System 2000 System 2000 automatic control switch Safety instructions. 2 Device components

Similar documents
System 2000 System 2000 presence detector Comfort top unit. 1 Safety instructions. 2 Device components

System 2000 Automatic control switch 2 Standard. 1 Safety instructions. 2 Device components. 3 Function. Order-No. : Operating instructions

System 3000 Motion detector top unit 1.10 m Standard, Motion detector top unit 2.20 m Standard

1 Safety instructions. 2 Device components. Observer 220. Art.-No.: W 220 WW. Operationsmanual

Standard automatic switch 1.1 m, Standard automatic switch 2.2 m

1 Safety instructions. 2 Device components. Light Management Universal automatic switch m. Art.-No.: AS Operating instructions

Automatic switch attachment Standard Installation Instructions

1 Safety instructions. 2 Device components. Presence detector. Operating instructions

Operating Instructions. Room Temperature Controller 230/10 (4) A~ with NC contact and On/Off button

Presence detector Komfort attachment Installation Instructions

Remote alarm unit Art. Nr.:

User Manual 120/240/300 Outdoor Motion Detector

Gira Sensotec / Gira Sensotec LED Motion detector, orientation light and contactless switch in one

Gira nurse call system Installation, start-up, operation. Gira emergency set

II SL. Installation Guide. VOLTEX IMS64-2 Dual output indoor flush mount PIR motion detector IMS64-2

Product DELTA i-system DELTA profil titanium white 5WG HB11 pearl grey 5WG AB01 Motion detector

Motion detector UP 255, UP 256, UP 257, UP 258 5WG AB 5WG AB 5WG HB

Protecting you and your home

360º Surface Mount Ceiling PIR Light Controller

Infrascan Passive Infrared Motion Sensor Surface-Mount 753SSR Series. Installation Instructions

12W Round LED Wall/Ceiling Light with Microwave Sensor

18W Round LED Wall/Ceiling Light with Microwave Sensor

Operating instructions

360 Surface Mount Ceiling PIR Light Controller

Detailed operating instructions

Detector switch - Dual Tech

PRODUCT INFORMATION. Uses tough, high quality PC diffuser, resistant to fracture and to ultraviolet light to limit discolouring.

PRESENCE DETECTOR. PD-C360i/8 mini KNX PD-C360i/12 mini KNX / 13 7 REMOTE CONTROL PRESENCE DETECTOR

Compact Movement Activated Sensor Installation Instructions

Detailed operating instructions

UP 258E11 OPTISENS OFFICE

1. Basic safety information 3 2. Proper use 3

For assistance with the product please contact: HELPLINE. For a product brochure please contact:

For assistance with the product please contact: HELPLINE. For a product brochure please contact:

Product and Applications Description

OPERATING INSTRUCTIONS

360 Ceiling PIR Light Controller

3. Proper use. 4. Function. 1. Product characteristics. 2. Safety. Function description. Channel A light. Motion detector

60W Multi PIR Bulkhead

DETECTOR TRANSMITTER INSTALLATION & OPERATING. Cat No. TLTX2000B INSTRUCTIONS

1. Basic safety information 3 2. Proper use 3

Passive infrared ceiling sensor

1. Product characteristics 4 2. Safety 5 3. Proper use 5 4. Operation 6

PräsenzLight PräsenzLight PräsenzLight A.. PräsenzLight A..

luxcontrol lighting control system basicdim basicdim ILD Compact control module with ambient light sensor and motion sensor

11,9. Ordering data. Max. cable length sensor head 1 basicdim ILD lx 150 lx m 1

2000W PIR LIGHT CONTROLLER SLB2000-Black SLW2000-White INSTALLATION & OPERATING INSTRUCTIONS

11,1 30. Ordering data

Motion detector themova P360 KNX UP WH themova P360 KNX UP GR

PMCSF6 OCCUPANCY SENSOR

Detector switch - Dual Tech SCS

LUX Hardwired - Installation Notes

ARGUS movement detectors

3. Intended use. 4. Function. 1. Product characteristics. 2. Safety. Functional description. Channel A light. Motion detector

PresenceLight 180 PresenceLight 360

Description FEATURES. l Innovative dual mount system requires only one sensor for either flush or surface mount applications

compact office 24V compact office 24V Lux

360º FLUSH MOUNT CEILING PIR LIGHT CONTROLLER INSTALLATION & OPERATING. Cat No. SLFM360 INSTRUCTIONS

B.E.G. LUXOMAT KNX-OCCUPANCY DETECTOR

Surface Mount Wall PIR Light Controller. Model: PDWM1500. Installation & Operating Instructions

compact office 24V compact office 24V Lux

PresenceLight 180A-KNX.. PresenceLight 360A-KNX.. PresenceLight 180B-KNX.. PresenceLight 360B-KNX..

