NINE CHANNEL CONTROLLER OMNTEC

Similar documents
THREE CHANNEL CONTROLLER OMNTEC

SINGLE CHANNEL CONTROLLER

ELP21LU3-LF-HLOL THREE CHANNEL

PROTEUS Series OEL8000III-K. Tank Gauging System. Installation Manual

EQUIPMENT DATA SPECIFICATION AIR CONDITIONER. Telecom & Digital Signage Package NE015

EQUIPMENT DATA SPECIFICATION AIR CONDITIONER. Telecom & Digital Signage Package NE050

Zone monitor with isolator

Welcome to our world of Quality, Consistency and Reliability.

1993 Pond Rd., Ronkonkoma, NY Tank Gauging Liquid Level and Leak Detection Systems Relays. OEL8000II Installation Manual PRINT MENU DEL 1 ABC

Leak Detection System Leak Minder Model: LDA-1 Instruction Manual

Fire Systems. Product Catalogue

INSTRUCTION MANUAL. Revised: July 2, 2017 DRAWING NO REV. A LC1000 SERIES INTRINSICALLY SAFE ALARM CONSOLE

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

Safe-man Productivity System

FOSSILFUELKITAXWR02FFA1

Instruction manual. Version PRETREATmaker

Wayne County Community College District

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

PO Box 827 Hawley, MN (218) Fax (218)

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Electrical devices may only be mounted and connected by electrically skilled persons.

OIL WATER SEPARATOR ALARM CONSOLE SPECIFICATIONS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Public Safety DAS Annunciator Panel

FMP-DIS & FMP-EIS. Interstitial BriteSensor & Standard Sensor. Installation Instructions

21-light Remote Annunciator. Owner s Manual

STATUS ALARM HISTORY ALARM RESET

Model : SP601-15, 15T, 20, 20T, 30, 30T

5+2 DAY INSTALLATION. Digital Thermostat. residential. & 1-cool. up to. 1-heat PROGRAMMABLE HEAT COOL HEAT PUMP THERMOSTAT. Venstar Inc.

Beacon 800 Gas Monitor Operator s Manual

* These Remote Mics must be SPRM-GP

Sensors Monitoring Systems. Crank-Case Protection System (CPS)

GAS MONITOR Model Model

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

TS-RA1, TS-RA2 and TS-RK Tank Overfill Alarms

Product selector Analogue addressable devices

Product line training. Gregor Vialette June 2016

Greentrol Automation, Inc.

2016 Sales per Product

Design Standard Intrusion Detection

Nortec ME Series Evaporative Humidifier and Cooler. Humidification and Evaporative Cooling. humidity.com

Perfekt Glide-24 Perfekt Glide-30 Perfekt Glide-36 Built-in Range Hood Instruction Manual

Check It Panel. 1 Phase Simplex Demand Dose Operation, Maintenance & Installation Manual. Introduction. Safety Guidelines

ph REGULATOR INSTALLATION AND MAINTENANCE MANUAL

Since 1998, the Emergi-Lite brand has been included in the product portfolio of the Thomas & Betts Corporation.

Protocol Station Remote Alarm

2 HEAT - 1 COOL Meets Residential California Title 24

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

FlashGuard 3000B Dual Lighting System Troubleshooting Guide

Model 9001EXP Alarm. NOTE TO INSTALLER: Please leave this information with the Maintenance Department. LIMITED WARRANTY

ADVANTAGE 1200 EXTRACTOR

SERIES WM-20(T) & WM-40(T)

Centro-Matic Automated Lubrication Systems System Controls

AMC-RAM-4. Refrigerant Alarm Module USER MANUAL. Please read the installation and operating instructions completely and carefully before starting.

User s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

Model AV1LED Audio-Visual LED Light Installation and Maintenance Manual

Troubleshooting Guide For FG3000 Dual Medium Intensity Lighting System

Apartment Manager Fire Safety Manual

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

Figure 1. Figure 2. See notes 1 and 2 below.

