TECHNICAL GUIDE SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) LISTED ISO 9001 Certified Quality Management System Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.york.com Additional rating information can be found at www.ari.org/aridirectory. 261647-UTG-C-0108 DESCRIPTION The 10 SEER Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be custom-matched with one of UPG s complete line of evaporator sections, each designed to serve a specific function. Matching Air Handlers are available for upflow, downflow or horizontal applications to provide a complete system. Electric Heaters are available if required. Add-On coils are available for use with upflow, downflow or horizontal furnaces and air handlers. WARRANTY Three Phase Units: 1-year limited parts warranty. 5-year limited compressor warranty. FEATURES QUALITY CONDENSER COILS - The coil is constructed of enhanced copper tube and aluminum fins. COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard. PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating conditions occur. A liquid line filter-drier further protects the compressor. DURABLE FINISH - The cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted desert sand finish insure less fading when exposed to sunlight. LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof. TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications. LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds. LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing. EASY SERVICE ACCESS - Fully exposed refrigerant connections, a single panel covering the electrical controls and the molex plug in the control box connecting the condenser fan, make for easy servicing of the unit. SECURED SERVICE VALVES - Secured re-usable service valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging. U.L. and C.U.L. listed - approved for outdoor application. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240. FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
261647-UTG-C-0108 PHYSICAL AND ELECTRICAL DATA - 3 Phase MODEL AC036X1031 AC048X1031 AC060X1031 AC036X1041 AC048X1041 AC060X1041 Unit Supply Voltage 208-230V, 3φ, 60Hz 460, 3φ, 60Hz Normal Voltage Range 1 187 to 252 432 to 504 Minimum Circuit Ampacity 15.0 17.3 21.3 8.0 8.3 10.8 Max. Overcurrent Device Amps 2 25 30 35 15 15 15 Min. Overcurrent Device Amps 3 15 20 25 15 15 15 Compressor Type Recip Recip Scroll Recip Recip Scroll Compressor Amps Rated Load 10.9 11.7 16.0 5.8 6.1 8.0 Locked Rotor 78 78 125 40 39 67 Crankcase Heater No No No No No No Fan Motor Amps Rated Load 1.4 1.3 1.3.8.7.8 Fan Diameter Inches 18 22 22 18 22 22 Fan Motor Rated HP 1/4 1/4 1/4 1/4 1/5 1/4 Nominal RPM 1,100 850 850 1,100 850 850 Nominal CFM 2,750 3,250 3,450 2,750 3,250 3,450 Face Area Sq. Ft. 9.15 15.72 23.58 9.15 15.72 23.58 Coil Rows Deep 