A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION FIRE ALARM SYSTEM PART 1 GENERAL

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.

New Auburn University Veterinary Facility Gulf Shores, AL

C. All control equipment must have transient protection devices to comply with UL864 requirements.

1.3 REFERENCE STANDARDS

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

The following information shall become and form part of the contract documents.

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices.

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Functional Performance Test

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

FIRE & LIFE SAFTEY STANDARD

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

SECTION ADDRESSABLE FIRE ALARM SYSTEM

COLUMBIA PUBLIC SCHOOLS HVAC IMPROVEMENTS - PHASE COLUMBIA, MISSOURI

SECTION FIRE ALARM SYSTEMS

SECTION FIRE DETECTION AND ALARM

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

IN2 Digital, Addressable Fire-alarm System

NFPA 72 Code Changes vs 2013

SECTION INTRUSION DETECTION

Bold items are particular to the City of Euless

SECTION HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL)

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

Florida Building Code 2010

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

TECHNICAL DATA OBSOLETE

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

Fire Alarm System Fundamentals

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Changes in NFPA

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

HARRIS COUNTY HOUSING AUTHORITY

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

CONTENTS AUTOMATIC TRANSFER SWITCHES

Full Service Central Station Fire Alarm Listing Evaluation

DONALD H. BERG, ARCHITECT

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION AUTOMATIC TRANSFER SWITCHES

Chapter 4: Fire Protection Systems

FMR Installation Instructions. Addressable Fire System Controller

SECTION FIRE DETECTION AND ALARM

UNIFIED FACILITIES GUIDE SPECIFICATIONS

DESIGN & CONSTRUCTION GUIDELINES

OKLAHOMA STATE UNIVERSITY

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

INSPECTION AND TESTING FORM

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E

Voice Annunicated Fire Alarm System Page 1 of 26

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

SECTION CLEAN AGENT FIRE SUPPRESSION SYSTEMS

SECTION SECURITY TESTING AND COMMISSIONING

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

IN2 Lighting Control Devices

30.45 Electric Release PDRP-2001

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

SECTION GENERATOR PARALLELING CONTROLS

SECTION LIGHTING CONTROL DEVICES

LIGHTING CONTROL DEVICES

Transcription:

SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.02 SUMMARY This Section includes fire alarm systems, including manual stations, detectors, signal equipment, controls, and devices. Related Sections: The following Sections contain requirements that relate to this Section: 1. Division 15 Section "Fire Protection" for water-flow, pressure, or tamper switches connected to fire alarm system. 1.03 DEFINITIONS E. F. Alarm-Initiating Device: A manual station, smoke detector, heat detector, or sprinkler waterflow switch. Alarm Signal: Signifies a state of emergency requiring immediate action. Pertains to signals such as the operation of a manual station and the operation of a sprinkler system flow switch. Class B Wiring: Circuits electrically supervised such that a single break or a single ground fault condition will be indicated by a trouble signal at the FACP no matter where the break or ground fault condition occurs. Analog/Addressable System: Alarm, supervisory, and initiating devices directly connected, through the use of multiplexing circuits or devices. Supervisory Signal: Indicates abnormal status or need for action regarding fire suppression or other protective system. Trouble Signal: Indicates that a fault, such as an open circuit or ground, has occurred in the system. 1.04 SYSTEM DESCRIPTION General: Complete, analog/addressable, noncoded fire detection and alarm system with manual and automatic alarm initiation. General: Zoned, noncoded, addressable, microprocessor-based fire detection and alrm system with manual and automatic alarm initiation, analog addressable smoke detectors, and automatic alarm verification for alarms initiated by certain msoke detector zones as indicated. Audible Alarm Indication: By sounding of horns and bells. Functional Description: The following are required system functions and operating features: PWA 201130 28 3100/1

