ACHIEVING ENERGY-EFFICIENT DATA CENTER COOLING: DOES REDUCING FAN SPEED ALWAYS RESULT IN ENERGY SAVINGS?

Similar documents
H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

Liebert. CW kW Chilled Water Cooled Precision Air Conditioning For Data Centers

Liebert. Mini-Mate2 1 To 8 Tons Overhead Precision Cooling And Humidity Control

KEY POINTS OF DESIGN, INSTALLATION AND MAINTENANCE FOR CONFIGURING LIEBERT XD SYSTEMS. Technical Note

Liebert. Liqui-tect Leak Detection and Reporting Comprehensive Detection of Water Based Leaks in Critical Spaces

LIEBERT LIQUI-TECT 460 KIT ZONE LEAK-DETECTION SENSOR WITH CABLE

Liebert CW kW. Chilled Water Cooled Precision Air Conditioning For Data Centers. Precision Cooling For Business-Critical Continuity

Liebert Mini-Mate2 1 To 8 Tons

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

Liebert Mini-Mate2 1 To 8 Tons

Liebert HIROSS for Telecom

Liebert Mini-Mate2 1 To 8 Tons

Sustainable Techniques in Refrigerated Space

FTA200-A REMOTE ALARM PANEL

A/C Cooling Load calculation and measurement

Presented By: John Dolan, P.E.

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

Liebert Datamate: R-407C Parts Manual

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Liebert. Universal Monitor Monitoring, Control And Remote Communications For Critical Applications

WHAT IS AN ENERGY BALANCE AND WHY SHOULD I CARE?

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

FULLY SELF-CONTAINED AIR CONDITIONING WITH INDUSTRIAL DURABILITY

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

RSG16**S1M. Split System Air Conditioner 16 SEER

Liebert Challenger. Unmatched Environmental Control To Match Many Applications. Precision Cooling For Business-Critical Continuity

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

NRP MULTIPURPOSE HEAT PUMPS 2 AND 4-PIPE SYSTEMS PLUS PRODUCTION OF DOMESTIC HOT WATER

Air / Water Heat Pump - Compact Design Modulating 8 18 kw

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

ENGINEERING. Edition No. 13 October 2002

Liebert OVERHEAD COOLING IN A VARIETY OF CAPACITIES AND CONFIGURATIONS. Mini-Mate2. 1 to 8 Tons. Provides Precision Cooling And Humidity Control

Dehumidification: Energy Efficiency Comparisons

DIGI-CRAC DIGI-CRAH South 59 th Street Omaha, NE bes- tech.net

Variable refrigerant flow (VRF) systems

EnergyMaster. ENEC Monitoring System. An on-site supervision and remote monitoring solution

GEOTHERMAL DESIGN GUIDE

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

FTA550 JOCKEY PUMP CONTROLLERS

Technical Papers. 37th Annual Meeting. International Institute of Ammonia Refrigeration. March 22 25, 2015

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

SERVICE ASSISTANT OVERVIEW FDSI Online Training

Bring the fresh in. D E D I C A T E D O U T S I D E A I R S Y S T E M

Emerson Superheat Control. The smart solution for your application

FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

InRow Direct Expansion

50A KP 70A KP 90A KP 120A KP 150A KP 210A

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

Evaporative Cooling in a Hot-Dry Climate

Would You Bolt A Swamp Cooler To Your DX Rooftop Unit? [not exactly.]

Liebert Air-Cooled Fin/Tube Condensers

Fast Track Troubleshooting

THE ULTIMATE ROOFTOP SOLUTION

HVAC Water chiller selection and optimisation of operation

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

THE RIGHT SPEC. RIGHT NOW.

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Pressure Enthalpy Charts

TESTS OF ADSIL COATING

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Geothermal Comfort Systems

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

Technical Data Sheet. Brine/Water Heat Pumps 8 12kW - single phase 230V. Heliotherm Basic Comfort. Basic Comfort Advantages

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

Daikin VRV Systems Plugin VE2012 User Guide

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Prepared by: (415) Prepared for: Final Report May Contributors: Annn Edminster. Me!

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

16 SEER TWO-STAGE AIR CONDITIONERS

CO 2 EVAPORATOR DESIGN

GEOTHERMAL COMFORT SYSTEMS

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

Low GWP Refrigerants for Air Conditioning Applications

EWAD-TZ. Air cooled chiller with R-134a inverter driven screw compressor

Adding More Fan Power Can Be a Good Thing

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

Chiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off

Liebert PPC Second Generation Power Distribution Cabinet

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

Product Line Introduction. Karl Zhang Technical support engineer

Transcription:

ACHIEVING ENERGY-EFFICIENT DATA CENTER COOLING: DOES REDUCING FAN SPEED ALWAYS RESULT IN ENERGY SAVINGS?

