THE EVALUATION OF MULTI-ZONE AIR FLOW PATTERN AND VENTILATION RATES WITH TRACER GAS METHODS IN APARTMENT HOUSE

Similar documents
Home Performance Science

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

MECHANICAL VENTILATION

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings

Measurement of Ventilation and Inter-zonal Distribution In Single Family Homes

Are you Getting Your Fan Flows Right?

Ventilation System Description. September 8, 2000 HETA

Put the V back in HVAC

Ventilation Techniques. Topic 5 - Audio 53

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Measurement of Ventilation and Interzonal Distribution in Single-Family Homes

Temperature Distribution of Rotary Heat Recovery Units

Challenges and Methods of Estimating a Conceptual HVAC Design

Ventilation for New Low-Rise Residential Buildings July 20, 2015

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

USEFUL RESOURCES: Applicability. Item o of section 150. Review-Definitions Section 101

PERFORMANCES OF DAHT CONNECTED TO BUILDING AIRTIGHTNESS AND INDOOR HYGRO- THERMAL CLIMATE

Why ventilate? Dilute contaminants Control or aggravate humidity Comfort or lack of cooling Odors Provide oxygen

Effective ventilation is necessary for the comfort

VENTILATION TECHNOLOGY - RESEARCH AND APPLICATION. 8th AIVC Conference, ~berl ingen, Federal Republ ic of Germany September 1987 POSTER P6

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

BEST PRACTICE RECOMMENDATIONS

Ventilation Strategies for Healthy IEQ and Energy Efficiency

Indoor Environmental Quality

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

NATIONAL INSTITUTES of HEALTH FUME HOOD TESTING PROTOCOL. For CONSTANT VOLUME FUME HOODS

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

Smoke Management in High-Rise Structures

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

MD and Its Impact on Lab Facilities

Ventilation Strategies in Weatherization

A Study on Hierarchy of Spatial Configuration in Outpatient Department of General Hospital

Moisture, Ventilation & Global Weirding NEHERS Webinar Series

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

OCCUPANT INTERACTION WITH VENTILATION SYSTEMS 7th AIC Conference, Stratford-upon-Avon, UK

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

PRESSURE RELATIONSHIPS IN HOSPITAL CRITICAL-CARE FACILITIES

2006 Building Science Press All rights of reproduction in any form reserved.

Ventilation Solutions IAQ Canada

FirstEnergy Program Overview

Clearing the Air: Ventilation. RESNET Building Performance Conference San Diego, CA February 17 th, 2015

with minimal heat loss for a pleasant and healthy living environment

A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

A Necessity for Preventing Unsafe Backdrafts and Unhealthy Air

Bill McCullough. Director ERV Products. Dallas, TX

OPERATION INSTRUCTION

Assessment of H2S Complaints

A STUDY ON THE APPLICABILITY OF THE TIME-DIVISION HOT-WATER SUPPLY HEATING FOR ONDOL - THE RADIANT FLOOR HEATING SYSTEM IN KOREA

Mechanical Ventilation : How much is enough? Can there be Too Much? Subrato Chandra Resnet Meeting 2/20/07

Worried aboutthe air quality in your schools?

An experimental study of the impact of tunnel suppression on tunnel ventilation

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

ORT6WXA ORT9WXA Slide-out Rangehoods

Heat Recovery Ventilation: Fresh Healthy Indoor Air with all the Savings

CERV Fan and Duct Sizing Information

LEED for Homes Points

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

PDH & Professional Training

How to ensure Thermal Comfort in buildings with CFD

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

The V in HVAC: Mechanical Ventilation in ENERGY STAR Certified Homes

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Technical Information

50% 80% 7 Years. Filter. Ventilation Solutions IAQ Canada. Ventilate. of our time is spend indoors. Limited warranty on motors

Joseph Lstiburek, Ph.D., P.Eng, ASHRAE Fellow. Building Science. Adventures In Building Science. presented by

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

The Art of Building Science

Exhaust Makeup Air System What goes out, must come in

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation

EXHAUST FAN FLOW METER AND TRUEFLOW AIR HANDLER FLOW METER

THE AMOUNT OF ACCUMULATED DUST IN DUCTS OF NEW HVAC INSTALLATIONS

The 2018 Ventilation Extravaganza. Rick Karg Residential Energy Dynamics 2018

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system

A Study on Safety by Risk Assessment of Clean Room

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Design Architect s/applicant s Certification Of Threshold Criteria

Comfort and health-indoor air quality

18. Mechanical Ventilation

Controlled mechanical ventilation GB 03

The evil that men do lives after them; the good is oft interred with their bones.

