Manual No: Revision: D. Sump Sensor. Installation Guide

Similar documents
Manual No: Revision: D. Mag Sump Sensor. Installation Guide

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps

Interstitial Liquid Sensor - Fiberglass Tanks

Manual No: Revision: J. Groundwater Sensor. Installation Guide

Manual No: Revision: H. MicroSensor. Installation Guide

2 To 1 Sensor Input Box

Manual No: Revision: C. Overfill Alarm. Installation Guide

Manual No: Revision: G. Sensor Products. Application Guide

Installation Instructions. Remanufactured Veeder-Root Position Sensitive Sump Sensor. PMP # Replaces Veeder-Root #

Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors

Installation Instructions. Remanufactured Veeder-Root Sump Sensor. PMP # 62208, Replaces Veeder-Root # , -209

Installation Instructions. Remanufactured Veeder-Root Steel Tank Interstitial Sensor. PMP # 62420, Replaces Veeder-Root # , -460

FMP-ULS UNIVERSAL LIQUID SENSOR INSTALLATION GUIDE

Installation Instructions. Remanufactured Veeder-Root Overfill Alarm and. Acknowledgement Switch. Overfill Alarm PMP # OEM #

FMP-HIS AND FMP-HIS-U INSTALLATION GUIDE

Installation Instructions Manual No: Revision F

Instruction Sheet LTR - Low Water Cutoff for Hot Water Boilers

FMP-MWS. (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions

Variable Speed Flow Controller

FMP-DDS & FMP-DTS. Discriminating Dispenser Sump & Turbine Sump BriteSensor. Installation Instructions

FMP-DIS & FMP-EIS. Interstitial BriteSensor & Standard Sensor. Installation Instructions

AeroVent 3X Product Manual

FMP-DVS. Monitoring Well Discriminating Vapor Sensor (BriteSensor ) Installation Instructions

Installation Guide

Fuel Management System Setup Guide

AeroVent 1 Product Manual

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

Instruction Manual. Double Candy Apple Cooker

MN908 No. 282C Replaces 282B LB7013

INSTALLATION INSTRUCTIONS

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

C A Heating Cable Gland Kit

1SC-SSC Splice Connection Kit Installation Instructions

20 High velocity Air

WET/DRY VACUUM. QUEST for Continuous Improvement Windsor s Quality Management System is Certified ISO MODEL: T1. Operating Instructions (ENG)

Instruction Manual. Portion Cup Cheese Warmer

Colibri. Automatic Tank Gauge CL6 Series Installation Guide

150 WATT PORTABLE CLAMP LIGHT 35149

ELECTRIC FIREPLACE HEATER WITH SINGLE GLASS DOOR

MODEL HBX-1 P/N 3G59332

Model 2016, 2025, 2025BN, 2025ST Staging Cabinets Instruction Manual

Instruction Manual. Spiral Slicer

MC MC MC MC MC833130

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

Refrigerant Recovery Machine. Model No Operating Manual

AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions

Intrinsically Safe Transmitters, Option Code 2n

MaxLite LED High Bay Fixtures

DUST FREE CARBON Whole House Air Purifier

Instruction Manual. 36 in. and 42 in. Popcorn Staging Cabinets

INSTALLATION INSTRUCTIONS

ALL WEATHER SL-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL

DEDPV-705, DEDPV-705 Hi Alt Dryer Exhaust Duct Power Ventilator (DEDPV)

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

55-Gallon Dispenser Package

RK/ RK Oxygen Detector Operator s Manual

MODELS 304GC, 304GCX, 314GC, and 314GCX

JBM-100-LBTV2 Power Connection, Powered Splice, Dual Power Connection, or Splice with Junction Box

Installation Instructions

Hot Dog Roller Grills

TS-RA1, TS-RA2 and TS-RK Tank Overfill Alarms

Henny Penny Island Warmer Model HMI-103 Model HMI-105 TECHNICAL MANUAL

AeroVent Standard Product Manual

Instruction Manual. Dogeroo, Super Dogeroo, and Mini Dogeroo

INSTALLATION USE & CARE MANUAL ALL WEATHER SL-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER

Installation Manual September Opticom Infrared System. Model 798 Emitter Bezel Mount Kit

COMPRESSOR SERVICE REPLACEMENT KIT P/N (WCC 500A, 115/60, AIR COOLED)

PAT LOAD MOMENT INDICATOR DS 150 / 0038

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

AVANI Grinding Booth

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

Installation, Operation & Service Manual

1500W STOVE HEATER INSTRUCTION MANUAL. Item No: 050-HA-50090

Instruction Manual. Astro Staging Cabinet

(HSTAT Series) Instruction Manual

RK-02 Multi Point Detector Operator s Manual

Installation and Operating Guide Document No Vacuum Chambers Copyright 2017 Terra Universal Inc. All rights reserved.

