FULL REDUNDANT RING BUS FIRE DETECTION SYSTEMS FOR RAILWAY APPLICATIONS: EN 54-2, EN (VdS) Reducing False Alarms

Similar documents
Availability, Reliability, False Alarm Resistance Best Practice in Fire Alarm Systems. FIRE PROTECTION OF ROLLING STOCK 2 rd March 2017

Solution F2. Fire Alarm Control Panels one step ahead.

Solution F1. Fire Control Panels the new generation

designed for rail 5000 Series

Consultant Specification AGILE Wireless Fire Detection System

STANDARD TECHNICAL SPECIFICATION FOR AN ANALOGUE ADDRESSABLE FIRE DETECTION SYSTEM

Different types of Fire Alarm System

IQ8Control C Fire Alarm Panel

Intelligent addressable fire alarm control panel

The supplier and installer of the system should be approved by the local civil defence authority.

GO TOGETHER WITH CONSILIUM SUPERIOR ROLLING STOCK SAFETY SOLUTIONS

Fire and Gas Monitoring Panel ST7-HV

OOH740, OOHC740 Automatic fire detectors

Fire control panel detect 3004 plus and accessories

The EN54 Part 2 & 4 Fire System

The EN54 Part 2, 4 and 13 Fire System

PA/VA solutions for transport industry

On the job around the clock 24/7: Fire detection systems

LaserFOCUS VLF-250 Engineering Specification

Just as flexible as your plans The Bosch Modular Fire Panel 5000 Series

intelligent fire alarm ID60series panels

OH110, OP110, HI110 Automatic fire detectors

Evolution Analogue Addressable Fire System

Quick Selection Guide Fire Systems LSN Periphery

Modular Fire Panel 5000 Series Just as flexible as your plans

Touchpoint Pro Flexible Gas Control System

Analogue Detectors. Series 200 plus

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

SIL2-Interface/ -Signal Conditioners Series DuoTec

TOOLS 8000 SOFTWARE FOR THE ENTIRE LIFE CYCLE OF YOUR FIRE DETECTION SYSTEMS

Voice Alarm. Multifunctional Voice Alarm Systems. certified to EN54

FC724 Fire control panel

ARGE Guideline - Part 3 "System functionality fire detection and fire fighting systems in rolling stock"

FC723 Fire control panel

FC722 Fire control panel

Fire protection for rolling stock. Innovative solutions from Siemens Building Technologies. Answers for infrastructure and cities.

IMQ SPA scope as CertAlarm CCB and RTL. Last update: 12th June 2017

Product Guide MAN7030-2

Building Technologies

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide

CCU Family of Modules

Protecting you and your home

Answers for infrastructure. Cerberus PRO enjoy protecting

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

All the security you need in one housing

ID50series. intelligent fire alarm panels

FC722 Fire control panel

Addressable Fire Alarm Control Panel

SUPREMATouch. Modular Fire & Gas Detection System

Martin Huber 26September 2017 F&G SOLUTIONS FOR THE PROCESS INDUSTRY

FC724 Fire control panel

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Apollo Accreditation. Need further information? Visit

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

Addressable Fire Alarm Control System 2100 series

Fire Detection Systems Product Catalogue (Version )

Remote alarm unit Art. Nr.:

For Complete Fire and Gas Solutions

Fire alarm system EBL512 G3

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Touch Screen 1 loop Addressable Fire Alarm Panel

SUPREMATouch Modular Fire & Gas Detection System

Intelligent monitoring system for automobiles

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

SUPREMATouch. Modular Fire & Gas Detection System

CSP-204 CSP-208 CSP-104 CSP-108

TECHNICAL DATA SHEET ADDRESSABLE FIRE ALARM SYSTEMS FIRE ALARM CONTROL PANEL LF-6100 A 1/2

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

DESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM

Panel Mounted Fault Annunciator Series

Innovative protection that combines power and flexibility

The new detector from Rafiki

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

Continuous, real-time detection, alarming and analysis of partial discharge events

LINEAR HEAT SERIES FIBER OPTIC LINEAR HEAT DETECTION SYSTEM

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Fire control panels FC726 FC726-XA

APPLICATION NOTE. Document Type. Application Note. Document Title. Date January Version DS0167/Iss 2. ESP Technical Summary

561-MB256 plus. Intruder alarm control panel. Performance features

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

ADR Analog Addressable Fire Alarm Control Panel. Technical Manual. Control Panels. 3000En. En pdf