Indoor Thermal Environment of Residential Buildings in Three Cities of China

Time-Based Scheduling of Residential Ventilation

Practical and Effective Approaches to Residential Ventilation for Production Builders

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

VENTILATION CHAPTER 4

Performance of Heat Recovery Ventilation System with Ground Source Brine Heat Exchanger Pre- Heating System in the Context of nzeb

WHOLE-HOUSE VENTILATION SYSTEMS

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Transcription:

THE EVALUATION OF MULTI-ZONE AIR FLOW PATTERN AND VENTILATION RATES WITH TRACER GAS METHODS IN APARTMENT HOUSE DW Yoon 1, JY Sohn 2, SD Kim 3 and HS Kim 4 1 Dept. of Building Equipment and System Engineering, Kyungwon University, Kyunggi, Korea 2 School of Architectural Engineering, Hanyang University, Seoul, Korea 3 School of Environmental Engineering, University of City of Seoul, Seoul, Korea 4 Dept. of Architectural Engineering, Dankook University, Seoul, Korea ABSTRACT The air change rates of ventilation system and inter-zone airflow rates were investigated at the apartment house. The fully developed ventilation systems are designed to supply outside air at each room and gas range hoods are installed with makeup air to remove pollutants effectively from cooking processes. The airflow patterns and air balance could be changed due to the different operating conditions of the ventilation systems. Detailed testing of multi-zone airflow and ventilation rates were conducted using two different types of tracer gas method. The results of measurement and airflow pattern were compared with those of the design strategies. Air changes per hour were ranged from 0.38~1.33[h -1 ] at individual rooms. In the dining room and kitchen area, air change rates are varied from 4.69~10.59[h -1 ] with various operating conditions of range hoods. INDEX TERMS Inter-zone airflow, Ventilation, Tracer gas methods, Apartment house INTRODUCTION Ventilation has been concerned with HVAC system, but most of the effort has focused in the area of commercial buildings in Korea. Traditionally, ventilation of the residential building was not a major concern because people think that it was enough to get the fresh air through the operable windows and infiltration from the envelope leakage(yoon.2001). Since the energy crisis, building technology has been developed and houses have become much more energy efficient and air- tight. Poor indoor air quality is related to new building technology, new materials, and ventilation and energy management system. All of these factors have contributed to an increasing public concerns about indoor air quality and ventilation. Sick house and sick building symptom is newly issued with increasing chemicals at the newly constructed buildings. Apartment house air tightened and insulated has advantages to conserve energy but cause the indoor air quality problem. Due to the lack of the natural ventilation, poor indoor air quality and insufficient ventilation rate have resulted high risk of indoor environments from contaminants driven by finishing materials and residential activities such as cooking, cleaning and house keeping. It is urgent to apply the mechanical ventilation design systematically in apartment houses. The aim of this study is to chaise the airflow patterns at the apartment house where the mechanical ventilation system is fully developed with both of general Contact author email: dwyoon@kyungwon.ac.kr 296

ventilation and spot ventilation. The kitchen ventilation above the gas range is design to exhaust the fume directly without spreading the contaminants to other indoor space during the cooking process. It is important not to be contaminated the living area for healthy indoor environment. METHODS Selected Building All experiments are carried out in a real scaled model house as a show room constructed with exactly the same ventilation systems applied to a high-rise apartment house. The model house is located at the inside of the exhibition building of the show room. Ventilation system was designed to introduce proper amount of outside air to individual room with duct working, and the exhaust was installed at the kitchen and bathroom. It is important to remove the pollutants from the cooking process exactly before spreading to other indoor spaces. The ventilation system was designed to control the supply air volume properly and positive pressure was appeared at the individual room. The air balance is designed to lead the airflow to the kitchen ventilation hood when the ventilation is operating. Experimental Measurements Two types of tracer gas methods(doi, Satoshi.1996), such as constant concentration method and step-down method, were applied to measure the multi-room airflow patterns using SF 6 gas [Multi-Gas Monitor, 1302, INNOVA Denmark]. Ventilation rate and airflow patterns were evaluated for various operating conditions of kitchen ventilation. At each case of operation, air volumes of the spot ventilation and HVAC system were measured directly using airflow meter [Air Capture Hood, Model 8373 and Air Flow Meter 8360-M, TSI USA]. And then pressure differences were measured to know the airflow pattern between two adjacent rooms using manometer [Microprocessor Manometer MEDM 5k, Dwyer USA]. Also two types of tracer gas methods were applied to figure out the air volumes from infiltration and inter-zone cross flow. Constant concentration method, which releases SF 6 gas as tracer continuously and keeps the concentration of the tracer gas constant at whole area of the unit plan, is applied for determining airflow rate of outdoor air volume supplied to a individual room quantitatively. This air volume could be counted on both of infiltration and mechanical ventilation. As the constant concentration method should be kept tracer gas concentration constant at all rooms, the gas concentration was not effected by airflow from other rooms and it could be to measure the outside airflow rates entered individual room as infiltration. This method is possible to deal with variable conditions such as ventilation driving force' change. The tracer gas concentration was constantly made 5ppm as set point. And the next step, the measurement of the step-down method as concentration decay was performed to determine the inter-zonal flow at each room quantitatively. Finally it is possible to calculate the air volumes both infiltration from the window and inter-zone flow to adjacent room. Air change rate per hour is given by equation (1) using the constant concentration method. Discharge rate of tracer gas, which is varied with outside air volume introduced, is proportionally adjusted by measurement device automatically. 1 [ ( ) ( ) = F τ N τ V C h ] (1) Where N (t) and F(t) are the air change rate and tracer gas dosing rate at time t, V and C are 297