Installation and Operation Manual

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

Pump Out Vacuums Polyethylene & Steel

IMPORTANT INFORMATION - PLEASE READ CAREFULLY

Canister Vacuums S6EVO. Operations and Parts Manual. Models: S6EVO

SSS BPV- 40 Backpack Vacuum

Parts and Service Manual BURNISHER MODEL: MR , MR , MR , MR

COOPER POWER SERIES. CT Protector Retrofit Kit. Voltage Regulators MN225057EN. Effective March 2017 Supersedes March 2010 (S )

Wrap-Around TOTE Tank / IBC Heaters (TOTE and TOT Series)

Instruction Manual. Carmel Apple-Dip Warmer

52 CEILING FAN. Owner s Manual Models #50336, 50337

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

3-1/2 Gallon Parts Washer

Owner s Manual & Safety Instructions

Technical Data. Installation

DBF 4XL Dryer Booster Fans

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

User s Manual and Operating Instructions

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

Transcription:

Manual No: 576013-301 Revision: D Sump Sensor Installation Guide

Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this publication. Veeder-Root reserves the right to change system options or features, or the information contained in this publication. This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root. DAMAGE CLAIMS 1. Thoroughly examine all components and units as soon as they are received. If damaged, write a complete and detailed description of the damage on the face of the freight bill. The carrier's agent must verify the inspection and sign the description. 2. Immediately notify the delivering carrier of damage or loss. This notification may be given either in person or by telephone. Written confirmation must be mailed within 48 hours. Railroads and motor carriers are reluctant to make adjustments for damaged merchandise unless inspected and reported promptly. 3. Risk of loss, or damage to merchandise remains with the buyer. It is the buyer's responsibility to file a claim with the carrier involved. RETURN SHIPPING For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy" and "Parts Return" pages in the "Policies and Literature" section of the Veeder-Root North American Environmental Products price list. Veeder-Root 2003. All rights reserved.

Table of Contents Introduction Related Manuals...1 Contractor Certification Requirements...1 Safety Precautions...1 Sensor Installation Installation Hardware...3 Site Preparation...3 Mounting Sensor to Support Member...3 Wiring Procedure...5 Figures Figure 1. Sensor Mounting Examples...4 Figure 2. Sensor Field Wiring Diagram...5 Figure 3. Epoxy Sealing Field Connections...5 1

2 Table of Contents

Introduction This manual contains installation procedures for the Veeder-Root Sump Sensor (Part No. 794380-208 or 794380-209), in the following Veeder-Root consoles: TLS-3XX Consoles ILS-350 Console This manual assumes field wiring has been run from the console to the sump in which the sensor will be installed following instructions in the appropriate console s site prep manual. Important! Sump Sensor field wiring must not be connected to the console prior to sensor installation. Related Manuals Depending on your installed console, you must reference the appropriate manual below for sensor-to-console connections: 576013-879 TLS-3XX Consoles Site Prep Manual 576013-773 ILS-350 Console Site Prep and Installation Guide Contractor Certification Requirements Veeder-Root requires the following minimum training certifications for contractors who will install and setup the equipment discussed in this manual: Level 1 Contractors holding valid Level 1 Certification are approved to perform wiring and conduit routing, equipment mounting, probe and sensor installation, tank and line preparation, and line leak detector installation. Level 2/3 Contractors holding valid Level 2 or 3 Certifications are approved to perform installation checkout, startup, programming and operations training, troubleshooting and servicing for all Veeder-Root Tank Monitoring Systems, including Line Leak Detection and associated accessories. Warranty Registrations may only be submitted by selected Distributors. Safety Precautions The following safety symbols may be used throughout this manual to alert you to important safety hazards and precautions EXPLOSIVE Fuels and their vapors are extremely explosive if ignited. FLAMMABLE Fuels and their vapors are extremely flammable. OFF TURN POWER OFF Live power to a device creates a potential shock hazard. Turn Off power to the device and associated accessories when servicing the unit. INJURY Careless or improper handling of materials can result in bodily injury. 1

Sump Sensor Installation Guide Safety Precautions GLOVES Wear gloves to protect hands from irritation or injury. WEAR EYE PROTECTION Wear eye protection when working with pressurized fuel lines or epoxy sealant to avoid possible eye injury. READ ALL RELATED MANUALS Knowledge of all related procedures before you begin work is important. Read and understand all manuals thoroughly. If you do not understand a procedure, ask someone who does. WARNING This product is installed in areas where flammable liquids and explosive vapors may be present. Fire or explosion resulting in serious injury or death could result if the equipment is improperly installed or modified. Serious contamination of the environment may also occur. 1. Read and follow all instructions in this manual, including all safety warnings. 2. Comply with all applicable codes including: the National Electrical Code; federal, state, and local codes; and other applicable safety codes. 3. Sensor wiring conduit must not contain any other wires and must enter the console only through their designated knockouts. 4. Substitution of components may impair intrinsic safety. 2