1. Priority of Signals: Accomplish automatic response functions by the first point initiated. Alarm functions resulting from initiation by the first point are not altered by subsequent alarms. The highest priority is an alarm signal. Supervisory and trouble signals have second- and third-level priority. Signals of a higher-level priority take precedence over signals of lower priority even though the lower-priority condition occurred first. Annunciate all alarm signals regardless of priority or order received. 2. Noninterfering: Zone, power, wire, and supervise the system so a signal on one point does not prevent the receipt of signals from any other point. All points are manually resettable from the FACP after the initiating device or devices are restored to normal. Systems that require the use of batteries or battery backup for the programming function are not acceptable. 3. Signal Initiation: The manual or automatic operation of an alarm-initiating or supervisory-operating device causes the FACP to transmit an appropriate signal including: a. General alarm. b. Fire-suppression system operation alarm. c. Smoke detector alarm. d. Valve tamper supervisory. e. System trouble. 4. Transmission to Central Station: Automatically route alarm, supervisory, and trouble signals to Owner's central system, using listed and approved equipment. The dialer shall be part of the fire alarm panel such that the exact device in alarm shall be reported to the central station. 5. Silencing at FACP: Switches provide capability for acknowledgment of alarm; supervisory, trouble, and other specified signals at the FACP; and capability to silence the local audible signal and light a light-emitting diode (LED). Subsequent point alarms cause the audible signal to sound again until silenced in turn by switch operation. Restoration to normal of alarm, supervisory, and trouble conditions extinguish the associated LED and cause the audible signal to sound again until the restoration is acknowledged by switch operation. 6. Loss of primary power at the FACP sounds trouble signal at the FACP and indicates at the FACP when the system is operating on an alternate power supply. 7. Loss of primary power at the FACP sounds trouble signal at the FACP and the annunciator. An emergency power light is illuminated at both locations when the system is operating on an alternate power supply. 8. Annunciation: Manual and automatic operation of alarm- and supervisory-initiating devices is annunciated both on the FACP and on the annunciator, indicating the location and type device. 9. FACP Alphanumeric Display: Displays plain-language description of alarms, trouble signals, supervisory signals, monitoring actions, system and component status, and system commands. Display shall consist of 80 characters. 10. General Alarm: A system general alarm includes: a. Indicating the general alarm condition at the FACP and activate the existing panel. b. Identifying the device that is the source of the alarm at the FACP. c. Initiating audible and visible alarm signals throughout the building. d. Initiating transmission of alarm signal to the central station. 11. Manual station, waterflow, smoke detector or heat detector alarm operation initiates a general alarm. 12. Sprinkler valve tamper switch operation causes or initiates the following: PWA 201130 28 3100/2

a. A supervisory audible and visible "valve tamper" signal indication at FACP and annunciator. b. The location label for the device that has operated. c. Recordong of event on event log. d. Transmission of supervisory signal to central station. 1.05 E. F. G. H. I. 1.06 SUBMITTALS General: Submit the following according to Conditions of Contract and Division 1 Specification Sections. Product data for system components. Include dimensioned plans and elevations showing minimum clearances and installed features and devices. Include list of materials and NRTL Iisting data. Wiring diagrams from manufacturer differentiating between factory- and field-installed wiring. Include diagrams for equipment and for system with all terminals and interconnections identified. Indicate components for both field and factory wiring. System operation description covering this specific Project including method of operation and supervision of each type of circuit and sequence of operations for all manually and automatically initiated system inputs and outputs. Manufacturer's standard descriptions for generic systems are not acceptable. Operating instructions for mounting at the FACP. Operation and maintenance data for inclusion in Operating and Maintenance Manual specified in Division 1. Include data for each type product, including all features and operating sequences, both automatic and manual. Include recommendations for spare parts to be stocked at the site. Provide the names, addresses, and telephone numbers of service organizations that carry stock of repair parts for the system to be furnished. Product certification signed by the manufacturer of the fire alarm system components certifying that their products comply with indicated requirements. Submission to Authority Having Jurisdiction: In addition to routine submission of the above material, make an identical submission to the authority having jurisdiction. Include copies of annotated Contract Drawings as required to depict component locations to facilitate review. Upon receipt of comments from the Authority, submit them for review. Make resubmissions if required to make clarifications or revisions to obtain approval. Record of field tests of system. QUALITY ASSURANCE Installer Qualifications: A factory-authorized Installer is to perform the Work of this Section. Compliance With Local Requirements: Comply with the applicable building code, local ordinances, and regulations, and the requirements of the authority having jurisdiction. Comply with NFPA 70, "National Electrical Code." NFPA Compliance: Provide fire alarm and detection systems conforming to the requirements of the following publications: PWA 201130 28 3100/3