the air volume of the room and tracer gas concentration at a room. In step-down method, tracer gas concentration is measured with a gas analyzer at every point after releasing tracer gas into the room air. Air change per hour in step-down method is given by equation (2): N 1 C1 = ln (2) T C where C 1 and C are the tracer gas concentration at time t 1 and t, and Δ T means the time interval (t-t 1 ) of measurement. Table 1 shows the operating condition of the ventilation system in experiments. Airflow patterns were measured according to the various operating conditions. Case #1 shows the operating condition as a general ventilation concepts and Case #2 shows the fully operating condition of various kitchen ventilation. Table 1. The operating condition of the ventilation system in experimental design Location of Exhausts Case.#1 Case.#2 Kitchen Hood Kitchen Extra exhaust grill Multiuse room Constant exhaust on ceiling Make-up air supply Multiuse room hood Extra exhaust grill Make-up air supply ( : operating, : stop operating) RESULTS AND DISCUSSION Airflow with the Ventilation Strategies Ventilation system is designed to supply outside air only at the individual room, which could be maintaining positive pressure to prevent spreading the pollutants and odor emitted during cooking process. The exhaust grills are located in the kitchen area only in order to make the air stream for the kitchen direction. Outside air volume was decided according to the number of occupants as 20m 3 /h - 80m 3 /h. Also, It is the design strategies that 400 m3 /h of outside air is introduced at the kitchen and 350 m3 /h is introduced at the multiuse room as a make-up air when the range hoods are operating. Air change rates and air airflow patterns between rooms were measured for all cases of experiments. Airflow patterns were chased using smoke test and static pressure differences. In the case of general ventilation, individual room indicated slightly positive pressure due to the supply of outside air. And the negative pressure appeared in the kitchen, which is resulted from the constant exhaust without any supplying the make-up air. Outside air volume at the kitchen was measured about 440 m3 /h. Also supply air volume at the multi-use room was measured from 325 m3 /h to 331 m3 /h. It shows that the make-up air is maintained within 10% of the designed. Inter-zonal airflow rates among rooms were varied 298

with system operating conditions. Pressure differences between rooms measured with low values 0 ±1Pa during the general ventilation. But it is enough to find the airflow pattern in the whole area. Owing to the intensive exhaust in kitchen, the pressure difference between kitchen and living room were indicated to 5 ~ 6Pa. Evaluation of the Inter-zone Airflow Rate Two types of the tracer method and direct measurement of the supply air in ventilation system have realized to figure out the airflow rate via infiltration and inter-zone airflow between the adjacent rooms. At entrance hall and veranda areas where were affected by infiltration, the concentration was largely deviated but finally approached to set point of tracer gas when applying the constant concentration method. Figure 1 shows the outside airflow rate resulted from the constant concentration method. Air change rate is measured similar to the designed air volume of the mechanical ventilation system. Several areas such as an entrance hall and two verandas appear highly deviated profiles of airflow rates. Table 2 shows the averages of the air change rates measured by constant concentration method. Air volumes evaluated indicate very similar to those of the measured directly in rooms. Figure 1. The variation of total air volume evaluated by tracer gas methods Table 2. The average of air change rates measured by constant concentration method( m3 /h) Items Air change rate ( m3 /h ) Air change per hour Main room 34.2 0.69 Room(1) 20.6 0.61 Room(2) 16.3 0.59 Room(3) 15.8 0.51 Family room 24.1 1.34 Living room 68.3 0.67 Entrance room 25 3.90 Veranda(1) 59.4 2.32 Veranda(2) 23.2 1.69 299

