Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Similar documents
Low GWP Refrigerants for Air Conditioning Applications

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Study of R161 Refrigerant for Residential Airconditioning

Evaluation of HCFC Alternative Refrigerants

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

R32 Compressor for Air conditioning and Refrigeration applications in China

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Sub-Critical Operation of the CO2 Expander/ Compressor

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Control Method Of Circulating Refrigerant Amount For Heat Pump System

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

R-404A Alternative with Low Compressor Discharge Temperature

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Alternative Refrigerants For Household Refrigerators

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

PREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

HFO-1234yf Performance in a Beverage Cooler

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Gary Parker Refrigerants Product Manager

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Performance Measurement of R32 Vapor Injection Heat Pump System

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Simulation of the Working Process of an Oil Flooded Helical Screw Compressor with Liquid Refrigerant Injection

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Dynamic Simulation of Liquid Chillers

Thermodynamic Cycle Analysis of Mobile Air Conditioning System Using HFO-1234yf as an Alternative Replacement of HFC-134a

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Efficiency of Non-Azeotropic Refrigerant Cycle

ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/R32 in a Heat Pump Cycle

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

EXPERIMENTAL STUDY ON R1234YF HEAT PUMP AT LOW AMBIENT TEMPERATURE AND COMPARISON WITH OTHER REFRIGERANTS

Performance of CO2 Cycles with a Two-Stage Compressor

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Comparison of the High Side vs

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Development of Large Refrigerant Compressors

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Air-Cooled Heat Exchanger Performance for R410A

High Efficiency R-134a Compressor for Domestic Refrigerator

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Refrigerant Glide and Effect on Performances Declaration

Experimental comparison of a cascade refrigeration system operating with R744/R134a and R744/ R404a.

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

System Using Exhaust Heat from Residential GHPs

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

Gary Parker Refrigerants Product Manager

Development of HFC-134a Compressor for Domestic Refrigerator

Higher Efficiency, Lower Sound, and Lower Cost Air Conditioning Compressors: Part 1 Efficiency

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

2016 Annual Conference

New High Performance, Low GWP Refrigerants for Stationary AC and Refrigeration

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

Transcription:

Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm Ingersoll Rand / Thermo King, United States of America, Lars_Sjoholm@irco.com Cody Kleinboehl Ingersoll Rand / Thermo King, United States of America, CKleinbo@irco.com Young Chan Ma Ingersoll Rand / Thermo King, United States of America, youngchan_ma@irco.com Follow this and additional works at: http://docs.lib.purdue.edu/icec Sjoholm, Lars; Kleinboehl, Cody; and Ma, Young Chan, "Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors" (2014). International Compressor Engineering Conference. Paper 2328. http://docs.lib.purdue.edu/icec/2328 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

1390, Page 1 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm 1*, Cody Kleinboehl 2, Young Chan Ma 3 1* Ingersoll Rand - Thermo King Minneapolis, Minnesota, USA Lars_Sjoholm@irco.com, 952-887-3430 2 Ingersoll Rand - Thermo King, Minneapolis, Minnesota, USA CKleinbo@irco.com, 952-887-3429 3 Ingersoll Rand - Thermo King, Minneapolis, Minnesota, USA YoungChan_Ma@irco.com, 952-887-2526 *Indicates Corresponding Author Abstract Two economizer style compressors are explored, where the high pressure liquid is sub-cooled with a heat exchanger, while the evaporation side in the heat exchanger is connected to an intermediate compressor port. The intermediate port has a higher pressure than the suction pressure and a lower pressure than the discharge pressure. The two compressors being studied are of the scroll and screw type. One of the compressors is an open shaft compressor and the other one is a hermetic compressor. Both compressors have been modeled based on test data with R404A and at conditions that correspond to TRU (Transport Refrigeration Unit) applications. The compressor models have been used to explore lower GWP refrigerants such as R407A, R407F, N-40a, DR7 and DR33. For both compressors, each alternative refrigerant is compared against the baseline refrigerant R404A. This paper examines discharge temperature, capacity and capacity/input power (or COP, coefficient of performance) relative to the R404A baseline.