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

561-MB48. Intruder Alarm Control Panel

Labkotec Ice Detector

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

XP95 Sounder VAD Base

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

ADW 535 Line type heat detector

Engineering Guideline. pac- Carriers Type Universal

Panel Mounted Fault Annunciator Series

IQ8Quad. The highlight of every fire detection scenario. Fire detection technology

F&G detection system for LNG plants

SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS

Fire control panels FC360

Ei600ZW Z-Wave Module for 10 Year Smoke Sensor with Siren

Laptop / PC Programming Manual

Basic Fire Alarm SystemTraining. Arman Alnasar

Transcription:

* * * IFV BAHNTECHNIK e.v. * * * * * * FULL REDUNDANT RING BUS FIRE DETECTION SYSTEMS FOR RAILWAY APPLICATIONS: EN 54-2, EN 54-13 (VdS) Reducing False Alarms CONTENTS 1. History / System requirements 2. EN 54-2 FCAP, EN 54-13 approved and certified systems 2.1. Cabling structure / short circuit isolators 2.2. Reducing false alarms 2.3 Analogue / Digital protocol 3. Advantages of open protocol 3.1. Open protocol - Independence for the system operator 3.2. Closed protocol Dependency of system and supplier on the system operator 4. Distinction between pre-alarm / main-alarm 5. Main characteristic of the railway-tested fire alarm system NSC Solution F1 Rail combined with Apollo Discovery ring bus components 6. Conclusion Reinhard HOFER Technical Sales Manager NSC Sicherheitstechnik GmbH Reinhard RÖSSLER CEO Rail Services International Austria GmbH See also Presentation [D] FIRE-SAFETY Symposium (26-27 March ) 1 in APPENDIX.

* * * IFV BAHNTECHNIK e.v. * * * * * * 1. History / System requirements As an introduction, it can be stated that with modern ring bus detection technology through which analogue measurement values are transmitted bidirectionally via a digitized protocol to an EN 54-2 certified, microprocessor-controlled fire alarm control panel within an EN 54-13 certified system, the currently highest level of security against false and erroneous alarms can be provided through intelligent algorithms by using a digital protocol (drift compensation, event delay, filtering of recurrent detection patterns). Since the early 1990s, this detection technology has proven itself in commercial and also heavy industrial environments. Since about 2004, a few manufacturers have tested this technology according to the stringent requirements of the specific standards for environmental and ambient conditions in railway construction and have already used it successfully for several years. Recently, the strict requirements of the EN 45545 series were also applied to all products used in respect to flammability and toxicity. Nevertheless, EN 45545-6 [1] does not stipulate detailled rules for products and systems concerning requirements on EN 54 standards series. In addition, the ARGE Guidelines [2], which are best known within the rail industry, do not suggest a mandatory EN 54 approved and certified system. Only Chapter 3.4 in part 3 contains a reccomendation, but nothing compulsary. Excerpt from Chapter 3.4 - ARGE-Guideline, Part 3: The monitoring requirement has to be realized in accordance with DIN EN 54-2 (affects fire alarm central control panels) and DIN EN 12094-1 (affects gas extinguishing systems), as far as required for rail vehicles. 2. EN 54-2 FCAP, EN 54-13 certified systems 2.1 Cabling structure / short circuit isolators Compared to outmoded stub-like wiring structures, the highest degree of reliability is achieved on the line system with ring bus detection technology and input- and output-side short circuit isolators in accordance with EN 54-17 for each element (detectors, signal generators, I/O interfaces). An interruption of the ring leads to the activation of the isolators and 2 branch lines result, whereby 100% functionality is still guaranteed in this case. A simultaneous double line fault can be excluded on the basis of high-quality cabling in rail vehicles (FE 180). Due to the exclusive use of components certified in accordance with harmonized product standards of the EN 54 [3] series (FACP: EN 54-2, detector: EN 54-5, EN 54-7, signal generators: EN 54-3, short curcuit isolators: EN 54-17, I/O devices: EN 54-18), a high degree of interference resistance and interoperability is ensured in the system. The highest level of reliability and availability can be achieved in the area of the fire alarm control panel, as the FACP features redundant processors both on the central control unit and on the loop card. FIRE-SAFETY Symposium (26-27 March ) 2