FMP-ULS UNIVERSAL LIQUID SENSOR INSTALLATION GUIDE

RSC-1401CLTW /1651CLTW

SC-6 Six Supervised Control Module

Single Station Remote Alarm

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

FOR TM-16 EMERGENCY WARNING SYSTEM

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

DX100 Field Maintenance Guide

Series. Access Power Controllers. Installation Guide

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Model 9001, Alarm

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

Universal Remote Display

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

OPERATING INSTRUCTIONS INSTALLING THE WATER BOTTLE

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

SAFETY INFORMATION AND WARNINGS

RAM3 Remote Alarm Module

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Beacon 410A Gas Monitor Operator s Manual

PANIC EXIT POLICE LOCK

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3

FMP-MWS. (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions

Installation Instructions for W2H Series Signals

Hot Work Permit Program

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

Eclipse 90 UV Scanner Model A Version 1

Instruction Manual Model L2 RF Switch

Technical Reference Manual

ph / ORP REGULATOR INSTALLATION AND MAINTENANCE MANUAL

Transcription:

MNTEC Mfg., Inc. 1993 Pond Rd., Ronkonkoma, NY 11779 Tank Gauging Liquid Level and Detection Systems Relays LU9 NINE CHANNEL CNTRLLER MNTEC 631-467-5787 L1 L4 L2 L5 L3 SYSTEM DETECTING L7 L6 L8 TEST L9 HRN FF Phone 631-981-2001 Fax 631-981-2007 e-mail: support@omntec.com www.omntec.com

Table of Contents Table of Contents...2 SPECIFICATINS...3 Dimensions for mounting and knockouts...4 LU-series Installation Instructions...5 1. L-SERIES SENSR...5 L-1 SENSR...5 LS-ASC SENSR...6 LWF-* SENSR...7 2. CNTRL UNIT...8 INPUT PWER HKUP...8 REMTE ANNUNCIATR PTIN...8 SK-3 CNNECTR SEALING KIT...8 LU9 CNTRLLER CNNECTIN DIAGRAM...9 LU9 SYSTEM CNTRL DRAWING...10 LS-ASC SPECIFICATINS...11 L-1 SPECIFICATINS...12 LWF SPECIFICATINS...13 MNTEC LU-SERIES System peration and Test Instructions...15 LU-Series TRUBLESHTING PRCEDURES...16 LG SHEET...19 WARRANTY...20 MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 2 of 20 Rev: 1.0 Rev Date: 7-2-2010

MNTEC LU9 SPECIFICATINS MNTEC L1 631-467-5787 L4 MDEL VERFILL PRTECTIN LEAK DETECTIN CNTRLLER LU1 LU1 LU2 LU3 LU3 LU4 LU4 LU6 LU9 LU9 SERIAL NUMBER L2 L5 PRVIDES INTRINSICALLY SAFE CIRCUITS FR USE IN CLASS I GRUP D HAZARDUS LCATINS WHEN CNNECTED IN ACCR- DANCE WITH CNTRL DRAWING NUMBERS L1, L2, L3, L4, L6,L9 R 5L04 LISTED SYSTEM ELECTRICAL RATINGS L3 DETECTING L7 L8 L6 13.00 INPUT: 120 VAC, 60 Hz, 166 ma, 9.33 Watts max. PTINAL RELAY UTPUTS: 120 VAC, 1.25 a TYPE 4X ENCLSURE PRBE MAP TANK PRDUCT LCATIN L1 L2 L3 L4 L5 L6 L7 L9 TEST HRN FF 8.00 PWER INPUT 85-125 VAC, 47-440 Hz 16 Watts maximum PWER T SENSRS 2 VDC @ 13 ma WEIGHT DIMENSINS 6 LBS. (W) 9 x (H) 10.5 SENSR CABLE Shielded 22 AWG UL-E118830 CM Maximum length 2000 feet ENCLSURE NEMA 4X PERATING TEMPERATURE -40 to 140 F UL LISTED Intrinsically safe circuits for use in class I group D hazardous locations when connected in accordance with control drawings L9 AUDI/VISUAL CNSLE Audible alarm - 95 db pulsing horn with 30 second timeout light -Indicates liquid alarm for L-series sensors TEST BUTTN- When pressed will actually test entire system electronics from control panel to sensors GREEN LIGHT- indicates the power is on Horn off button - Silences the audible alarm when pressed SENSRS L-1 High level sensor LS-ASC Liquid sensor LWF Double wall liquid sensor ACCESSRIES RA-1 audio/visual remote annunciator RLY-RA Relay (consult factory) RA-1-NYS Remote annunciator with strobe (consult factory) LABELS Provided with controller MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 3 of 20 Rev: 1.0 Rev Date: 7-2-2010

MNTEC LU9 Dimensions for mounting and knockouts LU1 LU2 LU3 LU4 LU6 LU9 MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 4 of 20 Rev: 1.0 Rev Date: 7-2-2010

