NRG SYSTEMS, HINESBURG, VT

Similar documents
Advanced Lighting For Office

Daylight and Whole-Building Energy Analysis Using Radiance in IES <Virtual Environment>

Buidling 661 Annual Daylight Performance Modeling Studies

Adelaide Homes Design Guide 3 - Shading

Duke Tower Main Entrance Lobby Overview

Daylighting Control Design and Application Guide

A Guide for Applicants and Lighting Designers

Carpenter Center Cambridge, MA DAYLIGHT AS A DESIGN FACTOR Anahita Anandam

Lighting Design Criteria: Codes and Standards

Lindsey Beane. Executive Summary

Lighting Control Strategies. to meet code requirements save energy and improve building performance

Lord Stirling Community School

VENTAL V80 EXTERNAL LOUVRE BLINDS External Aluminium Louvre Blinds for Sunshading through Glazed Surfaces V80

University of California Santa Barbara. Student Resource Building

SAFETY AND ENVIRONMENTAL EDUCATION FOR DEVELOPMENT SEED

13-15, 2001 USING LIGHTING SIMULATION TO ASSESS THE PERFORMANCE OF AND INDIRECT OFFICE LIGHTING SYSTEMS IN DYNAMIC WORKPLACES

University Park, PA. The Pennsylvania State University Architectural Engineering Lighting and Electrical Faculty Advisor: Dr.

Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE

Lighting Existing Conditions and Design Criteria Report

Solon High School (Solon, Iowa) Human Factors Evaluation

Lighting Application Guide for K-12 Classrooms

DAYLIGHTING PERFORMANCE ON VENETIAN BLIND FOR HEALTHY APARTMENT HOUSING

Lighting in the workplace is it just about vision?

Are LED s ready for Prime Time?

LIGHTING NORTH FAÇADE AND PLAZA

Lighting Existing Conditions and Design Criteria Report

SMEAL COLLEGE OF BUSINESS BUILDING University Park, PA

Visual Responses of Visitors towards Daylighting in Museums: A case study of Malaysia

Surface Materials. Surface Material Reflectance. Acoustic Ceiling 80% Tile. Painted Gypsum 75% Wall Board. Vinyl Composition 32% Tile

Cosmetology Lab Redesign

Discomfort glare with complex fenestration systems and the impact on energy use when using daylighting control

Lighting Proposal Memo. Lighting Proposal. Angela Nudy Lighting/Electrical Dr. Mistrick Lighting Proposal Memo 1

Technical Assignment I

miniz Quick Start Guide

Eric Anderson. Technical Report 1. Existing Lighting Conditions

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130)

Technical Report One

fabric specification guidelines

L ig h t in g Dept h 8

Windows Influence on Room Daylighting in Residential Buildings

Lighting Concepts: Residential

City of Green Administration Building. Brian Koze November 12, Lighting Schematic Design Presentation

EVALUATING DAYLIGHT PERFORMANCE IN A PASSIVE SOLAR HOME: A STUDY BASED ON DESIGN SIMULATION AND POST- OCCUPANCY MONITORING RESULTS

Congress Elementary School (Milwaukee, Wisconsin) Human Factors Evaluation

Erin McCauley The Gateway Building

Jennifer Mers. Rio Hondo Library and Learning Resource Center. Executive Summary. General Building. Lighting/Electrical Option

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

External venetian blinds sunlight included 40% ENERGY SAVINGS WITH INTELLIGENT SUN SHADING

Windo-w Planning Principles

Optimal control for superior lighting performance

DAYLIGHT AS A VISUAL EXPERIENCE

Park Gate. Dubai, United Arab Emirates

MANDATORY MEASURES. There are two major steps for exterior spaces to comply with Title 24:

Solar Thermal Planning Worksheet Date: / /

POTENTIAL ENERGY SAVINGS WITH EXTERIOR SHADES IN LARGE OFFICE BUILDINGS AND THE IMPACT OF DISCOMFORT GLARE. Sabine Hoffmann, Eleanor Lee

TITLE 24 ICONOGRAPHY. Iconography System

Main Lobby Area (North Vestibule thru South Vestibule):

Code Review TITLE PRESENTED BY POURIA NIKNAM

COMMERCIAL LIGHTING DESIGN GUIDE

Lighting Existing Conditions and Design Criteria Report Brian Regan Ltg./Elect. Virginia Historical Society 10/8/03

Schematic Design Proposal Presentation

Holy Cross Hospital North Addition. Fall 2005 Phil Mackey

High Performance Lighting. Terry Egnor Senior Consultant NBI

Note: A summary of the applicable code sections is shown in the CEC _Table100A.

Momo Sushi. Robert Blecker ABS 643

Design and Build a. Solar House. Introduction. Design a model house that uses as little energy as possible to keep it warm.

Thesis Proposal Update #2

Waste not, want not. As part of our efforts to ensure we practice sustainability in our business, we ve printed this brochure on recycled paper.

Overview. The Reading Room

CONTROL SYSTEM. How to design daylight into your building using electronically tintable glazing.

