Horizontal & Horizontal Quiet Blower Coils

Similar documents
Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

CDH/CDV Horizontal and Vertical Direct Drive Air Handling Units

Installation, Operating & Maintenance Instructions. Air Handler Models: AH & AV

Installation, Operating & Maintenance Instructions. Horizontal Models: LH & HL

Installation, Operation, and Maintenance Manual

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Energy Efficient Easy to Install Extended Service Life. Horizontal Direct Drive Blower Coils

Installation & Maintenance Data IM Contents

40 RM/RMS Packaged Air-Handling Units

INSTALLATION MANUAL TVS FAN COIL UNITS VERTICAL HIGH-RISE. Redefine your comfort zone.

MANUAL INSTALLATION. Fan Column. v200 Issue Date: 01/18/ Price Industries Limited. All rights reserved.

ACBH/ACBV ACTIVE CHILLED BEAM INSTALLATION MANUAL. Date: 05/12 Reference # : L-50.

SERIES B VERTICAL FLOOR FAN COIL UNIT

Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch. IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

Installation Instructions

Installation Instructions

RBV Installation Manual

MODELS B1PA024, 030 AND 036

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2

Installation Instructions

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

Installation Instructions

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12

DC Motor Blower Kit Frames DC180ATZ and C180ATZ thru C400ATZ Installation & Operating Manual

Installation Instructions Remote Blowers

FAN POWERED VAV TERMINALS

Installation Instructions

Panel Fan Series Operators Manual (Galvanized and Polymer)

Owner s Guide and Installation Manual

BESF Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION

Installation and Maintenance Manual IM 1102

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

Installation Instructions

Owner s Guide and Installation Manual

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

Installation, Operating & Maintenance Instructions. High Performance Horizontal Models: HH & CH

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

Installation & Maintenance Instructions

SERIES C VERTICAL FLOOR FAN COIL UNIT

Ceiling Concealed Fan-Coil Unit

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Panel Fan Series Operators Manual (Galvanized and Polymer)

Enviro KES INSTALLATON MANUAL

SSL & SBS Engineering Guide

AXPR Wall Mounted Axial Panel Fans

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Types SDRA and SDRA-RG RENEWAL PARTS IDENTIFICATION

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

Installation Instructions

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

HP SERIES HPP Plenum Return Shown

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

WineZone Ceiling Mount Ductless Split 15

Manual installation AW-D. Direct Gas Fired Make-Up Air Series. Revision: v001 Issue Date: 12/12/ Price Industries Limited. All rights reserved.

Installation Instructions

Energy Efficient Easy to Install Extended Service Life. Vertical Direct Drive Blower Coils INSTALLATION, OPERATIONS AND MAINTENANCE MANUAL

Installation Instructions

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Owner s Guide and Installation Manual

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

e Heater/Exhaust Fan/Light User s Guide

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer)

IMPORTANT INSTRUCTIONS

Installation Guide & Owner s Manual. Water Source Heat Pumps Vertical / Horizontal 1 5 Nominal Ton GEOCOOL SERIES

PRODUCT CATALOG BLOWER COILS.

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

M Series Fan Filter Units

Easy installation. EZ80N EZ Fit Ventilation Fan INSTALLATION GUIDE READ AND SAVE THESE INSTRUCTIONS. Table of Contents

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

Installation Instructions

e Bath Fan with Light User s Guide

Owner s Guide and Installation Manual

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

3DIR52XXD Series Fan. Owner s Guide and Installation Manual. UL Model NO. : 3DIR52XXD

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS

Installation, Operation and Maintenance Manual

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

Installation Instructions

Transcription:

MANUAL INSTALLATION Horizontal & Horizontal Quiet Blower Coils BCH / BCHQ Series v200 Issue Date: 05/19/15 2015 Price Industries Limited. All rights reserved.