LU-series Installation Instructions READ ALL INSTRUCTINS PRIR T SYSTEM INSTALLATIN. ALL WIRING IS T BE DNE IN ACCRDANCE WITH ALL NATINAL AND LCAL ELECTRICAL CDES. PWER IS T BE FF DURING ANY WIRING. WIRE AND TEST ENTIRE SYSTEM BEFRE UTILIZING SK-3 CNNECTR SEALING KITS. STANDARD EQUIPMENT IS CMPATIBLE WITH MST PETRLEUM PRDUCTS. SME CHEMICAL AND SLVENTS REQUIRE SPECIFIC MATERIALS F CNSTRUCTIN. IF UNSURE F CMPATIBLE CNTACT MANUFACTURER. * For waste oil applications consult factory * 1. L-SERIES SENSR L-1 SENSR The L-1 sensor (see pg.8) is primarily used to detect a liquid level inside the tank. The sensor detects a single liquid level and is typically used for overfill protection at 90% tank capacity. Standard sensor part numbers are L-1-S (12 ), L-1-L (20 ), L-1-D (custom length). The L-1 sensor is installed into the tank via the 2 bushing which is an integral part of the sensor. This sensor screws directly into a 2 female threaded NPT (use a reducer bushing if necessary). 2 threaded NPT High level actuation point Connection of the sensor to the control unit cable is made in a junction box. For detailed wiring scheme refer to appropriate drawing (see pg.6 and 17). These connections must be made using supplied SK-3 connector sealing kit. MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 5 of 20 Rev: 1.0 Rev Date: 7-2-2010

LS-ASC SENSR The LS-ASC sensor (see pg.7) is designed to detect liquid in sumps or containment areas and steel interstitial spaces for above ground and underground tanks. 1. To install the LS-ASC sensor as an above ground sump sensor mount a junction box between 2 and 3 feet above bottom of containment area. Attach sensor to junction box via conduit or cable clamp, leaving a ¼ clearance between the sensor end and the bottom of the containment area. For detailed wiring scheme refer to appropriate drawing (see pg.6 and 17). Connect sensor cables to control unit cables in junction box using supplied SK-3 connector sealing kit. 2. To install the LS-ASC as a doublewall tank sensor remove the oiltight from the sensor cable. Feed the cable through the appropriate bushing required to adapt the interstitial port to 3/4 NPT (oiltight). Feed wires through oiltight, leaving it loose. Gently lower sensor down interstitial port until it rests on the bottom. Install oiltight into the bushing. Pull sensor up by the cable until it just comes off the bottom. Maintain this position and tighten the oiltight fitting. This is required to seal the interstitial port. All connections are made using the supplied SK-3 connector kit. ¾ NPT 2 x ¾ reducer ¾ NPT 2 x ¾ reducer MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 6 of 20 Rev: 1.0 Rev Date: 7-2-2010

LWF-* SENSR The LWF-* sensor (see pg.9) is designed to detect liquid in the interstitial space of a double wall fiberglass tank. 1. The LWF-* sensor is installed through the interstitial port. If the tank is pitched, locate the interstitial sensor at lowest elevation of tank. Insert sensor into the interstitial port and push down around outside of inner tank. When PVC handle contacts the inner tank the sensor should be located at the bottom of interstitial space. Reduce the riser to 3/4" NPT and install the supplied oiltight fitting. The oiltight fitting must be installed to prevent liquids from entering the interstitial space. Run conduit from interstitial man hole to the central junction box, located in the manway. Install a second oiltight on the sensor cable and pull sensor cable through conduit. Connect oiltight to conduit and tighten. For detailed wiring scheme refer to appropriate control drawing (see pg.6 and 17). Connect sensor wires in central junction box to control unit cable(s) and use SK-3 connector sealing kit. 4 x ¾ reducer MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 7 of 20 Rev: 1.0 Rev Date: 7-2-2010