1. NFPA 72, "Installation, Maintenance, and Use of Protective Signaling Systems." 2. NFPA 72E, "Automatic Fire Detectors." 3. NFPA 72G, "Guide for the Installation, Maintenance and Use of Notification Appliances for Protective Signaling Systems." E. NRTL Listing: Provide systems and equipment that are listed and labeled. 1. Terms "Listed" and "Labeled": As defined in the "National Electrical Code," Article 100. F. Single-Source Responsibility: Obtain fire alarm components from a single source who assumes responsibility for compatibility for system components. PART 2 - PRODUCTS 2.01 MANUFACTURERS Manufacturers: following: Subject to compliance with requirements, provide products by one of the 1. Cerberus Pyrotronics. 2. Fire Controllnstuments, Inc.. 3. Gamewell. 4. Notifier. 5. Simplex Time Recorder Co. 2.02 ADDRESSABLE DEVICES Alarm-Initiating Devices: Classified as addressable devices according to NFPA 72. 1. Communication Transmitter and Receiver: Integral to device. Provides each device with a unique identification and capability for status reporting to the FACP. 2. External Addressable Interface Unit: May be used where specified devices are not manufactured and labeled with integral multiplex transmitter and receiver. Arrange to monitor status of each device individually. 2.03 MANUAL PULL STATIONS Description: Double-action type, fabricated of metal or plastic, and finished in red with molded, raised-letter operating instructions of contrasting color. Stations requiring the breaking of a glass panel are not acceptable. Stations requiring the breaking of a concealed glass rod may be provided. Station Reset: Key-operated, switch-rated for the voltage and current at which it operates. Stations have screw terminals for connections. Key shall be keyed alike with Fire Alarm Contorl Panel. 2.04 SMOKE DETECTORS General: Comply with UL 268, "Smoke Detectors for Fire Protective Signaling Systems." Include the following features: 1. Factory Nameplate: Serial number and type identification. 2. Operating Voltage: 24-V d.c., nominal. 3. Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore them to normal operation. PWA 201130 28 3100/4

4. Plug-In Arrangement: Detector and associated encapsulated electronic components are mounted in a module that connects to a fixed base with a twist-locking plug connection. The plug connection requires no springs for secure mounting and contact maintenance. Terminals in the fixed base accept building wiring. 5. Visual Indicator: Connected to indicate detector has operated. Indicator shall flash during "normal" mode. 6. Analong photoelectric type with rotary dial for addressing. 2.05 OTHER DETECTORS Thermal Detector: Combination fixed-temperature and rate-of-rise unit with mounting plate arranged for outlet box mounting; 135-deg F fixed-temperature setting except as indicated. 2.06 ALARM-INDICATING DEVICES General: Equip alarm-indicating devices for mounting as indicated. Provide terminal blocks for system connections. All devices to comply with the requirements of ADA and UL 1971. Fire Alarm Horns: Electric-vibrating polarized type, operating on 24-V d.c., with provision for housing the operating mechanism behind a grille. Horns produce a sound pressure level of 87 db, measured 10 feet from the source. Visual Alarm Devices: 24-V d.c. strobe lights with clear polycarbonate lens and xenon flash tube. Mount lenses on an aluminum face plate. The word "FIRE" is engraved in minimum 1- inch-high letters on the lens. 1. Lamps have a minimum peak intensity of 75 candela. Strobe leads are factoryconnected to screw terminals. 2. Combination devices consist of factory-combined, audible and visual alarm units in a single mounting assembly. 2.07 FIRE ALARM CONTROL PANEL (FACP) E. F. General: Comply with UL 864, "Control Units for Fire-Protective Signaling Systems." Cabinet: Lockable steel enclosure. Arrange panel so all operations required for testing or for normal care and maintenance of the system are performed from the front of the enclosure. If more than a single unit is required to form a complete control panel, provide exactly matching modular unit enclosures. Accommodate all components and allow ample gutter space for interconnection of panels as well as field wiring. Identify each enclosure by an engraved, redlaminated, phenolic resin nameplate. Lettering on the enclosure nameplate shall not be less than 1 inch high. Identify individual components and modules within the cabinets with permanent labels. Systems: Alarm and supervisory systems are separate and independent in the FACP. Construction requiring removal of field wiring for module replacement is not acceptable. Control Modules: Types and capacities required to perform all functions of the fire alarm systems. Local, visible, and audible signals notify of alarm, supervisory, and trouble conditions. Each type of audible alarm has a distinctly different sound. Provide panel with 198 point analog/addressable capability. Resetting: Provide the necessary controls to prevent the resetting of any alarm, supervisory, or trouble signal while the alarm or trouble condition still exists. PWA 201130 28 3100/5

