Effect of Flow Distortion in Inlet Duct on the Performance of Centrifugal Blower

Similar documents
Effects of Volute Tongue Clearance and Rotational Speed on Performance of Centrifugal Blower Nitin S. Jadhav *, S. R. Patil

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Design And Analysis Of Centrifugal Pump

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

ICSV14. Cairns Australia 9-12 July, Noise reduction of handheld vacuum cleaners according to geometric optimization of air passages

Performance Analysis of Centrifugal Fan by CFD

Effects of Splitter Blades on Centrifugal Pump Performance - A Review

Introduction to Fans. The Basics of Fan Principles and Terminology

EFFECT OF GEOMETRICAL CHANGES OF IMPELLER ON CENTRIFUGAL PUMP PERFORMANCE

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

A Novel Approach for the Thermal Management. of PC Power Supply

EXPERIMENTAL ANALYSIS OF TIP CLEARANCE AND CHORD LENGTH FOR OPTIMUM DESIGN OF AXIAL FLOW FAN IN AIR COOLED HEAT EXCHANGER

Australian Journal of Basic and Applied Sciences

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

APPLICATION OF CFD SIMULATIONS FOR LOCATING OUTDOOR UNITS ON HIGH RISE TOWER Basant Kumar Gupta 1, Anand Patil 2

[Eswaran, 3(3): March, 2014] ISSN: Impact Factor: 1.852

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

What is the correct type of fan: Axial, radial, diagonal?

Air Flow Study inside the Supermarket Refrigeration System

Analysis of Centrifugal Pump with Closed Type Impeller for Slurry Operations

Heat Transfer in Evacuated Tubular Solar Collectors

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

Performance Study of Triple Concentric Pipe Heat Exchanger

Study of air circulation inside the oven by computational fluid dynamics.

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

AERODYNAMIC DESIGN OF KEY COMPONENTS OF THE LARGE-DISCHARGE AXIAL FAN AT HIGH ALTITUDE

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

ISSN (Online)

TITLE: Improvement in Heat Transfer Rate and Dynamics of Shrouded Fanned Radiator System

The Role of Computational Fluid Dynamic and Aeroacoustic Simulations in Reducing the Noise of a Forward-Curved Blade Radial Fan

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

FLOW AND PERFORMANCE INVESTIGATIONS OF CENTRIFUGAL BLOWERS WITH AEROFOIL BLADED IMPELLERS

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

Thermal Analysis of Concentric Tube Heat Exchanger Using Louvered Strip Inserts

USE OF CFD TOOL FOR IMPROVING DESIGN OF CENTRIFUGAL PUMP

CASE HISTORY: RETROFIT OF COAL MILL EXHAUST FAN STUDY OF FAN PERFORMANCE AND EROSION

Global Journal of Engineering Science and Research Management

Development of Large Size Hybrid Fan

SSRG International Journal of Thermal Engineering (SSRG-IJTE) volume 1 Issue1 Jan to April 2015

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Faculty of Mechanical and Manufacturing Engineering Universiti Tun Hussein Onn Malaysia Pt. Raja, Batu Pahat, Johor, MALAYSIA

Heat transfer and heating rate of food stuffs in commercial shop ovens

PERFORMANCE OF A MODEL IN-LINE VORTEX SEPARATOR. Keng-Choon Lee Geothermal Institute, The University of Auckland, Private Bag 92019, Auckland, New

American International Journal of Research in Science, Technology, Engineering & Mathematics

The Experimental Validation of Numerical Modeling of the Air Distribution in the Indoor Ice Rink Arena

Design, Development and Experimental Investigation of Volumetric Air Receiver

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Simulation on Counter Flow Heat Exchanger for Indirect Evaporative Cooling Applications Avinash Pandey 1 Dr. P.K.Jhinge 2

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

THE CONTROL METHOD OF THE INFLOW TURBU- LENCE INTERACTION NOISE FOR ROUTER COOLING FAN

High-efficiency Turbo Chiller (NART Series)

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Performance investigation of Air-conditioning system using ejector as expansion device

