APC APPLICATION NOTE #109

Similar documents
InRow Direct Expansion

InfraStruXure InRow SC

APC APPLICATION NOTE #119

ASHRAE JOURNAL ON REHEAT

Fundamental Principles of Air Conditioners for Information Technology

Performance Requirements for Air-Cooled Condenser

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Evaporator EM-1. Features. V.1. Ceiling Mount Evaporators

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

CB18/CBS18 Bulletin # September 1994 Supersedes August 1986

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

COOLING SPECIFIER S GUIDE EQUIPMENT PROTECTION SOLUTIONS COOLING

Installation Instructions

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

Guide Specifications for InRow Direct Expansion

COMMERCIAL HVAC EQUIPMENT Indoor Self-Contained Units

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

ENERGY RECOVERY HEAT PIPE HEAT EXCHANGERS

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

BUILDING VENTILATION GUIDE

How to Select and Size Enclosure Thermal Management Systems: White Paper, Title Page. How to Select and Size Enclosure Thermal Management Systems

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

HVAC DISTRIBUTION and DELIVERY SYSTEMS

BUILDING VENTILATION GUIDE FOR LG HVAC SYSTEM INSTALLATION

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

Model 8120 and 8126 Safety & Installation Instructions

Cabinet Cooler Systems

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS

Natatorium Economizer Vs. Conventional Dehumidifier

ShuttleAIRE Systems. A complete range of HVAC systems for small and medium sized vehicles.

32 Tips to Consider Before Purchasing an Electrical Enclosure Air Conditioner TABLE OF CONTENTS INTRODUCTION... 3 TECHNICAL FEATURES 4

Vortex Enclosure Coolers A/C ATEX

ANSI/AHRI Standard 911 (SI) 2014 Standard for Performance Rating of Indoor Pool Dehumidifiers

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Q-TEC QC-Series Chilled Water Air Conditioner

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

L14 ENVIRONMENTAL CONTROL TECHNICAL DATA

Continuous Commissioning: A Valuable Partner to Retrofit Projects

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

COPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Union County Vocational - Technical Schools Scotch Plains, New Jersey

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Dehumidifying with Dedicated Outdoor Air

Technical Assignment 3 11/15/04. Executive Summary

Vertical Air Handler Unit

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

FirstEnergy Program Overview

WHITE PAPER.

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

A/C Cooling Load calculation and measurement

Q-Tec TM QC-Series Chilled Water Air Conditioner

b.) Technical Information:

SeasonMaker ThinLine Fan-coil Units

Liquid desiccant dehumidification systems. Product guide

LV SERIES SINGLE-ZONE HEATING & COOLING SYSTEMS

Performance Rating of Computer and Data Processing Room Air Conditioners

Your safety and the safety of others are very important.

Best Practices for Condensing Boilers

Heat Recovery Units. Heat Recovery 1

Scholar III Unit Ventilator

Eclipse ER Indirect Air Heater

DIGI-VAV APPLICATIONS

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

INSTALLATION INSTRUCTIONS

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

Inffusers. idl20 (2 WAY) ids60 (4 WAY)

LV SERIES SINGLE-ZONE HEATING & COOLING SYSTEMS

50TM COMBINATION HEATING/COOLING UNITS

McQuay Suite Type N Top Mounted Hydronic Heat Incremental Packaged Terminal Air Conditioners C:

FORM EG2 (502) FlexSys Configured Packaged Rooftop Air Conditioning Units

DRYAIR Turnkey Dry Room Standards

Thermal Management INDEX. Management. Thermal TM-1

An Efficient Cold Store Facility

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

MFC Series Boiler Vent and Combustion Air Guide

Safety and Installation Instructions Model 1700

gforce Units Data Aire and Data Temp Series

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

PoolPak MPK Series. PoolPak.com. Environmental Control Systems REDUCED FOOTPRINT & WEIGHT COMPARED TO EARLIER GENERATIONS

ENCLOSURE COOLING. Glossary

Explanation of Cooling and Air Conditioning Terminology for IT Professionals

PAC, NQAC, HQAC, SQAC, EQAC AIR-COOLED CONDENSERS OPERATING AND INSTALLATION INSTRUCTIONS

Custom Air Handler Solutions Custom Units to Meet Your Unique Design Needs

ENERGY STAR Qualified Homes

turn to the experts R 410A DC INVERTER LIGHT COMMERCIAL SERIES

Transcription:

#109 Application Guidelines for the InfraStruXure InRow SC Condenser By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets. This application note outlines various considerations for the condenser section to ensure proper operation. Introduction The InfraStruXure InRow SC is an air cooled, self-contained, cooling-only air conditioner designed to be placed in-row. The inrow design allows waste heat from the IT equipment to be drawn into the return of the SC unit and neutralized before it mixes with the room air. Conditioned air is discharged into the cold aisle for immediate use by the equipment in the adjacent racks. The heat absorbed from the air stream must then be rejected from the room; this is accomplished by the condenser section in the upper half of the InRow SC enclosure. The condenser section is designed to be connected to a drop ceiling plenum. See Figure 1 for a diagram of the airflow. Figure 1 InfraStruXure InRow SC airflow diagram Hot discharge gas from the compressor enters the condenser coil, the condenser fans draws in air from the plenum and then blows it across the coil. Heat from the refrigeration system transfers to the air and that air is then discharged back into the plenum space. The condenser fan assembly contains 3 variable speed fans, controlled by the unit firmware. The condenser ducting kit consists of 3 flexible air ducts, each 6 foot long, 10 inch diameter (1.8m long, 254mm diameter) and a ceiling tile adapter plate. The ACSC100 comes with a 24 x 24 adapter; ACSC101 comes with a 600mm x 600mm adapter plate. The InRow SC unit overall has the same form-factor as a NetShelter SX rack, except is half the width (InRow SC is 300mm wide). 1 _

Standard Condenser Application Installation of the unit using the flexible air ducts and ceiling tile plate, connected to a building cooling system return plenum is the preferred method for managing condenser air on the InRow SC. The plenum must provide an adequate volume of airflow, within a set temperature range, and be able to treat the heat rejected by the unit on a continuous basis in order to ensure proper operation and prevent downtime. Review the requirements below to ensure the plenum can meet the unit s needs. If not, you must consider alternate means of managing the condenser air or a different cooling product entirely. The SC condenser fan speed is varied between a minimum of 30% to a maximum of 100%, see Figure 2 for a chart of airflow versus fan speed. The maximum condenser airflow is 850 CFM (1440 m 3 /hr) which requires the plenum to provide at least this much airflow to the condenser inlet and remove that much from the condenser discharge. The SC condenser must also receive air that is from 32-105 F (0-40 C), temperatures outside those limits will significantly impact the unit performance and can cause the unit to shut down. Finally, the InRow SC can reject up to 10 kw (34000 BTU/hr) of heat which must be treated by the building comfort cooling system or exhausted to the outside ambient air. All 3 of these requirements must be met on a continuous (24 x7) basis to ensure reliable operation of the InRow SC unit. If the building cooling system has night and weekend set backs, is shut down during the off-season and/or for maintenance, or has limited remaining capacity you may need to consider Condenser Air flow Rate [SCFM Figure 2 Airflow vs. Fan speed 900 800 700 600 500 400 300 200 30 100 Condenser Fan Speed [%] alternatives to the standard installation. Having a very large plenum is not substitute for proper ventilation and heat rejection. Heat rejected into the plenum still must get out of the facility and into the ambient environment. Otherwise it will simply accumulate in the plenum and cause the unit to shut down. While the actual size of the plenum is not critical, it is recommended that the plenum be at least 12 (300mm) deep to prevent restriction of the duct tubes outlets. 2

Condenser Airflow and Temperature Requirements The installation of the duct tubes can impact the airflow through the condenser. The maximum rated airflow through condenser is 850 CFM (1440 m 3 /hr), based on 6 feet (1.8m) of straight duct runs. Any bends in the tubes or extensions to the duct tubes create additional pressure drop that restricts the airflow though the condenser and reduces the performance of the unit. When installing the duct tubes, route them in the straightest possible manner and trim the excess if needed to minimize bending. Figures 3 and 4 show the maximum condenser airflow against additional pressure drop. As you can see any additional losses beyond the design conditions will reduce the airflow. Figure 3 Airflow vs. Pressure Drop (English) Additional Pressure Drop [in.w.c.] 0.50 0.40 0.30 0.20 0.10 0.00 400 550 630 850 Condenser Air Flow Rate [SCFM] Figure 4 Airflow vs. Pressure Drop (Metric) Additional Pressure Drop [Pa] 140 120 100 80 60 40 20 0 680 935 1070 1440 Condenser Air Flow Rate [m 3 /hr] 3