* * * IFV BAHNTECHNIK e.v. * * * * * * 2.2 Reducing False Alarms False alarms are alarms caused by external influences on an automatic fire detector (smoke detectors or multi-sensor smoke / thermal detectors) not caused by a fire (e.g., cigarette smoke, dust, fire work activities, water vapor, wantonness, rapid heat increase, etc.). Through the use of modern, analog-addressable ring bus detection technology with drift compensation, multiple adjustable alarm limits or additional programmable event delay (e.g. 10 seconds) and use of multi-criteria detectors (smoke / thermal) in specialized areas (e.g. switching cabinets, suspended ceilings, cooking areas, possibly even restrooms), false alarms can be minimized to a large degree by use of modern detection technology. If a false alarm variable is present over a longer period of time, a false alarm cannot ultimately be prevented 100% of the time, even with state-of-the-art technology, since with respect to analysis algorithms and adjustable event delay requirements of binding product standards for smoke and heat detectors, EN 54-7 and EN 54-5 must be observed and the compromise between the desired maximum immunity to false alarms and the fastest possible detection behavior is thus a limiting factor. If it turns out that this false alarm behavior in such areas occurs again and again, a different type of detection type (e.g. thermo-maximum or flame detector) must be selected. In some cases, programming a 2-detector dependency (2 detectors must respond before the main alarm criterion is reached at the FACP) can provide selective assistance. When using outmoded, conventional limit value detection technology or "smoke switches" without different configurable alarm thresholds, false alarms during operation are inevitable with this technology. In particular, the following causes are responsible for false alarms: 1) Shortly occurring, small amounts of smoke or smoke-like particles (e.g. dust, mist) can very likely lead to a false alarm. 2) Since, as a rule, drift compensation is not applied and the detectors cannot be configured with respect to the alarm threshold, a false alarm arises specifically in the event of an advanced degree of pollution in the presence of small amounts of smoke or smoke-like particles. The transmission of the alarm signal (without measurement value) is usually purely digital (relay) to a central location with binary input, thus no assessment of the alarm signal is possible there. False alarms can also be caused by a technical failure of the fire alarm system components (also cabling) without apparent external influences. FIRE-SAFETY Symposium (26-27 March ) 3

* * * IFV BAHNTECHNIK e.v. * * * * * * When using outmoded, conventional limit value detection technology or "smoke switches" with digital transmission (no transmission of analog values with bidirectional communication with a microprocessor-controlled fire alarm control panel in ring bus topology), technical false alarms may appear very likely and normally there is no way to analyse the reason for this failure. In such situations, components usually get changed much earlier than expected in relevant analysis. 2.3 Analogue / Digital protocol The term analogue is used to describe a signal which goes up and down stagelessly. See Fig 1. Signals that record phenomena such as the increase in smoke or heat are by nature analogue at their source and this is why modern fire detectors are called analogue. For example, a heat detector will record stageless increases in temperature from a typical starting point of 20 21 C (comfortable room temperature) to an alarm level of 55 C, however fast the increase. Each point on the analogue signal indicates a particular value. However, the problem with analogue signals is that if, during transmission, electrical corruption affects the signal, a 2 might appear as a 3, for example. FIRE-SAFETY Symposium (26-27 March ) 4

* * * IFV BAHNTECHNIK e.v. * * * * * * The term digital describes a signal that consists of a series of 0s and 1s, or offs and ons, which make up a message in binary arithmetic. The advantage of this system is that there is a much lower risk of the signal being transmitted poorly and hence giving the wrong information. Fig 2 shows the simple levels of 21, 22 and 23 (illustrated by the curve in Fig 1) as digital signals. As we learned in the last section, each degree in the example of a heat detector can be expressed in digital form (i.e., binary arithmetic). 30 degrees Celsius would then be 11110 and this is what would be transmitted to the FACP. A digital protocol is much less susceptible to corruption than the analogue protocol and is preferable in a life-critical system. Only digital protocols fulfill the high demands of EN 54-13. 3. Advantages of open protocol In the fire detection industry, intelligent systems use control panels and detectors (and, of course, devices such as sounders and interfaces), which communicate with each other by means of a protocol. Some manufacturers offer both panels and detectors. These companies do not need to disclose the nature of their protocol to anyone, since they offer all the elements needed to provide an intelligent system. No equipment supplied by other manufacturers is expected to be compatible with such systems, so the protocol used is said to be closed. FIRE-SAFETY Symposium (26-27 March ) 5