FREQUENCY ENHANCEMENT OF DUAL-JUNCTION THERMOCOUPLE PROBES

Analysis of ventilation system for a microwave assisted drying unit

Glossary of Terms Laboratory & Fume Exhaust Fans

Analysis and Optimization of Centrifugal Blower Using CFD

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 12, 2016 ISSN (online):

Heat transfer enhancement in an air process heater using semi-circular hollow baffles

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

EXPERIMENTAL INVESTIGATION OF HYBRID NANOFLUID ON THERMOSYPHON TYPE WICKLESS HEAT PIPE HEAT EXCHANGER THERMAL PERFORMANCE

Chapter 1. Introduction, Literature Review and Need of Study

A Study of Drying Uniformity in a New Design of Tray Dryer

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Rotodynamic Pumps INTRODUCTION:

LAB EQUIPMENT DETAILS

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

2. HEAT EXCHANGERS MESA

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

FAN TYPES CENTRIFUGAL FAN Forward Curve Centrifugal Fan

ANALYSIS ON EFFECT OF TEMPERATURE ON MOISTURE SEPARATION IN AIR COMPRESSOR

RESPONSE OF ANCHOR IN TWO-PHASE MATERIAL UNDER UPLIFT

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

AIR FLOW CHARACTERISTICS IN AN INDUSTRIAL WOOD PALLET DRYING KILN

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

Physical Mechanism of Convection. Conduction and convection are similar in that both mechanisms require the presence of a material medium.

DESIGN AND MANUFACTURING OF CHEMICAL AGITATOR

Water engineers and utilities are often

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

CHAM Case Study Numerical Simulation of a Air-to-air Cross-flow Heat Exchanger

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Solar air heater duct having triangular protrusions As roughness elements on absorber plate

Water Pumps. turbo-hydraulic pumps, positive-displacement pumps.

Numerical Analysis of Water Temperature Distribution in the Tank of. ASHPWH with a Cylindrical Condenser

Transcription:

Effect of Flow Distortion in Inlet Duct on the Performance of Centrifugal Blower Kalpesh W. Shirsath 1, S.R. Patil 2, Sumit M. Naik 3 PG Student 1,3, Assistant Professor 2 Department of Mechanical Engineering 1,2,3, AISSMS COE, SPPU, Pune, India 1,2,3. Email: kalpeshshirsath17@gmail.com 1, srpatil@aissmscoe.com 2, smtnk72@gmail.com 3 Abstract- In this paper, the effect of flow distortion in the inlet duct on the performance of centrifugal blower has been numerically and experimentally investigated. Numerical analysis was carried out on centrifugal blower with hub and tip distorter with 25 % blocked area in inlet duct. ANSYS Fluent 16.0 software was used for numerical analysis. Flow rate, total pressure, blower efficiency and discharge head were taken as performance parameters. Numerical analysis was also done for original centrifugal blower having straight circular inlet duct. According to IS: 4894-1987 experimentation was carried out on original centrifugal blower and modified centrifugal blower with tip and hub distorter. Performance parameters were evaluated from numerical and experimental. Validation of numerical with experimental was done. The indicated that flow distortion degrades the performance of centrifugal blower in terms of flow rate, blower efficiency and discharge head. The centrifugal blowers are nothing but one of the types of turbo machines which are primarily used for accelerating air continuously to accommodate large volume of air with slight increase in static pressure. Blowers are extensively used in industrial and commercial applications such as shop ventilation, material handling, boiler applications and vehicle cooling systems. Distortion in inlet duct refers to the non-uniform flow upstream of turbo-machines. Inlet flow distortion can be detrimentally affecting the performance of the fans, blowers and compressors in terms of static efficiency and pressure rise. Inlet flow distortions can also affect the stability limits of these turbo-machines in terms of aerodynamic and aero-elastic properties. [1] The problem of determining how much a turbomachine is affected by poor inlet flow conditions is an old one. It arises in HVAC design and installation, layout of hydraulic pumping systems and in the design of inlet configurations for both ground-based and airborne gas turbine compressors. [2] The flow non-uniformity is frequently generated at the entrance of impeller called as inlet distortion, which is divided mainly into two types of distortion. One is radial distortion and other is circumferential distortion. The radial distortion is further subdivided into tip distortion and hub distortion corresponding to the regions where obstacle is placed. Hub distortion is observed when axisymmetric obstacles are placed at a center portion of an inlet duct, such as a tachometer pick up and a hub cover. Axisymmetric boundary layers of an inlet duct or a return channel or an orifice plate are responsible for tip distortion. Non- Keywords- Centrifugal Blower; Hub distorter; Numerical analysis; Performance parameters; Tip distorter. axisymmetric obstacles are mainly responsible for 1. INTRODUCTION circumferential distortion. [3-4] In turbo-machineries such as compressors, due to limited space curved inlet duct are generally used to provide and guide air to casing. Such a curved inlet duct can generate flow distortion in compressor therefore deteriorate compressor stage performance. [5] Inlet flow distortions occurred due to various inlet duct configurations including obstacles, struts and bending duct can be seriously affected performance of centrifugal compressors. Kim et al. have conducted experimentation on centrifugal compressor with straight circular duct and a 90 curved duct with nozzle shape to compare stage efficiency. [6] Patil et al. have done experimentation and numerical simulation to investigate the effect different volute tongue clearances such as 6 %, 8 %, 10 % and 12.5 % of impeller diameter on the performance of centrifugal blower. Numerical simulation was done using ANSYS Fluent software. They used mathematical model as standard k-ε turbulence model for solving 3D Reynolds Averaged Navier Stokes equations. [7] Girish et al. have done CFD simulation of centrifugal blower using ANSYS CFX. They have obtained velocity vector and pressure counter plot for different blower speeds to evaluate performance parameters. [8] Naseri et al. have obtained experimental which determine adverse impact of inlet total pressure distortion on the performance of a micro gas turbine. Experimentation was carried out on the gas turbine which was exposed to inlet gas flow with 60 0, 120 0 and 180 0 circumferential distortion patterns. The performance of the gas turbine has been evaluated and compared with straight inlet gas flow case. [9] 2301