TABLE OF CONTENTS Product Overview Safety Precautions...1 Caution to Contractors...1 Receiving Inspection...1 Dimensional Data...2 Installation & Mounting Instructions General...5 Electrical Connection...5 Cooling/Heating Pipe Connections...5 Mounting the Unit...6 BCHQ Silencer Installation...7 BCH/BCHQ Field Reversible Coil Instructions...8 Drain Connection and Trap...9 Drives, Belts and Bearings...9 Start Up & Operation...10 Maintenance Fan and Drive Assembly...11 Coils...11 Filter(s)...11 Blower Coil Electric Coil Removal Instructions...12 Replacement Parts...13 Installation Checklist...16

PRODUCT OVERVIEW Safety Precautions A. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction. B. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. C. Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer: In the United States 2975 Shawnee Ridge Court Suwanee, Georgia USA 30024 Ph: 770.623.8050 Fax: 770.623.6404 In Canada or International Export Sales Office 638 Raleigh Street Winnipeg, Manitoba Canada R2K 3Z9 Ph: 204.669.4220 Fax: 204.663.2715 D. Before servicing or cleaning unit, switch power off at service panel and lock service panel to prevent power from being switched on accidentally. E. Protect flammable materials nearby when brazing, Use flame and heat protection barriers where needed. Always have a fire extinguisher ready. F. The manufacturer assumes no responsibility for personal injury or property damage resulting from improper handling, installation, service or operation of the product. Caution to Contractors Blower Coil units are not intended for use as temporary heat or ventilation sources during building construction. The coil units are not designed nor equipped to operate in a dusty construction environment. Recirculating fan wheels can become coated in construction dust, resulting in an unbalanced wheel. This in turn can contribute to reduced motor life. Inlet air filters, if supplied, would provide little protection as they would quickly become plugged with construction dust. Receiving Inspection All Price Blower Coil units are inspected before shipment. After unpacking the assembly, check it for damage. If any damage to the products is found, report it immediately to the delivery carrier. Ensure that all packing material is removed from the inside of the unit, especially around the blower wheel and coil section. BCHQ BCH priceindustries.com Horizontal & Horizontal Quiet Blower Coils - Manual 1

PRODUCT OVERVIEW DIMENSIONAL Data - BCH, BLOWER COIL HORIZONTAL PIC-FC ENCL AIR FLOW LH coil/drive/control configuration shown Handing is determined by looking at the inlet. Dimensional Data IP (in.) / SI [mm] Unit Nom. Size Fan Flow CFM [L/s] Flow Range Max TSP CFM [L/s] W.G. [L/s] 08 800 600-1000 2 [378] [283-472] [498] 12 1200 900-1400 3 [566] [425-661] [747] 16 1600 1300-1800 3.5 [755] [614-850] [872] 20 2000 1700-2400 3.5 [944] [802-1133] [872] 30 3000 2300-3400 3.5 [1416] [1085-1605] [872] 40 4000 [1888] 3300-4400 [1557-2077] 3.5 [872] W H L B C D E F G 30 [762] 38 [965] 44 [1118] 50 [1270] 52 [1321] 65 [1651] 15½ [394] 15½ [394] 18 [457] 18 [457] 25 [635] 25 [635] 43 [1092] 43 [1092] 43 [1092] 43 [1092] 50 [1270] 50 [1270] 81/4 [210] 91/4 [235] 81/4 [210] 93/4 [248] 121/4 [311] 123/4 [324] 101/4 [260] 101/4 [260] 111/4 [286] 111/4 [286] 13½ [343] 153/4 [400] 10 7 8 [276] 14 3 8 [365] 17 7 8 [454] 20 1 8 [511] 19 7 8 [505] 26 1 8 [664] 201/4 [514] 281/4 [718] 341/4 [870] 401/4 [1022] 411/4 [1048] 541/4 [1378] 131/4 [337] 131/4 [337] 153/4 [400] 153/4 [400] 223/4 [578] 223/4 [578] 1 7 8 [48] 1 7 8 [48] 11/4 [32] 11/4 [32] 31/4 [83] 1 1 8 [29] DIMENSIONAL Data - BCHQ, BLOWER COIL HORIZONTAL QUIET PIC-FC ENCL 2 Horizontal & Horizontal Quiet Blower Coils - Manual priceindustries.com

