INSTRUCTION MANUAL T-154. DOSSENA s.n.c. Via Federico Barbarossa s/n Cavenago di Adda tel Fax:

Similar documents
INSTRUCTION MANUAL T-935-FO ANALOGUE. TECSYSTEM S.r.l. TECSYSTEM S.r.l. protection relays. 12 protection relays

Table of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc

INSTRUCTION MANUAL T-935 FO DIGITAL

INSTRUCTION MANUAL T154. operates with ISO9001 certified quality system. TECSYSTEM S.r.l Corsico (MI) Tel.: Fax:

NT511 RS485 MODBUS INSIDE

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

CTT8 TEMPERATURE MONITOR DEVICE

MO n : 12JMC rév A

INSTRUCTION MANUAL T30 1MN0107 REV. 0. operates with ISO9001 certified quality system

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

Thermal protection device for electric units

INSTRUCTION MANUAL NT935 IR. operates with ISO9001 certified quality system

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

INSTRUCTION MANUAL NT935 IR. operates with ISO9001 certified quality system

02/11/2015

02/11/2015

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

03.03.mmm REV.2 09/01

R1000 / R1040 / R1080

Product Manual SZ1145

SACE PR021/K SIGNALLING UNIT

Installation, Operating and Maintenance Manual

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

Product Manual SZ1144

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

TC515 and TC600 Installation Manual. a Winters company

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Emotron M10 Shaft Power Monitor. Instruction manual English

Installation and Operating Manual

Product Manual SZ1009

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

NT210 + TPL210 RS485 MODBUS INSIDE

INSTRUCTIONS FOR THE LCR10 TEN INCH CIRCULAR CHART RECORDER

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

LUMA-NET 804CP / 808CP REMOTE CONTROL PANEL

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

Emerson Blue Easy Set 1H/1C

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point

C106 Coded Access Keypad

Temperature Controllers

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

eed quality electronic design USER s MANUAL

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

SCHMIDT LED Measured Value Display MD Instructions for Use

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

DTA. Motor thermistor relay. Benefits. Description

RS Pro Infrared Temperature Sensor

ACS-30-EU-EMDR- 10-MOD

Instructions for the fan motor control system with integrated wiring terminals SILVER C

RC-2000 Thermostat Installation Instructions

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

UFM-T100H US ES CA Power Alarm Test TM

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

DTA04. Motor thermistor relay. Benefits. Description

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

REGARD GAS DETECTION SYSTEM

MR3CCUHV Temperature/Defrost Control

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL

INSTALLATION & OPERATION MANUAL

BX444-Mc Gas Detector

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

SECTION AUTOMATIC TRANSFER SWITCHES

METEOROLOGICAL INSTRUMENTS

Long-Range Barrier Sensors

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Oxygen (O2) Single-Point Gas Detection System

Series Temperature Controller Instruction Sheet

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

Multi-Gas-Controller MGC2

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

Heat Pump Defrost Board Replacement Kit

IF79 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning

tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual

HTC-915-CONT. Heat-Trace Control system

Laboratory Airflow Monitors & Controls TYPE C STANDARD & NIGHT SETBACK LED & DIGITAL - VAV SYSTEMS

External Wireless Sounder

DRYTEK 1 - User Manual ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL

ACS-30-EU-VIA-DU-20-MOD

THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH.

Mark 25 Ultrapure Water Conductivity Analyzer

Carbon Monoxide Transmitter

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

External Wireless Sounder

Smart Temp. Model

CT224 Setup Tutorial

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

Model 96VTR ¼ DIN Process Controller

Transcription:

INSTRUCTION MANUAL T-154 DOSSENA s.n.c. Via Federico Barbarossa s/n 26824 Cavenago di Adda tel. +39 0371 44971 Fax: +39 0371 70202 http://www.dossena.it R.0 02/12/01 protection relays

BT MT 220VAC-24VAC PT-73 FIG.2 T-154 T-154 possible configuration of ALARM and FAULT relays parallel connection 1 2 3 4 5 6 7 8 9 10 11 Fig.3 2 protection relays

