FIRE EXTINGUISHER SPACING & INSTALLATION GUIDELINES

Similar documents
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

A Safe Workplace A Workplace Safety and Health Manual for Your Community Section: II-B Subject:

OPTIONAL INFORMATION PORTABLE FIRE EXTINGUISHERS SELF INSPECTION CHECKLIST

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

Safety Tips for the Office

National Fire Authority

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

Outdoor Festival and Special Event Guidelines

CITY OF DANIA BEACH Local Business Tax Receipt Division 100 W Dania Beach Blvd. Dania Beach, FL Phone: ext 3644 / Fax

June 2018 Safety Meeting Fire Extinguishers Part I

S12 Fire Safety Risk Assessment H&SFS01-1 / 9

PLACES OF ASSEMBLY CHAPTER 17

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street?

Dear Exhibitor, To assist in th. and safety issues that you may encounter with your booth.

INTERIOR FINISHES AND FIRE PROTECTION SYSTEMS

EXCELSIOR FIRE DISTRICT

Model Policy On Portable Fire Extinguishers (Ontario Version)

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

Stillwater Area Community Services Center Inc.

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

4. Distances to property line, buildings, other tents, parked vehicles and engines;

Township of Upper Providence Office of the Fire Marshal

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Large Family Daycare Guideline

Exhibits and Trade Shows Permit Application

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES

ATTACHMENT B FIRE CODE REQUIREMENTS FOR EXHIBITS AND SPECIAL EVENTS

FIREDEPARTMENT REGULATIONS AND GUIDELINES

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Product Catalog MADE IN THE USA

UFGS (June 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Note: The event coordinator is responsible for compliance of all regulations.

30 DAY TEMPORARY TENT APPLICATION ON EXISTING COMMERCIAL PROPERTY

MOBILE FOOD VENDING Food Trucks & Trailers

SafetyNet FIRE MARSHAL S OFFICE. Food Booth and Vendor Regulations

Product Catalog. Your Source for World Class Fire Protection Equipment. Hand Held Extinguishers. Restaurant Fire Suppression Systems

Fire Safety Handbook

Element 14.7 Fire Prevention and Control 2018

Risk Management Resources

INDEPENDENT FIRE EXTINGUISHER SALES & SERVICES. Your First Line of Defense Since 1971

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

Agency for Health Care Administration

Osceola County Department of Fire Rescue and Emergency Medical Services

extinguishers. extinguishers. Skills Objectives

Portable Fire Extinguishers

MWL Consulting Company

MULTI-LEVEL & COVERED BOOTH CONDITIONS

Savard Labor & Marine Staffing, Inc. Fire Prevention Program Rev3/14

SUPPRESSION SALES I INSTALLATION I SERVICE

Chapter 34 Flammable and Combustible Liquids

A Guide for Meeting NFPA 10 Subsection

Emergency Action and Fire Prevention

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

NOTICE TO PROSPECTIVE BUSINESSES STATEMENT OF INTENDED USE

Business Fire Inspection. City of Guadalupe

CITY OF OKLAHOMA CITY SPECIAL EVENT REQUIREMENTS Revised January, 2011

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

School Fire Safety Checklist

FIRE DEPARTMENT PERMIT GUIDELINES

Extinguishers. Commercial Industrial High rise buildings


(3) Chart. The following chart illustrates the above hours: TABLE INSET:

CITY OF INDUSTRY USE PERMIT SUPPLEMENT A

Flammable and Combustible Liquids Checklist

SEMINOLE FIRE DEPARTMENT TENT PERMIT CONDITIONS

UC Irvine Environmental Health & Safety TITLE: Special Events Program

TAMUCC Fire Safety Training

Note: The event coordinator is responsible for compliance of all regulations.