3.1 Closed protocol Dependency of system and supplier on the system operator * * * IFV BAHNTECHNIK e.v. * * * * * * Manufacturers of equipment using closed protocols claim that all elements of their equipment (detectors, panels, call points, interfaces, special detectors such as beam detectors) work harmoniously with each other, since they are all designed and made by the same company. The implication is that a system consisting of detectors and interfaces from one manufacturer and panels from another cannot work as well. 3.2 Open protocol - Independence for the system operator A number of manufacturers of detectors which use open protocol do not produce control panels; they have created partnerships with independent panel manufacturers and, in some cases, companies who offer special equipment such as aspirating detection systems. The detector manufacturer determines the protocol used by the detectors and publishes the information and technical data required by panel makers to design panels that will drive the detectors. Since all details of the protocol must be disclosed, it is referred to as an open protocol. The manufacturers of the components of a system with an open protocol would assert that products from different manufacturers of fire products work just as well as closed protocol products, and there might even be an advantage in different specialist manufacturers concentrating on their own skill areas. 4. Distinction between pre-alarm / main alarm In order to avoid panicked reactions by both the car personnel and the passengers in the event of false alarms, an area-wide acoustic, unlimited alarm should not be triggered right away when an alarm occurs at the FACP. Experience in recent years by railroad operators have shown that these alarms are no longer interpreted conscientiously both by car personnel and passengers in the event of repeated occurrence and therefore, regarding the emergency plan, which is also largely dependent on organizational and operational responses and measures, significant delays and hazardous situations are to be expected in an actual real fire event. This situation could be dangerous in that proven weak points would exist for the responsible staff of the operator in case of damage. It is therefore strongly recommended that a distinction be made between a "pre-alarm" and "main alarm" for the alarming concept and the emergency measures to be introduced. FIRE-SAFETY Symposium (26-27 March ) 6

* * * IFV BAHNTECHNIK e.v. * * * * * * 5. Main characteristic of the railway-tested fire alarm system NSC Solution F1 Rail combined with Apollo Discovery ring bus components System tested according to the latest rail standards (EN 50155, EN 50121-3, EN 60068, EN 61373, EN 45545-2) EN 54-2 tested FACP, EN 54-13 tested system (VdS) Multi-protocol panel, open protocol detectors and ring bus components Modern 2-wire ring bus detection technology, analog value transmission and evaluation via digitized protocol SIL 2 certified ring bus protocol Highest level of immunity to false alarms (drift compensation, event delay, filtering of recurrent detection patterns) Ring-bus-compatible components with analog value transmission: smoke detectors, multi-sensor detectors (smoke / thermal), UV / IR flame detectors, smoke suction system, line type heat detectors, manual fire detectors, I / O modules Detector housing have been meeting the highest standards with regard to flammability (V0 according to UL94) for many years Long-term certifications of detector components according to all international standards (VdS, LPCB, and many more) Many years of outstanding references regarding industrial capability far beyond standard requirements - independent of the rail sector (e.g.: -40 to + 70 C) Different detection modes and sensitivities can be adjusted via the FACP 2 LEDs integrated in the detector for 360 alarm verification Contamination level indicator of the detector can also be queried in the FACP display, no PC necessary Short circuit isolators (EN 54-17) in each element In case of malfunction, 2 branch lines without functional limitations are created from the ring 2 loops with 126 elements each can be connected, approximately 1000 m loop length possible for operation with ring bus-supplied signal generators Up to 128 panels can be networked via "ARCNET" fieldbus technology proven in industry, multi-master network, redundancy also possible Multi-protocol fire alarm control panel (2 "open protocol" detector manufacturers can be connected) FIRE-SAFETY Symposium (26-27 March ) 7

Backward compatibility of ring bus protocols used mainly until 1986 Assured of a good future * * * IFV BAHNTECHNIK e.v. * * * * * * The detector is addressed in the base with a binary coded address card Detectors can be exchanged easily by the operator without software addressing Mechanical removal protection of the detector integrated with locking screw EN 54-3 tested ring bus signal generator (tone type, volume and duration can be configured via FACP configuration software), e.g. 63 detectors with 63 signal generators per ring with 80 db sound level can be operated simultaneously, different volume values, sound types and duration programmable 100% redundant (processor redundancy in main CPU and loop card) Sheet steel housing, wear-free touch control panel Maximum EMC resistance 8 freely programmable macro keys (e.g. language switching, 18 languages integrated) 16 Digital outputs, 8 digital inputs, 4 potential-free relay 60 V DC, 0.5 A load, inputs and outputs expandable via ring bus-supplied I / O modules Extinguishing agent control monitored for short circuit / wire break Freely programmable according to Boolean algebra with Windows software (no paid software licenses) Redundant RS-232 and RS-485 interface on board Up to 64 LCD display and control panels can be connected to the FACP (optimum functionality for train conductors) Multi-protocol gateway can be connected for bidirectional connections to rail systems (MVB, WTB, CAN, ETH) - all data and events can be passed to a superior system. Even remote commands to the FACP can be realized (e.g. reset, signal generators off, detector shutdown and much more) Integrated modem interface (analog / ISDN / Ethernet) for remote access Optional Web server for remote access Non-volatile event memory for up to 10,000 messages (optionally expandable via SD memory card slot) Optional: single and multi-region extinguishing according to EN 12094-1 (gas extinguishing systems) FIRE-SAFETY Symposium (26-27 March ) 8