BCH16 11 1/4 30 1/4 2 3/8 2 1/8 1 7/8 16 5/8 34 1/4 15 3/4 BCH20 11 1/4 36 1/4 2 3/8 2 1/8 1 7/8 16 5/8 40 1/4 15 3/4 BCH30 16 1/4 37 1/4 3 3/8 2 1/8 2 7/8 23 5/8 41 1/4 22 3/4 BCH40 16 1/4 48 3 3/8 3 1/4 2 7/8 23 5/8 54 1/4 22 3/4 Horizontal & Horizontal Quiet Blower Coils METRIC UNITS (mm) PRODUCT UNIT SIZEOVERVIEW A B C D E L W H BCH08 235 413 54 54 41 359 514 337 BCH12 235 616 54 54 41 359 718 337 DIMENSIONAL BCH16 Data 286 - BCH/BCHQ, 768 - BLOWER 60 COIL 54 HORIZONTAL 48 WITH 422 MIXING BOX 870 400 BCH20 286 921 60 54 48 422 1022 400 All metric BCH30 dimensions 413 ( ) are 946 soft converted. 86 Imperial 54 dimensions 73 are converted 600 to 1048 metric and 578 rounded to the nearest millimeter. BCH40 413 1219 86 83 73 600 1378 578 ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER W B W B XY CONFIGURATION D E A D E A C H A H XZ CONFIGURATION L OPTIONAL OPTIONAL SIDE SIDE ACCESS PANELS A L YZ CONFIGURATION Dimensional Data - IP (in.) / SI [mm] Unit Size A B C D E L W H BCH08 91/4 [235] 161/4 [413] 2 1 8 [54] 2 1 8 [54] 1 5 8 [41] 14 1 8 [359] 201/4 [514] 131/4 [337] BCH12 91/4 [235] 241/4 [616] 2 1 8 [54] 2 1 8 [54] 1 5 8 [41] 14 1 8 [359] 281/4 [718] 131/4 [337] BCH16 111/4 [286] 301/4 [768] 2 3 8 [60] 2 1 8 [54] 1 7 8 [48] 16 5 8 [422] 341/4 [870] 153/4 [400] BCH20 111/4 [286] 361/4 [921] 2 3 8 [60] 2 1 8 [54] 1 7 8 [48] 16 5 8 [422] 401/4 [1022] 153/4 [400] BCH30 161/4 [413] 371/4 [946] 3 3 8 [86] 2 1 8 [54] 2 7 8 [73] 23 5 8 [600] 411/4 [1048] 223/4 [578] BCH40 161/4 [413] 48 [1219] 3 3 8 [86] 31/4 [83] 2 7 8 [73] 23 5 8 [600] 541/4 [1378] 223/4 [578] priceindustries.com Horizontal & Horizontal Quiet Blower Coils - Manual 3

PRODUCT OVERVIEW DIMENSIONAL Data - BCH, BLOWER COIL HORIZONTAL WITH ELECTRIC HEAT ELECTRIC HEAT OPTION: 18"(457) MAXIMUM DOOR SWING Dimensional Data IP (in.) / SI [mm] Unit B C J Size 08 81/4 [210] 101/4 [260] 12 [305] 12 91/4 [235] 101/4 [260] 12 [305] 16 81/4 [210] 111/4 [286] 12 [305] 20 93/4 [248] 111/4 [286] 12 [305] 30 121/4 [311] 13½ [343] 17 [432] 40 123/4 [324] 153/4 [400] 17 [432] LH coil/drive/control configuration shown Handing is determined by looking at the inlet. DIMENSIONAL Data - BCHQ, BLOWER COIL HORIZONTAL QUIET WITH ELECTRIC HEAT 18"(457) MAXIMUM DOOR SWING LH coil/drive/control configuration shown Handing is determined by looking at the inlet. 4 Horizontal & Horizontal Quiet Blower Coils - Manual priceindustries.com