Checklist for workstations with computer monitors

Café DUSON- Overview

Adelaide Homes Design Guide 4 - Winter warming

Annual environmental performance evaluation of light and heat in daylight harvesting systems using Radiance and NewHASP

The Influence of the Courtyard Geometry on the Passive Lighting Energy Savings Jie TAN 1,* Xin GUO 2 and Ming-ping ZHANG 1

Installation manual SP3

HunterDouglas Silhouette Shades are unique and extremely versatile window shades; soft as silk, elegant as a curtain and practical as a venetian

University of California, San Diego Cal IT 2 Brian Smith. Schematic Design Presentation 06 December 2005

C ontrolsystems Themostadv ingenious a n cedsensor-basedcontrols.now integratedintoourmostpopularfixtures.

OUTDOOR BLINDS + EXTERIOR VENETIAN BLINDS

A N A L Y S I S 1 : View of Geisinger Gray s Woods Ambulatory Care Campus from Gray s Woods Boulevard. Personal Photo.

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG-1-A

ENVIRONMENTAL STRATEGY FOR ROW HOUSE- CAPE TOWN

Lighting System Conceptual Design

DAYLIGHTING ANALYSIS. Generic Design/Analysis Methods (applicable to all sorts of systems)

Depth Work Part 1: Lighting Design

Using high light reflectance acoustical ceilings to increase the energy efficiency of buildings

Lighting Depth: Courtyard Franklin Care Center, Franklin Lakes, NJ

Synco-GAMMA Application Guide. School building class room. Answers for infrastructure.

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2012

Reduce lighting energy costs with controls

ISOLIEREN & GESTALTEN MIT GLAS SANCO

SECTION LIGHTING REGULATIONS

Lighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY

Architectural Blinds & Dynamic Solar Facades. No single factor has more environmental impact on a building than solar heat gain.

Demand Responsive Lighting Controls

Sample Thermal Comfort Survey. Section 1 Background Information. How many years have you been working in this building?

LUMINOUS ENVIRONMENT AND OCCUPANT S SATISFACTION AT OPEN- PLAN OFFICE (Case Study: Jawa Pos Office, Grha Pena 4 th Floor, Surabaya)

Transcription:

Daylighting Case Studies NRG SYSTEMS, HINESBURG, VT Project Highlights Daylight windows separated from view windows Advanced daylightredirecting blinds Low partitions, with desks oriented at right angles to windows Open loop photocontrol system NRG Systems is a manufacturer of wind measurement systems for the wind turbine industry. NRG s towers, wind sensors and data loggers help their clients to effectively site and operate wind turbines. Part of their commitment to improving our world and protecting the environment is a 31,000 sf manufacturing and office building that includes a wide range of sustainable features. This case study focuses on the south facing office areas, and how incoming sunlight and diffuse daylight is managed by advanced window blinds, to create a comfortable and efficient workplace. NRG s building is located in Hinesburg Vermont, between Lake Champlain and the first ridge of the Green Mountains. The elevation is 300, latitude 44 N, and the climate is temperate with cold winters and moderate summers. Frequent winter snow and low winter sun angles create bright and challenging visual conditions for the south facing spaces.

DAYLIGHTING DESIGN The south facing offices have a continuous row of 2 high daylighting windows between 8 and 10 from the floor, supplemented by view windows below. The view window sills are at 3 6, with a 7 head height. The view windows occupy about 45% of the width of the façade and are broken up according to the functional areas within. Overall the window South facing office with advanced blinds and roller shades. Note pattern of re directed sunlight on the ceiling, and the orientation of suspended luminaires parallel to the window wall. to wall ratio 1 is approximately 50% and visible light transmittance of the glass is 41%. All the upper windows, and some of the view windows, are fitted with innovative inverted, mirror finish blinds manufactured by Warema. These blinds are set at an angle to redirect incoming sunlight up to the ceiling. In the lower view windows, the blinds also have perforations along the inner edge to preserve a filtered view out of the window even if the blinds are fully closed to block sunlight. The view windows in some open office areas are fitted with woven roller shades manufactured by Mechoshade. The shades are designed to shield occupants near the windows from solar heat, and to reduce glare from low altitude sun. Both sets of blinds are manually controlled by occupants, rather than by automatic systems. Interior daylight levels are increased by high reflectance walls (75%) and ceiling (90%), and by low (4 6 ) partitions between desks. 1 Measured relative to the exterior wall area Mahone Group 2011

LIGHTING CONTROLS Advanced reflective blinds bounce sunlight up to the ceiling. VISUAL ENVIRONMENT The electric lighting system provides direct/indirect light from suspended luminaires, arranged in two rows parallel to the windows. The control system is a centralized open loop system, which dims luminaires to different levels in response to a daylight reading from a single sensor positioned in a south facing second floor clerestory. The location of the sensor was chosen to replicate the orientation and view available from the office windows. The building s energy management system constantly tracks lighting energy use, and can give hourly energy use for each lighting circuit. The open office ambient lighting system provides around 28 footcandles and has an installed power density of 1.3 W/sf. It is also controlled by auto on/auto off occupancy sensors. The visual environment is a truly open office without partitions, which allows daylight to spread across the entire space, and allows occupants to have long views both within the space and through windows to the outside. Light colored surfaces reduce contrasts to increase visual comfort. Contrast between the windows and the ceiling is reduced due to light bounced up by the advanced blinds. Luminance map showing reduced window contrast due to light bounced upward by the advanced blinds. Green areas indicate brighter areas from reflected sunlight and/or luminaires.