6. Conclusion * * * IFV BAHNTECHNIK e.v. * * * * * * All technical measures described above were successfully implemented by Rail Services International Austria GmbH, together with the Detection System manufacturer NSC Sicherheitstechnik GmbH, in agreement with the operator during the equipping of prototypes of the standard IC and ICN passenger car fleet of the Swiss Federal Railways. The aim was to drive through the Gotthard Base Tunnel with as few false alarms as possible with a state-of-the-art system certified in compliance with standards. Summary With the use of modern ring bus detection technology through which analogue measurement values are transmitted bidirectionally via a digitized protocol to an EN 54-2 certified, microprocessor-controlled fire alarm control panel within an EN 54-13 certified system, the currently highest level of security against false alarms can be provided through intelligent algorithms (drift compensation, event delay, filtering of recurrent detection patterns). Zusammenfassung in DEUTSCH Durch den Einsatz moderner Ringbusmeldetechnik, bei der analoge Messwerte über ein digitalisiertes Protokoll bidirektional zu einer EN 54-2 geprüften, mikroprozessorgesteuerten Brandmelderzentrale innerhalb eines EN 54-13 geprüften Systems übertragen werden, durch intelligente Auswertealgorithmen (Ruhewertnachführung, Driftkompensation, Ereignisverzögerung, Filterung von immer wieder auftretenden Detektionsmustern), kann das derzeit höchste Maß an Fehl- und Täuschungsalarmsicherheit geboten werden. Contact to the AUTHOR(s): Reinhard HOFER Reinhard RÖSSLER Position: Technical Sales Manager Austria CEO Organisation: NSC Sicherheitstechnik GmbH Rail Services International Austria GmbH Address: Wiener Straße 131, A 4020 Linz Domaniggasse 2, A 1100 Vienna Fon: +43(0) 732 997078 +43(0) 1 617 77 71 Fax: +43(0) 732 997078-78 +43(0) 1 617 77 71-28 E-mail: r.hofer@nsc-sicherheit.de rroessler@railsi.at Internet: www.nsc-sicherheit.de www.railsi.at Copyright Schriftenreihe BAHNTECHNIK AKTUELL (Band 54 / ) FIRE SAFETY Alle Rechte beim Verlag des IFV Bahntechnik e.v., Salzufer 17-19, SG 20, 10587 Berlin www.fachpublikationen-online.de >>> ISBN 978-3-940727-47-3 FIRE-SAFETY Symposium (26-27 March ) 9

REFERENCES : * * * IFV BAHNTECHNIK e.v. * * * * * * SOURCES (standards and guidelines): [1] EN 45545-6 Railway applications - Fire protection on railway vehicles - Part 6: Fire control and management systems [2] ARGE Guideline - Part 1: "Fire detection in rolling stock" ARGE Guideline - Part 2: "Fire fighting in rolling stock" ARGE Guideline - Part 3: "System functionality fire detection and fire fighting systems in rolling stock" [3] EN 54-2: Fire detection and fire alarm systems - Part 2: Control and indicating equipment EN 54-3: Fire detection and fire alarm systems - Part 3: Fire alarm devices - Sounders EN 54-5: Fire detection and fire alarm systems - Part 5: Heat detectors - Point detectors EN 54-7: Fire detection and fire alarm systems - Part 7: Smoke detectors - Point detectors using scattered light, transmitted light or ionization EN 54-17: Fire detection and fire alarm systems - Part 17: Short-circuit isolators EN 54-18: Fire detection and fire alarm systems - Part 18: Input/output devices INTERNET REFERENCES: [4] http://www.apollo-fire.co.uk/media/2863/pp2099_open,_closed_and_digital_protocols_- _what_does_it_all_mean_issue_4.pdf (Zugriff am 06.03.) FIRE-SAFETY Symposium (26-27 March ) 10