DIESEL Engine Fire Pump Controllers Features

Similar documents
FDF Foam Pump Controllers Features

FT60 Reduced Voltage - Autotransformer

DIESEL Engine Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features

Transfer Switch Features

Transfer Switch Features

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers

FDJ SERIES Jockey Pump Controllers Features

Remote Alarm Panels Features

FD30 Full Voltage - Across the Line July 2011

Fire Pump Controllers Foam (Additive) Controllers

Customer Connection Terminals Connection terminals for external customer connections, are located at the top of the Power I/O board.

EATON DFDAP-M / FDAP-M Remote Alarm Panels

Fire Pump Controllers Medium Voltage Controllers

FT20 Full Voltage - Limited Service. Electrically and Mechanically

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch

FT40 Reduced Voltage - Part Winding. Electrically and Mechanically

Soft Start Series MP700 Solid State, Reduced Voltage

Across-the-Line SERIES MP300 Combined Manual and Automatic

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

Drawing Submittal Package

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch

Technical Data Submittal Documents

Drawing Submittal Package

Variable Frequency Drive SERIES MP800 VFD

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass

Centro-Matic Automated Lubrication Systems System Controls

Technical Data Submittal Document

EATON LMR Plus Electric Fire Pump Controllers

AS950 REFRIGERATED SAMPLERS

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

NS (A) ECN

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

DGC-500 DIGITAL GENSET CONTROLLER

Options for Diesel Fire Pump Controllers

AS950 PORTABLE SAMPLERS

AS950 ALL-WEATHER REFRIGERATED SAMPLERS

Fire Pump Controller. For Electric Motor Driven Fire Pumps. Wye Delta Reduced Current Types

DGC-1000 DIGITAL GENSET CONTROLLER

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

Microprocessor Based Wye-Delta Reduced Current Type Starting

MANUAL FOR MODEL FD4 FIRE PUMP CONTROLLERS

Installation Guide for models:

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for models:

SECTION Fire Pumps

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

Technical Data Submittal Documents

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

INTELLIGENT FIRE ALARM CONTROL PANEL

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

MASTER DIESEL FIRE PUMP CONTROLLER

Commercial and Light Industrial Fire Alarm Control Panel

MASTER DIESEL FIRE PUMP CONTROLLER

Conventional Releasing Control Panel

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

Guide Specification Model CTG Automatic Transfer Switch

Specification/ Data Sheet

FTA550 JOCKEY PUMP CONTROLLERS

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

CONSTANT PRESSURE CONTROLLER

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

SP-1000X. Panic Device Power Controller Installation Guide. Rev

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

PILOT SERIES MPT700TS

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power.

PARAGON Commercial Refrigeration Controls

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

Med Touch Master Alarm

MR-2602 Two Zone Fire Alarm Control Panel

/ How To Order

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power.

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power.

AL600ULADA. NAC Power Extender. Installation Guide

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Series. Access Power Controllers. Installation Guide

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. HZM-Series-Class I, Div 2 Battery Unit. Instalation instructions

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

AL800ULADA. NAC Power Extender. Installation Guide

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

TECHNICAL DATA OBSOLETE

Transcription:

1-1 Product Description The FD100 Diesel Engine Controller is designed to control and monitor 12 or 24 volt, diesel fire pump engines. All models are listed by UL and ULC, and approved by Factory Mutual and CSA, as well as meeting or exceeding the requirements of NFPA 20 and NFPA 70. Product Microprocessor Control EATON Cutler-Hammer FD100 Diesel Engine Fire Pump Controllers are microprocessor based. All events surrounding the operation of the controller are stored within the memory, thus giving the ability to diagnose and troubleshoot problems based on an actual history of events. Events are time and date stamped. A main display unit provides a read-out of parameters such as current pressure, volts and amps and will display error messages as well as provide alarm indication. A status report is available which can be printed locally. The status reports provide a record of the state of the controller as it was left after commissioning. Pressure Transducer: 0-600 psi Each FD100 controller is equipped with a stainless steel, 0-600 psi pressure switch capable of withstanding a momentary surge pressure of 1000 psi. Run Period Timer The run period timer is built into the FD100 microprocessor and can be accessed via the membrane / keypad. It is programmable from 0-60 minutes and should be reset to thirty (30) minutes when the controller is placed in service. Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status LED is also visible on the front of the printer. Green indicates - Printer Operational while yellow indicates - Out of Paper. Last 1024 Messages The internal microprocessor stores the most recent 1024 messages in it s memory. The messages can be printed, viewed on the LCD screen or downloaded to a computer. Each message is time and date stamped. The LCD display acts as a paperless chart recorder. Common Alarm Relay The FD100 controller has a common alarm relay which energizes whenever there are any alarm conditions present. This relay is energized under normal conditions and has LED status indication. Additional Output Relays Two additional output relays labeled Future #1 and Future #2, can be user programmed to operate for ten (10) different functions. Programming is done in the FD100 menu using the membrane / keypad. Alarm Relay Ratings All alarm relays are rated at 10 Amps, 220VAC 1/3HP resistive load only. Engine Crank Cycle Upon detecting a drop in system pressure, the microprocessor sends a start signal to the engine, initiating its crank cycle. The crank cycle consists of six periods of 15 second duration, separated by five rest periods of 15 second duration alternating on each set of batteries. If the engine does not start within this cycle, an audible and visible Fail to Start alarm is activated. Should voltage of either battery fall below 67% of normal during the crank cycle, a Battery Failure alarm will be activated and the FD100 will alter the cranking sequence by continuing the process with the remaining good battery. The crank cycle terminates when the engine starts. The FD100 continues to monitor the batteries and engine for conditions such as: water temperature, oil pressure and speed (RPM). NEMA 2 Enclosures All FD100 controllers come standard with NEMA 2 enclosures unless otherwise ordered. Available options include: NEMA 3R, 4, 4X, 12. AC Power Failure The FD100 microprocessor retains a record in it s memory whenever AC power is applied / restored to the controller. The LCD display indicates the message AC Power OK. Weekly Test Timer Each diesel controller is equipped with a Weekly Test Timer, 24 hour clock, to automatically exercise the engine once a week for the time specified as per NFPA Pamphlet No. 20. Relay Board The FD100 Relay Board is clearly labeled with pullapart terminal blocks for ease of wiring and connections. All relays are labeled with full description as well as corresponding three letter designation as indicated on the wiring diagram. A visual LED indicates the energized state of the relay. All plug-in relays are identical 3PDT, allowing complete interchangeabilty. All terminal numbers are indicated on both the stationary and moveable portion of the terminal blocks. Pump Room Trouble and Engine Trouble common alarm relays are standard.

1-2 Product Alarm & Status Indication The display panel is equipped with sixteen indication LED s which indicate various functions and operations of the controller. They are colour keyed to the urgency of the indication. Green indicates normal running conditions, Yellow indicates supervisory alarms and Red indicates critical alarms. LCD Display / Function Panel The 2 line liquid crystal display allows viewing of all programming parameters in addition to battery and pressure information without opening the front door of the controller. Messages can also be downloaded to a laptop computer via the communications port located on the top of the main microprocessor board. Alarm LED s Auto Mode Fail to Start Low Oil Pressure Engine Overspeed Engine Run Battery Failure Charger Failure Low Fuel Level High Fuel Level Fuel Spill High Engine Temperature Low Pump Room Temperature High Reservoir Level Low Reservoir Level Technical Data and Specifications Line Terminals (Incoming Cables) Recommended Wire Size Terminal Number Distance Stranded # 14 Stranded # 14 Stranded # 10 Stranded # 10 Stranded # 8 (1.63 mm) (1.63 mm) (2.59 mm) (2.59 mm) (3.26 mm) 1-5, 9, 10, 16-38, L, N 39-134 Ground 6, 7, 8, 11 6, 7, 8, 11 N. A. N. A. N. A. 0 feet to 25 feet (7.62m) 25 feet to 50 feet (7.62-15.24m) Standards & Certification The FD100 Diesel Engine Fire Pump Controllers meet or exceed the requirements of Underwriters Laboratories, Underwriters Laboratories Canada, Factory Mutual, the Canadian Standards Association, New York City building code, and are built to NFPA 20 standards. For CE Approved Dimensional drawing - see Page 1-5. N. Y. C. APPROVED

