ADRIATIC VF. Active chilled beam with cooling, heating and ventilation QUICK FACTS

Similar documents
Swegon PACIFIC. Integrated chilled beam PACIFIC CHILLED BEAM KEY FIGURES

PARASOL EX. Suspended comfort modules QUICK FACTS

PARAGON. Compact comfort module. Key figures

ADAPT Parasol EX. Energy-saving, suspended comfort module QUICK FACTS

Primo Hotel. General. Indoor climate units for hotel rooms

Waterborne Climate Systems

CHILLED BEAM CASSETTE IQ STAR LYRA

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

iq Star LYRA II chilled beam cassette

KLIMA Active Chilled Beams

Units for suspended ceilings

iq Star LYRA II chilled beam cassette

Units for suspended cei lings

CONDOR. Supply air ceiling QUICK FACTS

Use. Worth noting. Key figures. Installation. linx industries chilled beams. the beam is mounted on a standard T-support.

Use. Worth noting. Key figures. Installation. linx industries chilled beams

Product Data. Features/Benefits. 36CBAC,AE,AF,AH,AQ,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm

COMPACT Air & Heat. Contents

Passive chilled beams

PARAGONTM Comfort module for hotel rooms and hospital wards

lindab ventilation Lindab Comfort Waterborne indoor climate solutions Product overview

Units for suspended ceilings Type DID632

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

Contents. Technical Description of the Air Handling Unit General, Specification Function, Functional Sections

HOTEL CHILLED BEAM IQ STAR SILENCIA

Polaris-I-60. active chilled beam. the future of space conditioning

Cooling Strip Model SPB

Ceiling diffusers. Type DLQL

Demand-controlled Ventilation Leading edge products for demand-controlled ventilation

Chilled Ceiling Elements

LindabArchitect. Supply air beam. lindab we simplify construction

Halton Rex for Vario R6O - Variable air volume chilled beam

Active Chilled Beams

LYRA » ENERGY EFFICIENT CASSETTE CHILLED BEAM AIR DIFFUSION LYRA

lindab we simplify construction LindabIndoorClimateSolutions Product overview Airborne Solutions

Halton Rex 600 Basic R6B - Active chilled beam

Type VDW WITH LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH INDIVIDUALLY MANUALLY ADJUSTABLE AIR CONTROL BLADES

SEMCO CHILLED BEAMS INDOOR AIR QUALITY AND ENERGY SAVINGS FANLESS FILTERLESS SPACE CONDITIONING

Ceiling swirl diffusers

Carat. Chilled beams. Use. Worth noting. Installation. Key figures. lindab chilled beams

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD

LindabCapella. Supply air beam

Ceiling swirl diffusers

ACBH/ACBV ACTIVE CHILLED BEAM INSTALLATION MANUAL. Date: 05/12 Reference # : L-50.

Halton CPT Passive Chilled Beam

CASSETTE UNIT. Comfort Circle

Swegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION

Air distribution systems. Opticlean OC-Q...

Krantz. Multifunction exposed ceiling AVACS. Cooling and heating systems

System architecture. Air treatment Index

NEW AR-L AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS. Higher energy efficiency. Increased thermal comfort

Displacement Ventilation

U tube models PTU 09, 12, 15, 25, 30, 35, 40, 45. single linear tube models PTS 09, 12, 15, 25, 30, 35, 40, 45

Optimizing the use of Chilled Beams for health and comfort GUNNAR SVENSSON

Super WISE. System product for Swegon s system for demand-controlled ventilation

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

TTC. TTC Active supply air diffuser. Product description SUPPLY AIR DIFFUSER - ACTIVE [CEILING MOUNTED] Introduction. Simplicity

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

42 Kevlar. Instruction Manual. Kichler Lighting 7711 East Pleasant Valley Road P.O. Box Cleveland, Ohio

SECTION AIR DUCT ACCESSORIES

60" Tulle PatioTM. Instruction Manual. A Kichler Select ceiling fan

CHH - Active Chilled Beam. Halton CHH. Active Chilled Beam

GOLDTM. Air Handling Units with Built-in Control Equipment that offer Economical Operation.

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Air distribution systems. Opticlean OC-Q... DS 4136 E /1

TTC. TTC Active supply air diffuser. Product description. Introduction SUPPLY AIR DIFFUSER - ACTIVE [CEILING MOUNTED] Simplicity

System technology. Demand controlled ventilation WISE.