In Table 1 you can see how different bends impact the pressure drop as well. Please note the differences between inlet and outlet when making any calculations of additional losses; the inlet and outlet are in series, so the figures are additive. The relationship between flow rate through the duct tubes and the friction loss is shown in Figure 5; use this chart when considering extending the duct tubes beyond the standard 6 foot (1.8m) length. It is recommended that you have no more than 0.25 (65 Pa) of additional pressure drop on the condenser tubes to avoid excessive restriction on the airflow. When the maximum condenser airflow is reduced the maximum allowable condenser inlet temperature is also reduced, this is discussed below. Table 1 Losses due to bends in duct tubes Dynamic Pressure Drop at Sea Level Condenser Inlet Duct Condenser Outlet Duct Bend Type in. w.c. Pa in. w.c. Pa 45 0.018 4.7 0.005 1.2 60 0.024 6.2 0.006 1.6 90 0.030 7.8 0.008 1.9 Figure 5 Friction Loss vs. Flow Rate The next consideration after airflow is the temperature of the condenser inlet air. The SC is rated using 95 F (35 C) air into the condenser. Higher air temperatures will result in the unit s maximum cooling capacity being reduced. This may impact your application depending on the load within the room. Reducing the condenser inlet temperature will not increase the unit capacity beyond the published values, however the unit will require less condenser airflow to reject the same amount of heat and consume less power. See section on Condenser Ducted to Other Rooms for additional discussion. Figure 6 shows a chart comparing the inlet temperature versus cooling performance, based on a constant 850 CFM (1440 m 3 /hr) of airflow. As illustrated, with inlet temperatures above 105 F (40 C) the capacity reduction becomes much more extreme. The unit has a 4

High Head Pressure Protection feature which will proactively decrease the unit s cooling capacity in order to reduce the refrigerant discharge pressure and prevent the unit from shutting down on a high head pressure alarm, avoiding a total loss of cooling. If the airflow to the condenser is restricted for any reason, then that maximum allowable inlet temperature is reduced. See Table 2 for temperatures compared to restricted condenser airflows. Even modest restrictions to airflow will have a significant impact on the upper temperature limit. Humidity of the condenser inlet air is not a factor that needs to be considered, however condensation inside the duct tubes and the SC condenser section must be avoided. See section on Condenser Ducted to Outdoors for additional discussion related to this. 110 Figure 6 Capacity vs. Condenser Inlet Temperature 100 Cooloing Capacity [%] 90 80 70 60 50 80 85 90 95 100 105 108 26.7 29.4 32.2 35.0 37.8 40.6 42.2 Condenser Entering Air Temperature[ o F] [ o C] Table 2 Restricted Airflow Temperature Limitations Additional Pressure Drop [in w.c.] (Pa) (Without Compensation Fan) 0.0 0.1(25) 0.25(64) 0.45(116 Condenser Air Flow Rate [SCFM] (m 3 /hr) 850 (1440) 700 (1990) 550 (935) 400 (680) Maximum Condenser Entering Air Temperature [ o F] ( o C) 108 (42.2) 103 (39.4) 98 (36.7) 88 (31.1) Alternative Condenser Installations Many facilities do not have ceiling plenums that meet the heat rejection needs of the SC. In these situations you must plan for alternate methods of installing the unit or modify the plenum so it does meet the requirements. For example, if the building 5