2. DETAILS OF CENTRIFUGAL BLOWER The centrifugal blower setup is specified according to IS: 4894-1987. Main components of original centrifugal blower contain casing, straight circular inlet duct, outlet duct and impeller. In this paper original centrifugal blower is indicated by M 0. The various parameters of original centrifugal blower are given in Table 1. Table 1. Parameters of original centrifugal blower Sr. No. 1 2 Parameters Impeller outlet diameter (mm) Impeller inlet diameter (mm) 280 140 3 No. of blades 12 4 Impeller blade type Backward inclined 5 Inlet duct diameter (mm) 130 6 Inlet duct length (mm) 550 7 Motor speed (RPM) 2800 (a) differentiates the inlet duct of centrifugal blowers. The changes made in inlet duct of centrifugal blower are shown in Fig. 1 (b) and (c). 3. NUMERICAL ANALYSIS ANSYS Fluent 16.0 software was used for numerical analysis of centrifugal blowers. The three dimensional model of centrifugal blower having only casing and impeller were first created in Solid Works 2015 software. Further modification such as modeling of inlet duct, outlet duct and passages were done in Design Modular of ANSYS Fluent. Rotating zone and stationary zone were solved by Multiple Frames of Reference in rotating reference frame and stationary reference frame respectively. A rotating reference frame was set to impeller wheel with rotational speed and other parts were referred as stationary frame. In meshing process, tetrahedral elements were selected for the elements of rotating impeller and hex elements were defined for the inlet duct, outlet duct and casing of centrifugal blower. Meshing size of element was taken as 5 mm. The flow of air inside centrifugal blower is generally turbulent flow. Hence to solve 3D Navier- Stokes equations standard k-epsilon model was selected. Here k represents turbulent kinetic energy and epsilon denotes turbulent dissipation. Inlets, outlets and impeller of original and modified centrifugal blowers were taken as boundary conditions. The atmospheric pressure was defined as the inlet boundary condition at the entrance of the inlet duct. Also outlet boundary condition was set as atmospheric pressure at the exit of outlet duct. Rotational motion was given to impeller and considered as moving wall. Sufficient iterations were given until solution was converged. After convergence of solution numerical were obtained in vector plots, counter plots and streamlines. Velocity vector and pressure counter plots for centrifugal blowers M 0, M 1 and M 2 are shown in Fig. 2 to Fig. 7 respectively. (b) (c) Fig. 1. Inlet duct of (a) centrifugal blower M 0, (b) centrifugal blower M 1, (c) centrifugal blower M 2 To know the effect of distorted inflows on performance of centrifugal blower, obstacles such as tip and hub distorter were placed inside inlet duct without changing other parameters. The tip and hub distorter with 25 % blocked area in inlet duct of centrifugal blowers are defined as modified centrifugal blowers M 1 and M 2 respectively. Fig. 1 Fig. 2. Pressure counter plot of centrifugal blower, M 0 2302