1 1 1 1 1 1 Fin / Inches 18 18 18 18 18 18 Liquid Line OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line OD (Field Installed) 3/4 7/8 7/8 3/4 7/8 7/8 Unit Charge (Lbs. - Oz.) 4 3-15 7-5 9-15 3-15 7-5 9-15 Charge Per Foot, Oz. 4.68.70.70.68.70.70 Operating Weight Lbs. 170 206 228 170 206 228 1. Rated in accordance with ARI Standard 110, utilization range A. 2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection. 3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection. 4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value. DIMENSIONS A C Unit Model Dimensions (Inches) Refrigerant Connection Service Valve Size A 1 B C Liquid Vapor 036 19 35 23 3/4 048 27 37 27 3/8 7/8 060 39 37 27 1. Including Fan guard. B 2 Unitary Products Group
261647-UTG-C-0108 Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 Phase Outdoor Unit AC036X10(3,4)1 AC048X10(3,4)1 AC060X10(3,4)1 Unit Orifice (s) 1 67, 71, 73 81 90 Factory R-22 Charge, lbs-oz 3-15 7-5 9-15 Unit Orifice (s) 2,3 Additional Charge, Oz FC/MC/PC/UC36 61 + 3 FC/MC/PC/UC42 FC/MC/PC/UC48 81 + 15 FC/MC/PC/UC60 90 + 5 AHP18 AHP24 AHP36 75 + 11 AHP42 75 + 11 AHP48 81 + 20 AHP60 90 + 5 F*FP036 61 + 5 F*FP042 F*FP045 F5FP048 81 + 15 F5FP060 90 + 5 FOOTNOTES: 1. These orifices are packed in the Customer packet of each outdoor unit. 2. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224. 3. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications. PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above. 4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set. Unitary Products Group 3
261647-UTG-C-0108 COOLING CAPACITY - With Air Handler Coils AIR HANDLER UNIT ELECTRIC MODEL MODEL HEAT KW 2 COIL MODEL 1 1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number. 2. Single phase units require single phase 2HK heaters. = Not applicable. COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils FURNACE** COOLING COIL UNIT MODEL CFM RANGE MODEL RATED NET MBH W (MIN.-MAX.) CFM TOTAL SENS. W 3 PH 10 SEER AC WITH MA RATED CFM TOTAL COOLING NET MBH MA12B 10 17 FC/MC30B 1200 33.6 24.9 10.00 9.10 AC036X10(3,4)1 MA12B 10 17 FC/MC36B 1200 33.8 25.0 10.00 9.20 MA12B 10 17 FC/MC42B 1200 34.4 25.5 10.15 9.30 MA16C 10,15,18 21 FC/MC42C 1500 44.5 32.9 10.00 9.15 MA16C 10,15,18 21 FC/MC48C 1600 46.0 34.0 10.10 9.50 AC048X10(3,4)1 MA20D 10,15,18,20 24 FC/MC48D 1600 46.0 34.0 10.10 9.50 MA16C 10,15,18 21 FC60C 1600 47.0 34.0 10.40 9.70 MA20D 10,15,18,20 24 FC/MC60D 1600 47.0 34.0 10.40 9.70 AC060X10(3,4)1 MA20D 10,15,18,20 24 FC/MC60D 1750 58.5 39.8 10.00 10.25 3 PH 10 SEER AC WITH AHP/SHP AHP36 5,8,10,15,18 17 1235 35.0 24.2 10.30 11.00 AC036X10(3,4)1 F*FP036 5,8,10,15,19 24 1200 34.4 35.2 10.20 9.30 F*FP042 5,8,10,15 21 1200 34.4 25.2 10.15 9.20 AHP/SHP48 5,8,10,15,20 24 1600 47.0 34.4 10.40 9.70 AC048X10(3,4)1 AHP/SHP60 