1) TECHNICAL SPECIFICATIONS AUXILIARY POWER SUPPLY Rated voltage 24-240 Vac-dc Maximum ratings 20-270 Vac-dc INPUTS OUTPUTS 3 or 4 inputs RTD Pt100 sensors-3 wires removable rear terminals input channels protected against electromagnetic noises and spikes sensors length cables compensation up to 500 m (1mm²) TEST AND PERFORMANCES Assembling in accordance with CE rules Protection against electrical and magnetic noises: CEI-EN50081-2/50082-2 Dielectric strength: 2500 Vac for 1 min. from relays to sensors, relays to power supply, power supply to sensors Accuracy: ± 1% full scale, ±1 digit Ambient operating temperature: -20 C to 60 C Humidity: 90% non-condensing ABS self-extinguishing housing-noryl 94VO Opt. Frontal plastic protection Opt. Protection treatment of electronic part Frontal polycarbonate-ip65 Burden: 3VA Data storage: 10 years minimum Digital linearity of sensors signal Self-diagnostic circuit DIMENSIONS 96x96 mm-din43700- depth 140mm (with rear terminals) 2 alarm relays (ALARM-TRIP) 1 alarm relay for fan control (FAN) 1 alarm relay for sensor fault or working anomaly (FAULT) output contacts capacity: 5A-250 Vac res. DISPLAYING AND DATA MANAGEMENT 1 display 13 mm high with 3 digits for displaying temperatures LED for displaying reference channel LED indicating alarm or trip channel LED indicating fault Temperature monitoring from 0-200 C 2 alarm thresholds 2 alarm ON-OFF thresholds for fan control Sensors diagnostic (Fcc-Foc-Fcd) Entering the programming by frontal push button Automatic output from programming cycle after 1 minute of no operation Wrong programming automatic display Programmed data call out Possibility of setting automatic channel scanning, hottest channel, manual scanning Maximum temperatures and alarms storage protection relays 3

2) MOUNTING Make a hole with the dimensions of 92x92 mm in the panel plate. Fasten firmly the unit by the fixing blocks included with each unit. 3) POWER SUPPLY The T-154 unit has a universal power supply. It can be supplied with 24 to 240 Vac or dc without respect to polarities. The ground cable must be fixed to terminal # 41. ATTENTION: the unit may be damaged by overvoltage when power is supplied directly form the secondary of the transformer it is monitoring. This may occur when the 220V is obtained directly from the secondary winding and there are fixed capacitors online. 4) ALARMS AND FAN CONTROL ELECTRICAL CONNECTIONS Take the removable terminal board off the unit before wiring. ALARM and TRIP relays energize only when the prefixed temperature limits are reached (NO Fail Safe) or reset when the prefixed temperature limits are reached (Fail Safe). In order to protect the electronic apparatus, we suggest the application of the electronic dischargers of the series PT-73 mono or double phase. Alternatively, we suggest the application of a 24 Vac or better 24 Vdc power supply. The FAULT relay always energizes when the apparatus is powered and it resets when the Pt100 s are damaged or when there is no power voltage. The FAN relay can be used for fan control or else it can be included in the conditioning circuit of the transformer box. 5) THERMOMETRIC SENSORS CONNECTION Each Pt100 sensor has three conductors : one white and two red (CEI 75.8) Fig.1 shows the disposition in the terminal board of the connection cables to the unit. Channel 2 must be always referred to the central column of the transformer. Channel 4 must be always referred to the core of the transformer or else to the ambient Pt100 sensor, if you want to monitor the temperature of the transformer box through the T-154 unit. 4 protection relays

6) MEASURE SIGNALS TRANSPORT All the transport cables of the Pt100 measure signals must absolutely: be divided from the power ones be realized with shielded cable with twisted conductors have a section of min 0.5 mm² be twisted if you have no shield be firmly fixed in the terminal board have tinned or silvered conductors All units of the T series have the sensors linearization with a max error of 1% v.f.s.. It s available a special cable for the measure signal transport with all the protection requirements in accordance with CEI Norms: mod. CT-ES 7) THERMOMETRIC SENSORS DIAGNOSTIC In the event one of the thermometric sensors installed on the machine to protect is damaged, the FAULT relay energizes immediately, the ALARM and TRIP LED s of the damaged channel (Chn) lighten and the FAULT LED is lightening. The screen will automatically display a message showing the fault condition: Fcc sensor is short circuited Foc sensor is open During the unit normal operation, if the Fcd/YES function has been selected, the display show Fcd indicating that a sensor is damaged and the LED corresponding to the affected channel will lighten (Chn). The FAULT relay energizes giving a signal to the operator. After the replacement of the damaged sensor, you can RESET the alarm pushing RESET until the display shows the message RST. 8) TEMPERATURES DIAGNOSTIC When one of the thermometric sensors surveys a temperature exceeding by 1 C the alarm limit, after 4 seconds the ALARM relay will energize and the ALARM LED of the affected channel (Chn) will switch on. The same occurs when the TRIP temperature limit is detected: the TRIP relay energizes and the TRIP LED corresponding to the affected channel is lightening. When the surveyed temperature declines of 1 C below the prefixed limit for the ALARM and TRIP switching, the relays de-energize and the respective LED s switch off. protection relays 5

