MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

Similar documents
MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130)

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

MANDATORY MEASURES MANDATORY LIGHTING CONTROLS (a) Area Controls: Manual controls that control lighting in each area separately

Here we see the list of auto shutoff controls we will cover in the next few slides

TITLE 24 ICONOGRAPHY. Iconography System

Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE

INSPECTION REQUIREMENTS: ENERGY CODE LIGHTING & ELECTRICAL NON-RESIDENTIAL

Code Review TITLE PRESENTED BY POURIA NIKNAM

MANDATORY MEASURES DAYLIGHTING. (Reference: Sub-Chapter 4, Section 130)

California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings

Hospitality Title Solutions

Are LED s ready for Prime Time?

Education Title Solutions

Office Title Solutions

WSA120: New Energy Codes and Lighting Controls

Healthcare Title Solutions

ASHRAE October 18, 2013

What s New in the 2013 Energy Code? Changes to mandatory Title 24 lighting requirements

Decoding 2016 Title 24, Part 6

California Title Design Guide for Smart Lighting Control and Energy Solutions

Note: A summary of the applicable code sections is shown in the CEC _Table100A.

Code Compliance Commercial Application Guide

visual environment technologies etcconnect.com

Codes and Controls Commercial Building Energy Code Requirements for Light Control. Michael Jouaneh, CEM, LEED AP September 20, 2012

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

MANDATORY MEASURES. There are two major steps for exterior spaces to comply with Title 24:

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Demand Responsive Lighting Controls

Lighting Summary - Interior

Lighting Control Strategies. to meet code requirements save energy and improve building performance

Dissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard & 2013

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

WELCOME TITLE 24 REQUIREMENTS & THE MAXLITE PRODUCT LINE. 9/5/14 Webinar Presented by: Greg Murphy

CA TITLE 24 QUICK SOLUTIONS GUIDE FOR

PRESCRIPTIVE APPROACH

Energy Codes. Connected Lighting simplified by Eaton. design and application guide

Aesthetic, energyefficient. control solutions for hospitality facilities QUICK GUIDE TO LIGHTING CONTROL FOR HOTELS

Best practices in lighting design to comply with California s Title 24 energy code

SENSORS. Vacancy Sensors. Occupancy Sensors A4-A7 A-1

Best practices in lighting design to comply with California s Title 24 energy code

Lighting Controls. Energy-Saving Solutions For Efficient Buildings

A Guide for Applicants and Lighting Designers

Wireless Lighting Control Made Easy

Lighting Application Guide for K-12 Classrooms

Advances in Lighting Controls and the Impact of ASHRAE Requirements. Rich Rattray, LC OSRAM SYLVANIA

Ceiling Mount Sensors B4-B9. Occupancy and Vacancy Sensors B10-B15 B16-B17. Wall Mount Occupancy Sensors B-1

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG-1-A

2018 IECC Electrical & Lighting Systems

ANSI/ASHRAE/IES

Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ Tel

Table of Contents. Fast Fact. Sensor Models 2 Advantages of Sensors 3 FAQs 4-5

Daylighting Control Design and Application Guide

Reduce lighting energy costs with controls

SECTION LIGHTING CONTROL DEVICES AND CONTROL PANELS

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2012

Advanced Lighting For Office

Application Guide to CA Title 24

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Oregon Non-Residential Building Energy Code

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

B. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.

August 15, 2013 Page 1 of 19

600 Watt Dimmer Install Guide

F series. echoflex. Slim Line Dimming Controller. Product Overview ER1S-FC

ANSI/ASHRAE/IES

visual environment technologies etcconnect.com

F series. Complete Room Controller. echoflex Powered by ETC. Product Overview ERDRC-FC

LPCMPIRM65 & LPCMPIRDSI65

Exit Routes. Introduction/Overview. OSHA Regulations. Exit Route

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

2016 Electrical Supplemental Plan Review List

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 26 ELECTRICAL

Dimming Ballast + Controls and CALCTP Bonus. New Product Overview

2017 Lighting Incentive

Product Guide. Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs.