Contact, Overview, Index. Ceiling Heating/Chilled. Plexus. Professor. Pilot. Architect. Polaris I & S. Plafond. Podium. Celo. Cabinett. Capella.

Linear Floor Heaters

Instructions for the BASIC Air Handling System, Sizes General 1.1 Description of the System

1. SAFETY RULES WARNING WARNING. 8. Avoid placing objects in the path of the blades.

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

TELLUS. Complete HVAC substation for air handling, cooling, heating and hot tap water. Main benefits. General

Modular Active. Chilled. Beams

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

installation, operation & Maintenance manual Floor-mounted Induction units acb 30/35

installation, operation & Maintenance manual Floor-mounted Induction units

Installation S

THE QUALITY BRAND IN FANS

LØV-R. Svalbard-H. Chilled beam for corner installation between wall and ceiling

raymagic quad Installation, Operation & Maintenance Manual

installation, operation & Maintenance manual acb ceiling-mounted cassette models

Chilled Beam/Induction Unit

Ceiling air diffuser INDULTHERM INDULTHERM-e

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

TELLUS. Complete HVAC substation for air handling, cooling, heating and hot tap water. Main advantages. General

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

Energy-efficient heat source provides comfort in large rooms

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008

Easy Dose Chemical Injection and Dispensing System DEMA Engineering Company

DADANCO E U R O P E. Induction unit. Installation, operation & maintenance manual. Induction Units

Air Conditioning Clinic

Swegon CASA R120. Ventilation unit with rotary heat exchanger HOME VENTILATION

Installation S

39HX. High-efficiency dual-flow air handling unit PRODUCT SELECTION DATA. Plug & play unit (built-in control) Class A+ across entire range

LEGEND: ROOMS ROOMS ACMV OVERHAUL HANGER LAYOUT FOR 202&203 SECOND MEZZANINE FLOOR TYPICAL FRONT ELEVATION FOR HIGHWALL MOUNTED INDOOR UNIT

Transcription:

Active chilled beam with cooling, heating and ventilation QUICK FACTS The ADRIATIC VF is a chilled beam with integrated recirculated air opening in the face plate. Air is discharged into the room along the ceiling. Integrated VariFlow airflow distribution for simple adjustment at the site. An attractive chilled beam designed for suspended installation. Cooling capacity Btuh/ft CFM/ft inwg T mk F T l F 520 6.5 0.24 18 18 614 9.7 0.22 18 18 708 12.9 0.22 18 18 Primary airflow: Pressure range: Total cooling capacity: Heating capacity: Size - Length: Width: Height: Up to 125 CFM.12 to.28 inwg Up to 9563 BTU/hr Up to 11612 BTU/hr From 48 to 142 in. (nominal) increments of 24 in. 14.3 in. 6.8 in.

Contents Technical description... 3 Operation... 4 Installation... 4 ADRIATIC VF with VariFlow... 6 ADRIATIC VF with ADC... 7 Accessories... 8 Technical Data... 9 ProSelect... 10 Acoustics...11 Dimensions... 12 Specification... 14 Product... 14 Accessories... 15 Temperature, airflows and communication... 16 2 Swegon reserves the right to alter specifications. 04-05-2016

Technical description ADRIATIC VF The ADRIATIC VF is a closed, active climate beam with two-way air discharge. Cooling and ventilation or cooling, heating and ventilation. Installation The ADRIATIC VF is designed for suspended installation from hangers or mounting directly against the ceiling. Connection dimensions: Cooling (water): plain pipe end with available 1/2-inch NPT connector. Heating (water): plain pipe end with available 1/2-inch NPT connector. Air: 5 inch nominal duct connection Suspension: The units are delivered without mounting accessories. If mounting accessories are required, they can be ordered separately. The SYST MS M8 assembly piece is required for suspended installation from hangers. The SYST MD4S is required for mounting the beam directly against the ceiling Operation Cooling Heating (optional) Ventilation ADC air deflectors VariFlow airflow distribution Application The ADRIATIC VF is well-suited for use in all types of rooms with waterborne climate cooling: Offices and conference rooms Hotels Classrooms Data processing rooms Bank premises Restaurants Advantages of the ADRIATIC VF The ADRIATIC VF has an attractive design and extremely low installation height that fits well in all types of room decor. Since the ADRIATIC VF is a closed climate beam with integrated recirculating air opening in the face plate, it can be mounted directly against the ceiling without affecting circulation air slots. The ADRIATIC VF combines the superior air discharge properties of ceiling units with the stringent design requirements of suspended climate beams. The discharge of air along the ceiling provides the optimal coanda effect that is always the objective when it is desirable to maintain low air velocities in the occupied zone. The connection components, valves and dampers are concealed in a simple manner by an attractive connection casing. The casing is installed after the climate beam has been suspended and connected. Swegon s ADC air diffusers, which are standard, provide for the adjustment of the air throw performance of the climate beam. Integrated VariFlow airflow distribution for simple volume adjustment on-site. The airflow can be varied to suit the application by means of nozzle strips. The fixed nozzles guarantee that the airflow will be correct and all-in-all offers a flexible and simple solution. www.eurovent-certification.com www.certiflash.com 04-05-2016 Swegon reserves the right to alter specifications 3