INSTALLATION & MOUNTING INSTRUCTIONS General Price Blower Coils are designed to be durable and manufactured for sturdy construction. The units must still be handled with great care and no force or pressure applied to the coil or piping. When handled, the unit should be carried in an upright position holding onto the mounting points on the horizontal units and holding onto the bottom of the vertical units. Do not handle the unit using coil stubout connectors, as damage may occur at brazed joint(s).the blower coils are not suitable for outdoor installations. The units should never be stored or installed where it may be subjected to a hostile environment such as rain, snow, or extreme temperatures. Care must be taken during and after installation to prevent foreign material such as paint, drywall mud or dust from entering the drain pan or the motor or blower wheels. Failure to do so may have serious effects on the unit performance and may cause premature failure if foreign material is allowed to be deposited into the motor or blower. Some job conditions may require the unit to be covered temporarily until installation. WARNING: Do not tamper with control components. Electrical Connection CAUTION: Disconnect all incoming power before any electrical installation or service is performed on the unit(s). All field wiring is to be in accordance with the National Electrical Code ANSI/NFPA No. 70 or the Canadian Electrical Code, Part 1, CSA Standard C 22.1. Refer to the product identification label on each unit for information to determine the field wire size. Check voltage requirements prior to power supply connection. Refer to the electrical label located near the electrical control box and also refer to the schematic drawing provided on the underside of the electrical control box cover. If upon energizing the electric motor excessive noise is apparent, shut down the unit. Determine the cause by checking for packing materials, etc. and reenergize after corrective action has been taken. Cooling/Heating Pipe Connections The piping must be installed in a counter flow configuration to achieve optimal performance. The water inlet should be located on the leaving air side of the coil and at the bottom of the coil and the outlet should be located in the top opposite corner to provide the necessary purging of air, as shown below. The valve packages are easily damaged when introduced to excessive amounts of heat. Great caution must be made when the connections are made with sweat or solder joints. The valve must be in the open position during all soldering and brazing operations. Heat should be dissipated with a wet cloth wrapped around the valve body. Automatic valves must have the control cartridge removed for soldering. CAPTION COIL OUTLET COIL OUTLET CAP AIR FLOW COIL COIL INLET CAP priceindustries.com Horizontal & Horizontal Quiet Blower Coils - Manual 5

INSTALLATION & MOUNTING INSTRUCTIONS Mounting the Unit Install ductwork to comply with ASHRAE Fundamentals Handbook, local building codes and the National Electric Code. Locate unit support in accordance with the mechanical and structural plans. Hanging rods should be securely attached to joints or to mounting anchors which are properly secured to slab construction with lugs or poured in place anchors. All units are equipped with 5/8 knockouts in each corner of top and bottom panels for suspension rods to pass through as shown to the right. Do not use Hanger brackets to install unit. Ensure the unit is installed so there is sufficient clearance for normal servicing. The drain pan is sloped toward the outlet connection when the unit is installed level and plumb. Ensure main power to the unit has been disconnected prior to performing any electrical work or inspection of the circuitry. WARNING: Ensure that the mechanical fastener used on the hanger rod forms a lock so that it is incapable of vibrating loose. Serious injury and/or property damage may occur if the unit is not properly mounted. CAPTION 6 Horizontal & Horizontal Quiet Blower Coils - Manual priceindustries.com

INSTALLATION & MOUNTING INSTRUCTIONS BCHQ Silencer Installation BCHQ unit arrives at the job site in 2 separate pieces - the basic unit and the discharge silencer. Factory provides installation angles for attachment of the silencer to the discharge of the unit. NOTE: The silencer section has to be installed so the blower outlet opening and silencer inlet opening are aligned. Otherwise the airflow path will be blocked and the unit will not provide the desired air flow or sound performance. CAPTION * EXTENDED TAB TO INSERT UNDER BLOWER CUT OFF PLATE CORRECT WRONG CAPTION CORRECT WRONG NOTE: It is recommended to wrap the silencer section externally in the field to prevent condensation from moisture. priceindustries.com Horizontal & Horizontal Quiet Blower Coils - Manual 7

INSTALLATION & MOUNTING INSTRUCTIONS BCH/BCHQ Field Reversible Coil Instructions Price Blower Coils are equipped with Field Reversible Coils, meaning they can be changed from left hand to right hand arrangement. The example below details how to change the coil configuration from LH to RH. 1. Remove the filter side access panels and both coil access panels (Figure 1). 2. Remove the 6 screws on the inlet of the unit holding the coils in place (Figure 2). 3. Slide the coil and drain pan out of the unit. Remove the coils from the drain pan (Figure 3). 4. Below where the drain pan was located, there will be 2 screws. Remove them from the bottom and relocate them to the side furthest from where the new drain will be located. This ensures that the drain pan is sloped properly (Figure 4). 5. Rotate the drain pan 180 so that the drain connection is on the desired side. 6. Flip the coils so that the connections are on the desired side. Note that the air will still enter the coil through the same face (Figure 5). 7. Re-attach the coil to the unit using the 6 screws removed in step 3. 8. Re-attach the coil and filter access panels. FIGURE 1 FIGURE 2 REMOVE SCREWS INLET VIEW VIEW FIGURE 4 REMOVE SCREWS FROM BOTTOM COIL COIL ACCESS PANEL FILTER ACCESS PANELS PANELS COIL ACCESS PANEL PANEL REMOVE SCREWS FROM BOTTOM FIGURE 3 FIGURE 5 RELOCATE SCREWS TO HOLES FURTHEST FROM NEW DRAIN SIDE RELOCATE SCREWS TO HOLES FURTHEST FROM NEW DRAIN SIDE CAP 8 Horizontal & Horizontal Quiet Blower Coils - Manual priceindustries.com