5,8,10,15,20,25 24 1600 47.0 34.4 10.40 9.70 F5FP048 5,8,10,15,20,25 24 1600 45.5 33.7 10.00 9.15 F5FP060 5,8,10,15,20,25 24 1600 46.5 34.4 10.00 9.70 AC060X10(3,4)1 AHP/SHP60 5,8,10,15,20,25 24 1750 58.5 39.8 10.00 9.80 F5FP060 5,8,10,15,20,25 24 1750 58.5 39.8 10.00 9.80 Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 80 F entering air temperature, 50% RH, and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTU s at 95 F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. AC036X10(3,4)1 AC048X10(3,4)1 AC060X10(3,4)1 1050 1350 1400 1800 1525 1975 SENS. SEER 1 SEER 17 FC/MC/PC/UC30B 1200 33.6 24.9 10.00 9.10 17 FC/MC/PC/UC36B 1200 33.8 25.0 10.00 9.20 17 FC/MC/PC/UC42B 1200 34.4 25.5 10.15 9.30 14 HC30 1200 33.8 25.0 10.00 9.20 17 HC36 1200 34.4 25.5 10.15 9.30 HD36 1200 34.8 25.8 10.00 8.95 21 FC/MC/PC/UC42C 1500 44.5 32.9 10.00 9.15 21 FC/MC/PC/UC48C 1600 46.0 34.0 10.10 9.50 24 FC/MC/PC/UC48D 1600 46.0 34.0 10.10 9.50 21 FC/MC/PC/UC60C 1600 47.0 34.0 10.40 9.70 24 FC/MC/PC/UC60D 1600 47.0 34.0 10.40 9.70 21 HC48 1600 45.5 33.7 10.00 9.45 24 HC60 1600 47.0 34.0 10.40 9.70 HD36 1600 45.5 33.7 10.00 9.50 HD48 1600 46.5 34.4 10.20 9.65 24 FC/MC/PC/UC60D 1750 58.5 39.8 10.00 10.25 24 HC60 1750 58.5 39.8 10.00 10.25 HD48 1750 58.5 39.8 10.00 10.25 1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up. EER EER 4 Unitary Products Group
ACCESSORIES *Refer to Price Manual for specific model numbers. HARD START KIT - Provides increased starting torque for areas with low voltage. COMPRESSOR BLANKET - Designed to further reduce the normal compressor operating sound. Refer to price pages for specific match-ups. OFF CYCLE TIMER DELAY - Provides a 5-minute off cycle to prevent rapid recycling of the compressor. ROOM THERMOSTATS - A wide selection of compatible thermostats are available to provide optimum performance and features for any installation. 1H/1C, manual change-over electronic non-programmable thermostat. 1H/1C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat. 1H/1C, auto/manual changeover, electronic programmable. * For the most current accessory information, refer to the price book or consult factory. 261647-UTG-C-0108 SOUND POWER RATINGS* UNIT MODEL (dba) 036 82 048 82 060 80 * Rated in accordance with ARI 270-95 Standards. TYPICAL INSTALLATION 60 OVERHEAD CLEARANCE 10 CLEARANCE COIL AREA MINIMUM 24 SERVICE ACCESS CLEARANCE ON ONE SIDE WEATHERPROOF DISCONNECT SWITCH THERMOSTAT TO FURNACE OR AIR HANDLER TERMINAL BLOCK NEC CLASS 1 WIRING NEC CLASS 2 WIRING TO INDOOR COIL NOTE: ALL OUTDOOR WIRING MUST BE WEATHERPROOF. SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT CONTROL ACCESS PANEL TYPICAL FIELD WIRING - 3 Phase Application ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES POWER WIRING 208/230-3-60 460-3-60 24 VOLT CONTROL WIRING MINIMUM 18 GA. WIRE (NEC CLASS 2) POWER WIRING CONTROL WIRING FACTORY WIRING FURNACE OR AIR HANDLER TERMINAL BLOCK GND. LUG CONTACTOR TERMINALS COIL * TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT. C Y R G W * Y R G W CONDENSING UNIT ROOM THERMOSTAT ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY. Unitary Products Group 5