Fig. 3. Pressure counter plot of centrifugal blower, M 1 Fig. 6. Velocity vector plot of centrifugal blower, M 1 Fig. 4. Pressure counter plot of centrifugal blower, M 2 Fig. 5. Velocity vector plot of centrifugal blower, M 0 Fig. 7. Velocity vector plot of centrifugal blower, M 2 4. EXPERIMENTATION Experimentation was carried out on original and modified centrifugal blowers. An experimental setup of centrifugal blower was according to IS: 4894-1987. Photograph of experimental setup of blower is shown in Fig. 8. An electric motor of 0.5 HP with threephase was used to drive the centrifugal blower. The input of four way inlet and one way outlet valve was connected to inlet duct and also output of this valve was connected to one limb of the manometer. U-tube manometer was connected through four side tappings at the entrance side of the inlet duct to measure static pressure which later used to calculate flow rate as shown in Fig. 8. At exit side of inlet duct, measurement of average static pressures was done by using U-tube manometer. It was also connected at the outlet of the blower to calculate outlet total pressure. Dimmer-stat was used to vary voltage from zero to rated value of 415 V; hence rated rpm of motor is achieved. Current and voltage measurements were done by analogue ammeters and voltmeter respectively. 2303

Total pressure (Pa) 600 500 400 300 200 100 0 Numerical 452.07 553.89 541.79 Experimental 489.96 547.77 529.14 Fig. 8. Photograph of the experimental setup 1: U-tube manometers, 2: Dimmer-stat, 3: Voltmeter, 4: Ammeters, 5: Inlet duct hub distorter, 6: four way inlet one way outlet valves, 7: Modified centrifugal blower, M 2 5. RESULT AND DISCUSSION Numerical and experimental of original and modified centrifugal blowers for flow rate, total pressure, blower efficiency and discharge head are shown in Fig. 9 to Fig. 12 respectively.. Flow rate (m 3 /hr) 700 600 500 400 300 200 100 0 Numerical 652.33 517.43 506.24 Experimental 637.23 544.17 537.65 Fig. 9. Numerical and experimental for flow rate Both numerical and experimental show that flow rate is maximum in original centrifugal blower, M 0 as effective flow area is more in case of original centrifugal blower. Modified centrifugal blower M 2 shows least flow rate as compared to others. From Fig. 10 it can be seen that total pressure is occurred to be more in case of modified centrifugal blower, M 1. Increment in total pressure is seen in modified centrifugal blowers because of inlet static pressure along with velocity pressure is increased. Fig. 10. Numerical and experimental for total pressure Blower efficiency (%) 56 52 48 44 40 Numerical 51.46 50.61 48.56 Experimental 53.85 52.33 49.95 Fig. 11. Numerical and experimental for blower efficiency Discharge head (mm of H 2 O) 20 15 10 5 0 Numerical 15.72 12.21 11.76 Experimental 17.34 13.39 12.61 Fig. 12. Numerical and experimental for discharge head. 2304