INSTALLATION & MOUNTING INSTRUCTIONS Drain Connection and Trap Drain lines should be the same size as the drain connection and require a drain trap to allow proper drainage of the coil condensate. Failure to install a proper trap will cause excessive amounts of condensate to pool in the drain pan which can lead to condensate carryover. Drives, Belts and Bearings Prior to starting the unit: 1. Remove the shipping screws (white-headed screws) from the blower/motor assembly. 2. Check the alignment of the belt sheaves by applying a straight edge. Adjust if necessary. Make sure there is adequate clearance between the sheaves and the fan frame. To align the sheaves, place a straight edge from the outer edge of one sheave (A) to the outer edge of the other (B). If the sheaves are unequal widths, the offset distance will be (W2-W1)/2, as shown in Figure 1. If there is a setscrew present, torque to 120 +/- 10 in-lb. 3. Tighten all set screws on the fans, sheaves and bearings. 4. Check the belt tension. The ideal belt tension is the lowest belt tension at which the belt drive will not slip. Over tensioning causes reduced belt and bearing life. Do not apply belt dressing. Proper belt tension must be used to ensure the design life of the belt is met. Failure to do so will result in premature belt failure, excessive bearing load, belt noise, and reduced performance. Adjust belt tension using the steps below: i. Loosen the 4 motor base nuts shown in Illustration 4A. ii. Adjust the motor position by turning the adjustment bolt shown in Illustration 4A to remove the slack in the belt. iii. Adjust motor position until the belt tension meets the requirements outlined by the belt manufacturer. The belt tension can be checked using a belt tension tool shown in Illustration 4C. iv. Once the tension is correct, tighten the 4 motor base nuts. CAPTION DRAIN TRAP H L X H = INTERNAL STATIC PRESSURE OF THE UNIT + 1 X = ½ OF H L = H + X + PIPE DIAMETER ILLUSTRATION 4A MOTOR BASE NUTS ADJUSTMENT BOLT ILLUSTRATION 4B DEFLECTION OF APPLIED FORCE FORCE FIGURE 1 A B ILLUSTRATION 4C W1 OFFSET W2 priceindustries.com Horizontal & Horizontal Quiet Blower Coils - Manual 9

INSTALLATION & MOUNTING INSTRUCTIONS Start Up & Operation General Before beginning start up operation, familiarize yourself with the unit, options, accessories, controls so you understand proper system operation. All personnel should have a good working knowledge of general start-up procedures and have the appropriate start-up and balancing guides available for consultation. Fan & Drive Assembly Prior to start up; ensure that all ductwork, grilles, filters and access panels are installed. The static pressure drop of the duct system components must meet the design conditions. Price blower coils are factory set to operate at the design pressure. If the pressure is too low the motor can overheat and if the pressure is too high the fan will not operate properly and generate excessive noise. All units are equipped with a variable pitch drive pulley to allow for field adjustment of the fan speed. To reduce the fan speed, loosen the set screw on the drive pulley and turn the pulley so that the faces move further apart. To increase fan speed, turn the pulley so that the faces move closer together. When adjusting the fan speed, be sure to re-align the belt sheaves before resuming operation. Cooling/Heating Prior to the water system start-up and balancing, the chilled/ hot water systems should be flushed to clean out dirt and debris, which may have collected in the piping during construction. During this procedure, all unit service valves must be in the closed position. This prevents foreign matter from entering the unit and clogging the valves and metering devices. Filters should be installed in the piping mains to prevent this material from entering the units during normal operation. During system filling, air venting from the unit is accomplished by the use of the standard manual air vent fitting installed on the coil. The air vent screw should be turned counterclockwise no more than 1-½ turns to operate the air vent. CAUTION: The air vent provided on the unit is not intended to replace the main system air vents and may not release air trapped in other parts of the system. Inspect the entire system for potential air traps and vent those areas as required, independently. In addition, some systems may require repeated venting over a period of time to properly eliminate air from the system. Air System Balancing All duct-work must be complete and connected, and all grilles, filters, access doors and panels must be properly installed to establish actual system operating conditions BEFORE beginning air balancing operations. Each individual unit and attached duct-work is a unique system with its own operating characteristics. For this reason, air balancing is normally done by balance specialists who are familiar with all procedures required to properly establish air distribution and fan system operating conditions. These procedures should not be attempted by unqualified personnel. After the proper system operation is established, the actual unit air delivery and the actual fan motor amperage draw for each unit should be recorded in a convenient place for future reference. The manufacturer assumes no responsibility for undesirable system operation due to improper design, equipment or component selection, and/or installation of ductwork, grilles, and other field supplied components. Water System Balancing A complete knowledge of the hydronic system, its components, and controls is essential to proper water system balancing and this procedure should not be attempted by unqualified personnel. The system must be complete and all components must be in operating condition BEFORE beginning water system balancing operations. Each hydronic system has different operating characteristics depending on the devices and controls in the system. The actual balancing technique may vary from one system to another. After the proper system operation is established, the appropriate system operating conditions such as various water temperatures and flow rates should be recorded in a convenient place for future reference. Before and during water system balancing, conditions may exist which can result in noticeable water noise or undesired valve operation due to incorrect system pressures. After the entire system is balanced, these conditions will not exist on properly designed systems. 10 Horizontal & Horizontal Quiet Blower Coils - Manual priceindustries.com