261647-UTG-C-0108 COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. AC036X10(3,4)1 INDOOR COIL MODEL NO. FC/MC/PC/UC30 CONDENSER ID CFM 1150 1250 1350 ENTERING AIR ID DB ( F) 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB ( F) 72 67 57 72 67 57 72 67 57 T.C. 38.3 36.1 34.4 37.9 36.3 34.6 38.0 36.4 34.9 75 S.C. 24.0 23.7 24.0 24.1 24.5 24.7 24.7 25.3 25.2 K.W 3.19 3.14 3.09 3.23 3.20 3.14 3.26 3.23 3.18 T.C. 36.9 34.6 32.2 36.9 34.9 32.6 37.0 35.2 33.0 85 S.C. 24.2 23.7 22.9 24.7 24.6 23.9 25.3 25.5 24.8 K.W 3.45 3.39 3.30 3.50 3.44 3.36 3.53 3.49 3.40 T.C. 35.5 33.2 30.0 35.8 33.6 30.4 36.0 34.0 31.0 95 S.C. 24.3 23.6 21.9 25.4 24.9 23.6 26.0 25.6 24.4 K.W 3.71 3.63 3.52 3.76 3.69 3.58 3.80 3.75 3.62 T.C. 33.2 30.4 26.7 33.4 30.8 27.2 33.6 31.3 27.7 105 S.C. 23.7 22.5 20.7 24.5 23.6 21.9 25.4 24.6 23.0 K.W 3.97 3.84 3.71 4.02 3.91 3.77 4.06 3.96 3.81 T.C. 31.0 27.6 23.5 31.1 28.2 24.2 31.3 28.5 24.4 115 S.C. 23.1 21.3 19.6 23.9 22.6 20.7 24.8 23.7 21.6 K.W 4.22 4.06 3.90 4.29 4.13 3.94 4.33 4.18 4.00 T.C. 28.7 24.8 20.2 28.9 25.6 21.1 29.0 25.7 21.0 125 S.C. 22.5 20.2 18.4 23.2 21.6 19.6 24.2 22.7 20.2 K.W 4.47 4.28 4.09 4.56 4.35 4.11 4.60 4.40 4.19 NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature. Air Handler Coil T.C. S.C. KW MA12B FC / MC30B 1.00 1.00 1.00 MA12B FC / MC36B 1.01 1.00 0.99 MA12B FC / MC42B 1.02 1.02 0.98 AHP36 1.04 0.97 0.83 F*FP036 1.02 1.41 0.98 F*FP042 1.02 1.01 0.99 FC/MC/PC/UC30B 1.00 1.00 1.00 FC/MC/PC/UC36B 1.01 1.00 0.99 FC/MC/PC/UC42B 1.02 1.02 0.98 HC30 1.01 1.00 0.99 HC36 1.02 1.02 0.98 HD24 1.02 1.02 1.02 HD36 1.04 1.04 1.02 6 Unitary Products Group
COOLING PERFORMANCE DATA Multipliers for determining the performance with other indoor sections. 261647-UTG-C-0108 AIR CONDITIONER MODEL NO. AC048X10(3,4)1 INDOOR COIL MODEL NO. FC/MC/PC/UC42 CONDENSER ID CFM 1200 1400 1600 ENTERING AIR ID DB ( F) 85 80 75 70 85 80 75 70 85 80 75 70 TEMPERATURE ID WB ( F) 72 67 62 57 72 67 62 57 72 67 62 57 T.C. 53.4 48.9 45.1 40.2 54.3 49.8 45.9 41.3 54.9 50.3 46.4 41.8 75 S.C. 32.2 32.3 31.0 32.5 34.0 34.0 32.7 34.7 35.2 35.3 33.9 35.9 K.W 4.32 4.15 4.00 3.83 4.44 4.26 4.11 3.95 4.53 4.36 4.21 4.04 T.C. 52.0 47.5 43.7 39.2 52.7 48.3 44.5 40.0 53.2 48.7 45.2 40.5 85 S.C. 32.2 32.3 31.1 32.7 34.1 34.1 32.8 34.7 35.4 35.5 34.5 36.0 K.W 4.62 4.43 4.26 4.07 4.74 4.55 4.38 4.18 4.84 4.65 4.48 4.28 T.C. 49.0 44.9 41.3 36.9 49.6 45.5 42.0 37.6 50.0 45.8 42.4 38.3 95 S.C. 31.6 31.6 30.4 31.8 33.5 33.7 32.4 33.8 34.9 35.0 33.7 35.6 K.W 4.91 4.70 4.51 