Spartan Peripheral Devices. TE 256S Thermostat Applications

Similar documents
SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

Touch Screen Thermostat. MTSC/SUPER, MTSC24/SUPER Series. MTS/SUPER, MTS24/SUPER Series. Owner s manual and technician settings

Document # R01

ET10 Series Stand-alone LCD Fan Coil Thermostat

Control Sequence Number

ETAF Series VDC Fan output LCD Fan Coil Thermostat

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

TC-9102 Applications

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH,

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

Verasys System Operation Overview Technical Bulletin

Reference Guide for Microprocessor Controller

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

1.0 Digital Controller

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat

Reference Guide for Microprocessor Controller

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

I/O ZONE 560/583 USERS GUIDE

T6590 Series FAN-COIL CONTROLLER FEATURES APPLICATIONS PRODUCT DATA

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals

Reference Guide for Microprocessor Controller

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

Application and Instructions for Field Adjustment of the Control (Model FX06) in Digital Control Option D12A, Space Control with Discharge Air Reset

Networkable Fan Coil Controller Specification and Installation Instructions

CONTENTS. Installation Guide. VT7200 Series

SEQUENCE OF OPERATIONS

BAC-4000 Series AppStat

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage

U ser's Guide PC6010

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

T6590 Series FAN-COIL CONTROLLER

INSTALLATION & OPERATION MANUAL

OPERATING INSTRUCTIONS

T7300F Multistage Conventional or Heat Pump Programmable Commercial Thermostat

CN7232 Advanced Garage Ventilation Controller

NCU Mounting Details

Installer Manual KNX Touchscreen Thermostat

MARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER

TEC1100 Series Thermostats

TB7300 Series Communicating Fan Coil Thermostats 24 VAC/FOR COMMERCIAL AND LODGING HVAC APPLICATIONS

USER S MANUAL. Remote Controller 88-MACC007-1A-EN

2017 products.koer.com Page 1 of 14

Reciprocating Chiller

Digital Precise Air Control - DPAC

Power Flame Incorporated

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

AirTrak. Digital Control System. User Manual. Touchscreen Systems

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Johnson Controls Fan Coil Units and Direct Digital Controls

1.0 Digital Controller

Job Name Control Systems Description Date

Inspection Phase Three. Mechanical, Electrical & Plumbing Section 503

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

MHWW-24-H-1 Chilled/Hot Water Hi-Wall Fan Coil 2-Pipe Heat / Cool Fan Coil 24,000 BTUH

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil 2-Pipe Heat / Cool Fan Coil 9,000 BTUH

XE99 SERIES FAN-COIL THERMOSTATS 2-PIPE & 4-PIPE FAN-COIL CONTROL FEATURES APPLICATION PRODUCT SPECIFICATION SHEET

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

Electric Coils. Blower Coils. Product Information

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network

EnOcean Parameters: Access Code 20 Note: For use with 902MHz devices ONLY.

Catalog ThinLine Horizontal Fan Coils. Type FCHC, FCHH and FCHR. Exposed Horizontal Cabinet. Recessed Horizontal Cabinet

Installation Instructions. Applications. North American Emissions Compliance. Installation. Part No , Rev. Issued February 8, 2010

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Tranquility Digital Quick Start Guide

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

T170 Thermostat. Installation and Maintenance Manual. 24 VAC/ VAC 3-Speed Fan Control (Continuous or Cycling) or Staged Fan Control

TER Active Room Temperature Sensor (Controller),

AdaptAire. Digital Control System. User Manual. Expert Systems

Humidity Controller Specification and Installation Instructions. Model HRO20

MARVEL MINI HVAC MICROPROCESSOR CONTROLLER

Table of Contents. Unit Ventilator

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Installation and Maintenance Manual IM

N M AirControl AHU. Control manual

Catalog ThinLine Horizontal Fan Coils. Type FCHC, FCHH and FCHR. Exposed Horizontal Cabinet. Recessed Horizontal Cabinet