MAINTENANCE Fan and Drive Assembly 1. Disconnect all incoming power before servicing the unit. 2. Price Blower Coil units are supplied with permanently lubricated motors. 3. The blower and motor should be inspected annually for accumulation of dust and dirt. Clean as necessary. 4. Blower and motor can be accessed without disconnecting ductwork. CAUTION: Motor may be very hot. Ensure motor has cooled before service. 5. Motors up to 460V are provided with automatic overload protection. If the motor overheats and trips the thermal overload, it will automatically reset after cooling down to a proper operating temperature. 575V motors are equipped with manual motor protectors and will need to be reset should they overload. Should overload occur, check that all ductwork, grilles, filters and access doors are properly installed. 6. Check belts regularly for proper tension and wear. Retension and replace as necessary. MOTOR FULL LOAD AMPS Nominal Horsepower Phase Voltage ½ ¾ 1 1 ½ 2 3 5 115 9.8 13.8 16.0 - - - - 1 208 5.4 7.6 8.8 11.0 - - - 230 4.9 6.9 8.0 10.0 - - - 208 2.4 3.5 4.6 6.6 7.5 10.6 16.7 3 230 2.2 3.2 4.2 6.0 6.8 9.6 15.2 460 1.1 1.6 2.1 3.0 3.4 4.8 7.6 600 0.9 1.3 1.7 2.4 2.7 3.9 6.1 Coils 1. Disconnect all incoming power before servicing the unit. 2. Coils can be inspected through either bottom or side access panels. To service the coils, remove the coil service door. 3. The coil should be inspected periodically for accumulation of dust and dirt. Clean as necessary. Cleaning can be done by brushing the coils in the direction of the fins as to not damage them. Compressed air can also be used to blow out the dust particles in the coil. Vacuum up all dust particles so they can not damage the blower and motor. 4. Clean drain pan as required. To remove the drain pan, disconnect and remove the coils. Filter(s) 1. Inspect return air filters on a regular basis to avoid excessive restriction of air flow. Clean or replace filters as required. Filter can be accessed from either side of unit or from the bottom. CAUTION: Do not operate unit without filters or filter access panels installed. 2. Replacement filter sizes are listed below. Unit H (in) W (in) Quantity BCH/BCHQ 08 14.375 10.875 2 BCH/BCHQ 12 14.375 14.875 2 BCH/BCHQ 16 16.875 17.875 2 BCH/BCHQ 20 16.875 20.875 2 BCH/BCHQ 30 23.875 21.375 2 BCH/BCHQ 40 23.875 27.875 2 NOTES: Motor full load amps refer to the National Electric Code (NFPA 70). Actual nameplate amps may vary. NEC data was extrapolated for 277V. Motors are 60Hz, open drip proof, ball bearing, single speed rated at continuous duty up to 104 F (40 C). For 50Hz motor applications, please contact your local Price representative priceindustries.com Horizontal & Horizontal Quiet Blower Coils - Manual 11