The general safety requirements in the IFC were developed to. General Precautions against Fire CHAPTER

Salt Lake Community College FIRE EXTINGUISHER TRAINING

DEPARTMENT OF FIRE AND EMERGENCY SERVICES

Correctly Classifying and Determining Fire Protection Requirements for High- Hazard Group H Occupancies in New York State (2010 codes)

FIRE MARSHAL REGULATIONS

WHAT IS FIRE? In order to have a fire, there must be three elements: Heat -- enough to make the fuel burn

Department of Public Safety

CHANGES TO THE TEXT OF THE 2010 CODE BOOKS

Fire and Life Safety Review Form

GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard

Agency for Health Care Administration

To expedite the plan review and inspection processes, please refer to the information below.

Report on First Revisions with Statement June 2014 NFPA 101

FACILITY REGULATIONS

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

PALM SPRINGS FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS, CONVENTIONS AND SPECIAL EVENT GATHERINGS BASED ON THE 2010 CALIFORNIA FIRE CODE

FIRE PROTECTION SYSTEMS

READY FOR CHANGE. A Guide for Meeting the NFPA Compliance Standard for Portable Fire Extinguishers

Apartment Fire & Safety Inspection. City of Guadalupe

OCCUPANCY INSPECTION FORM

All temporary special events held within the City of Orlando must be approved and inspected by the Orlando Fire Department prior to holding the event.

WSU-TFREC Fire Safety Training

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

Fire Prevention Plan

FOOD PREPARATION WITHIN EXHIBITS

SANDUSKY FIRE DEPARTMENT Fire Prevention Bureau. Dear Prospective Food Vendor:

Three elements of fire. Heat Oxygen Fuel. Remove one of the three and the fire is extinguished.

Transcription:

FIRE EXTINGUISHER SPACING & INSTALLATION GUIDELINES Town of Brighton Office of the Fire Marshal October 2018

Fire Extinguisher Spacing & Installation Guidelines Scope The Fire Code of New York specifies the type, size and number of fire extinguishers that facilities are required to have. This guideline describes the basic requirements contained in the Fire Code of New York and the National Fire Protection Association Chapter 10-2013 Edition. Licensing Requirements No person shall engage in or conduct the trade of installing, charging, filling, maintaining, recharging, refilling, repairing and/or testing rechargeable fire extinguishers or fire extinguishing systems within the Town of Brighton without first having obtained a license therefore issued by the Fire Marshal or his designee. The Fire Marshal or his designee may issue a license under this Chapter 73 to any applicant holding a license to engage in the trade issued by the City of Rochester Fire Department or holding any other license to engage in the trade issued by another jurisdiction which the Fire Marshal determines has requirements for its issuance that are substantially similar to the licensing requirements of the City of Rochester Fire Department. Where Required Portable fire extinguishers shall be installed in the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A:10-B:C. 2. Within 30 feet (9144 mm) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Decoding UL Rating You will find a UL Rating in the title of the fire extinguishers. For example, an ABC Fire Extinguisher might have a UL Rating of 4-A:80-B:C. Fire extinguishers are rated as to which class of fires for which they are appropriate. Fire extinguishers are also rated with respect to the fires they will control. The larger the number given, the larger fire they will control. For example, a 4A-rated extinguisher will control a larger fire than will a 2A-rated extinguisher. Size ratings are not provided for class C fires since this rating simply refers to the fact that the extinguishing chemical will not conduct electricity. What do the letters mean in the alpha numeric classification? The letter represents the type of fire that can be put out with a particular extinguisher. Fires are divided into five categories in order to determine what type of chemical (dry chemical, carbon dioxide, etc.) will safely extinguish the fire.