Sensor Installation Installation Hardware The Sump Sensor s Installation kit is shown in Table 1: Table 1. Sump Sensor Installation Kit (P/N 330020-076) Item Qty. Description Part No. 1 2 Mounting strip 330314-001 2 2 #4-20 x 3/8 Plastite screw 510500-398 3 3 1/4-20 x 1/2 Bolt, hx hd 503328-001 4 3 1/4-20 Speed nut 511000-232 5 2 Wire nut 576008-461 6 1 Sealing pack 514100-304 7 1 Cord grip 331028-001 8 2 Tie wrap 510901-337 Site Preparation OFF 1. Check that the Sump Sensor s field wiring is not connected to the console. Mounting Sensor to Support Member 1. Make sure no liquid exists in the sump. Failure to comply can result in undetected potential environmental and health hazards. 2. Attach one of the mounting strips to the top of the sensor using the 2 Plastite screws provided as shown in Figure 1. Important! The sensor must be positioned in the lowest part of the sump and it must be mounted in a true vertical position to ensure proper operation of the float switch contained inside. 3. Depending on your mounting requirements (again see Figure 1), attach the second mounting strip to the first strip using two 1/4-20 x 1/2-inch screws and speed nuts. With the sensor resting on the bottom of the sump, wrap the mounting strip around the support member and secure it using a 1/4-20 x 1/2-inch screw and speed nut. 4. Carefully bend the mounting strip so that the sensor is in a true vertical position and still rests on the bottom of the sump. 5. Install the cord grip into the junction box. Feed the sensor cable through the cord grip on the junction box. Tighten the cord grip nut to ensure a water-tight seal at the cable entry. 3

Sump Sensor Installation Guide Mounting Sensor to Support Member Existing conduit or piping Cable to junction box and seal-off (see below) Cable to junction box and seal-off (see below) Product pipe Sump sensor* (installation examples) Sump base *Sump sensor should: 1. Rest on the base of the sump. 2. Be positioned as close to outer wall as possible. 3. Be mounted in a true vertical position. 4. Be installed only in a dry sump. Cord grip Weatherproof junction box with 1/2-inch N.P.T. threads (16 cubic inch volume minimum) Epoxy seal per NFPA specs Cable from piping sump sensor Rubber grommet seal clamped on inside - or as recommended by sump manufacturer Sump 1/2'' Rigid conduit to console sensors\pssinst.eps Figure 1. Sensor Mounting Examples 4

Wiring Procedure 1. Using wire nuts, connect the two-wire sensor cable to the field wires in the sensor junction box (see Figure 2). Note, the Sump Sensor wiring has no polarity. To Interstitial Sensor Interface Module Seal-off Black Red From Sensor sensors\pswir.eps 1/2'' rigid conduit Epoxy sealed connections in a weatherproof junction box Figure 2. Sensor Field Wiring Diagram 2. Do NOT terminate drain wire at this location, ground drain wire at console only. 3. Seal wire nuts with epoxy sealant following the instructions in Figure 3. CAUTION: Epoxy sealant is irritating to eyes, respiratory system, and skin. Can cause allergic skin reaction. Contains: epoxy resin and Cycloaliphatic epoxycarboxylate. Precautions: Wear suitable protective clothing, gloves, eye, and face protection. Use only in well ventilated areas. Wash thoroughly before eating, drinking, or smoking. 4. Push the epoxy sealed bag into the junction box. Replace and tighten the junction box cover. A B C From probe, sensor, or transducer To console Make sure that the ends of cable sheathing are submerged in sealant Tie wrap Wire nuts Instructions: NOTE: When temperature is below 50 F (10 C), keep resin in a warm place prior to mixing (e.g., in an inside pocket next to body). 1. Open epoxy sealant package, and remove resin pak. 2. Holding resin pak as shown in A, bend pak along long length. 3. As shown in B, firmly squeeze the RED SIDE of the resin, forcing it through the center seal and into BLACK SIDE. 4. Mix thoroughly to a uniform color by squeezing contents back and forth 25-30 times. 5. Squeeze mixed, warm resin into one end of bag and cutoff other end. 6. Slowly insert wiring connections into sealing pack until they fit snugly against the opposite end as shown in C. 7. Twist open end of bag and use tie wrap to close it off and position the tie wrapped end up until the resin jells. probes\epxy2w.eps Figure 3. Epoxy Sealing Field Connections 5. Consult the appropriate console site prep manual to connect the Sump Sensor to the console. 5

Veeder-Root has sales offices around the world to serve you. Headquarters 125 Powder Forest Drive Simsbury, CT 06070-7684 Tel: (860) 651-2700 Fax: (860) 651-2719 Email: marketing@veeder.com