2. CNTRL UNIT The control unit (see pg.1) should be mounted in a manned area. Route sensor control cable through conduit from the junction box to the control unit. Sensor control cables enter the control unit through the output port only. The cables are wired as shown in the appropriate drawing (see pg.6). The control unit accepts any possible combination of L- series sensors. INPUT PWER HKUP Input power requirements are: 85 125 VAC 16 Watts max 47 440 Hz Input power cable should be wired in accordance with all pertinent electrical codes. This cable should enter the control unit through the input power port only. The power is hooked up to the power supply and wired as per control drawing (see page 17). NTE: EARTH GRUND TERMINAL MUST BE CNNECTED. REMTE ANNUNCIATR PTIN Mount remote annunciator (see pg.16) within audio / visual range of the filling operator. NTE: the remote must be outside of the HAZARDUS AREA. Pull appropriate low voltage wire from the remote to the control unit. See appropriate drawing for wiring details. Run wires through output port. Connect color coded nuts. SK-3 CNNECTR SEALING KIT Make all splices using SK-3 connector kit (supplied) MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 8 of 20 Rev: 1.0 Rev Date: 7-2-2010

LU9 CNTRLLER CNNECTIN DIAGRAM REMVABLE SENSR INPUT CNNECTR REMVABLE SENSR INPUT CNNECTR PTIN BARD FUSE CLR CDE CABLES FRM SENSRS T REMVABLE SENSR INPUT CNNECTRS 1 FRM SENSR #1 2 3 FRM SENSR #2 4 5 FRM SENSR #3 6 7 BLACK FRM SENSR #1, #2, & #3 8 SHIELD DRAIN 9 BLACK FRM SENSR #4, #5, & #6 10 SHIELD DRAIN 11 FRM SENSR #4 12 13 FRM SENSR #5 14 15 FRM SENSR #6 16 17 FRM SENSR #7 18 19 FRM SENSR #8 20 21 FRM SENSR #9 22 23 BLACK FRM SENSR #7, #8, & #9 24 SHIELD WIRES T PTIN BARD F.G. L LW VLTAGE UTPUTS T RELAY BX SENSR INPUTS FRNT KNCKUT REAR KNCKUT WARNING: THIS TERMINAL MUST BE CNNECTED T EARTH N GRUND T MAINTAIN INTRINSIC SAFETY PTINAL UTPUTS INPUT PWER 1 GREEN - HRN 2 + HRN 3 BLACK GRUND 4 SENSR #1 5 RANGE SENSR #2 6 BLUE SENSR #3 7 BRWN SENSR #4 8 YELLW SENSR #5 9 PURPLE SENSR #6 10 SLATE SENSR #7 11 PINK SENSR #8 12 TAN SENSR #9 120VAC WIRES T PWER SUPPLY F.G. FIELD GRUND L LINE N NEUTRAL NTE: To maintain proper shielding, BLACK sensor wires and SHIELD DRAINS should not be connected together at sensors. MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 9 of 20 Rev: 1.0 Rev Date: 7-2-2010

LU9 SYSTEM CNTRL DRAWING PTENTIALLY FLAMMABLE AREA L Series Sensor #1 L Series Sensor #2 L Series Sensor #3 L Series Sensor #4 L Series Sensor #5 L Series Sensor #6 L Series Sensor #7 L Series Sensor #8 L Series Sensor #9 CKT 1 CKT 2 CKT 3 CKT 7 CKT 8 CKT 9 CKT 4 CKT 5 BLACK SHIELD DRAIN BLACK SHIELD DRAIN BLACK SHIELD DRAIN 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 REMVABLE INPUT CNNECTR REMVABLE INPUT CNNECTR REMVABLE INPUT CNNECTR CNTRL EQUIPMENT ELECTRNICS C N N F C N N E C T R SYSTEM EARTH FRUND AC LINE AC NEUTRAL E P T I N A L I N T E R F A C E 1 - HRN 2 + HRN 3 GND 4 L1 5 L2 6 L3 7 L4 8 L5 9 L6 10 L7 11 L8 12 L9 + V - V W E R U P P L Y GREEN BLACK RANGE BLUE BRWN YELLW PURPLE SLATE PINK TAN N L F.G. PTINAL REMTE INPUT LINE VLTAGE 85-132 VAC 25VA 47-63 Hz CKT 6 CLASS 1, GRUP D HAZARDUS AREA NTES N PRBES NN-HAZARDUS AREA NTES N CNTRL EQUIPMENT CNTRL DRAWING N. L9 1. THE INTRINSICALLY SAFE FIELD WIRING SHALL BE INSTALLED IN ACCRDANCE WITH ARTICLE 504 IN THE NATINAL ELECTRIC CDE ANSI/NFPA 70 2. ALL PRBES ARE ELECTRICALLY IDENTICAL AND MAY BE INTERCHANGED ALLWING SYSTEM FLEXIBILITY 3. PRBE T CNTRL UNIT CABLE WILL BE TW PAIR F #22AWG WITH SHIELD AND DRAIN PVC JACKETED UL-118830 CM. CABLE LENGTH WILL BE LIMITED T 2000 FEET MAXIMUM 1. ALL WIRING MUST MEET LCAL AND NATINAL ELECTRICAL CDES 2. SYSTEM EARTH GRUND MUST BE CNNECTED T TERMINAL F.G. T INSURE INTRINSIC SAFETY AND MUST BE LESS THAN 1Ω WITH RESPECT T EARTH GRUND 3. PTINAL REMTE REQUIRES #22 AWG LW VLTAGE CMMUNICATIN CABLE MINIMUM MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 10 of 20 Rev: 1.0 Rev Date: 7-2-2010

