Using Embedded Tube Radiant Cooling Systems to Maximize LEED Points

Similar documents
ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

Radiant Heating & Cooling for Commercial Buildings

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

APPLICATION GUIDE BEAMS

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

7. MECHANICAL SYSTEM DESIGN

Displacement Ventilation in Classrooms

ProRadiant Controls, Valves and Actuators

1. Packaged Variable Air Volume (VAV) Rooftop Units (RTU) with Hot Water Reheat. 2. Geothermal Heat Pump VAV Rooftop Units with Hot Water Reheat

with Radiant ALSO: REEVES JOURNAL WATER TREATMENT CASE STUDIES NEWS: THREE BIG ANNIVERSARIES The Western Authority on Plumbing, HVAC and Piping

RADIANT COOLING SYSTEMS OPPORTUNITIES FOR RADIANT COOLING IN NORTH AMERICAN CONSTRUCTION DALE HANSCOMB, REHAU Sales Manager Building Technology

RADIANT COOLING RESEARCH SCOPING STUDY

Modular Active. Chilled. Beams

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Thermally Active Structures for Green Buildings: Introduction and Designing the System. Golden Gate Chapter, October 16, 2013

Uponor Climate Cŏntrol Network System Thermostat Installation and Operation Guide RADIANT HEATING SYSTEMS UPONOR CLIMATE SYSTEM THERMOSTAT

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

The Ed Roberts Campus

Heating Installation Guide published by

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

HVAC DISTRIBUTION and DELIVERY SYSTEMS

HVAC 101. H V A C S y s t e m s

Chilled Beams. Getting a Warmer Reception

Variable Air Volume with Indoor Air Quality

CONSTRUCTION AND ENERGY COSTS FOR RADIANT VS. VAV SYSTEMS

High Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

CEE 243. Week 2 HVAC systems at Y2E2

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions

A. ASHRAE Handbook HVAC Applications, Snow Melting and Freeze Protection

Raised Access Floor - (AE Breadth Area)

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Applications and Piping Strategies for Condensing Boilers - Introduction

Solstice Air to Water Heat Pump

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

DADANCO Technical Paper

EarthWise System Seminar

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

CONTROLLED CHILLED BEAM PUMP MODULE

Best Practices for Condensing Boilers

CONTROLLED CHILLED BEAM PUMP MODULE

Technical Assignment 3

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Versa- Hydro. up to 96% Efficient

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

Energy-Efficiency Measures List

Des Places Residence Hall

Technical Assignment 3 11/15/04. Executive Summary

New and Emerging HVAC Technologies. Rod Rhoads, GDS Associates Dave McCullaugh, Mitsubishi Electric Trane HVAC US Dave Binz, Cambridge Engineering

Inffusers. idl20 (2 WAY) ids60 (4 WAY)

Relative Humidity in Schools Jim Cummings and Chuck Withers

Better Design, Better Control, Better Systems.

Overview: EPIC* radiant systems project. FlexLab Infrared Image of Radiant System

TABS Radiant Cooling Design & Control in North America: Results from Expert Interviews

Hydronic & HVAC Control Systems

Dehumidifying with Dedicated Outdoor Air

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Zehnder Rittling Corporate Headquarters and Manufacturing Facility

GARCIA GALUSKA DESOUSA Consulting Engineers

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

Outdoor Reset Control Theory FULL versus PARTIAL reset

Hello, my name is Sarah Hilden and I am a Marketing Engineer in the C.D.S. group at Trane.

Hello, my name is Audra Benzschawel and I m a marketing engineer in the C.D.S. Slide 1 TRACE 700

Continuous Commissioning: A Valuable Partner to Retrofit Projects

(2.1) Design Conditions...5 (2.2) Ventilation Requirements..5 (2.3) Heating and Cooling Loads...6

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget

Small Building Program Design Phase Assistance

HVAC Controls Upgrades: Requirement Details ( )

Building air conditioning systems using Ice-Cel thermal storage can be designed which cost little or no more than conventional chiller-only systems.

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

heat interface units A BOILER WITHOUT A FLAME

August 15, 2013 Page 1 of 19

Climate Cŏntrol Multifunction Hydronic Control Installation and Operation Manual. Uponor Radiant Heating and Cooling Systems

2016 Title 24 HVAC Topics. June 4, 2013

A REASONABLE ALTERNATIVE TO CHILLED BEAMS Dan Int-Hout Chief Engineer

FACILITIES MANAGEMENT

ENGINEERING AND CONSTRUCTION BULLETIN

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

Being Radiant. Planning in-slab hydronic heating and cooling. solutions for the construction industry June 2014

Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA

Wal-Mart HE.5 Supercenter

Focus PLUS: SNOWMELT ELECTRIC RADIANT RADIANT PRODUCT ROUNDUP. The Western Authority on Plumbing, HVAC and Piping

Ve r s a - Hyd ro. 96% Efficient. The cost effec t i ve. ersa-hydro

LOW TEMPERATURE HYDRONIC HEATING FOR COLD CLIMATES TRAVIS SMITH PRESIDENT T AND T MOUNTAIN BUILDERS INC

Transcription:

San Joaquin ASHRAE Chapter Using Embedded Tube Radiant Cooling Systems to Maximize LEED Points Devin Abellon, P.E. Business Development Manager Uponor November 4, 2010

LEED v3 new construction LEED Topic SUSTAINABLE SITES 26 WATER EFFICIENCY 10 ENERGY & ATMOSPHERE 35 MATERIALS AND RESOURCES 14 INDOOR ENVIRONMENTAL QUALITY 15 INNOVATION IN DESIGN 6 REGIONAL PRIORITY 4 Possible Points

LEED v3 new construction LEED Topic ENERGY & ATMOSPHERE Credit 1: Optimize Energy Performance Credit 3: Enhanced Commissioning Credit 4: Enhanced Refrigerant Management Credit 5: Measurement & Verification INDOOR ENVIRONMENTAL QUALITY Credit 1: Outdoor Air Delivery Monitoring Credit 2: Increased Ventilation Credit 3: Construction IAQ Plan Credit 6.2: Controllability of Systems Thermal Comfort Credit 7: Thermal Comfort Design/Verification INNOVATION IN DESIGN Credit 1: Innovation in Design Possible Points 26 6 5

RADIANT COOLING High Mass Low Mass Thermally Activated Building System (TABS) Overhead slab or floor slab Thermal mass Larger surface area Moderate temperatures (e.g.,65f) Suspended or surface-mount Faster response Typically less surface area Colder temperatures (e.g.,55f)

2 nd LAW of thermodynamics Clausius Statement: Heat generally cannot flow spontaneously from a material at lower temperature to a material at higher temperature.

HUMAN COMFORT

HUMAN COMFORT ASHRAE Standard 55 Six Four Factors: AIR TEMP AIR MOVEMENT HUMIDITY CLOTHING METABOLISM RADIANT TEMP

RADIANT TEMPERATURE Average Uncontrolled Surface Temperature Area weighted average of the surface temperatures of all uncontrolled surface Mean Radiant Temperature Average of the AUST and the surface temperature of the controlled surface Operative Temperature Average of the Mean Radiant Temperature and the Air Temperature

RADIANT TEMPERATURE Room Temp. = 78.0 F AUST = 78.0 F MRT = 72.0 F Operative Temp. = 75.0 F

SOLAR GAIN

SOLAR GAIN

SOLAR GAIN

SOLAR GAIN

RADIANT COOLING System Advantages Ability to Deal with High Direct Solar Gains Superior Human Comfort Greater Architectural Freedom Reduced Drafts and Noise Energy Efficiency

ENERGY EFFICIENCY 100% peak power LBNL Findings: Chiller 62.5% 37.5% 18.8% 9.3% 34.4% Fan and motor Load from lights Air transport load Other loads 57.7% 1.5% - Pumps 7.5% 9.4% 1.9% 34.4% Depending on the climate, a radiant cooling system in conjunction with a dedicated outside air system (DOAS) could save between 17% - 42% over the baseline VAV system Source: LBNL Conventional HVAC system Radiant cooling HVAC system

ENERGY EFFICIENCY Pacific Northwest National Laboratory A radiant cooling system in conjunction with a dedicated outside air system (DOAS) could save as much as 53% over the baseline HVAC system National Renewable Energy Laboratory / U.S. Department of Energy 50% Energy Savings over ASHRAE 90.1 can achieved using a radiant heating and cooling system American Institute of Architects

ENERGY EFFICIENCY Case Studies Suvarnabhumi Bangkok Airport Bangkok, Thailand 30.5% Energy Savings California Academy of Sciences San Francisco, California LEED Platinum Western Science Center Hemet, California LEED Platinum Cooper Union New York, New York LEED Platinum NREL Research Support Facility Golden, Colorado LEED Platinum David Brower Center Berkeley, California LEED Platinum The Chartwell School Seaside, California LEED Platinum Portola Valley Town Center Portola, California LEED Platinum