Lighting Control Solutions for Parking Facilities

Distributed Low-Voltage Power System. design and application guide

Hubbell Controls Application Guide to CA Title 24 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING CONTROL

C A L I F O R N I A E N E R G Y C O M M I S S I O N

Time Warner Center at Columbus Circle, the home of Related s offices. Credit: Green Light New York

COMcheck Software Version Interior Lighting Compliance Certificate

Advanced Lighting Control for High Building Performance

Universal Lighting Technologies is a subsidiary of Panasonic Electric Works Co., Ltd., a member of the Panasonic Group. Technical Product Information

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

Chapter 17, Initiating Devices

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR

Dimmable General Area Use High Bay 320 Watt LED Light Fixture - Low Profile - High Efficiency

Indoor Controls. SpaceWise SWZG2. Wireless technology

Lumination LED Luminaires

Connectivity Control Confidence

Agency for Health Care Administration

NRG SYSTEMS, HINESBURG, VT

For additional information regarding R-3.1 residential care facilities please contact (951)

Applied Lighting Controls

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

2017 Michigan Energy Code Changes Electrical Provisions-Commercial Michigan Energy Code Training and Implementation Program

Transcription:

MANDATORY MEASURES INDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130.1)

MANDATORY LIGHTING CONTROLS 1. 130.1 (a) Area Controls: Manual controls that control lighting in each area separately 2. 130.1 (b) Multi-level Controls: Dimmability. Allow occupants to choose the appropriate light level for each area 3. 130.1 (c) Shut-off Controls: Automatically shut off lighting or reduce light levels when illumination is not needed 4. 130.1 (d) Automatic Daylighting Controls: Adjust electric lighting in response to the presence of daylight 5. 130.1 (e) Automated Demand Response: Receive and automatically respond to demand response (DR) signals Section 130.1 3/26/2015 SLIDE 47 SECTION 3

MANUAL ON/OFF CONTROLS An area is a space enclosed by ceiling-height partitions. All lighting in each area must be controlled separately from luminaires in other areas by manual on/off lighting controls that are: 1. Readily accessible 2. Located in the same room or area as the lighting they control and with the lighting in view 3. Able to provide any required dimming or multi-level controls steps in addition to on/off Section 100.1 3/26/2015 SLIDE 48 SECTION 3

EGRESS LIGHTING Up to 0.2 watts per square foot of lighting may remain on during occupied hours only for emergency egress. This lighting must be designated for emergency egress on building plans. When controls are required to shut off all lighting in a building, this includes emergency egress lighting. Draft Measure Information Template Egress Lighting Controls, 2013 California Building Energy Efficiency Standards, California Utilities Statewide Codes & Standards Team, March 2011 Section 130.1 (a) 3/26/2015 SLIDE 49 SECTION 3 MANDATORY MEASURES

SEPARATELY CONTROLLED LIGHTING SYSTEMS General lighting must be controlled separately from all other lighting systems in an area. Display lighting must each be separately controlled on circuits of 20 amps or less. For example, window displays must be controlled separately from wall displays, which must also be controlled separately from case displays. When using track lighting: General, display, ornamental, and special effects lighting must be separately controlled. Section 130.1 (a) 3/26/2015 SLIDE 50 SECTION 3 MANDATORY MEASURES

PUBLIC RESTROOMS Any public restroom with two or more stalls may use a manual switch that is not accessible to unauthorized personnel. All other lighting controls are still required. Section 130.1 (a)2 3/26/2015 SLIDE 51 SECTION 3

MIXED-USE BUILDINGS For some mixed-use buildings, (e.g. high-rise residential, hotels, and motels) the common areas must comply with the Nonresidential Lighting Standards, while dwelling units must comply with the Residential Lighting Standards. Photo: UC Davis 3/26/2015 SLIDE 53 SECTION 3 MANDATORY MEASURES

MULTI-LEVEL LIGHTING CONTROLS Title 24 sets a minimum number of control steps and illuminance uniformity requirements for most major luminaire types (see TABLE 130.1-A). These requirements are required in addition to any mandatory manual, daylight, shut-off, or demand response controls. The criteria in 130.1 (b) applies to general lighting for enclosed areas that: Are at least 100 ft 2 in size Have a connected lighting load over 0.5 W/ft 2 Have more than one luminaire or more than two lamps Controlled lighting in daylit zones over 0.3 W/ft 2 Section 130.1 (b) 3/26/2015 SLIDE 54 SECTION 3