MNTEC Non-product distinguishing ptic Sensor LS-ASC DRY CNDITIN LED LED DETECTR PRISM CABLE LENGTH 12 FEET WET CNDITIN 3/4 NPT NIPPLE 3 SHIELD DRAIN 1-5/8 BLACK LS-ASC SPECIFICATINS U.L. LISTED 5L04 Intrinsically safe Class I, Group D Hazardous Locations when connected in accordance with control drawing nos. L1, L2, L3, L4, L6, L9 PRINCIPLES F PERATIN LIQUIDS (ex: fuel, water) photo ptic DRY CNDITIN Normally closed light beam ALARM CNDITIN pens (refracts) normally closed light beam PERATING TEMPERATURE SENSR CABLE -40 T +140 F Shielded 22 AWG UL-E118830 CM Maximum length 2000 feet PWER 2 VDC @ 13 ma RESPNSE TIME Immediate WEIGHT 1/2 pound MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 11 of 20 Rev: 1.0 Rev Date: 7-2-2010

MNTEC L-1 Liquid Level ptic Sensor Principles of peration Cable length 3 feet LED DRY CNDITIN LED DETECTR SHIELD DRAIN (BARE WIRE) 3/4 NPT 2 NPT BLACK WET CNDITIN PRISM D* 1-5/8 5/8 L-1 SPECIFICATINS U.L. LISTED 5L04 Intrinsically safe Class I, Group D Hazardous Locations when connected in accordance with Control Drawing nos. L1, L2, L3, L4, L6, L9 PRINCIPLES F PERATIN LIQUIDS (ex: fuel, water) Photo ptic DRY CNDITIN Normally closed light beam ALARM CNDITIN pens (refracts) normally closed light beam PERATING TEMPERATURE SENSR CABLE -40 T +140 F Shielded 22 AWG UL-E118830 CM Maximum length 2000 feet PWER 2 VDC @ 13 ma RESPNSE TIME Immediate WEIGHT 2 pounds MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 12 of 20 Rev: 1.0 Rev Date: 7-2-2010

MNTEC LWF Non-product distinguishing Fiberglass tank dry interstitial sensor LIQUID TIGHT STRAIN RELIEF SUPPLIED WITH 20 FT F CABLE Principles of peration DRY CNDITIN LED DETECTR LED 18 SHIELD DRAIN BLACK PRISM WET CNDITIN LENGTH CUT T TANK SPECIFICATIN 1-5/8 5/8 LWF SPECIFICATINS PERATING TEMPERATURE -40 T +140 F PRINCIPLES F PERATIN LIQUIDS (ex: fuel, water) Photo ptic DRY CNDITIN Normally closed light beam ALARM CNDITIN pens (refracts) normally closed light beam PWER SENSR CABLE 2 VDC @ 13 ma Shielded 22 AWG UL-E118830 CM Maximum length 2000 feet WEIGHT 2 pounds RESPNSE TIME Immediate MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 13 of 20 Rev: 1.0 Rev Date: 7-2-2010

