FUNDERMAX GMBH FIRE TEST REPORT

Similar documents
FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

SIGMADEK, LTD. FIRE TEST REPORT

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio

Fire Performance of Translucent Systems

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL

PERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

We Identify and S.T.O.P. Your Noise Problems

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

PERFORMANCE TEST REPORT. Rendered to: SOLATUBE INTERNATIONAL, INC.

ENGINEERING EVALUATION

CAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"

ASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet

Public Comment No. 2-NFPA [ Section No ]

Refrigerating Appliance DOE Test Report

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

CAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK 13045

GUARDIAN FIRE TESTING LABORATORIES, INC.

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

CAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

Report of Surface Burning Characteristics Test on Acoustical Panel

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

Declaration of Conformity

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

TEST REPORT. Contact No: SAMPLE NOT DRAWN BY OUR LABORATORY. THE RESULTS RELATE ONLY TO THE ITEMS TESTED

Refrigerating Appliance ErP Test Report

Abrasion Resistance of Fluoropolymer and polyester Coatings

Fire Risk and CODE Compliance For Fabric Wrapped Acoustic Panels

BCTC CARPET TECHNICAL CENTRE

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

January 26, Mr. Larry Sunshine Bentax USA 418 Meadow Street Fairfield CT Dear Mr. Sunshine:

Acoustical Surfaces, Inc.

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198"

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

CAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"

In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Classification of Fire Performance of Wall and Ceiling Lining Materials

CLT Adhesive Tests in Support of Mass Timber Buildings

Glass fibre rovings - Non-metallic materials

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

Heat and Smoke Release of a Ceiling-Installed Speaker

Environmental Health & Safety Policy & Procedure #24

Guidance Note. 3. Fire Propagation and flame Flame Spread in in Powder Coatings. Abrasion Resistance of Fluoropolymer and polyester Coatings

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

Test report for a Teldor Cables SLA-6-01X08- ZAHRH-DD Fibre Optic cable to IEC :1999

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

D U R ETHAN AND POCAN F OR THE ELECTRI CAL IN D U STRY N EW HALOGE N-FRE E FLAME-RETARDANT

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS

BS 476: Part 6: 1989+A1:2009

Transcription:

FUNDERMAX GMBH FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON 19 MM MAX COMPACT REPORT NUMBER I0002.02-121-24 TEST DATE 01/29/18 ISSUE DATE 02/16/18 RECORD RETENTION END DATE 01/29/22 PAGES 10 DOCUMENT CONTROL NUMBER RT-R-AMER-Test-2780 (10/18/17) 2017 INTERTEK

REPORT ISSUED TO FUNDERMAX GMBH Klagenfurter Str. 87-89 9300 St. Veit an der Glan Austria SECTION 1 SCOPE Intertek Building & Construction (B&C) was contracted by FunderMax GmbH, Veit an der Glan, Austria, to evaluate the flame spread and smoke developed properties of 19 mm MAX Compact. Testing was conducted at the Intertek B&C test facility in York, Pennsylvania. Results obtained are tested values and were secured by using the designated test method(s). A summary of test results and the complete graphical test data is reported herein. This report does not constitute performance certification of this product nor an opinion or endorsement by this laboratory. SECTION 2 SUMMARY OF TEST RESULTS Specimen I.D.: 19 mm MAX Compact by FunderMax GmbH ASTM E84 Test Results FLAME SPREAD INDEX SMOKE DEVELOPED INDEX 25 130 For INTERTEK B&C: COMPLETED BY: Ben Samson REVIEWED BY: Ethan Grove TITLE: Technician Fire Testing TITLE: Manager Fire Testing SIGNATURE: SIGNATURE: DATE: 02/16/18 DATE: 02/16/18 BTS:ddr This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample(s) tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Version: 10/18/17 Page 2 of 10 RT-R-AMER-Test-2780

SECTION 3 TEST METHOD The specimens were evaluated in accordance with the following: ASTM E84-17a, Standard Test Method for Surface Burning Characteristics of Building Materials SECTION 4 MATERIAL SOURCE/INSTALLATION The test specimen was submitted to Intertek directly from the client. Samples were not independently selected for testing. Intertek has not verified the composition, manufacturing techniques or quality assurance procedures. The specimens, identified as 19 mm MAX Compact by FunderMax GmbH, were received in good order. SECTION 5 LIST OF OBSERVERS NAME Ben Samson Nate Brillhart COMPANY Intertek B&C Intertek B&C Version: 10/18/17 Page 3 of 10 RT-R-AMER-Test-2780