9) COOLING-FAN CONTROL The T-154 unit, if suitably programmed, can control the ON-OFF of the transformer fans according to the set temperature values. The fans of the machine can be controlled in two different ways: using the temperatures surveyed by the sensors on the three columns Channel 1.2.3 ALARM and TRIP LED CH1.2.3 illuminated (e.g. ON at 80 C - OFF at 70 C) by an additonal sensor (CH4/YES) for the ambient temperature inside the transformer box. CHF 4 ALARM e TRIP LED Ch4 illuminated (e.g. ON at 40 C - OFF at 30 C) Press UP or DOWN key to select this function. 10) FAN TEST By programming (hxx) you can establish to have the fans set for 5 minutes every xx hours, independently on columns or ambient temperature values. This function has the purpose to verify periodically the fans working, when they are not in use. By setting h00 this functions is disabled. 11) DISPLAY MODE By pressing DISPLAY MODE you can select one of the three display modes: AUTO : the display shows automatically the temperature of the hottest channel. MAN : each channel may be viewed manually by pressing the UP or DOWN key. T.MAX : the unit shows the max. temperature recorded by the sensors and any alarm recorded after the last reset. 12) WORKING PROGRAM CONTROL To review the entered values momentarily press PRG key and continue to do so advancing to each programmed value. Press ENT to return to normal operating mode. 6 protection relays

13) LAMP TEST It is advisable to carry out this test on a regular basis to ensure all lamps are functioning normally. Pressing the TEST key at any time allows the user to test all lamps. If any lamp is not functioning the unit must be returned for repair. 14) ALARM RELAYS TEST All relays may be tested using the following procedure. Press and hold the TEST key for 5 seconds. Initially all LED s illuminate, changing to the main screen display flashing TST. Release the test key when the yellow relay test LED illuminates. The screen display will show the relay selected for testing and the respective LED will be illuminated. The relays to test will be indicated on the display by: Fan :cooling relay Flt :Pt100 fault relay Alr :alarm relay trp :trip relay Use the Scroll UP or DOWN keys to make the selection. Press the SET key to perform the test on the selected relay. To reset press the RESET key. To discontinue operation and revert to normal operation, press the TEST key. At the start of the test, a timer is automatically initiated which reverts the unit to normal operation if no inputs are detected for a period of five minutes. 15) ALARM RELAY EXCLUSION The alarm relay will change contact state when the alarm set point temperature value is reached. An illuminated alarm LED provides indication of the affected channel. To reset the relay contact, press the RESET key. The alarm LED corresponding to the affected channel will start flashing to indicate that an alarm temperature value has been reached. If the set point alarm value is exceeded up to a value of 5 C below the set trip threshold, the alarm relay will change contact state again and the alarm LED will illuminate. Once again press the RESET key to reset the relay contact. When the trip set point temperature value is reached, the trip relay will change contact state and both the yellow alarm and the red trip LED s illuminate. 16) IMPORTANT NOTICE Before conducting the insulation test, disconnect the power supply to the unit to avoid damage. protection relays 7