Operation Installation Figure 1. Cooling and ventilation. A = Room air B = Primary air and chilled room air Figure 2. Heating and ventilation. A = Room air B = Primary air and heated room air Figure 3. Typical installation, showing optional water valves and actuators, air balancing damper, installation kit and controls. 4 Swegon reserves the right to alter specifications. 04-05-2016

Range of products held in stock: Inquire with your nearest Swegon office for current stock levels. Available to order: With horizontal connection: 48 to 144 inches nominal. Inquire about special sizes. With vertical connection: 60 to 168 in. nominal. Inquire about special sizes. Standard lengths above are available with 24 in. increments. Flexible nozzle configuration by means of VariFlow Nozzle configuration, i.e. the number of nozzle openings in the air duct for discharging air to the room. For further particulars, refer to ProSelect software. The number of nozzle configurations that are possible to set is enormous, however the basic concept is based on three different fixed nozzles: L = Low flow for low airflows, M= Medium Flow for medium-sized airflows, H= High Flow for high airflows and combinations of these. You can also combine the nozzle settings for the airflows if a one-way version is used (70/30%). Waterborne heating, Variant -B See the section on heating. Internal connection ( -I): With 12 in. empty section and end panel without openings for pipes and an air duct. Designed for vertical connection to the climate beam. For particulars of the capacity, calculate the active length as follows: L active = L rated - 12 in. ADRIATIC VF with ADC The Swegon ADRIATIC VF climate beam contains ADC as standard. ADC stands for Anti Draft Control, which enables you to set the diffusion pattern of the air being distributed to avoid risk of draft. A number of ADC sections with four air deflectors per section are arranged on each side of the unit. Each section is adjustable from a straight setting to 40 air deflection to the right or left in increments of 10. This provides enormous flexibility and can be easily adjusted without having to affect the system as a whole. The static pressure is not affected by ADC. The sound level increases slightly when the air deflectors are set for V-shape air discharge. For more information, see Swegon s ProSelect sizing program. The ADRIATIC VF with ADC, among others, offers the following benefits: Shorter distance between contra-discharging climate beams. Simple correction of the direction of air discharge to compensate for obstructions. Simple to adjust at the site. Enables the user to adjust the comfort setting in the room. Offers great flexibility for future conversion of the rooms. Special Types The ADRIATIC VF can, on enquiry, be supplied painted in an optional color or relief finish paint. For further particulars about special types, get in touch with your nearest Swegon representative. Figure 4. Access from below. 04-05-2016 Swegon reserves the right to alter specifications 5

ADRIATIC VF with VariFlow Swegon s built-in airflow diffuser can be set to three different positions and makes it possible to field-adjust the airflow. The ADRIATIC VF with VariFlow, among others, offers the following benefits: Shorter delivery time because the stocked products have a substantial working range. It is simple to change the airflow if changes are made in the installation. Asymmetrical airflow (for example 70/30%) can be set directly on the stocked product. Interacts very well with our ADC air deflectors. Combined, there is enormous potential to control air distribution patterns and air motion. Figure 5. Example of symmetrical air distribution with VariFlow. Figure 6. Example of asymmetrical air distribution with VariFlow. Figure 7. Example of displaced air distribution with VariFlow. 6 Swegon reserves the right to alter specifications. 04-05-2016