1390, Page 2 1. Introduction There is a proposed need for using lower global warming potential (GWP) refrigerants in transport refrigeration applications. The most common refrigerant today for transport refrigeration is R404A, which has a GWP of almost 4,000. The last time there was a major refrigerant change, the transport refrigeration industry, together with the commercial refrigeration industry changed from R502 to R404A. One of the primary motives of the change was to reduce ozone depletion potential (ODP). Among others, some of the refrigerants considered were: R407A, R407B, R407C, R134a, R22, R507, R404A and 69L. Of these candidates, R404A and R507 demonstrated very similar behavior. These two refrigerants were pursued mainly because they have very similar vapor pressure, capacity and discharge temperature. In addition, they have zero ozone depletion potential. These similarities meant that compressor type, compressor displacement and refrigeration systems could remain relatively unchanged. However, there were issues surrounding lubricants, COP, and relatively high GWP. The lubricant issue was solved with a switch from alkylated benzene or mineral oil based lubricants to Polyolester (POE) based lubricants. Maintaining high COP was not as important at the time, because energy prices were relatively low. Today, high COP is much more important for two reasons. Overall energy prices are considerably higher than during the last refrigerant change and COP is affecting indirect GWP. The high direct GWP of R404A and R507 is primarily due to the R143a component. All potential replacements for R404A do not include R143a. This paper mainly deals with non-flammable refrigerants (class A1), which typically have a GWP in the range of 1,000 to 2,000. One example of a mildly flammable refrigerant (class A2L) is also included. Mildly flammable refrigerants typically have a GWP in the range of 4 to 700. Flammable refrigerants such as hydrocarbons (class A2) are not discussed. Carbon dioxide (CO2) is not discussed because of its very different fluid properties. See Table 1 for the refrigerants being simulated. Table 1: Basic Characteristics of Simulated Refrigerants Temperature Glide at 1 atm. ( F) Critical Temperature ( F) Vendor Refrigerant Name(s) Flammability Class GWP MW R32 R125 R143a R134a R1234yf R1234ze Baseline R404A A1 3922 97.606 0.0% 44.0% 52.0% 4.0% 0.0% 0.0% 1.4 161.70 Common R407A A1 2107 90.113 20.0% 40.0% 0.0% 40.0% 0.0% 0.0% 11.5 180.10 Common R407F A1 1825 82.06 30.0% 30.0% 0.0% 40.0% 0.0% 0.0% 11.5 180.80 Honeywell HDR-47; N-40a A1 1346 87.037 25.0% 25.0% 0.0% 21.0% 9.0% 20.0% 13.7 186.00 DuPont DR-33; XP40; R449A A1 1410 87.44 24.0% 25.0% 0.0% 26.0% 25.0% 0.0% 10.9 183.00 DuPont DR-7 A2L 246 79.799 36.0% 0.0% 0.0% 0.0% 64.0% 0.0% 10.7 186.00 2. Compressor Type and Refrigeration System Traditionally, reciprocating compressors have been used in transport refrigeration applications. These compressors are single-stage and typically have two, four or six pistons. The refrigeration system for cooling is relatively simple, having one expansion valve and a suction gas to condensed liquid heat exchanger (See Figure 1). This type of compressor and refrigeration system is well proven, but also has some disadvantages. Due to the suction to liquid heat exchanger, the discharge temperature becomes rather high, which limits the choice of refrigerants. The compressor and system also limit the choice of basic vapor pressure, especially for lower vapor pressure refrigerants such as R134a or R1234yf. To accommodate lower vapor pressure refrigerants, reciprocating compressor footprints must become rather large for the transport application. Other factors that affect compressor footprint are oil sump size, oil sump placement and the capacity control system. This paper deals with

1390, Page 3 economizer or vapor injection rotary compressors of the scroll and screw type. This paper also compares the economizer refrigeration system shown in Figure 2, using alternative refrigerants. In the economizer system, the suction gas and economizer gas can be maintained with relatively low superheat. The economizer gas is introduced to a flute or pocket in the compression process that is between suction and discharge pressure. This extra economizer gas provides the benefit of lowering the compressor discharge temperature. In extreme operating conditions, such as low cargo box and high ambient temperatures, additional techniques must be used to regulate compressor discharge temperature. One technique is liquid injection, which affects the compressor s COP. However, liquid injection has a minimal effect on capacity if liquid is introduced to a flute or pocket that is isolated from suction pressure. Another technique to control discharge temperature is compressor oil cooling, which can improve COP. Both liquid injection and oil cooling add cost and complexity to the system. Economizer systems with both screw and scroll compressors have been in operation for quite some time in transport refrigeration applications [Sjoholm, 1996]. Figure 1: Vapor Compression Cycle with Suction to Liquid Heat Exchanger Figure 2: Vapor Compression Cycle with Economizer Heat Exchanger & Compressor