ROOM THERMOSTATS KNX BASIC DOCUMENTATION

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

Catalog ThinLine Vertical Fan Coils. Type FCVC, FCVH, FCVS Vertical Design. Model FCVC. Model FCVS

York 25-Ton VAV Rooftop Unit

Single Zone LCD Thermostat Operating Instructions

ERV Vertical Unit Ventilators

T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

Catalog ThinLine Vertical Fan Coils. Type FCVC, FCVH, FCVS Vertical Design. Model FCVC. Model FCVS

Safety, Installation, and Operation Manual

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

Application Guide siemens.com/thermostats

T6580 FAN COIL CONTROLLER

Transcription:

Spartan Peripheral Devices TE 256S Thermostat Applications Revision 1.0 TE 256S modulating Proportional plus Integral controller is specifically designed to control heating and cooling with 6 port modulating ball valve and variable speed ECM fan in fan coil units. It includes ability to reduce energy in unoccupied mode and Minimum Fresh air CFM mode requirement as per AHRAE directives. Specification: Thermostats front Panel Features: Large LCD screen Indicating: Room Temperature Set Point Fan Mode Fan Speed Time and Day Front Buttons use: Set Point adjust by UP and DOW arrows buttons Fan button to toggle Fan Mode AUTO/RUN Mode and Set button to enter Engineer Mode for parameters setting. A) Set : Minimum/Maximum CFM in % B) Set: Temperature set point for Economy Mode triggered from external contact ON/OFF button to switch power to the thermostat OFF

Appearance: Wiring Diagram: Features : Fan Sequence: The control output AO2 to the fan is 0 10Vdc modulating to control Variable air flow ECM type of fan. The Minimum CFM representing 0 5 Vdc indicated as 0% 50% and Maximum CFM representing 5 10Vdc indicated as 50% 100% on the thermostats display in the Engineer Mode can be set by Ventilation or Control contractor. The thermostat will then control with in this preset range as described in sequence of operation. The fan mode sequence control is selectable on the thermostat with the fan select button by the end user. The fan mode will appear on the thermostat display with fan icon and Auto, Run ON/OFF Button When the ON/OFF button is switch OFF the fan output will go to 0Vdc and the fan will be off. The valve output will go to 5Vdc and the 6 port valve will be fully closed, no heating no cooling.

Fan Mode Auto: The fan output will be controlled from the temperature control when the temperature is satisfied the valve output is 5Vdc valve is closed and the fan output will go to 0Vdc and the fan will be off. When there is a temperature demand heating or cooling the fan will start at minimum speed (as preset by the ventilation contractor) and ramps up proportionally to the maximum speed (as preset by the ventilation contractor) as required by the temperature controller. Fan Mode Run as per AHRAE Directive : The fan output will be controlled from the temperature control, when the room temperature reaches the set point the valve output is 5Vdc valve is closed and the fan output will go to minimum Vdc (as set by ventilation contractor) and the fan will continuously run delivering minimum CFM for the required space as per ASHRAE bulletin. When there is a temperature demand heating or cooling the fan will ramp up proportionally to the maximum speed (as preset by the ventilation contractor) as required by the temperature controller. 6 Port Control Valve sequence: The control output AO1 to the 6 port control valve is 0 10Vdc modulating to control over 0 90º rotation. At 0 Vdc the ball valve is in 0º position and 100% heating At 0 4.5 Vdc the valve modulates heating over 30º rotation At 5 Vdc the valve is in 45º position and both Heating and Cooling is closed At 5.5 10Vdc the valve modulates cooling over 30º rotation At 10 Vdc the valve is in 90º position and 100% cooling 1 Vdc dead band insures no heating and no cooling when set point is satisfied, there is no possibility of water infiltration from hot water to chilled water system.

Energy Conservation features as per ASHRAE directive: A) Occupied and unoccupied schedule can be programmed for maximum four periods for every day of the week. Individual heating and cooling set points can be set. B) Additional feature is provided for optional external sensor input, it can be external motion detector, interface for connecting to hotel key card, lighting interlock signal or interface with window or door contact. Contact closure will trigger energy conservation mode with preset adjustable heating and cooling set points.