ADRIATIC VF with ADC The Swegon ADRIATIC VF climate beam contains ADC as standard. ADC stands for Anti Draught Control, which enables you to set the diffusion pattern of the air being distributed to avoid risk of draught. A number of ADC sections with four air deflectors per section are arranged on each side of the unit. Each section is adjustable from a straight setting to 40 air deflection to the right or left in increments of 10. This provides enormous flexibility and can be easily adjusted without at all having to affect the system as a whole. The static pressure is not at all affected by ADC. The sound level increases slightly when the air deflectors are set for V-shape air discharge. For more information, see Swegon s ProSelect sizing program. The ADRIATIC VF with ADC, among others, offers the following bebefits: Shorter distance between contra-discharging climate beams Simple correction of the direction of air discharge to compensate for obstructions Simple to adjust at the site Enables the user to adjust the comfort setting in the room Offers great flexibility for future conversion of the rooms. Figure 8. Swegon s ADC air deflectors. Figure 9. Flexible air discharge with ADC. 1. Climate beam with ADC set to V-shape. 2. Climate beam with ADC set to L-shape. 3. Climate beam with ADC set for avoiding obstacles. 04-05-2016 Swegon reserves the right to alter specifications 7

Accessories CRP Commissioning damper Circular commissioning damper with perforated damper blade designed for climate beam installations and a manual actuator with knob. FH Flexible connection hose Flexible hose with stainless steel braided jacket. Choice of lengths and threaded or push-fit connection to building chilled water supply. SYST CA Angled duct connection Connection piece for vertical connection, 90. T-KA Connection casing, connection against a wall Connection casing to be mounted in the extended section of the climate beam and beyond to a wall designed for concealing pipe and duct connections. MD4S assembly piece Special assembly piece for installation directly against the ceiling. SYST MS M8 assembly piece Assembly piece for suspended installation containing threaded rods of various lengths (7.9, 19.7 and 39.4 in.). Specify the length required as needed. The set also contains plastic caps designed for concealing the threaded rods and giving the beam a more attractive appearance. Ceiling mounting brackets, nuts and washers are included in the set. Recommended limit values water Max. recommended operating pressure: 230 PSI Max. recommended test pressure for 350 PSI testing a completed installation: Recommended min. cooling water flow: 0.5 GPM Increase in temperature, cooling water: 3.6-9 F Min. permissible inlet flow temperature: Should always be sized so that the system operates without condensation Decrease in temperature, heating water: 3.6-18 F Max. permissible inlet flow temperature: 140 F Recommended min. hot water flow: 0.21 GPM The min. recommended water flow per circuit ensures evacuation of any air pockets in the circuit. Figure 10. Installation directly against the ceiling, MD4. Figure 11. Casing for connection against a wall. 1. Remove the plastic end panel of the climate beam. 2. Attach the wall mounting bracket on the wall. 3. Push the mounting plate to fit over and rest on the top of the climate beam. 4. Fit the casing in the wall mounting bracket and against the beam. Lock the casing in position by pushing it up to engage in the mounting plate. 8 Swegon reserves the right to alter specifications. 04-05-2016

M H L ADRIATIC VF Technical Data Flexible nozzle configuration by means of VariFlow (see Figure 12) A large number of variants can be configured by adjusting the nozzle strips. Each nozzle strip is 24 in. long and can easily be adjusted with a supplied tool to the required position. There are three different settings (different sized fixed nozzles) on each nozzle strip: L= Low for low airflows M= Medium for medium large airflows H= High for high airflows Each side can also be freely configured for asymmetrical airflows. The number of nozzle strips for a certain length of beam is always the same. For specifying asymmetrical distribution, see Figure 13 which describes the mutual relation between the sides viewed from above (Top view) based on the arrangement of the water pipes. For more detailed information, refer to the Swegon Pro-Select sizing program available at the website: www.swegon.com There are different numbers of nozzle strips depending on the nominal length: 48 in. 4 nozzle strips (2 + 2 strips) 72 in. 6 nozzle strips (3 + 3 strips) 96 in. 8 nozzle strips (4 + 4 strips) 120 in. 10 nozzle strips (5 + 5 strips) 144 in. 12 nozzle strips (6 + 6 strips) Figure 13. air flow, pages 1-4. L/2 90 90 Figure 14. Pressure relationship, air. Figure 12. Change of nozzle configuration by means of an adjustment tool. p i = p s = p l = nozzle pressure (measured in the measurement hose or in the center of the nozzle). pressure upstream of the unit and damper. throttling range, mounted damper. 04-05-2016 Swegon reserves the right to alter specifications 9