1390, Page 4 Two economizer type compressors have been tested with R404A. One compressor has an open drive shaft (Compressor A) and the other compressor is driven by a refrigerant gas cooled motor (Compressor B). One of the compressors is a screw type and the other one is a scroll type. The basic test configuration for the compressors is shown in Figure 3. This system makes it possible to test compressor performance, using different economizer mass flow and economizer pressure for a given discharge and suction pressure. In this case, the total isentropic efficiency is defined as strict isentropic efficiency [Sjoholm, 1986]. Compressor characteristic curves are generated from test data using numerical methods [Erickson, 1998]. Using this approach, compressor performance can be evaluated for different economizer pressures or balance points. In addition, refrigerants with different thermodynamic behavior and properties can be simulated. All the simulation data is compared at conditions corresponding to -10 F cargo box temperature and 80 F ambient temperature. Figure 3: Test Stand Configuration for Economizer Compressors In the comparison, the refrigerants being simulated have various amounts of glide. To account for this, the following assumptions have been made: The average condensing temperature is based on the 1) average bubble temperature and 2) average dew point temperature. The average evaporating temperature is based on an 1) economizer sub-cooled temperature from the bubble point at condensing pressure and 2) a dew point at the evaporating pressure. An ideal economizer heat exchanger is assumed. In an ideal economizer heat exchanger, the vapor and liquid refrigerant leave the heat exchanger at the same temperature. For the main suction gas and the economizer suction gas, a superheat of 40 F is used in the simulation. The isentropic and volumetric efficiency equations used in the simulation are the same for all refrigerants. The calculated efficiencies will be different for each refrigerant depending on differences in pressures, temperatures and enthalpies. All simulation results are compared with R404A as the baseline refrigerant.

1390, Page 5 3. Simulation Results Figure 4 shows discharge temperature simulation results for Compressors A and B, relative to R404A for refrigerants DR33, R407F, DR7, N-40a and R407A. All refrigerants being simulated show higher discharge temperatures relative to R404A. Figure 4: Discharge Temperature versus R404A Baseline Figure 5 shows capacity simulation results for Compressors A and B, relative to R404A. Refrigerants DR7 and R407F show higher capacity relative to R404A. DR33, N-40a and R407A show lower capacity relative to R404A. Figure 5: Capacity versus R404A Baseline

1390, Page 6 Figure 6 shows capacity/input power simulation results for Compressor A and B, relative to R404A. All refrigerants show higher capacity/ input power relative to R404A. Figure 6: Capacity/Input Power versus R404A Baseline 4. Conclusion All refrigerants being simulated show higher discharge temperatures than R404A. In practice, higher discharge temperatures can be managed using liquid refrigerant injection or compressor oil cooling for a portion of the operational envelope. The capacity changes range from -7% to +6% relative to R404A. To account for changes in capacity, different compressor displacements or speeds can be implemented. All refrigerants show approximately 4% higher capacity/input power relative to R404A. The trends appear to be similar regardless of whether the compressor is hermetic or open drive. Of the refrigerants being simulated, DR7 and DR33 appear to be the most suitable candidates for use in an ideal economizer system. If the desire is to use a low GWP refrigerant that behaves similarly to R404A (or R502), none of the simulated refrigerants are suitable.

1390, Page 7 References Achaichia, N., FO : une nouvelle génération en cours de développement, Cold Chain Forum Becerra, E., Motta, S., Spatz, M., 2010 Low Global Warming Alternative Refrigerants for Stationary AC&R Application, 2010 International Symposium on Next-generation Air Conditioning and Refrigeration Technology, Tokyo, Japan Erickson, L., 1998, Rating Equations for Positive Displacement Compressors With Auxiliary Suction Ports, Proceedings of International Compressor Engineering Conference, Purdue University, West Lafayette, IN, USA Minor, B. H., Rinne, F., 2012 Low GWP R404A Alternatives for Commercial Refrigeration, Chillventa, Nurnberg, Germany Sjoholm, L., 1996, Helical Lobed Compressor for Transport Refrigeration, Proceedings of International Compressor Engineering Conference, Purdue University, West Lafayette, IN, USA Sjoholm, L., 1986 Important Parameter for Small, Twin-Screw Compressors, Proceedings of International Compressor Engineering Conference, Purdue University, West Lafayette, IN, USA Acknowledgements The authors wish to thank the management of Ingersoll Rand and Thermo King for permission to publish this paper. The authors also wish to thank Jeff Berge, Robert Srichai and Ken Schultz for supporting this work.