Individual room has zonal airflow between adjacent rooms and the outside air volume supplied by mechanical ventilation system. After measurement of constant concentration method, the concentration decay (step-down) method was applied to find the total airflow rate in the individual room. Total airflow rate is ranged over 20~30 m 3 /h more comparing to air volume measured by the constant concentration method. Those air volumes are assured that of which caused by inter-zone airflow between adjacent individual rooms. Table 3 shows the total airflow rates and inter-zone airflow between individual rooms. Hereby the total air change rates indicate the air volume combined both of the outside air by ventilation system and the cross airflow rates between rooms. It was found that total airflow in the rooms was decreased when the kitchen ventilation was off condition. The inter-zonal flow was decreased too with the same situation. Even though the driven force for the exhaust in the kitchen was increased, inter-zonal flow was relatively decreased. It seems that the range hood operating with the make-up air makes smoother for the inter-zone airflow and maintains the air balance effectively in the unit of the apartment house. Table 3 the airflow rates between rooms in each case of measurements( m3 /h) Family Main Items Room(1) Room(2) Room(3) room room Supply Air Volume with 20.6 16.3 15.8 24.1 34.2 Mechanical Ventilation System Total Airflow Rate 44.5 36.9 48.3 46.1 45.6 Case Airflow Rate moved to #1 23.9 20.6 32.5 22.0 11.4 other Rooms Total Airflow Rate 42.5 31.4 38.8 45.7 43.6 Case Airflow Rate moved to #2 21.9 15.1 23.0 21.6 9.4 other Rooms No indicates total airflow volume in the room [m 3 /h] 1 family room 2 room(1) 3 room(2) 4 living room 5 main room 6 room(3) 7 kitchen 8 multi-use room 9 entrance hall 10 veranda(1) 11 veranda(2) Figure 2. Example of the airflow patterns and airflow rates.(case #1 and Case #2). 300

Airflow Patterns in the apartment house From the measurement of static pressure and the smoke test, airflow pattern was chased in whole unit of the model house. The airflow patterns and the air volumes introduced are shown in Figure 2. Because the model house is located at the inside of the covered building, the model house is not affected directly by the outdoor weather condition. Air infiltration is occurred at the veranda area and the rooms faced on the outside. In every case of measurement, the inter-zone airflow patterns are well matched to the design strategies for the mechanical ventilation system. It is found that the polluted matter emitted from the cooking process could be exhausted directly without spreading to the other areas. The room air introduced by mechanical ventilation has finally moved to the kitchen and multiuse room for exhausts through bedroom and living room in turns. And the outside air volumes introduced by the ventilation system and air infiltration into veranda and entrance hall have been pretty much well balanced in apartment as total air volumes intakes. CONCLUSION The airflow patterns and the performance of the mechanical ventilation system were measured in the fully developed model house of apartment complex. According to the operating conditions of ventilation system, the air change rates and the airflow routes were investigated quantitatively using tracer gas techniques. The conclusions of this study were as follows. 1) Inter-zonal airflow patterns are well matched with the design strategies of the ventilation system. Airflow routes are as follows; Bedroom Living room Dining room Kitchen Multiuse room for exhausts. 2) The performance of the ventilation system and the cross inter-zonal flows between rooms were evaluated quantitatively. Especially using two types of tracer gas methods and pressure differences between rooms, it could be figure out the air change rate for inter-zonal flow between rooms. Also the overall performance of the ventilation system in rooms was evaluated with the various operating situation of the local ventilation system. 3) When supplying additional outside air as make-up at the kitchen, total air balance in the apartment house could be assured the more effective performance of the exhaust system. The variation of the exhaust air volume in the kitchen area didn t have an influence on the air balance in living room or other rooms at the selected house. REFERENCES Yoon, DW. 2001. Evaluation on the Performance of the Ventilation System in an Apartment House, International Symposium on BUEE 2001, Seoul Korea. Doi, Satoshi. 1996. Measurement of Multi-zone Airflow in Experiment House, ROOMVENT 96, pp55~60 ASHRAE.1989. ASHRAE Standards 62-1989, Ventilation for acceptable indoor air quality, ASHRAE, USA. Commission of the European Communities. 1992. European Concerted Action, Indoor Air Quality and Its Impact on Man, Report No. 11, Guidelines for Ventilation Requirements in Buildings, Office for Publications of the European Communities, Luxembourg. AIVC.1995. A Guide to Energy Efficient Ventilation, Air Infiltration and Ventilation Center, Great Britain. AIVC.1994. Ventilation and Building Air-tightness, Air Infiltration and Ventilation Center, Great Britain. 301