MULTI-LEVEL LIGHTING CONTROLS Each luminaire must meet the multi-level control requirements. Controlling alternating luminaires or rows of luminaires does not meet the requirements. 50% Power 100% Power Section 130.1 (b) 3/26/2015 SLIDE 55 SECTION 3

TABLE 130.1-A Section 130.1, page 138 3/26/2015 SLIDE 56 SECTION 3

MULTI-LEVEL LIGHTING CONTROLS In addition to meeting the dimmability requirements, each luminaire must also be controlled with one of the following strategies: Manual dimming Lumen maintenance Tuning Automatic daylighting Demand response Section 130.1 (b) 3/26/2015 SLIDE 57 SECTION 3

AUTOMATIC SHUT-OFF CONTROLS Automatic shut-off controls turn lights off when a space is unoccupied. All lighting must be controlled by one or more of the following: 1. Occupant sensing control 2. Automatic time-switch 3. Building Energy Management System 4. Other control mechanism capable of automatically shutting off all lights for vacant periods A single control may not monitor more than 5,000 ft 2 Photo: Lutron Section 130.1 (c) 3/26/2015 SLIDE 58 SECTION 3

AUTOMATIC SHUT-OFF CONTROLS Space parameters Each room needs to be separately controlled. A single control may not monitor more than 5,000 square feet of floor area (20,000 square feet in malls and single-tenant retail spaces). Applications The following types of lighting must be separately controlled: 1. General 2. Display 3. Ornamental 4. Display case Section 130.1 (c) 3/26/2015 SLIDE 59 SECTION 3 INDOOR LIGHTING CONTROLS

AUTOMATIC SHUT-OFF CONTROLS Space parameters Each room needs to be separately controlled. A single control may not monitor more than 5,000 square feet of floor area (20,000 square feet in malls and single-tenant retail spaces). Applications The following types of lighting must be separately controlled: 1. General 2. Display 3. Ornamental 4. Display case Section 130.1 (c) 3/26/2015 SLIDE 60 SECTION 3

AUTOMATIC SHUT-OFF CONTROLS Countdown timer switches may only be used in: 1. Single-stall bathrooms smaller than 70 ft 2 2. Closets smaller than 70 ft 2 3. Server rooms smaller than 500 ft 2 If time-based controls are used, occupants there after hours must be able to activate lighting as needed: Manual switch Temporary override Occupancy-based control Section 130.1 (c) 3/26/2015 SLIDE 61 SECTION 3

AUTOMATIC SHUT-OFF CONTROLS Adaptive controls in secondary spaces Controls for lighting in corridors and stairwells must be capable of: Partially reducing lighting power during hours of operation in addition to Providing full shut-off functionality when the building is vacant. Section 130.1 (c) 3/26/2015 SLIDE 62 SECTION 3

AUTOMATIC SHUT-OFF CONTROLS Warehouse aisles and open areas 1. Each aisle must be independently controlled 2. Minimum automatic 50% reduction in lighting power when vacant Section 130.1 (c) 3/26/2015 SLIDE 63 SECTION 5 INDOOR LIGHTING CONTROLS

AUTOMATIC SHUT-OFF CONTROLS Corridors and stairwells Sensors/controls should be activated from all potential entrances Minimum automatic 50% reduction in lighting power when vacant Exceptions for hospitality and residential applications Photo: Cree, Inc. Section 130.1 (c) 3/26/2015 SLIDE 64 SECTION 3

AUTOMATIC SHUT-OFF CONTROLS Spaces that are exempt from automatic shut-off controls requirements: 1. Buildings with lighting in continuous use 24 hours/day, 365 days/year 2. Areas where partial on/off controls are required instead of shut-off controls (such as stairwells and corridors) 3. Electrical equipment rooms 4. Emergency egress lighting Section 130.1 (c) 3/26/2015 SLIDE 68 SECTION 3