4.31 5.02 4.81 4.64 4.43 5.13 4.92 4.74 4.53 T.C. 45.6 41.6 38.4 34.3 46.0 42.2 39.0 35.0 46.2 42.5 39.3 36.2 105 S.C. 30.5 30.6 29.5 30.9 32.6 32.8 31.5 32.8 34.1 34.2 32.7 34.5 K.W 5.18 4.96 4.76 4.54 5.30 5.07 4.88 4.67 5.39 5.18 4.99 4.83 T.C. 41.8 38.3 35.3 31.7 42.3 38.8 35.8 33.0 42.5 39.0 36.2 33.5 115 S.C. 29.3 29.5 28.2 29.6 31.6 31.4 30.1 31.5 33.0 32.9 31.5 32.0 K.W 5.42 5.18 4.98 4.76 5.52 5.31 5.10 4.94 5.63 5.41 5.21 5.06 T.C. 38.0 35.0 32.3 29.1 38.6 35.4 32.7 31.0 38.8 35.5 33.2 30.8 125 S.C. 28.1 28.4 26.9 28.3 30.6 30.0 28.7 30.2 31.9 31.6 30.4 29.5 K.W 5.66 5.40 5.20 4.98 5.74 5.55 5.32 5.21 5.87 5.64 5.43 5.29 NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature. Air Handler Coil T.C. S.C. KW MA16C FC / MC42C 0.97 0.97 1.04 MA16C FC / MC48C 1.00 1.00 1.00 MA20D FC / MC48D 1.00 1.00 1.00 MA20D FC / MC60D 1.02 1.00 0.98 MA16C FC60C 1.02 1.00 0.98 AHP / SHP48 1.02 1.01 0.98 AHP / SHP60 1.02 1.01 0.98 F5FP048 0.99 0.99 1.04 F5FP060 1.01 1.01 0.98 FC/MC/PC/UC42C 0.97 0.97 1.04 FC/MC/PC/UC48C 1.00 1.00 1.00 FC/MC/PC/UC48D 1.00 1.00 1.00 FC/MC/PC/UC60C 1.02 1.00 0.98 FC/MC/PC/UC60D 1.02 1.00 0.98 HC48 0.99 0.99 1.01 HC60 1.02 1.00 0.98 HD36 0.99 0.99 1.00 HD48 1.01 1.01 0.98 Unitary Products Group 7
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. AC060X10(3,4)1 INDOOR COIL MODEL NO. FC/MC/PC/UC60 CONDENSER ID CFM 1450 1700 1950 ENTERING AIR ID DB ( F) 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB ( F) 72 67 57 72 67 57 72 67 57 T.C. 61.2 58.5 56.3 61.8 59.1 56.9 62.3 59.6 57.5 75 S.C. 37.6 37.4 37.1 40.1 39.9 39.5 42.5 42.3 41.8 K.W 4.66 4.57 4.51 4.67 4.58 4.53 4.68 4.58 4.55 T.C. 60.6 58.0 55.0 61.2 58.6 55.8 61.9 59.3 56.7 85 S.C. 37.6 37.3 36.5 40.2 39.9 39.1 42.8 42.5 41.7 K.W 5.26 5.13 5.08 5.27 5.14 5.10 5.28 5.15 5.11 T.C. 60.0 57.4 53.7 60.7 58.5 54.8 61.4 59.0 55.8 95 S.C. 37.5 37.1 35.9 40.3 39.8 38.8 43.1 42.6 41.6 K.W 5.86 5.70 5.65 5.87 5.71 5.67 5.88 5.72 5.68 T.C. 58.1 54.6 50.0 58.9 55.7 51.3 59.7 56.8 52.7 105 S.C. 36.9 36.0 34.4 39.8 39.0 37.3 42.7 41.9 40.2 K.W 6.54 6.39 6.29 6.56 6.42 6.30 6.57 6.45 6.32 T.C. 56.2 51.8 46.3 57.1 53.2 47.9 57.9 54.5 49.5 115 S.C. 36.2 34.9 32.9 39.3 38.1 35.9 42.3 41.2 38.8 K.W 7.23 7.07 6.92 7.25 7.12 6.94 7.26 7.17 6.97 T.C. 54.3 49.0 42.6 55.2 50.6 44.5 56.2 52.3 46.4 125 S.C. 35.6 33.8 31.4 38.7 37.2 34.4 41.9 40.5 37.4 K.W 7.92 7.76 7.55 7.94 7.83 7.58 7.96 7.90 7.62 Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature. Air Handler Coil T.C. S.C. KW MA20D FC / MC60D 1.00 1.00 1.00 AHP / SHP60 1.01 1.02 1.02 F5FP060 1.00 1.02 1.02 HC60 1.00 1.00 1.00 HD48 0.99 1.00 1.02 Subject to change without notice. Printed in U.S.A. 261647-UTG-C-0108 Copyright by Unitary Products Group 2008. All rights reserved. Supersedes: 261647-UTG-B-0108 Unitary 5005 Norman Products York OK Group Drive 73069