RADIANT COOLING Performance Sensible Cooling A radiant cooling system can effectively manage a portion of building s sensible load 12 14 BTUH/SF Direct Solar Loads In areas with high direct solar loads, the systems capacity can significantly increase to 25 32 BTUH/SF

RADIANT COOLING Typical Parameters Tubing Cross-linked polyethylene (PEX) barrier tubing 5/8 diameter 6 to 9 on center spacing Maximum tubing length per loop 350 Operating Water Temperatures 55 F to 58 F 5 F to 8 F temperature differential Surface Temperature Minimum 66 F

RADIANT COOLING Typical Construction Slab on Grade Flooring Structural Slab PEX Tubing Wire Mesh / Rebar Insulation Compacted Grade

RADIANT COOLING Typical Construction Suspended Slab Structural Slab PEX Tubing Wire Mesh / Rebar Metal Deck Insulation

RADIANT COOLING Typical Construction Topping Slab Topping Slab PEX Tubing Wire Mesh Insulation Structural Slab

RADIANT COOLING Typical Construction Wood Deck Flooring Topping Slab PEX Tubing Wood Deck Insulation

RADIANT COOLING Manifolds

RADIANT COOLING Manifold Locations

RADIANT COOLING Piping Diagrams Mixing with Heating/Cooling Switchover

RADIANT COOLING Piping Diagrams Primary/Secondary Piping

RADIANT COOLING Piping Diagrams Local Secondary Injection

Uponor CONTROLS Control Points 24vac ON TX TX Port CAT5 Space Temperature Indoor Relative Humidity Operative Temperature Operating Water Temperatures Slab Temperature Control Valves Circulating Pumps Outdoor Temperature Outdoor Relative Humidity To Building Network Link Active RUN RX RX Ethernet Service Modem ON TX TX RUN RX Secondary1 Secondary2 Secondary3 Secondary4 Secondary5 Snowmelt 1 Snowmelt 3 FILED MODULES DZCM uponor Router uponor Field Modules Digital Zone Control Modules 1 Port 2 Port 3 Port 4 Port 5 Port 1 Port 2 Port 3 Port 4 Port 5 Mix1 Mix2 Mix3 Mix4 Mix5 Snowmelt 2 Snowmelt 4 24vac 10 Thermostats per controller OAS 24vac uponor DZCM uponor ZVDC HOT WATER RETURN HOT WATER SUPPLY COLD WATER RETURN COLD WATER SUPPLY DIVERTING GLOBE VALVE GLOBE VALVE / VALVE / CIRCUIT DIVERTING VALVE CIRCUIT SETTER SETTER Supply Temp LOW LOSS HEADER / 3WAY MODULATING DECOUPLER VALVE uponor uponor Supply Water Controller Return Temp

CONTROLS Control Strategies Base load with radiant cooling system and operate as a differential to air setpoint Utilize indoor adaptive rest strategy to optimize target water temperature for maximum effectiveness Continuously monitor indoor relative humidity for condensation control

RADIANT COOLING Condensation Concerns Condensation Surface condensation will occur if the surface temperature drops below the dew point Solution Continuously monitor indoor relative humidity and maintain supply water temperature 2 degrees above dew point at all times

CONTROLS Control Strategies Responsiveness High thermal mass provides inertia against temperature fluctuations Heat transfer from the thermal mass to the space is instantaneous whenever there is a temperature difference Thermal mass evens out fluctuations in internal temperature Secondary system used to handle high load densities

COST Typical Cost Factors No Cost Structural Slab already part of the construction budget Chilled water source typically already part of the budget Additional Cost Cost of tubing, manifolds, fittings, circulators Insulation Increased Labor Reduced Cost Smaller air handling units, ductwork, diffusers, etc. Reduced ceiling space requirements may allow for reduced floor to floor heights Potential to reduce electrical service size Reduced Maintenance Cost Less airside equipment to maintain

COST Typical Cost Factors Pacific Northwest National Laboratory Study Average cost of the radiant system, including central plant $9.31/ SF (7-8 year payback) 2010 R.S. Means Cost Data Average cost of materials & labor (excluding chilled water source) $4.25 - $5.43/ SF Innovations for Reduced Cost Big Box Retailer 2-1/2 year payback

RADIANT COOLING Summary Benefits Can be used to dramatically reduce overall building energy use Superior Human Comfort Improved architectural freedom Performance 12-14 BTUH/SF Sensible, up to 25-32 BTUH/SF with direct solar for radiant floor installations Important Considerations Controls Installation Methods Installation and Life-Cycle Costs

Questions?