G. Alphanumeric Display and System Controls: Arrange to provide the basic interface between human operator at the FACP and addressable system components, including annunciation and supervision. A display with a minimum of 80 characters shows alarm, supervisory, and component status messages. Arrange keypad for use in entering and executing control commands. Include on both the central fire alarm control panel and the remote annunciator. 2.08 EMERGENCY POWER SUPPLY General: Components include valve-regulated, recombinant lead acid battery, charger, and an automatic transfer switch. Battery nominal life expectancy is 10 years minimum. Battery capacity is adequate to operate the complete alarm system in normal or supervisory (nonalarm) mode for a period of 24 hours. At the end of this period, the battery has sufficient capacity to operate the system, including alarm-indicating devices in either alarm or supervisory mode for a period of 5 minutes. 1. Magnetic door holders are not served by emergency power. Magnetic door holders are released when normal power fails. Battery Charger: Solid-state, fully automatic, variable-charging-rate type. Provide capacity for 150 percent of the connected system load while maintaining the batteries at full charge. In the event batteries are fully discharged, the charger recharges them fully within four hours. Charger output is supervised as part of system power supply supervision. Automatic transfer switch transfers the load to the battery without loss of signals or status indications when normal power fails. 2.09 WIRE Line-Voltage and Low-Voltage Circuits: Solid copper conductors with 600 V-rated insulation. 2.10 TAGS Tags For Identifying Tested Components: Comply with NFPA 72H. PART 3 - EXECUTION 3.01 INSTALLATION, GENERAL Install system according to NFPA Standards referenced in Parts 1 and 2 of this Section. Fire Alarm Power Supply Disconnect: lockable handle or cover. Paint red and label "FIRE ALARM." Provide with 3.02 EQUIPMENT INSTALLATION Manual Pull Stations: Mount semi-flush in recessed back boxes with operating handles 54 inches above finished floor or as indicated. Water-Flow Detectors and Valve Supervisory Switches: station required to be supervised. Connect for each sprinkler valve PWA 201130 28 3100/6

Smoke Detectors: Install ceiling-mounted detectors not less than 4 inches from a side wall to the near edge. Install detectors located on the wall at least 4 inches but not more than 12 inches below the ceiling. For exposed solid joist construction, mount detectors on the bottoms of the joists. On smooth ceilings, install detectors not over 30 feet apart in any direction. Install detectors no closer than 5 feet from air registers. Audible Alarm-Indicating Devices: Install not less than 90 inches above the finished floor nor less than 6 inches below the ceiling. Install bells and horns on flush-mounted back boxes with the device- operating mechanism concealed behind a grille or as indicated. Combine audible and visual alarms at the same location into a single unit. E. Visual Alarm-Indicating Devices: Install adjacent to each alarm bell or alarm horn and not less than 80 inches above the finished floor and at least 6 inches below the ceiling. F. Device Location-Indicating Lights: Locate in the public space immediately adjacent to the device they monitor. G. Fire Alarm Control Panel (FACP): Surface mount with tops of cabinets not more than 6 feet above the finished floor. H. Annunciator: Recess mount with the top of the panel no more than 6 feet above the finished floor. 3.03 WIRING INSTALLATION Wiring Method: Install wiring in metal raceway according to Division 16 Section "Raceways." Conceal raceway except in unfinished spaces and as indicated. Wiring Within Enclosures: Install conductors parallel with or at right angles to the sides and back of the enclosure. Bundle, lace, and train the conductors to terminal points with no excess. Connect conductors that are terminated, spliced, or interrupted in any enclosure associated with the fire alarm system to terminal blocks. Mark each terminal according to the wiring diagrams of the system. Make all connections with approved crimp-on terminal spade lugs, pressure-type terminal blocks, or plug connectors. Cable Taps: Use numbered terminal strips in junction, pull or outlet boxes, cabinets, or equipment enclosures where any circuit tap is made. System Wiring: For the low-voltage portion of the fire alarm system, install No. 16 AWG conductors and 75-deg C insulation in wet, damp, or dry locations. For line-voltage wiring, install No. 12 AWG size with insulation rated 75 deg C minimum. E. Color Coding: Color-code fire alarm conductors differently from the normal building power wiring. Use one color code for alarm circuits wiring and a different color code for supervisory circuits. Color-code audible alarm-indicating circuits differently from alarm-initiating circuits. Use different colors for visual alarm-indicating devices. Paint fire alarm system junction boxes and covers red. F. Risers: Install at least 2 vertical cable risers to serve the fire alarm system. Separate risers in close proximity to each other with a minimum one-hour-rated wall, so the loss of one riser does not prevent the receipt or transmission of signal from other floors or zones. G. Wiring to Central Station Transmitter: 1-inch conduit between the FACP and the central station transmitter connection as indicated. Install number of conductors and electrical supervision for connecting wiring as required to suit central-station monitoring function. Final connections to terminals in central station transmitter are made under another contract. PWA 201130 28 3100/7