ProSelect Cooling The cooling capacities have been measured in conformance with EN 15116 Standard. Detailed performance data is available online selection software ProSelect, available at www.swegon.com. The following can be read in the Proselect: The length of the climate beam (inches) The primary airflow (CFM) The noise level for an open damper, with ADC Nozzle pressure (inwg) Airborne cooling capacity (BTU) Waterborne cooling capacity (BTU) N.B. The total cooling capacity is the sum of the airborne and waterborne cooling capacities. 10 Swegon reserves the right to alter specifications. 04-05-2016

Table 1. Capacity, natural convection, cooling (BTU/hr) Length Temperature, room water, F ΔT mk 10.8 12.6 14.4 16.2 18 19.8 21.6 48 in. 168 205 243 287 328 376 420 72 in. 263 321 386 451 519 591 662 96 in. 359 441 526 615 710 806 905 120 in. 454 557 666 782 898 1021 1147 144 in. 550 676 809 946 1089 1239 1393 For a water flow of 1 GPM Heating Additional heat Heating coil The heating function is intended for use only as a supplement if surplus heat is available; however, during shorter periods a smaller amount of surplus heat will be needed, for example in the evening and at night. The supply air fan must then be in operation in order for the additional heat to reach the room. The supply air is used for mixing the warm air with chilled air, which is why the temperature distribution in the room is completely dependent on the ratio between supply air and the capacity taken from the climate beam. The heat is conducted along the ceiling which, in order to work properly, requires low supply flow temperature and a certain impulse. A temperature gradient of 9.7 F is normally obtained between floor and ceiling. Recommendations for heating operation Max. permissible inlet flow temperature: 140 F Min. permissible heating water flow:.21 GPM Nozzle pressure, p i : >.12 inwg For perimeter walls with large glazed surfaces, it is recommended that radiant heating in the ceiling or radiators along the perimeter wall be used for compensating the radiant cooling energy of the glazed surfaces. For advice concerning other conditions, contact Swegon. Acoustics Diagram 1 shows the total generated sound power (L Wtot db), as a function of the airflow and pressure drop across the damper. By correcting LWtot with the correction factors from Table 1, the sound power levels for the corresponding octave bands can be obtained (L W = L wtot + K ok ). Refer to ProSelect Web at www.swegon, for detailed acoustical analysis. Diagram 1. Throttling range of SYST CRPc 9-125 damper. inwg.80.40.20.16.12.08.04.02.016.012 40 45 50 L Wtot60 db 55.008 6.3 8.5 10.6 21.2 42.4 63.6 84.8 106 211.9 423.8 CFM 636 Table 2. Sound power level for CRPc 9-125 damper, Correction factor, K ok Size Mid-frequency (Octave band) Hz CRPc 63 125 250 500 1000 2000 4000 8000 125 0-2 -9-15 -20-25 -29-35 Tol. + 2 2 2 2 2 2 2 2 0% 100% 04-05-2016 Swegon reserves the right to alter specifications 11

Dimensions Figure 15. 4.9 in. duct connection, end view. A = Cooling, 1/2" NPT threaded connection or stub out for flexible hose. Figure 19. Internal connections (-I), long side view. L = Length, ADRIATIC VF Lu = length to the division of the face plate. Figure 16. 4.9 in. duct connection, end view. B = Heating, 1/2" NPT threaded connection or stub out for flexible hose. Figure 20. Internal connections (-I), top view. Installation space Length, ADRIATIC VF Nominal dimensions: 48, 72, 96, 120, 144 in. Length: Nominal.6 in (+.2 to.1 in.) Length to the division of the face plate, Lu = L / 2 Figure 17. Horizontal connections in end panel, long side view. L = Length, ADRIATIC VF Lu = length to the division of the face plate. Figure 21. SYST MS M8 assembly piece. Figure 18. Horizontal connections in end panel (-OH), top view. 12 Swegon reserves the right to alter specifications. 04-05-2016

F1 Figure 22. MD4S assembly piece. F20 F30 Figure 23. Internal connections (-I), vertical connections. The duct bend and hose must be ordered separately. Table 3. Dimensions, vertical connection to the climate beam. a b c d 6.8 in. 4.7 in. 7.1 in. (length of hose) 2.8 in. Figure 25. Flexible connection hose. SYST FH. FI = compression fitting, specify length. F20 = push-fit both ends, specify length. F30 = push fit to chilled beam, 1/2" NPT connection to building chilled water supply. Specify length. Contact nearest Swegon office for flexible hose options. Figure 24. CRPc 9-125 Commissioning damper. Table 4. Dimensions, SYST CRPc 9-125 a b c d 7.2 in. 4.9 in. 1.6 in. 1.7 in. 04-05-2016 Swegon reserves the right to alter specifications 13