AUTOMATIC DAYLIGHTING CONTROLS Automatic daylight controls adjust electric lighting power when ample daylight is available. Ample daylight is defined by the standards as 150% of the designed light level for electric lighting. Automatic daylighting controls are required for luminaires that: Photo: CLTC 1. Provide general lighting 2. Are at least half in a skylit or sidelit area 3. Are in an area where the total installed general lighting power is at least 120 watts 4. Are located in an area which has at least 24 ft 2 of glazing Photo: Lutron Section 130.1 (d) 3/26/2015 SLIDE 69 SECTION 3

AUTOMATIC DAYLIGHTING CONTROLS Automatic daylighting controls requirements: 1. Controlled lighting with an LPD greater than 0.3 W/ft 2 must have multi-level lighting in accordance with Table 130.1-A. 2. Controlled lighting + daylight must equal or exceed the controlled electric lighting level without daylight. 3. When there is ample daylight detected, the general lighting power in that space must be reduced by at least 65%. Section 130.1 (d) 3/26/2015 SLIDE 70 SECTION 3

DEMAND RESPONSE When the demand for electricity threatens to exceed supply, the power grid becomes less stable and the risk of outages increases. Demand response (DR) programs allow end users to temporarily reduce their electricity use in response to a notice or automated signal sent from a utility, independent system operator (ISO) or other power provider. This flexibility helps reduce peak demand and maintain grid stability. Currently, participating customers also receive financial incentives. Image: Lutron Section 130.1 (e) 3/26/2015 SLIDE 72 SECTION 3

DEMAND RESPONSE How DR Works In traditional, non-automated DR programs, a local service provider sends notification of a pending DR event to facility managers, via e-mail, phone call or text message, requesting a reduction in electricity consumption for a limited period of time. Auto DR Automated demand response (ADR) programs make use of energy management technologies and controls to respond to DR events more quickly and reliably. The provider issues an automated DR signal to energy management control systems enrolled in ADR programs. The systems then automatically respond by reducing electricity use according to pre-programmed load shed strategies. Section 130.1 (e) 3/26/2015 SLIDE 73 SECTION 3

DEMAND RESPONSE Lighting is extremely well-suited to DR 1. Peak demand periods typically overlap daylight hours 2. Research indicates illuminance levels can be reduced by as much as 20% without occupants detecting the change 3. Light levels can be immediately restored when DR events end Buildings larger than 10,000 ft 2 must be capable of responding to a DR signal by automatically reducing lighting power at least 15% below the total installed lighting power while maintaining the uniformity requirements listed in Table 130.1-A. Spaces that use less than 0.5 W/ft 2 and non-habitable spaces, such as storage closets, are exempt and cannot be counted toward ADR compliance. Section 130.1 (e) 3/26/2015 SLIDE 74 SECTION 3

DEMAND RESPONSE What is a DR-capable system? A DR system reduces electricity demand in response to a notice or automated signal from utilities, independent system operators or other power providers. Manual DR Requires occupant to manually adjust lighting systems in response to a phone call, e-mail, system notification, etc. Automatic DR The removal of human interaction from the process allows faster reaction to DR events. An electronic DR message will be broadcasted to energy management control systems when an electricity grid experiences high period of high demand or limited supply. 3/26/2015 SLIDE 75 SECTION 3

DEMAND REPONSE DEVICES 3/26/2015 SLIDE 76 SECTION 3

CHECK YOUR UNDERSTANDING: DEMAND RESPONSE An 80,000 ft 2 building is being constructed. It will contain 10 tenant spaces, each 8,000 ft 2 in size. Do these tenant spaces need to comply with the requirements for automatic demand response? 3/26/2015 SLIDE 77 SECTION 3

SUMMARY OF MANDATORY LIGHTING CONTROLS DISCUSSION: What types of controls will retail spaces typically require? 1. Manual switches (What needs to be switched separately?) 2. Automatic shut-off controls (Where are they required?) 3. Automatic daylighting controls (Which lighting systems must comply?) 4. ADR (How large does a building need to be?) 3/26/2015 SLIDE 78 SECTION 3 INDOOR LIGHTING CONTROLS