3.04 GROUNDING Ground equipment and conductor and cable shields. For audio circuits, minimize to the greatest extent possible ground loops, common mode returns, noise pickup, cross talk, and other impairments. Provide 5-ohm ground at main equipment location. Measure, record, and report ground resistance. 3.05 E. FIELD QUALITY CONTROL Manufacturer's Field Services: Provide services of a factory-authorized service representative to supervise the field assembly and connection of components and the pretesting, testing, and adjustment of the system. Pretesting: Upon completing installation of the system, align, adjust, and balance the system and perform complete pretesting. Determine, through pretesting, the conformance of the system to the requirements of the Drawings and Specifications. Correct deficiencies observed in pretesting. Replace malfunctioning or damaged items with new and retest until satisfactory performance and conditions are achieved. Prepare forms for systematic recording of acceptance test results. Report of Pretesting: After pretesting is complete, provide a letter certifying the installation is complete and fully operable, including the names and titles of the witnesses to the preliminary tests. Final Test Notice: Provide a 1 0-day minimum notice in writing when the system is ready for final acceptance testing. Minimum System Tests: Test the system according to the procedures outlined in NFPA 72H, Chapters 2 and 4, and NFPA 72E, Chapter 8. Minimum required tests are as follows: 1. 2. 3. 4. 5. 6. 7. 8. Verify the absence of unwanted voltages between circuit conductors and ground. Megger test all conductors other than those intentionally and permanently grounded with electronic components disconnected. Test for resistance to ground. Report readings less than 1-megohm for evaluation. Test all conductors for short circuits utilizing an insulation-testing device. With each circuit pair, short circuit at the far end of the circuit and measure the circuit resistance with an ohmmeter. Record the circuit resistance of each circuit on the record drawings. Verify the control unit is in the normal condition as detailed in the manufacturer's operating and maintenance manual. Test initiating and indicating circuits for proper signal transmission under open circuit conditions. One connection each should be opened at not less than 10 percent of the initiating and indicating devices. Observe proper signal transmission according to class of wiring used. Test each initiating and indicating device for alarm operation and proper response at the control unit. Test smoke detectors with actual products of combustion. Test the system for all specified functions according to the manufacturer's operating and maintenance manual. Systematically initiate specified functional performance items at each station including making all possible alarm and monitoring initiations and using all communications options. For each item, observe related performance at all devices required to be affected by the item under all system sequences. Observe indicating lights, displays, signal tones, and annunciator indications. PWA 201130 28 3100/8

9. Test both primary power and secondary power. Verify, by test, the secondary power system is capable of operating the system for the period and in the manner specified. F. G. H. Retesting: Correct deficiencies indicated by tests and completely retest work affected by such deficiencies. Verify by the system test that the total system meets the Specifications and complies with applicable standards. Report of Tests and Inspections: Provide a written record of inspections, tests, and detailed test results in the form of a test log. Submit log upon the satisfactory completion of tests. Tag all equipment, stations, and other components at which tests have been satisfactorily completed. 3.06 CLEANING AND ADJUSTING Cleaning: Remove paint splatters and other spots, dirt, and debris. Touch up scratches and mars of finish to match original finish. Clean unit internally using methods and materials recommended by manufacturer. Occupancy Adjustments: When requested within one year of date of Substantial Completion, provide on-site assistance in adjusting sound levels and adjusting controls and sensitivities to suit actual occupied conditions. Provide up to three visits to the site for this purpose. 3.07 DEMONSTRATION Provide the services of a factory-authorized service representative to demonstrate the system and train Owner's maintenance personnel as specified below. 1. Train Owner's maintenance personnel in the procedures and schedules involved in operating, troubleshooting, servicing, and preventive maintaining of the system. Provide a minimum of 8 hours' training. 2. Schedule training with the Owner at least seven days in advance. Provide a separate quotation for a monitoring and maintenance contract directly to the Owner with a copy being submitted to the Electrical Engineer. END OF SECTION PWA 201130 28 3100/9