CLASS A FIRES CLASS B FIRES CLASS C FIRES CLASS K FIRES Fires fueled by organic, combustible materials such as wood, cloth, paper, rubber, and many plastics. These fires pose a risk to restaurants with woodburning stoves, campgrounds, and other outdoor venues. Fires fueled by flammable liquids, combustible liquids, petroleum greases, tars, oil-based paints, solvents, lacquers, alcohol, and flammable gases. These fires can be prominent in gas stations, bars, and chemistry labs. Electrical fires involving energized electrical equipment, such as shortcircuiting machinery and overloaded electrical cables. These are a danger in breaker rooms, server rooms, or any area with a high volume of electrical equipment. A major danger in restaurant kitchens, Class K fires occur in cooking appliances that utilize a flammable cooking media such as vegetable or animal oils and fats. What do the numbers in the alpha numeric classification mean (ie. 1A:10B:C)? There is a number rating. For Type A fires, a 1 would have the equivalent of 1¼ gallons of water, a 2 would be equivalent to 2½ gallons, 3 would be 3¾ gallons of water, and so forth. For Type B and Type C fires, the number represents the square footage that the extinguishing agent would cover. For example, a number 2 would cover two square feet and a 5 would extinguish an area five square feet and so forth Now that you know exactly what the numbers mean, let s observe how extinguishers compare qualitatively to one another. Let s compare an extinguisher with a 4-A:80-B:C rating to one with a 1-A:10-B:C rating. Based on what you ve learned above, you know that: 4-A:80-B:C is 4x more potent against Class A fires than 1-A:10-B:C. 4-A:80-B:C is 8x more potent against Class B fires than 1-A:10-B:C. Both extinguishers can combat class C fires.

Basic Fire Extinguisher Selection, Numbers and Location 1. For each area, determine the hazard classification using the definitions below. Light (low) Hazard: Light hazard occupancies are locations where the total amount of Class A combustible materials, including furnishings, decorations, and contents, is of minor quantity. This may include some buildings or rooms occupied as offices, classrooms, churches, assembly halls, guestroom areas of hotels/motels, etc. This classification anticipates that the majorities of content items are either noncombustible or so arranged that a fire is not likely to spread rapidly. Small amounts of Class B flammables used for duplicating machines, art departments, etc. are included in this classification provided that they are kept in closed containers and safely stored. Ordinary (light) Hazard: Ordinary hazard occupancies are locations where the total amount of Class A combustibles and Class B flammables are present in greater amounts than expected under light (low) hazard occupancies. These occupancies could consist of dining area, mercantile shops and allied storage, light manufacturing, research operations, auto showrooms, parking garages, workshop or support service area of light (low) hazard occupancies, and warehouses containing Class I or Class II commodities as defined in NFPA 231, Standard for General Storage (Class I and Class II commodities include noncombustible products on wooden or certain plastic pallets, in ordinary cardboard cartons or in paper wrappings, or in slatted wooden crates, solid wooden boxes, multiple-thickness paperboard cartons with or without pallets. The products are allowed to contain a limited amount of plastics.) Extra (High) Hazard: Extra hazard occupancies are locations where the total amount of Class A combustibles and Class B flammables present, in storage, production use, and/or finished product is over and above those expected and classed as ordinary (light) hazards. These occupancies could consist of woodworking, vehicle repair, aircraft and boat servicing, cooking area, individual product display showrooms, product convention center displays, and storage and manufacturing processes such as painting, dipping, coating, including flammable liquid handling. Also included is warehousing or in-process storage of other than Class I and Class II commodities (i.e. plastics as a part of product or package) 2. Using the table below determine what size and type of fire extinguisher you need; how many you need and the maximum allowed travel distance to a fire extinguisher. Note: a small, higher hazard operation (such as a spray booth) located in a larger area can be provided with an extinguisher specifically for that operation while the rest of the fire extinguishers in the area are rated for the overall hazard of the area. An example is provided on the last page of this document. Please also note that this chart addresses general situations, not special hazards. Special situations are addressed in 4) below. 3. Locate the fire extinguishers throughout the facility to satisfy the number of extinguishers needed based on square footage and the maximum travel distance. In general, fire extinguishers should be located near exit doors and in exit paths so that employees do not have to go deeper into a building to get a fire extinguisher, thus compromising their ability to exit should that be necessary. Fire extinguisher must be mounted on the wall or a post or placed on shelves. The bottom of the extinguisher must be between 4 and 48 inches off the ground. 4. The above information and the following are general guidelines. Special situations exist for which additional guidance is needed. For example, open tanks of flammable liquids, high piled storage of combustible materials, large scale spraying of flammable liquids, etc. For situations such as these, contact the Office of the Fire Marshal at (585) 784-5220 for assistance