RA-Series Remote High Level Alarm RA-1 RA-2 RA-3 RA-4 MNTEC REMTE HIGH LEVEL ALARM MNTEC REMTE HIGH LEVEL ALARM MNTEC REMTE HIGH LEVEL ALARM MNTEC REMTE HIGH LEVEL ALARM TANK 1 TANK 2 TANK 1 TANK 2 TANK 3 TANK 1 TANK 2 TANK 3 TANK 4 7.00 7.00 Internal Wiring Color Code 7.00 7.00 Warning: Low voltage inputs only Warning: Low voltage inputs only Warning: Low voltage inputs only Warning: Low voltage inputs only 5.03 (+) BLACK (-) 5.03 RANGE (+) BLACK (-) 5.03 BLUE RANGE (+) BLACK (-) 5.03 BLUE RANGE BRWN (+) BLACK (-) (+) GREEN (+) GREEN (+) GREEN (+) GREEN SIDE VIEW MUNTING DIMENSINS SPECIFICATINS Audible Alarm 95 db pulsing horn Red Light Liquid-high-level alarm Response Time Immediate Power Input 12VDC @200mA maximum from controller Wire 22 AWG minimum Weight 1 lb. 5.03 4.02 4.21 6.18 Note: It is recommended that knockouts be placed in the bottom of the enclosure MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 14 of 20 Rev: 1.0 Rev Date: 7-2-2010

MNTEC LU-SERIES System peration and Test Instructions 1. n the front panel the Green SYSTEM DETECTING light should be on indicating that system is up and running 2. If sensors are not in alarm, all Red lights should be off ptical sensors are solid state and use a normally closed light loop in a prism for sensing. When liquid is present at sensor, the normally closed loop of light is open, thus sending an alarm signal back to the alarm panel. The panel responds by turning on the appropriate light and sounding an audible alarm S S Dry Condition Wet Condition 3. Since system sensors are solid state and work with normally closed loop of light, sensors can be tested as follows: Press the test button on alarm panel and observe panel lights If all lights illuminate and audible alarm sounds, system test is complete When test button is pressed a signal is sent to sensor to turn its light off. What this does is put the sensor into an alarm condition The sensor then responds as explained in part (2) 4. System should be tested on at least weekly basis 5. Every alarm, malfunction and test result should be recorded in a dated signed log Manufactured by: Installed by: MNTEC Mfg., Inc. 1993 Pond Rd. Ronkonkoma, New York 11779 Phone 631-981-2001 Fax 631-981-2007 MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 15 of 20 Rev: 1.0 Rev Date: 7-2-2010

LU-Series TRUBLESHTING PRCEDURES FR LU-SERIES CNTRLLERS WHEN USED WITH ELECTR-PTIC SENSRS 3 YELLW GREY PTIN BARD System Detecting 8 REMVABLE SENSR INPUT CNNECTR WARNING: THIS TERMINAL MUST BE CNNECTED T EARTH GRUND T MAINTAIN INTRINSIC SAFETY F.G. N L 2 SHIELD DRAIN (BARE WIRE) 8 13 BLACK 12 9 10 Be sure the following criteria are met before proceeding: 1. Controllers have there own separate isolated Earth Ground 2. Controllers have there own separate isolated Field Ground 3. The Controller should have 13.8 VDC on the output of the power supply (Across the yellow-positive and gray-negative wires) 4. 120VAC wires are in there own separate isolated conduit 5. Remote Annunciator wires are in there own separated isolated conduit 6. Sensor wires are in there own separate isolated conduit 7. Sensor shield drain wire is not connected to black wire at sensor splice 8. Black & shield drain are connected to ground at removable input connector 9. Sensor head (prism) is not exposed to any external light (i.e.: sunlight, indoor light, etc) 10. Sensors are free of dirt and debris 11. Sensor extension cables are minimum 3 conductor #22 AWG shielded with drain wire 12. Sensors wires do not exceed 2000 ft. 13. The System Detecting Light should be illuminated 6 BLACK SHIELD DRAIN 12 1 7 11 5 4 Be sure that the sensor head (prism) is not exposed to any external light (ie: sunlight, indoor light, etc.) MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 16 of 20 Rev: 1.0 Rev Date: 7-2-2010

Troubleshooting Procedures LU-SERIES Controller LIGHTS TEST BUTTN System HRN HRN FF BUTTN Detecting SYSTEM DETECTING LIGHT SYMPTM TRUBLESHTING PRCEDURE RESULT Red Light does not come on when test button is pressed. 1) Unplug sensors Removable input connector at controller. Does the red Light illuminate? 2) Check wiring at removable input connector. Concentrate on white, black and shield wire inputs from sensors, making sure no shorts are present. Replug connector and press test button. Does the Red Light illuminate? 3) Check splice at sensor for moisture or mis-wire (concentrating on white and black wires from sensor). Correct problem and press test button. Does the Red Light illuminate? 4) Remove sensor from installation, connect at controller, shroud from light and press test button. Sensor head (prism) is not exposed to any external light (ie: sunlight, indoor light, ect.). Does the Red Light illuminate? (YES) controller is functioning. Proceed to step 2. (N) controller is not functioning (consult factory). (YES) system is functioning properly. (N) Proceed to step 3. (YES) problem are in the wire connections at splice (N) sensor is not functioning properly. Proceed to step 4. (YES) problem in wire run to sensor. System is functioning properly. (N) The sensor failed (consult factory) MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 17 of 20 Rev: 1.0 Rev Date: 7-2-2010