MAINTENANCE Blower Coil Electric Coil Removal Instructions CAUTION: Disconnect all incoming power before any electrical installation or service is performed on the unit(s). Ensure line power is off to the Blower Coil Control Panel. The control panel contains hazardous voltages when energized; make certain that incoming line voltage has been disconnected. The Blower Coil Electric Coil assembly, seen in Illustration A, can be removed by following the steps listed below: 1. Open the control panel and disconnect any incoming wires that are not integrated in the enclosure; i.e. main supply and motor wires, as seen in Illustration B. 2. Disconnect the 90 wire conduit fitting from the control box and ensure the motor wires are pulled out of the control box. 3. Use a utility knife to cut the sealant between the perimeter of the control panel and the outlet ductwork. 4. Using a 1/4 driver, remove the screws securing the control panel to the outlet ductwork. There will be 3-4 screws located near the inside corners of the control box. See Illustration C. 5. Once the sealant has been separated and the screws have been removed, the electric coil can slide out of the ductwork. Grab the control box securely and slide the coil out of the unit horizontally. See Illustration D. Be cautious when cutting the sealant and removing the screws as they are the only securing medium for the electric coil. NOTE: See Electric Coils manual for troubleshooting. ILLUSTRATION B ILLUSTRATION C ILLUSTRATION A ILLUSTRATION D Illustration C 12 Horizontal & Horizontal Quiet Blower Coils - Manual priceindustries.com

MAINTENANCE Replacement Parts Component Part# Description 019891-001 1/2 HP, 1PH, 115/230V, Cap start motor, 56 frame 019891-002 3/4 HP, 1PH, 115/230V, Cap start motor, 56 frame 019891-003 1 HP, 1PH, 115/230V, Cap start motor, 56 frame 019891-007 1/2 HP, 3PH, 208-230/460V, Motor, 56 frame 019891-008 3/4 HP, 3PH, 208-230/460V, Motor, 56 frame 019891-009 1 HP, 3PH, 208-230/460V, Motor, 56 frame 019891-010 1-1/2 HP, 3PH, 208-230/460V, Motor, 56 frame 019891-011 2 HP, 3PH, 208-230/460V, Motor, 56HZ frame 019891-012 3 HP, 3PH, 208-230/460V, Motor, 56HZ frame Fan Motors 019891-013 5 HP, 3PH, 208-230/460V, Motor, 184T frame 019891-015 2 HP, 1 PH, 208-230V, Motor, 56H frame 019891-016 1/2 HP, 575V, Motor, 56 frame 019891-017 3/4 HP, 575V, Motor, 56 frame 019891-018 1 HP, 575V, Motor, 56 frame 019891-019 1-1/2 HP, 575V, Motor, 56H frame 019891-020 2 HP, 575V, Motor, 56 frame 019891-021 3 HP, 575V, Motor, 182T frame 019891-022 5 HP, 575V, Motor, 182T frame Motor Base 019073-001 Adjustable motor base for 56 Frame Motors 019073-002 Adjustable motor base for 184 Frame Motors 100187-001 90-6T Blower 100187-002 90-8T Blower Blowers 100187-003 100-6T Blower 100187-004 100-7T Blower 100187-005 120-9R Blower 100187-006 150-9T Blower Blower Flex Connector 042181-001 FLEX DUCT CONNECTOR, UL 214 LISTED priceindustries.com Horizontal & Horizontal Quiet Blower Coils - Manual 13