Use of hub and tip distorter degrades performance of centrifugal blower in terms of blower efficiency. Modified centrifugal blowers M 1 and M 2 shows less efficiency as compared to original centrifugal blower M 0. Efficiency is occurred to be minimum in modified centrifugal blower M 2 as shown in Fig. 11 Reduction in discharge head is occurred in both modified centrifugal blowers M 1 and M 2 which can be seen in Fig. 12. Hence modified centrifugal blowers with tip and hub distorter are unable to build up static pressure rise. Comparison of numerical with experimental is done for validation purpose. From Table 2 and Table 3, it can be seen that numerical has well matched with experimental of original and modified centrifugal blowers. As deviations occurred between numerical and experimental are within 6 %, hence it ensures validity. Table 2. Comparisons of numerical with experimental of modified centrifugal blower, M 1 for performance parameters Performance parameters Flow rate (m 3 /h) Total pressure (Pa) Blower efficiency (%) Numerical Experimental Deviation 517.43 544.17 4.91 % 553.89 547.77 1.12 % 50.61 52.33 3.28 % Table 3. Comparisons of numerical with experimental of modified centrifugal blower, M 2 for performance parameters Performance parameters Flow rate (m 3 /h) Total pressure (Pa) Blower efficiency (%) Numerical Experimental Deviation 506.24 537.65 5.85 % 541.79 529.14 2.39 % 48.56 49.95 2.78 % 6. CONCLUSION The study was conducted on how inlet flow distortion affects the performance of centrifugal blower. In modified centrifugal blower with hub distorter minimum flow rate is occurred and it is decreased by 22.39 % than original centrifugal blower at rated rpm. Modified centrifugal blower with tip and hub distorter shows increment in total pressure than original centrifugal blower by 22.52 % and 19.84 % respectively. Modified centrifugal blower with hub distorter shows least efficiency as compared to others. It is decreased by 5.63 % with respect to original centrifugal blower. Modified centrifugal blower with hub distorter shows larger drop in discharge head and which is 25.19 % with respect to original centrifugal blower. Compared with undistorted case performance of centrifugal blower falls in order of tip and hub distortions. REFERENCES [1] Wenqiang Zhang, Mehdi Vahdati, Influence of the Inlet Distortion on Fan Stall Margin at Different Rotational Speed, Proceedings of Shanghai, Global Power and Propulsion, 2017. [2] T. Wright, S. Madhavan, J. Dir, Centrifugal fan performance with distorted inflows, Journal of Engineering for Gas Turbines and Power, volume 106, pages 895-900, 1984. [3] Ariga I., Kasai N., Masuda S., Watanbe Y., Watanbe I., The effect of inlet distortion on performance characteristics of a centrifugal compressor, Journal of Engineering for Gas Turbines and Power, pages 223-230, 1983. [4] Dr.Basharat Salim, Performance of a radial blower with curved inlet duct, International Journal of Emerging Technology and Research, volume 2, Issue 4, pages 99-118, 2015. [5] Ben Zhao, Harold Sun, Leilei Wangb, Manxiang Song, Impact of inlet distortion on turbocharger compressor stage performance, Applied Thermal Engineering, volume 124, pages 393-402, 2017. [6] Y Kim, A Engeda, R Aungier and G Direnzi, The influence of inlet flow distortion on the performance of a centrifugal compressor and the development of an improved inlet using numerical simulations, Proceedings of the Institution of Mechanical Engineers, Part A: Journal of Power and Energy, pages 323-338, 2001. [7] Sunil R. Patil, Sandip T. Chavan, Nitin S. Jadhav, Shivaraj S. Vadgeri, Effect of volute tongue clearance variation on performance of centrifugal blower by numerical and experimental analysis, Materials Today: Proceedings, volume 5, pages 3883-3894, 2018. 2305

[8] Girish A R, Prajwal Sandyal, Lokesh. K.S, Varun N, CFD simulation of centrifugal blower using ANSYS CFX, National Conference on Advances in Mechanical Engineering Science, pages 34-38, 2016. [9] Alireza Naseri, Shervin Sammak, Masoud Boroomand, Alireza Alihosseini, Abolghasem M. Tousi, Experimental Investigation Of Inlet Distortion Effect On Performance Of A Micro Gas Turbine, Journal of Engineering for Gas Turbines and Power, 2017. (A.1) 2306