Type of Hazard Basic Minimum Extinguisher Rating Maximum Travel Distance(ft) / Coverage Area to Extinguishers (sq. ft) Light hazard 2A 10B:C 75 feet Maximum coverage of 3,000 square feet per unit of A (thus a 2A extinguisher can cover 6000 sq. ft) Ordinary Hazard with moderate amounts of Class A combustibles and only minimal amounts of flammable/combustible liquids and gases. 2A 10B:C 75 feet Maximum coverage of 1,500 square feet per unit of A (thus a 2A extinguisher can cover 3,000 sq. ft.) Ordinary hazard with moderate amounts of flammable/combustible liquids and gases. Examples: Parking garages, small laboratories, and hardware stores Option 1 2A 10B:C ------- Option 2 2A 20B:C 30 feet ------- 50 feet Maximum coverage of 1,500 square feet per unit of A (thus a 2A extinguisher can cover 3,000 sq. ft.) -------- Maximum coverage of 1,500 square feet per unit of A (thus a 2A extinguisher can cover 3,000 sq. ft. Extra hazard - all types Option 1* 4A 40B:C ----- Option 2 4A 80B:C *4A 40B:C 30 feet ----- 50 feet Maximum coverage of 1,000 square feet per unit of A (thus a 4A extinguisher can cover 4,000 sq. ft.) ------- Maximum coverage of 1,000 square feet per unit of A (thus a 4A extinguisher can cover 4,000 sq. ft.) may be hard to locate new larger size ok Commercial kitchens 2A 1B: C; Recommend using throughout the restaurant ----- Class K 30 feet Maximum coverage of 1,000 square feet per unit of A (thus a 4A extinguisher can cover 4,000 sq. ft.) Size and Distribution For Light (Low) and Ordinary (Moderate) hazard occupancies, the minimum fire extinguisher designation shall be 2-A:10B:C. (Commonly known as a 5 lb. extinguisher). Maximum travel distance to extinguishers shall not exceed 75 feet. 2½ pound, or kitchen extinguishers are not addressed in the fire code. While these have been accepted to meet requirements in apartments buildings in the past, they are no longer considered acceptable. Extinguisher requirements for apartments can now be met by placing a 1-A:10-B:C extinguisher in each apartment, or by placing a 2-A:10-B:C on the outside of apartment unit within the hallway in such a manner as to meet the 75-foot requirement stated above. Commercial Kitchen Fire Extinguishers Commercial cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. The extinguisher shall be located within a 30-foot travel distance of commercial-type cooking equipment.

Conspicuous Location Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the Fire Marshal determines that the hazard posed indicates the need for placement away from normal paths of travel. Unobstructed and Unobscured Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. Hanger and Brackets Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangars or brackets supplied. Hangars or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer s installation instructions. Height above Floor Portable fire extinguishers having a gross weight not exceeding 40 pounds shall be installed so that its top is not more than 5 feet above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds shall be installed so that the top is not more than 3.5 feet above the floor. The clearance between the floor and the bottom of the installed hand-held extinguishers shall not be less than 4 inches. Cabinets Cabinets used to house fire extinguishers shall not be locked. Exceptions: 1. Where fire extinguishers subject to malicious use or damage are provided with a means of ready access. 2. In Group I-3 occupancies and in mental health areas in Group I-2 occupancies, access to portable fire extinguishers shall be permitted to be locked or to be located in staff locations provided the staff has keys. Marking Portable fire extinguishers mounted in cabinets or wall recesses or set on shelves shall be placed in a manner such that the extinguisher operating instructions face outward. The location of such extinguishers shall be marked conspicuously.

Maintenance Fire extinguishers shall be subjected to maintenance not more than 1 year apart, at the time of hydrostatic test, or when specifically indicated by an inspection. Each fire extinguisher shall have a tag or label securely attached that indicates the month and year the maintenance was performed and that identifies the person performing the service.