SYMPTM TRUBLESHTING PRCEDURE RESULT 1) Check if sensor is actually in alarm (YES) correct alarm condition. Red Light (submerged) remains on. 2) Check wiring at removable input connector concentrating on red, white, black and shield wire inputs from sensors. Make sure no open circuits are present. Re-plug the connector and press test. Does the Red Light stay on? 3) Disconnect sensor wires from removable sensor input connector. Connect a jumper from the white input to the black input at the connector. Make sure all sensor wiring is disconnected. Does the Red Light stay on? 4) Check DC voltage from red input to black input. Is it 7.5 9V DC? (N) proceed to step 2. (YES) proceed to step 3. (N) System is functioning properly. Problem was in the wire or connections. (YES) Controller is not functioning properly (consult factory) (N) Controller driver boards are functioning properly. Proceed to step 4. (YES) proceed to step 5 (N) Controller is not functioning properly. Consult factory. (YES) proceed to step 6. Horn does not sound on controller when the TEST button is pressed. 5) Check splice at sensor for moisture or mis-wire. Correct problem. Does the Red Light stay on? 6) Connect sensor directly to controller. Make sure sensor head is not exposed to light during test. Does the Red Light stay on? 1) Are any Red Lights illuminated on controller? 2) Shut down system for 30 seconds. Turn system back on. Does horn sound when hitting the TEST button? 3) While holding the TEST button down put a voltmeter on the positive and negative on the back of the horn. Do you get 13.8 volts +/- 1? (N) If light goes off before pressing test button and goes on after pressing test button System is functioning properly. Problem was in the connection or wire. (YES) Sensor is not functioning properly (consult factory) (N) Problem is in the wire or connections. (YES) Make sure at least one input is not in alarm state. Then proceed to step 2. (N) proceed to step 2. (YES) Controller is functioning properly. (N) Controller is not functioning properly. Proceed to step 3. (YES) Your horn does not work. Replace horn. (N) Your horn board is not working (consult factory) MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 18 of 20 Rev: 1.0 Rev Date: 7-2-2010

LG SHEET DATE NAME SYSTEM STATUS SIGNATURE MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 19 of 20 Rev: 1.0 Rev Date: 7-2-2010

WARRANTY The seller MNTEC Mfg., Inc. warrants to buyer defects when properly installed, and maintained by user. The sellers sole obligation is to repair or replace parts found to be defective, or non-conforming for one year and only after evaluation by factory. The liability of the seller shall not exceed the price paid for the components found to be defective. The above warranty is exclusive of all other warrantees whether implied or expressed. Seller assumes no obligation for special or, indirect damages incurred by user. All standard tank gauging systems are free of defects when properly installed and maintained by user. Warranty on tank gauging systems will only be effective after proper documentation has been submitted by the buyer to MNTEC Mfg., Inc. The sellers sole obligation is to repair or replace parts found to be defective, or non-conforming for one year and only after evaluation by factory. The liability of the seller shall not exceed the price paid for the components found to be defective. The above warranty is exclusive of all other warrantees whether implied or expressed. Seller assumes no obligation for special or indirect damages incurred by user. All standard replacement parts, "add-ons", or spare parts are free of defects when properly installed and maintained by user. The sellers sole obligation is to repair or replace parts found to be defective or non-conforming for 90 days and only after evaluation by factory. The liability of the seller shall not exceed the price paid for the components found to be defective. The above warranty is exclusive of all other warrantees whether implied or expressed. Seller assumes no obligation for special or indirect damages incurred by user. Equipment not covered by this warranty includes, but is not limited to: custom equipment, pressure transducers, and control systems. MNTEC Mfg., Inc., 1993 Pond Road, Ronkonkoma, NY 11779 Phone (631) 981-2001 Fax (631) 981-2007 www.mntec.com File Name: LU9 rev1-0.doc Page 20 of 20 Rev: 1.0 Rev Date: 7-2-2010