MAINTENANCE Component Part# Description Coils NOTE: XX in Coil Part # represents the number of circuits in the coil. 023441-1XX BCH Water Coil, 6 Row, Size 08 023441-2XX BCH Water Coil, 6 Row, Size 12 023441-3XX BCH Water Coil, 6 Row, Size 16 023441-4XX BCH Water Coil, 6 Row, Size 20 023441-5XX BCH Water Coil, 6 Row, Size 30 023441-6XX BCH Water Coil, 6 Row, Size 40 023442-1XX BCH Water Coil, 4 Row, Size 08 023442-2XX BCH Water Coil, 4 Row, Size 12 023442-3XX BCH Water Coil, 4 Row, Size 16 023442-4XX BCH Water Coil, 4 Row, Size 20 023442-5XX BCH Water Coil, 4 Row, Size 30 023442-6XX BCH Water Coil, 4 Row, Size 40 023443-1XX BCH Water Coil, 1 Row, Size 08 023443-2XX BCH Water Coil, 1 Row, Size 12 023443-3XX BCH Water Coil, 1 Row, Size 16 023443-4XX BCH Water Coil, 1 Row, Size 20 023443-5XX BCH Water Coil, 1 Row, Size 30 023443-6XX BCH Water Coil, 1 Row, Size 40 023444-1XX BCH Water Coil, 2 Row, Size 08 023444-2XX BCH Water Coil, 2 Row, Size 12 023444-3XX BCH Water Coil, 2 Row, Size 16 023444-4XX BCH Water Coil, 2 Row, Size 20 023444-5XX BCH Water Coil, 2 Row, Size 30 023444-6XX BCH Water Coil, 2 Row, Size 40 023445-1XX BCH Water Coil, 3 Row, Size 08 023445-2XX BCH Water Coil, 3 Row, Size 12 023445-3XX BCH Water Coil, 3 Row, Size 16 023445-4XX BCH Water Coil, 3 Row, Size 20 023445-5XX BCH Water Coil, 3 Row, Size 30 023445-6XX BCH Water Coil, 3 Row, Size 40 023447-1XX BCH Water Coil, 8 Row, Size 08 023447-2XX BCH Water Coil, 8 Row, Size 12 023447-3XX BCH Water Coil, 8 Row, Size 16 023447-4XX BCH Water Coil, 8 Row, Size 20 023447-5XX BCH Water Coil, 8 Row, Size 30 023447-6XX BCH Water Coil, 8 Row, Size 40 14 Horizontal & Horizontal Quiet Blower Coils - Manual priceindustries.com

MAINTENANCE Component Part# Description 042313-001 2" Merv 8 filter, 14.375 x 10.875 042313-002 2 Merv 8 filter, 14.375 x 14.875 042313-003 2 Merv 8 filter, 16.875 x 17.875 042313-004 2 Merv 8 filter, 16.875 x 20.875 042313-005 2 Merv 8 filter, 23.875 x 21.375 Filters 042313-006 2 Merv 8 filter, 23.875 x 27.875 042314-001 2 Merv 13 filter, 14.375 x 10.875 042314-002 2 Merv 13 filter, 14.375 x 14.875 042314-003 2 Merv 13 filter, 16.875 x 17.875 042314-004 2 Merv 13 filter, 16.875 x 20.875 042314-005 2 Merv 13 filter, 23.875 x 21.375 042314-006 2 Merv 13 filter, 23.875 x 27.875 019011-001 1 Pole, 120-277V Disconnect Switch 019903-003 2 Pole, 204-240V 019011-002 3 Pole, 208-600V 019416-001 24V Magnetic Contactor, 1 Pole 019416-002 24V Magnetic Contactor, 2 Pole 019418-001 24V Magnetic Contactor, 3 Pole Control Components 019436-001 120/24V Transformer, 50VA 019436-011 208-240/24V Transformer, 50VA 019439-001 277/24V Transformer, 50VA 00-14050 480/24V Transformer, 50VA Fuse Block 019459-001 Fuse Block 600V 30A priceindustries.com Horizontal & Horizontal Quiet Blower Coils - Manual 15

MAINTENANCE Installation Checklist Receiving & Inspection Receiving & inspection Unit received undamaged All parts accounted for Unit arrangement/hand correct Handling and Installation Unit mounted level and plumb Correct electrical service Proper access available for unit and components Correct overcurrent protection provided Correct service switch/disconnect provided Code compliance for all components Shipping screws and hardware removed Unit protected from dirt and foreign matter Set screws tightened Belt properly tensioned Cooling/Heating Connections Unit mounted level and plumb Proper access available for unit and components Correct chilled water line to the unit Correct hot water line to the unit Code compliance for all components Drain pan sloped properly Ductwork Connections All ductwork, grilles, filters and access panels are installed Correct supply and return grille type and size Insulate ductwork as required Control outside air to protect from heat/cold Electrical Connections Refer to unit wiring diagram Wiring in code compliance Connect power service 16 Horizontal & Horizontal Quiet Blower Coils - Manual priceindustries.com

NOTES priceindustries.com Horizontal & Horizontal Quiet Blower Coils - Manual 17