cooling system has night and weekend set backs, this may cause operational issues with the InRow SC during those periods due to reduction of air movement within the plenum and accompanying rise in plenum temperature. It may be possible to modify the plenum to include additional equipment, such as roof ventilators or VAV boxes. These devices can provide the ventilation needed during off-hours to reject the heat from the SC unit to the outdoors. This allows for a standard installation of the InRow SC because the plenum can now be considered to be continuously available. A consulting engineer or design-build contractor should be involved in the process of determining the feasibility of this approach and selection of ventilation equipment. Other possibilities include connecting both the condenser inlet and outlet directly to the ambient air for heat rejection, drawing and discharging condenser air from an adjacent room in the facility, or fabricating custom duct work to act as a substitute plenum, which then ties into the building return system. While none of these scenarios are specifically endorsed by APC, they can be very effective at rejecting heat from the SC. Condenser Ducted Outdoors Connecting the SC condenser ducts directly to the outdoors is possible and there are several factors that need to be considered when investigating this approach. It is recommended that outdoor air be filtered and preconditioned for optimal operation of the SC unit. As mentioned there is a recommended upper limit of 105 F (40 C) on the inlet air temperature for the condenser; this minimizes any reduction in the unit cooling capacity. There is also a recommended lower limit; entering condenser air temperatures below 32 F (0 C) may cause condensation on the outer casing of the SC units depending on indoor conditions. Additionally, the SC does not provide for alternate means of low ambient control, other than the fan speed control. At very low temperature, the condenser fans may not be able to modulate low enough to prevent erratic operation of the unit. Alterations to the piping system to install head pressure control valves or other methods of head pressure control will void all factory warranties and violate UL or other safety certifications, so inlet temperatures below 32 F (0 C) must be avoided. The duct tubes inlets/outlets also need to be protected from a variety of environmental concerns. Dust filters, debris screens, rain and snow shields, and appropriate wall louvers or roof caps need to be installed. All these additions will affect static pressure load to the condenser fans and must be taken this into account. Booster fans will most likely be required to overcome the additional pressure drop, see the section on Custom Duct Work for additional discussion on this. Condenser air drawn from parking garages, industrial zones, coastal areas, or other areas with air containments or air entrained with corrosive chemicals is prohibited. The InRow SC does not have coil coatings or other corrosion resistant materials in the condenser section. Operation in these environments can damage the unit and reduce its operating life. Condenser air drawn from environments classified as hazardous or explosive is also prohibited. The SC is not an explosion proof product; operation in environments classified as hazardous will result in damage to facilities, equipment and possibly personal injury or death. 6

Condenser Ducted to Other Rooms Another approach is to connect the condenser ducts to an adjacent room. This solution can overcome the lack of ceiling plenum or the complexity of preconditioning outdoor air. Similarly, the condenser inlet can be taken from the server room itself and only the condenser exhaust discharged into another part of the building, or outside. This causes the room to be negatively pressurized, drawing in unwanted contaminants and unconditioned air. That infiltration air can introduce additional heat and moisture into the space, reducing the effectiveness of the SC. This risk can be mitigated by adding a louver in the door or wall that connects to an adjacent space that has conditioned air, such as an office area. Using room air for the condenser inlet will reduce its airflow requirements and thus reducing the volume of infiltration air into the room, which in turn helps the SC unit maintain a more stable temperature in server room or wiring closet. This has an additional benefit of reducing the power consumed by the condenser fans. Figure 7 shows how the airflow requirements are significantly reduced as the inlet temperature decreases. For example, with an evaporator return air condition of 85 F, 33 %RH, a condenser inlet temperature of 70 F (21 C) would require only 450 CFM (765 m 3 /hr). This translates approximately into a 250 Watt reduction in unit power consumption and drives down total cost of ownership. Figure 7 Airflow vs. Inlet Temperature 425 psig Discharge Pressure Line, 85F/33% RH Return Air 950 70 78 87 Condenser Entering Air Temp [F] 92 850 750 650 550 450 350 Condenser Air Flow Rate [CFM] Custom Duct Work Field designed and fabricated duct work can be provided to act as a substitute plenum space, connecting to a building return system, or in lieu of a direct connection to the outdoors. There are 3 duct connections on the unit; the rear-most duct is for 7

condenser inlet air, and the remaining 2 ducts are for condenser exhaust. The condenser exhaust ducts can be merged to one duct for simplicity. Inlet and outlet ducts should be sized to have minimum air pressure drop, see the discussion above regarding friction losses and airflow restrictions. Booster fans will usually be required to compensate for the pressure drop due to long duct runs. In all cases the duct work must meet the same requirements as the other installation methods in terms of adequate volume and temperature of airflow, protection from the environment and continuous availability. Duct installations also need to meet all applicable local and national codes. About the Author: David Roden is the Product Information Manager for Small Cooling Solutions at American Power Conversion (APC). Previously David was the Senior Applications Engineer for precision cooling solutions at APC, supporting data center projects worldwide. Prior to joining APC, David served as an officer in the United States Army. He received a Bachelors degree in mechanical engineering from Rensselaer Polytechnic Institute in Troy, NY and is a member of ASHRAE. 8