SECTION 6 TEST PROCEDURE This report describes the results of testing conducted in accordance with ASTM E84-17a; Standard Test Method for Surface Burning Characteristics of Building Materials. The test method is for comparative surface burning behavior of building materials by determining a flame spread index (FSI) and a smoke developed index (SDI). This test is generally applicable to exposed surfaces, such as finish materials for ceilings or walls, provided that the material or assembly of materials, by its own structural quality or the manner in which it is tested and intended for use, is capable of supporting itself in position or being supported during the test period. The use of supporting materials on the underside of the test specimen may lower the flame spread index from that which might be obtained if the specimen could be tested without such support. This method may not be appropriate for obtaining comparative surface burning behavior of some cellular plastic materials. Testing of materials that melt, drip, or delaminate to such a degree that the continuity of the flame front is destroyed, results in low flame spread indices that do not relate directly to indices obtained by testing materials that remain in place. ASTM E84-17a Section 1.3 The purpose of the method is to determine the relative burning behaviour of the material by observing the flame spread along the specimen. Flame spread and smoke density developed are reported, however, there is not necessarily a relationship between these two measurements. It is the expressed intent of the test method to provide only comparative measurements of surface flame spread and smoke density of the tested material against measurements for select grade red oak flooring and fiber-cement board when tested under specific fire exposure conditions. The test method exposes a nominal 24-ft (7.32-m) long by 20-in. (508-mm) wide test specimen to a controlled air flow and flaming fire exposure adjusted to produce a specific flame spread distance vs time calibration using select grade red oak flooring. The test method does not provide information regarding heat transmission through the tested surface, the effect of aggravated flame spread behavior resulting from the proximity of combustible walls and ceilings, or the classification or definition of materials as non-combustible using flame spread index alone. This standard should be used to measure and describe the properties of materials, products, or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products, or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment which takes into account all of the factors which are pertinent to an assessment of the fire hazard of a particular end use. There were no deviations from the requirements prescribed in ASTM E84. Version: 10/18/17 Page 4 of 10 RT-R-AMER-Test-2780

SECTION 7 TEST SPECIMEN DESCRIPTION MANUFACTURER* FunderMax GmbH PRODUCT TYPE* High pressure laminate (HPL) SERIES/MODEL* MAX Compact COMPOSITION* High pressure decorative laminates (HPL) acc. To EN 438 type CGS sheets based on thermosetting resins (usually called laminates) CONDITIONING TIME 72+ hr. SPECIMEN SIZE 24 in. wide x 161-1/2 in. long THICKNESS 3/4 in. SPECIMEN SECTIONS 2 TOTAL WEIGHT 145.3 lbs. COLOR White SIDE TO FLAME* Client specified material was bilateral SUPPORT USED* Material was self-supporting MOUNTING METHOD Material was self-supporting SUBSTRATE USED* No substrate was utilized CEMENT BOARD 1/4 in. thick fiber cement board was placed on top of the sample. *From the client's material description and/or instructions Note: Specimens were conditioned as per the requirements of Section 6.4 of ASTM E84. Version: 10/18/17 Page 5 of 10 RT-R-AMER-Test-2780

SECTION 8 TEST RESULTS TEST RESULTS Test Date 01/29/18 Test Operator Ben Samson Flame Spread Index (FSI) 25 Smoke Developed Index (SDI) 130 Red Oak Calibration (% * Min) 91.14 TEST DATA FSI (unrounded) 26.2 SDI (unrounded) 129.8 FS * Time Area (Ft * Min) 50.8 Smoke Area (% * Min) 118.3 Fuel Area ( F * Min) 6076.9 TEST OBSERVATIONS Ignition Time Max Flame Front Advance Time to Max Flame Front Max Temp At Exposed T/C Time To Max Temp Dripping Observed Flaming On Floor Observed After Flame Top Observed After Flame Floor Observed Sagging Observed Delamination Observed Shrinkage Observed Fallout Observed Cracking Observed Observations After the Test 01:18 (Min:Sec) 7.4 Feet 06:52 (Min:Sec) 751.1 F 09:58 (Min:Sec) 05:17 (Min:Sec) 10:02 (Min:Sec) 10:02 (Min:Sec) 00:29 (Min:Sec) Version: 10/18/17 Page 6 of 10 RT-R-AMER-Test-2780

SECTION 9 PHOTOGRAPHS Photo No. 1 Exposed Surface of the Test Specimen (Pre-test) Photo No. 2 Unexposed Surface of the Test Specimen (Pre-test) Version: 10/18/17 Page 7 of 10 RT-R-AMER-Test-2780

SECTION 9 (Continued) PHOTOGRAPHS Photo No. 3 Unexposed Surface of the Test Specimen (Post-test) Photo No. 4 Exposed Surface of the Test Specimen (Post-test) Version: 10/18/17 Page 8 of 10 RT-R-AMER-Test-2780

SECTION 10 GRAPHS Graph No. 1 - Flame Spread Distance Versus Time Graph No. 2 Light Obscuration Versus Time Graph No. 3 Tunnel Air Temperature Versus Time Version: 10/18/17 Page 9 of 10 RT-R-AMER-Test-2780

SECTION 11 REVISION LOG REVISION # DATE PAGES REVISION 0 02/16/18 N/A Original Report Issue Version: 10/18/17 Page 10 of 10 RT-R-AMER-Test-2780