17) PROGRAMMING IMPORTANT: PROGRAM LED switched off: VISUALIZATION Mode PROGRAM LED illuminated: PROGRAMMING Mode N KEY DISPLAY NOTES 1 PRG/SET To begin programming press and hold PRG/SET. PRG will flash for 7 sec. When PRG stops flashing, default alarm setpoint will appear on display. Program LED will light 2 Enter the desired Limit setpoint. 3 PRG/SET TRIP set T appears 4 Enter the desired Trip setpoint. 5 PRG/SET FAN appears on display 6 Enter FAN YES or NO YES: FAN contacts enabled NO: FAN contacts disabled 7 PRG/SET OFF appears on display 8 PRG/SET The OFF T appears 9 Enter desired setpoint for fan to turn off only if YES was chosen at step 6. 10 PRG/SET ON appears on display 11 PRG/SET The ON T appears 12 Enter the desired temperature for fan to turn on only if YES was chosen at step 6. 13 PRG/SET CH4 appears on the display 14 Enter CH4 YES or NO 15 PRG/SET Status of FAN control will appear on the display as CHF YES: Ch4 enabled NO: CH4 disabled 16 set up CH 1,2,3, or CH4 respective LED alight 17 PRG/SET Status of FAN control TEST will appear on the display as h00 18 set up the number of hours 19 PRG/SET Fcd appears on display 20 Enter Fcd YES or NO 21 PRG/SET PRG appears on display only if at step 6 you chose YES h00 = function disabled Fcd YES = unit will indicate damaged sensor. Fcd NO = indicator off. 22 set up Prg YES or no 23 ENT PRG/SET Programming is completed. Press ENT to return to normal operating mode. Prg NO = program cannot be changed The unit will perform the light test. 8 protection relays

18) WARRANTY The T series units are warranted for a period of 12 months from the delivery date marked on the unit. Warranty is limited to repair or replacement of the defective products and no contingent liabilities will be accepted. Warranty will be voided if the unit is found to be tampered with or when it has been damaged as a result of incorrect input or power supply connections (out of the max working limits 20+270 Vac-dc). Warranty will be voided if the unit is damaged as a result of transitory overvoltages. Freight expense is not covered under warranty. In case of dispute, the qualified FORUM is the one in Milan. 19) PT100 EXTENSION CABLE: TECHNICAL SPECIFICATIONS Cable 20xAWG 20/19 cu/stg Section 0.55 mm² Antiflame Insulation PVC105 In accordance with CEI 20.35 IEC 332.1 Max. working temperature: 105 C Conformation : 4 terns of the numbered conductors (1-1-1...4-4-4) RRW twisted and coloured conductors Shield cu/stg PVC Antiflame protecting covering External diameter 9.0 mm Skeins of 100 m 20) PROGRAMMING REHABILITATION IN CASE OF BLOCK (Prg no) In the event program access is blocked the display will show SET and then display nop. To gain access, press the ENT key and return to normal operation. Touch the PRG key and then, press and hold the TEST key for approximately 7 seconds until the flashing PRG screen display ends, and the message nch is displayed. NOTE: this procedure removes the lockout feature. To block access again, this feature must be reprogrammed. protection relays 9

TROUBLESHOOTING PROBLEMS CAUSES / SOLUTIONS The unit will not switch on, with control power energized Channel 4 is indicating fault and displaying FOC (only three Pt100 sensors are connected) One of the 3/4 channels is indicating fault and displaying FOC/FCC When switching the unit on-off, the alarm and trip relays energize All the sensors are displaying FCC. The temperature indicated by one or more channels is wrong. With a control power source of 24 VDC the unit switches off and will not switch back on. Sudden activation of the trip relay with normal operating temperature. One channel caused the occurrence. Check the terminal block for correct installation. Check for voltage at the terminal block Wrong programming of the unit. Repeat programming. Check the sensors connection. Look for damaged sensors. Replace damaged sensor Strong electrical noise is being picked up on the power line. Install a transient suppressor (PT-73.) Check to ensure the shield of the sensor cable is connected to the panel ground. Install shielded cable (Mod. CT-ES) or twist the sensor conductors. Wrong wiring connections. The terminal block is upside-down. The sensors are defective. Check the sensor resistance with an Ohmetre. The unit is calibrated incorrectly. Return for repair. Check the input voltage is between 20-24 VDC. Reconnect to a stable source of power. Return if unit does not respond Sensor defective (Fcd). Replace the sensor. 10 protection relays

FIG.1 T-154 ELECTRICAL CONNECTION Pt100 SENSORS CONNECTION CH 1 CH 2 CH 3 CH 4 13 14 15 16 17 18 19 20 21 22 23 24 RELAYS CONNECTION 1 2 3 4 5 6 7 8 9 10 11 ALARM TRIP FAULT FAN Pt100 42 41 40 POWER SUPPLY 24-240 VAC-VDC WHITE RED RED protection relays 11

T154 TEST DESCRIPTION The unit was submitted to the following tests during production: N Description 1 PC board test 2 Input test 3 Test of relay contacts and outputs 4 Key test 5 Lamp test 6 Calibration at 100 and 200 C (for temperature monitoring units) 7 Software test 8 Burn-in minimum 24h Date of shipment: 12 protection relays