Contractor demarcation/point of connection Specification Product Figure 26. Points of connection. A = Cooling: The plumbing or mechanical contractor connects the beam to the building chilled water supply. B = Heating: The plumbing or mechanical contractor connects the beam to the building chilled water supply. C = Ventilation: The ventilation contractor connects the beam to the primary air supply. Weight Table 5. Weight Weight per foot, ADRIATIC VF length < 96 in. length > 120 in. ADRIATIC VF c aa- b- c- dddd/dddd Climate beams Incl. ADC air deflectors Length: -OH: 48, 72, 96, 120, 144 in. -I: 60, 84, 108, 132, 165 in. Operation: A = Cooling and supply air B = Cooling, heating and supply air Connection: -OH = Horizontal connection -I = Internal connection Nozzle configuration: See ProSelect for selections. Dry weight 7.4 lbs/ft. 7.7 lbs/ft. Weight, filled with water 8.1 lbs/ft. 8.4 lbs/ft. Ordering examples Active climate beam for suspended installation with cooling, ventilation and length 96 in.: ADRIATIC VF c 96-A-OH (2L2M/2L2M). Ordering Key Type ADRIATIC VF active climate beam including ADC air deflectors for cooling and ventilation or cooling, heating and ventilation. The units are supplied painted in Swegon s standard shade of white, RAL 9003, gloss ratio 30 ±6%. Contractor demarcation Swegon s limits of supply are at the points of connection for water and air respectively. At these connection points, the pipework contractor connects to plain pipe ends, fills the system, bleeds it and tests the pressure in the circuits. The ventilation contractor connects to the duct connections with dimensions as specified on the basic size drawing under "Dimensions Contractor Demarcation/Points of connection". If valves and actuators are installed in the connection section, this must take place before the damper and ventilation duct is connected. When mounting a casing, the end panel must be removed before the unit can be mounted in the ceiling. The units are delivered without mounting parts for suspended installation. 14 Swegon reserves the right to alter specifications. 04-05-2016

Accessories Flexible connection hose (1) SYST FH F1 aaa 0.5 Clamping ring coupling against Connection casing ADRIATIC VF c T-KA aaa pipe on both ends Length: 11.8, 19.7, 27.6 in. Length: 4.7, 11.8, 19.7, 27.6 in. Dimension (Ø) 0.5 in. Loose end panel ADRIATIC VF c T-GL aa UH = Without openings MH = With openings Flexible connection hose (1) SYST FH F20 aaa 0.5 Quick-fit coupling (push-on) against pipe on both ends Length: 10.8, 18.7, 26.6 in. Dimension (Ø) 0.5 in. Asssembly piece (For installation directly against the ceiling) SYST MD 4S Asssembly piece SYST MS M8 aaaa- b- RAL9003 (For suspended installation) Length of threaded rod: 7.9, 19.7, 39.4 in. 1 = Threaded rod only 2 = Double threaded rods with thread locking device. Flexible connection hose (1) SYST FH F30 aaa 0.5 Quick-fit coupling (push-on) against pipe on one end, 1/2-inch NPT sleeve nut on the other end Length: 7.9, 15.7, 23.6 in. Dimension (Ø) 0.5 in. Connection piece (90 duct bend) SYST CA-125-90 Commissioning damper SYST CRPc 9-125 04-05-2016 Swegon reserves the right to alter specifications 15

OK ADRIATIC VF Temperature, airflows and communication CONDUCTOR The optimum solution for individual control of the temperature and airflow in each room. Can be easily modified for either demand-controlled or constant airflows. Communication is possible with Swegon s WISE system and with external supervision systems via Modbus. 8 7 6 5 9 4 10 1 3 2 23 C 1 = Controller 2 = Room unit with wireless or wired communication 3 = Valve actuator for cooling and heating water 4 = Condensate sensor As required: 5 = Communication via Modbus 6 = Transformer 7 = Motorized ventilation damper 8 = External temperature sensor 9 = Window contact 10 = Key card holder or presence sensor Guide specifications Contact Swegon for current guide specifications. 16 Swegon reserves the right to alter specifications. 04-05-2016