (NPT) 465 lbs (316.2) 1480 lbs (671.3) *When calculating the total dry weight of the humidifier, the control cabinet weight must be added to the reservoir weight. Due to product improvement, catalog dimensions and specifications are subject to change without notice.

Capacities & Piping SXDDR-6 Model Number Humidifier Capacity in Pounds per Hour (kg/hr) Steam Pressure in psig (Kpa) at the control valve 5 psig (34.5) 10 psig (69.0) 13 psig (89.6) 15 psig (103.4) SXDDR-12R 560 (254.0) 1265 (573.8) 1810 (821.0) 2035 (923.1) Actual humidifier capacity may vary due to the heat loss from the humidifier reservoir. The ambient air temperature, air velocity, and injection tube system will affect the rate of heat loss from the reservoir. The capacities shown are based on a noninsulated humidifier reservoir tested in a 70 F environment. Control Valve Pneumatic Actuated Shown (by PURE, Typ. 3) Vacuum Breaker (by others, Typ. 3) Water Supply Line Wye Strainer (by PURE, Typ. 3) Shut-off Valve (by others, Typ. 3) Steam Supply Line (Typ. 3) Typ. 3 Condensate Steam Trap (by PURE, Typ. 3) 1 SW Reservoir Non-Pressurized Condensate Return Line or Figure 4 PIPING NOTES: 1. Do not install piping across the front of the heat exchanger. 2. Dashed line piping is by others. 3. Do not use PVC or plastic piping for any of the piping connections to the humidifier. 4. A shut-off valve must be installed in the steam supply line prior to the wye strainer (valve by others). Reference Figure 4. 5. Allow a minimum side clearance equal to the unit width dimension for removal of the heat exchanger (see page SXDDR-7 for unit dimensions).

Dimensions, Weights, & Layout SXDDR-7 NEMA-12 Humidifier Control Cabinet (reference control cabinet notes) Steam Outlet Connection (size and qty. will vary with application) 16.00 (40.6) B Cabinet Depth: 6.00 (15.2) (not supplied with optional control cabinet factory mounted) Removal (allow a minimum side clearance equal to dimension B ) 3.625 (9.1) 1) Door has been removed from the drawing for clarity 2) Control cabinet is shipped loose for field mounting unless optional factory mounting is specified 3) Control cabinet 1/4 - NPT Fill Inlet Connection Low Water Float Switch Top View Humidifier Cover D Steam Supply Inlet Typ. 3 C 3/4 NPT Condensate Outlet Typ. 3.75 (1.9) 3/4 NPT Overflow Drain Valve Side Entry A Front View Right Side View Unit Dimensions in Inches (cm) and Weight in Pounds (kg)* Model Number Dim. A Dim. B Dim. C Dim. D Shipping Operating SXDDR-12R 54 (137.2) 27.25 (69.2) 43.5 (110.5) 2 (NPT) 845 lbs (383.3) 1628 lbs (738.4) *When calculating the total dry weight of the humidifier, the control cabinet weight must be added to the reservoir weight. Due to product improvement, catalog dimensions and specifications are subject to change without notice.

Specification Sample SXDDR-8 Humidifier 1. The humidifier shall be steam-heated heat exchanger type as manufactured by PURE Humidifier Co. of Chaska, Minnesota. 2. The humidifier shall be tested and approved by ETL/ETL-C Testing Laboratories, Inc. (ETL# 472940). 3. The humidifier shall have an evaporating reservoir with a gasket sealed cover which is capable of operating at pressures of at least 19 (48 cm W.C.) without steam or water leaks. The reservoir shall be made of type 304 stainless steel with welded joints. 4. The humidifier shall be designed to facilitate easy removal of the heat exchanger for periodic scale removal and inspection. The cover and heat exchanger shall be secured to the unit by the use of quick release clamps. The heat exchanger shall be removable from the side of the humidifier without disturbing the cover or injection tube system. 5. Humidifier shall be field convertible from a steam heat exchanger style SXDDR humidifier to an electric immersion heater style ESDDR humidifier with a simple change of the side entry assembly. 6. A stainless steel float operated low water cut-off switch shall be provided. The float switch shall provide positive low water cut-off of the humidifier steam supply control valve. 7. A stainless steel float operated water fill valve mounted on the top near the front shall be provided. The fill valve shall provide automatic refilling of the humidifier reservoir. The water inlet shall be located to allow a minimum water gap of 1-1/2 (3.81 cm). 8. The humidifier shall have a 3/4 (1.9 cm) over-flow pipe to prevent overfilling of the humidifier reservoir. 9. The heat exchanger shall be constructed of type 304 stainless steel rectangular transfer tubes and headers for improved scale removal and cleaning. 10. A normally closed steam control valve with equal percentage flow characteristics that provides sufficient capacity as required shall be provided. The valve operator (pneumatic modulating standard) or electric modulating (optional) shall be supplied by PURE Humidifier Co.. 11. The humidifier shall be supplied with a float and thermostatic condensate trap and a pipe line wye strainer. 12. The humidifier shall be provided with an ETL/ETL- C listed JIC NEMA 12 control cabinet, shipped loose (optional factory mounting available). The control cabinet shall be made of 14-gauge steel with ANSI 61 gray polyester powder coating, continuous hinge and oil-resistant gasket. The panel shall include a factory wired sub-panel with control valve interlock, time delay relay, fused control circuit transformer, numbered terminal block, and main power fusing. 13. The control panel shall have a factory wired time delay relay circuit. The delay circuit shall prevent cycling of the low water interlock circuit due to water fluctuations within the humidifier reservoir. 14. The control system shall maintain humidification during the fill cycle to maintain a consistent relative humidity.