TWO STAGE POWER DISTRIBUTION Introduction Energy efficiency is a top criterion when selecting a data center precision cooling system, but determining the actual energy efficiency of cooling units is not a simple matter. On the surface, it may seem logical to believe that reducing the fan speed on a direct expansion (DX) precision cooling unit will save energy. Indeed, as fan speed is reduced, the motor power reduces by a cube relationship. For example, a 20 percent reduction in air volume results in an approximate 50 percent power reduction of the fan motor. But that is only part of the story. This technical note demonstrates that overall efficiency suffers when fan speed is reduced on fixed scroll cooling systems. In addition, the risk of coil freeze and wasteful rehumidification are increased. 2

Energy Efficiency is Reduced At Lower Air Volumes Figure 1 shows that energy efficiency (coefficient of performance) goes down as the air volume is reduced. Coefficient of performance is the cooling capacity per energy input (expressed as Watts of sensible cooling per Watts of electrical power input). The reason for this is that the cooling capacity diminishes at a faster rate than the reduction in energy. Compressor On-time Increases at Lower Air Volumes, Increasing Energy Consumption Because reducing the air volume reduces the cooling capacity, for a given cooling load the compressors must stay on longer in order to meet the load. For example, Figure 2 shows the impact on energy consumption resulting from a 70 percent reduction in fan speed. Note that the full-load (100 percent fan speed) sensible capacity is 199.8 kbtuh, while the sensible capacity at 70 percent fan speed is 162.2 kbtuh. In both cases the compressor power is about the same, 20.4 kw versus 20.1 kw. However, as a result of reducing the cooling capacity, for the same cooling load (140 kw for this example), the compressor stays on longer to meet the load: 70.1 percent operation for full air volume versus 86.3 percent operation for 70 percent air volume, as shown in Figure 2. Reducing air volume on a fixed capacity compressor increases latent cooling capacity and increases the risk of coil freeze. Digital scroll compressors do not carry that risk. Sensible EER vs. Fan Speed Fixed Capacity Compressor 2.1 Energy Efficiency, SCOP 2.05 2 1.95 1.9 1.85 1.8 60% 65% 70% 75% 80% % Fan Speed 85% 90% 95% 100% Figure 1: As fan speed is reduced on a fixed capacity compressor, so is energy efficiency. 3

TWO STAGE POWER DISTRIBUTION The result is that over a period of one year, the compressor operation increases from 125,271 kwh to 151,954 kwh, a 21 percent increase in compressor energy consumption. As predicted, the fan energy was lowered from 4.1 kw to 1.5 kw a 63 percent reduction in energy consumption. Reducing Fan Speed Alone Does Not Reduce Energy Consumption 100% FAN SPEED 70% FAN SPEED Sensible Load, kbtuh 140.0 140.0 Sensible Capacity 199.8 162.2 Compressor kw 20.4 20.1 % Compressor Operation 70.1 86.3 Compressor kwh 125,271 151,954 Fan kw 4.4 1.5 Fan kwh 38,544 13,140 However, since the compressor energy makes up most of the energy consumption, the reduction in fan power is more than offset by the increase in compressor energy. The reduced air volume case actually results in a 1 percent increase in system energy consumption in effect a tie. Another challenge to efficiency resulting from reducing air volume on a fixed capacity compressor is that the latent cooling capacity increases. Latent cooling capacity is the amount of moisture removed from the air. In this case, a 20 percent reduction in air volume causes the latent cooling capacity to double from 20 kbtuh to 40 kbtuh. Over- dehumidification results in even more energy consumption by rehumidifying. Conversely, using Digital Scroll compressors mitigates this problem. Digital scroll compressors modulate as the air volume is decreased. Because the average refrig-erant flow is reduced, the evaporator coil runs warmer, reducing the latent capacity. (See figure 3.) Sum kwh 163,815 165,094 Figure 2: Reducing fan speed results in lower sensible capacity, causing longer compressor on-time, here representing a 21% increase in compressor energy consumption over one year. 60 Latent Cooling vs. Air Volume Latent Cooling Capacit, k BTUH 50 40 30 20 10 0 Fixed Capacity Compressor Digital Scroll Compressor 60% 70% 80% % Fan Speed 90% 100% Figure 3: Digital scroll compressors reduce the need for rehumidification when the fan operates at lower speeds. 4

When air volume is decreased, the cooling coil temperature also decreases, causing a risk of coil freeze, as Figure 4 illustrates. The risk of coil freezing is higher if certain conditions occur simultaneously: low air volume, high wetbulb temperature and low condensing temperature. By contrast, when a digital scroll compressor is used and modulates as air volume decreases, the evaporator temperature actually increases compared to a fixed scroll compressor. When the digital scroll modulates to reduce cooling capacity, the refrigerant flow rate is reduced, resulting in a higher evaporator temperature than when at full flow. Evaporator Temperature vs. Air Volume Fixed Capacity Compressor Average Evaporator Temperature, Degrees F 45 44.5 44 43.5 43 42.5 42 41.5 41 40.5 40 60% 70% 80% 90% 100% % Fan Speed Figure 4: Lower air volume and lower evaporator temperature increase the risk of coil freeze in fixed compressor systems. 5

TWO STAGE POWER DISTRIBUTION Evaporator Temperature vs. Air Volume Digital Scroll with VFD Fan Modulation Average Evaporator Temperature, Degrees F 50 49.5 49 48.5 48 47.5 47 46.5 46 45.5 45 60% 70% 80% % Fan Speed 90% 100% Figure 5: A digital scroll compressor s modulation lowers refrigerant flow rate, producing a higher evaporator temperature. 6

Conclusion Lowering fan speed does not necessarily improve the energy efficiency of a DX cooling system. In fact, overall efficiency suffers when fan speed is reduced on fixed scroll cooling systems, and the risk of coil freeze and wasteful rehumidification are increased. Choosing a cooling system that utilizes digital scroll compressors that finely modulate fan speed and temperature depending on room conditions overcomes the inefficiencies and risks of fixed capacity compressor operation. To see how much energy you can save by using digital scroll compressors, available only on Liebert cooling systems from Vertiv, visit Liebert.com and click Efficiency Without Compromise. 7

VertivCo.com Vertiv Headquarters, 1050 Dearborn Dr. Columbus, OH 43085, USA 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. TN-00012 (R05/11)