1-3 Dimensions Standard Enclosure - Type NEMA 2, 12 Dimensions in Inches and (Millimeters). Approx. Weight Lbs. (Kg) 250 (113) N. Y. C. APPROVED NOTE: 1. All Enclosures finished in Fire Pump red. 2. Cable Entrance bottom only. 3. Standard Enclosure type NEMA 2,12 4. Enclosure made from #14 Gauge (0.75) HR Steel.

1-4 Dimensions Standard Enclosure - Type NEMA 3R (* 4, 4X) Dimensions in Inches and (Millimeters). Approx. Weight Lbs. (Kg) 250 (113) NOTE: 1. All Enclosures finished in Fire Pump red. 2. Cable Entrance bottom only. 3. Standard Enclosure type NEMA 3R 4. Enclosure made from #14 Gauge (0.75) HR Steel. N. Y. C. APPROVED * NEMA 4, 4X enclosures are supplied: Without wall mounting holes. With 1/4 Turn latches instead of 3 point handle.

1-5 Dimensions Standard Enclosure - Type CE Approved Dimensions in Inches and (Millimeters). Approx. Weight Lbs. (Kg) 250 (113) N. Y. C. APPROVED NOTES: 1. All enclosures finished in FirePump red. 2. Cable Entrance either top or bottom. 3. Standard Enclosure type NEMA 2.

1-6 Electrical Wiring Schematic N. Y. C. APPROVED

1-7 Electric Motor Connections FD110 CE Approved Diesel Engine Controllers N. Y. C. APPROVED

1-8 Field Connections Main Terminal Block 1. On Catepillar Engines only - Terminal #12 is used for the Fuel Solenoid. 2. On Catepillar Engines - Terminal #1 is not used except when a raw water valve is used. 3. After 1987, most engines did not require the use of terminal #7 - (Alt. Circuit) Relay Card Terminal Blocks NOTES: 1. All alarm contacts are rated 10 amps, 220VAC, 1/3 HP resistive load only. 8 Available for customer connections. See Note #1 for the ratings.

1-9 Catalog Number Selection FD100 Diesel Engine Controller Catalog Numbering System FD N Type Options 100 = Standard C4 - Remote Contacts (2 Form C) Low Reservoir 110 = CE Approved C5 - Remote Contacts (2 Form C) High Reservoir C6 - Remote Contacts (2 Form C) Low Fuel C7 - Remote Contacts (2 Form C) High Fuel Battery Voltage C8 - Remote Contacts (2 Form C) Fuel Spill 12L = 12VDC Lead Acid E1 - NEMA 3R - Raintight Enclosure 24L = 24VDC Lead Acid E2 - NEMA 4 - Watertight Enclosure 12C = 12VDC Ni-Cad * E3 - NEMA 12 - Dust Tight Enclosure 24C = 24VDC Ni-Cad * E5 - NEMA 4X - 304 Stainless Steel E8 - Tropicalization E9 - NEMA4X-PaintedSteel E10 - NEMA 4X - 316 Stainless Steel Negative Ground Polarity EX - Export Crating F - Floor Stand F2 - Floor Stand - 2 Inch Height Supply Voltage LO - Powered Louver Contacts A = (110-120V 50/60HZ) P7 - Pressure Switch c/w Pilot Light B = (220-240V 50/60HZ) P8 - Shutdown (Requires P7 Option) C = (380-415V 50/60HZ) P10 - Pressure Transducer - Sea Water D = (460-480V 60HZ) P13 - Externally Mounted Pressure Transducer E = (575-600V 60HZ) R1 - Space Heater (120 / 220V) R2 - Space Heater c/w Thermostat R3 - Space Heater c/w Humidistat R4 - Low Room Temperature Switch Language S1 - Fuel Level Switch, 16 Inch L1 = English S2 - Fuel Level Switch, 45 Inch L2 = French ECM - Electronic Engine Controller L5 = Spanish + - Additional Alarm Relays (Specify Function and Quantity) * Specify No. of Cells: Voltage of each cell in the battery:

1-10 Product Selection FD100 Diesel Engine Controller Catalog Numbering System Catalog Number Selection Chart Catalog Number Selection Chart Catalog Number Voltage Price Catalog Number Voltage Price FD100-12L-N-A 110-120V $6,290 FD100-12L-N-D 460-480V $6,780 FD100-24L-N-A 50 / 60 HZ $6,410 FD100-24L-N-D 60 HZ $6,900 FD100-12C-N-A $6,290 FD100-12C-N-D $6,780 FD100-24C-N-A $6,410 FD100-24C-N-D $6,900 FD100-12L-N-B 220-240V $6,290 FD100-12L-N-E 575-600V $6,780 FD100-24L-N-B 50 / 60 HZ $6,410 FD100-24L-N-E 60 HZ $6,900 FD100-12C-N-B $6,290 FD100-12C-N-E $6,780 FD100-24C-N-B $6,410 FD100-24C-N-E $6,900 FD100-12L-N-C 380-415V $6,890 FD100-24L-N-C 50 / 60 HZ $7,010 FD100-12C-N-C $6,890 FD100-24C-N-C $7,010 Options Catalog Number Option Selection Designation Description Price C4 Remote Contacts (2 Form C) Low Reservoir $75 C5 Remote Contacts (2 Form C) High Reservoir $75 C6 Remote Contacts (2 Form C) Low Fuel $75 C7 Remote Contacts (2 Form C) High Fuel $75 C8 Remote Contacts (2 Form C) Fuel Spill $75 E1 NEMA 3R - Raintight Enclosure $380 E2 NEMA 4 - Watertight Enclosure $700 E3 NEMA 12 - Dust Tight Enclosure $25 E5 NEMA 4X - 304 Stainless Steel $1900 E8 Tropicalization $275 E9 NEMA 4X - Painted Steel $1400 E10 NEMA 4X - 316 Stainless Steel $3000 EX Export Crating $525 F Floor Stand Std. F2 Floor Stand - 2 Inch Height $25 L1 English Language Std. L2 French Language Std. L5 Spanish Language $200 LO Powered Louver Contacts $175 P7 Pressure Switch c/w Pilot Light $570 P8 Shutdown (Requires P7 Option) Std. P10 Pressure Transducer - Sea Water $600 P13 Externally Mounted Pressure Transducer $250 R1 Space Heater (120 / 220V) $185 R2 Space Heater c/w Thermostat $250 R3 Space Heater c/w Humidistat $250 R4 Low Room Temperature Switch $145 S1 Fuel Level Switch, 16 Inch $180 S2 Fuel Level Switch, 45 Inch $200 ECM Electronic Engine Controller N/C + Additional Alarm Relays (Each) $75

1-11

FIRE PUMP CONTROLLERS Fire Pump Controller Family FD20 Limited Service Controller FD30 Across-the-Line FD40 Part Winding FD50 Primary Resistor FD60 Autotransformer FD70 WYE DELTA (Star-Delta) Open Transition FT SERIES Transfer Switches FD100 / 110 Diesel Engine Controllers FDM Medium Voltage Controllers FDF Foam Pump Controllers FDC Compact Controllers FDR Residential Controllers FD80 WYE DELTA (Star-Delta) Closed Transition FDJP / JY Jockey Pump Controllers FD90 Soft Start FDAP-M Remote Alarm Panels For more information on Eaton Cutler-Hammer Fire Pump Controllers, email us at chcfirepump@eaton.com or call us at 1-877-860-7955. EATON Cutler-Hammer 403 East Lake Blvd., Airdrie, Alberta, T4A 2G1 Canada tel: 403-948-7955 fax: 403-948-6967 www.chfire.com 2005 Eaton Corporation All Rights Reserved Printed in Canada Publication No.: