standard response elo upright and pendent sprinklers (storage-density/area)

Similar documents
TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

standard response elo upright sprinkler

TECHNICAL DATA OBSOLETE

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

quick response horizontal sidewall sprinkler vk360 (K8.0)

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

micromatic Standard response Horizontal Sidewall sprinkler

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

TECHNICAL DATA. Page 1 of 6

micromatic standard response stainless steel sprinklers

standard/quick response extended coverage light and ordinary hazard elo sprinklers

microfast and microfasthp quick conventional sprinklers

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

micromatic Standard response Horizontal Sidewall sprinkler

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

micromatic standard response Upright sprinkler VK100 (K5.6)

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

MICROMATIC STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK104 (K5.6) TECHNICAL DATA

quick response Sprinkler 105a October 25, 2010

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

standard response Fusible Link Upright sprinkler VK204 (K8.0)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

microfast quick response Pendent sprinkler VK302 (K5.6)

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

microfast quick response extended coverage hsw sprinkler vk606

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

Microfast quick response Fusible element hsw sprinkler

standard response fusible link sidewall sprinkler VK112 (K5.6)

standard response dry horizontal sidewall sprinklers

microfast sr/qr extended coverage pendent sprinkler

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

standard response large orifice dry

standard response/ quick response extended coverage

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Pip Cap: Brass UNS-C31400 or UNS-C31600

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

MicrofastHP EC/QREC FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK611 (K5.6) TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

freedom residential horizontal sidewall sprinkler Vk450 (k4.2)

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

STANDARD/quick. Sprinkler 42o. August 8, 2011

DRY VERTICAL SIDEWALL SPRINKLERS TECHNICAL DATA

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

TECHNICAL DATA vk470 (K3.0)

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

TECHNICAL DATA. 2. LISTINGS AND APPROVALS NOTE: Viking Dry Vertical Sidewall Sprinklers are NOT listed or approved. Sprinkler 103a.

freedom residential pendent sprinkler vk466 (K5.2)

TECHNICAL DATA OBSOLETE

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

TECHNICAL DATA. Page 1 of 5

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

TECHNICAL DATA OBSOLETE

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

December 14, 2015 Page 1 of 7 TECHNICAL DATA

Transcription:

December 5, 2008 Sprinkler 13e 1. DESCRIPTION The Viking Standard Response ELO Upright and Pendent Sprinklers are thermosensitive glass bulb spray sprinklers available in several different finishes and temperature ratings to meet design requirements. The special Polyester and Teflon coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive atmospheres and are culus listed as corrosion resistant as indicated in the Approval Chart. (Note: FM Global has no approval classification for Teflon and Polyester coatings as corrosion resistant.) The extra-large orifice provides greater flows at lower pressures than standard orifice or large orifice sprinklers. This feature allows reduced pipe sizing for hydraulically calculated sprinkler systems, which require high densities of water. Viking Standard Upright Pendent Response Extra-Large Orifice Sprinklers may eliminate the need for a fire pump or reduce the size of the pump if it is required. On existing systems, replacing large orifice sprinklers with extra-large orifice sprinklers may provide the higher densities required to allow an increase in the hazard classification of an occupancy. Viking sprinklers may be ordered and/or used as open sprinklers (glass bulb and pip cap assembly removed) on deluge systems. Refer to Ordering Instructions on page 13f. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA 89-92-E, Volume 3 NOTE: Upright Sprinkler VK530 and Pendent Sprinkler VK536 are Listed and Approved as Specific Application Sprinklers as indicated in Design Criteria on page 13h. Refer the Approval Chart on page 13g and Design Criteria on page 13h for culus Listing and FM Approval requirements that must be followed. 3. technical data Viking Technical Data may be found on Specifications: Available since 1992. The Viking Corporation s Web site at Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to http://www.vikinggroupinc.com. 500 psi (34.5 bar). The Web site may include a more recent Thread size: 3/4 NPT or 20 mm BSP edition of this Technical Data Page. Nominal K-Factor: 11.2 U.S. (161.3 metric*) *Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to -65 F (-55 C) Overall Length: 2-5/16 (58.7 mm) Material Standards: Sprinkler Frame: Brass UNS-C84400 Deflector: Brass UNS-C26000 Bulb: Glass, nominal 5 mm diameter Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Compression Screw: Brass UNS-C36000 Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape For Teflon Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order Standard Response Extra-Large Orifice Upright and Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Form No. F_010692 Replaces page 13e-i dated April 4, 2008. (Added FM Approval for Sprinkler VK536.)

Sprinkler 13f December 5, 2008 Finish Suffix: Brass = A, Chrome-Enloy = F, White Polyester = M-/W, Black Polyester = M-/B, Black Teflon = N, Wax Coated = C Temperature Suffix ( F/ C): 155 /68 = B, 175 /79 = D, 200 /93 = E, 286 /141 = G, OPEN = Z (Teflon only). For example, sprinkler VK530 with a Brass finish and a 155 F/68 C temperature rating = Part No. 09679AB Available Finishes And Temperature Ratings: Refer to Table 1 Accessories: (Also refer to the Sprinkler Accessories section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 05118CW/B (available since 1981). B. Wrench for recessed pendent and/or coated sprinklers: Part No. 11663W/B** (available since 2001) **A ½ ratchet is required (not available from Viking). Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. Installation Refer to appropriate NFPA Installation Standards. 5. Operation During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the glass bulb expands, causing the bulb to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. inspections, tests and maintenance Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. availability Viking Standard Response Extra-Large Orifice Upright and Pendent Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. Guarantee For details of warranty, refer to Viking s current list price schedule or contact Viking directly. Figure 1: Upright Sprinkler VK530 and Wrench 05118CW/B

December 5, 2008 Sprinkler Temperature Classification TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Nominal Temperature Rating 1 Maximum Ambient Ceiling Temperature 2 Bulb Color Ordinary 155 F (68 C) 100 F (38 C) Red Intermediate 175 F (79 C) 150 F (65 C) Yellow Intermediate 200 F (93 C) 150 F (65 C) Green High 286 F (141 C) 225 F (107 C) Blue Sprinkler Finishes: Brass, Chrome-Enloy, White Polyester, Black Polyester, and Black Teflon Corrosion-Resistant Coatings 3 : White Polyester, Black Polyester, and Black Teflon in all temperature ratings. Wax-Coated Brass for sprinklers with the following temperature ratings: 155 F (68 C) Lt. Brown Wax 175 F (79 C) Brown Wax 200 F (93 C) Brown Wax 286 F (141 C) Dk. Brown Wax 4 1 The sprinkler temperature rating is stamped on the deflector. Footnotes Sprinker 13g 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on page 13g. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and Teflon coatings. For Teflon coated open sprinklers only, the waterway is coated. 4 Wax melting point is 170 F (76 C) for 286 F (141 C) temperature rated sprinklers. Base Part Number 1 SIN Sprinkler Style Approval Chart Standard Response Extra-Large Orifice Upright and Pendent Sprinklers Thread Size Maximum 175 PSI (12 Bar) WWP Nominal K-Factor Overall Length Listings and Approvals 3 (Refer also to Design Criteria on pg 13h.) NPT BSP U.S. metric 2 Inches mm culus 4 FM NYC 6 09679 VK530 Upright 3/4 -- 11.2 161.3 2-5/16 58.7 A5, B3, C4 B2 -- 14819 VK530 Upright -- 20 mm 11.2 161.3 2-5/16 58.7 A5, B3, C4 B2 -- 07961 VK536 Pendent 3/4 -- 11.2 161.3 2-5/16 58.7 B3Y, C3Z, C4Y B1X B3Y, C3Z, C4Y 14820 VK536 Pendent -- 20 mm 11.2 161.3 2-5/16 58.7 B3Y, C3Z, C4Y B1X -- Approved Temperature Ratings A - 286 F (141 C) B - 155 F (68 C), 175 F (79 C), 200 F (93 C), and 286 F (141 C) C - 155 F (68 C), 175 F (79 C), and 200 F (93 C) Approved Finishes 1 - Brass 2 - Brass and Chrome-Enloy 3 - Brass, Chrome-Enloy, White Polyester 5, Black Polyester 5, and Black Teflon 5 4 - Wax-Coated Brass (corrosion resistant) 5 - Brass with 200 F (93 C) Wax Coating (corrosion resistant); Maximum ambient ceiling temperature = 150 F (65 C). Footnotes 1 Base part number shown. For complete part number, refer to Viking s current price schedule. Escutcheons X - Standard surface-mounted escutcheons Y - Standard surface-mounted escutcheons or the Microfast Model F-1 Adjustable Escutcheon Z - Standard surface-mounted escutcheons or the Microfast Model F-1 Adjustable Escutcheon, or recessed with the Micromatic Model E-1 or E-2 Recessed Escutcheon 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 culus Listed as corrosion-resistant. 6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 3.

Sprinkler 13h December 5, 2008 culus Listing Requirements: DESIGN CRITERIA (Also refer to the Approval Chart on page 13g.) Standard Response Extra-Large Orifice Upright Sprinkler VK530 and Pendent Sprinkler VK536 are culus Listed for installation in accordance with the latest edition of NFPA 13 for standard upright and pendent spray sprinklers: Designed for use in hazard occupancies up to and including Extra-Hazard Group II with a minimum operating pressure of 7 psi (0.5 bar). Sprinklers VK530 and VK536 are also culus Listed for use in High-Piled Storage Occupancies as defined in NFPA 13 with a minimum operating pressure of 7 psi (0.5 bar). The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray upright and must be followed. FM Approval Requirements: Standard Response Extra-Large Orifice Upright Sprinkler VK530 and Pendent Sprinkler VK536 are FM Approved as control mode density/area (CMDA) sprinklers for use in Ordinary and Extra-Hazard Occupancies, as well as High-Piled Storage Occupancies with a minimum operating pressure of 10 PSI (0.7 bar). Refer to the latest applicable FM Loss Prevention Data Sheets (including 2-8N and 8-9) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from culus and/or NFPA criteria. Also: When acceptable to the Authority Having Jurisdiction, Viking Standard Response Extra-Large Orifice Sprinklers VK530 and VK536 may be used as specific-application heads with a density of.6/2000 ft. 2 for wet systems or.6/2600 ft. 2 for dry systems to protect single-, double-, multiple-row, and portable rack storage of Class I-IV, Group A and B Plastics, cartoned, expanded or unexpanded, as well as exposed unexpanded when the following conditions are met: A maximum storage height of 20 ft. (6.1 m). A maximum ceiling height of 25 ft. (7.6 m). A 36-inch (914 mm) minimum clearance from the deflector to the top of storage. Otherwise, design to the appropriate density/area requirements. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to pages SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Figure 2: Wrench 11663W/B for Coated and/or Recessed Pendent ELO Sprinklers

December 5, 2008 Sprinker 13i Figure 3: Sprinkler Dimensions Figure 4: Pendent Sprinkler VK536 Dimensions with the Model F-1, Model E-1 and E-2 Recessed Escutcheons

THIS PAGE INTENTIONALLY LEFT BLANK Form No. F_010692 Replaces page 13e-i dated April 4, 2008. (Added FM Approval for Sprinkler VK536.)