DAYLIGHTING PERFORMANCE The graph below shows weekday illuminances from daylight, on the first row of desks next to the window. Illuminances were measured by a ceiling mounted sensor looking down at the desk area. The colored lines show sunny days, broken out by month, while the black line shows overcast days. Daylight illuminance is higher in the winter months than the summer months, which suggests that the window blinds (and winter snow) are successfully redirecting low angle sunlight on to the ceiling while allowing occupants to control solar glare. In the summer the first floor upper windows are shaded by a photovoltaic array mounted above them, also reducing sun penetration. In this building, sunny days produce brighter interior conditions than overcast days. The daylight autonomy for the first row of desks is 27% (i.e., daylight levels exceed the working illuminance of 30 footcandles for 27% of the time between 8:30 and 5:30, over the course of a year). Daylight autonomy for the second row of desks is 8%. These values are low compared with good design phase daylight autonomy values (typically >70% for the first row, and 40 60% for the second row), but the values at NRG are measured values of daylight autonomy, i.e., they include reductions in daylight levels due to the occupants use of blinds. The graph below shows that although daylight levels were consistent, they were low, most likely due to the blinds being partially closed by occupants. Mahone Group 2011

ENERGY PERFORMANCE Energy performance was logged between July and December, to include a complete range of solar angles. The two rows of open office luminaires respond to daylight differently, as shown by the measured data in the graph below. The set points for the second row mean that it does not begin to dim down until the exterior illuminance reaches 3,000fc (a sunny, or bright overcast day). The first row begins to dim down at 900fc, and reaches its lowest level (around 60% output) when the exterior daylight level is 1,500fc (an average overcast day). The open office lighting system typically consumes 0.9 W/sf during the work day, compared to its installed power of 1.3 W/sf a reduction of 31%. This reduction is due to occupancy control of some luminaires, as well as to the photocontrols. Based on the whole six month period of data collection, the lighting is estimated to consume 2.7 kwh/sf annually. A building with the same installed lighting power density, with the lighting switched on for the typical 3000 hours per year would consume 4.2 kwh/sf annually, so the NRG building saves 36% relative to that base case. A newlyconstructed and non daylit building would require less installed lighting power to meet code, and would typically consume approximately the same amount of lighting energy as the NRG building with its advanced daylighting features.

OCCUPANT COMFORT SURVEYS An online survey of the occupants received 16 complete responses. Two surveys were conducted one in the summer and one in the winter to see whether the performance of the system differed over the course of the year. For four of the questions, the results are shown relative to a benchmark of high performance daylit buildings from a recent study 2. The overall response to lighting quality was strongly positive (positive responses are to the right on the chart below). However, one third of the survey respondents found the space to be uncomfortably bright, and this was due to daylight rather than electrical lighting. The occupant responses remained consistent between summer and winter except for complaints about excessive brightness being slightly higher in summer, although this was not a statistically significant difference due to the small number of responses. In lighting research, complaints of excessive brightness are almost never due to high overall levels of light; instead they are due to glare from specific sources such as direct or reflected sunlight coming through gaps in the roller shades. The responses to every question were statistically significant, i.e. they were different from no opinion. A third of the respondents felt the space was uncomfortably bright due to daylight rather than electrical lighting. 2 Heschong Mahone Group. 2011. Daylight Metrics Project: Final Report. California Energy Commission, PIER program. Mahone Group 2011

LESSONS LEARNED The dimming photocontrol system at NRG is successful. We estimate that it saves 20 30% of lighting energy use compared with having the luminaires at full output, while achieving light levels consistent with IES guidance, and maintaining high levels of occupant comfort. Because the first row fixtures dim down to only 60% output, and the second row fixtures do not dim down at all, the savings could technically have been much greater. The advanced blinds are effective at bouncing sunlight up to the ceiling, increasing daylight penetration into the interior spaces and improving the brightness and uniformity of the daylighting Some occupants report that the space is uncomfortably bright in the summer. This may be due to sunlight penetrating through the roller blinds, especially at lower sun angles in the morning and evening. Adjustable blinds may have been a better choice, which occupants could have positioned to block varying sun angles as needed. Adjustable blinds with perforations can preserve a filtered view while also blocking the sun. Measured daylight autonomy levels are comparatively low. Using adjustable blinds instead of roller blinds may have helped to increase daylight autonomy and increase savings from the photocontrols. Additional savings may have been achieved by using manual on rather than automatic on occupancy sensors, requiring occupants to choose to switch the lights on when they enter the space, if adequate daylight is not present. A later addition of photovoltaic cells mounted above the south facing daylight windows on the lower floor creates some shading of these windows during the summer, reducing the daylight energy savings.