Save energy. ARGUS presence detectors

Saving energy with Gira

Description of the application programme for KNX occupancy detectors version 3.1

Laser Distance Sensor Type M Analog-Output

64.7 Ø85. (1) Sensor inset (2) Lens pluggable. (3) Protection cover (covers the high-voltage terminals). (4) Ceiling (drill hole Ø70mm).

luxcontrol lighting control system basicdim basicdim ILD 5DPI 14f Compact control module with ambient light sensor and motion sensor

False Ceiling HF Sensors

Tri-level Control HF Sensor

1. Basic safety information 3 2. Proper use 3

Tri-level Control HF Sensor

Alarm System SECURE AS 302

5800-OD Wireless Outdoor Motion Sensor Installation Instructions

THE INNOVATIVE SOLUTION FOR MORE LIGHTING COMFORT LEDOTRON. DIGITALLY DEFINED DIMMING.

luxcontrol lighting control system basicdim basicdim ILD 5DPI 14f Compact control module with ambient light sensor and motion sensor

Movement controller comfort, Flush-mounted (Up) xx, xx

BIANCO SENSOR FLUSH MOUNT 15W MODEL # GBCL400HFSR

Data sheet. Function description. Benefits

Devices for Special Applications

ECO-IR 360C NT. Presence detector. Art. Nr Bedienungsanleitung 2. Notice d utilisation 22. Installation manual 42

luxcontrol lighting control system basicdim basicdim ILD 16DPI 69f Compact control module with ambient light sensor and motion sensor

Ceiling PIR HS presence detector. Product Guide. Overview. Features

DALI MSensor 02 Multi-sensor for DALI system

Connections, displays and operating elements E F. 20s 3min

Movement-based energy control

B.E.G. LUXOMAT. Find the right detector.

LIGHT SYSTEMS CATALOG

2. Safety. 4. Function

IP 55 (category II) IP 54 (category II) 4. Connection. 1. Basic safety information. 2. Proper use. 5. Installation. 3. Description.

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

KingShield. - Occupancy Detectors NEW. For complete Lighting Control... ORION RANGE. P High performance for optimum switching of all types

Model: PDFM1500. Installation & Operating Instructions 360º Flush Mount Ceiling PIR Light Controller

30W LED PIR FLOODLIGHT. Model: LEDX30PIRB Model: LEDX30PIRWH

Mounting bezel Retaining spring. Detects movement within the detection range, allowing load control in response to changes in room occupancy.

Model: PDSM1500. Installation & Operating Instructions 360º Surface Mount Ceiling PIR Light Controller

Introduction. Sizing Of Lighting

Instruction manual EN

5W LED Energy Saver PIR Bulkhead

SCS motion sensors Surface/wall mounting - PIR

Transcription:

pure white Order-No. : 2270 02 colour aluminium Order-No. : 2270 04 Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe the instructions may cause damage to the device and result in fire and other hazards. Danger of electric shock. Always disconnect before carrying out work on the devise or load. At the same time, take into account all circuit breakers that supply dangerous voltage to the device or load. Danger of electric shock. Device is not suitable for disconnection from supply voltage. The load is not electrically isolated from the mains even when the device is switched off. Do not press on the sensor window. Device can be damaged. The device is not suitable for use as a burglar alarm or other alarm. These instructions are an integral part of the product, and must remain with the end customer. 2 Device components Figure 1 (1) Flush-mounted insert (2) Motion detector cover (3) Adjuster sens (4) Adjuster time (5) Adjuster lux (6) Brightness sensor (7) LED display, behind the lens (8) Lens (9) Decor ring (10) Push-on cover 82563812 18.11.2011 1/8

3 Function Intended use - Automatic switching of lighting depending on the heat motion and ambient brightness. - Operation with concealed insert for dimming, switching or extension insert, 3-wire - Ceiling installation on flush-mounted insert Product characteristics - Run-on time, sensitivity and brightness threshold settable - Test operation for checking the detection area - Short-time operation to control signal encoders - Dimming phase in combination with dimming insert - Saving a switch-on brightness with dimming inserts - Dimming lights with dimming inserts - Manual switch-on possible via extension insert, 2-wire, or installation button - 78 lens segments in 5 recording levels - Extension of the detection area in combination with the 3-wire extension insert - Detection area can be limited using push-on cover Automatic operation The controller detects heat motions of people, animals and objects. - The light is switched on if a person enters the monitored detection area and the brightness is below the set threshold. - The light is switched off if no more movement is detected in the detection area and the follow-up time has elapsed. Dimming phase with dimming insert If the motion detector cover is fitted on a dimming insert, then when the run-on time elapses the lighting is dimmed to minimum brightness and then switched off. The time from the start of dimming to switching-off is always approx. 30 s. If a motion is detected during the dimming phase, the motion detector switches the lighting to the stored switch-on brightness again. Behaviour in case of a mains failure - Less than 0.2 seconds: the old switching position is restored after mains return. - 0.2 seconds to approx. 2 seconds: when the power returns, the lighting is switched on again for the run-on time. Each detected movement restarts the run-on time again. - Longer than 2 seconds: when the power returns, the motion detector carries out a brief calibration process. Then the lighting remains switched on for the run-on time. Each detected movement restarts the run-on time again. LED display (7) Main device LED lights up during the calibration process. LED lights up when a motion is detected if the lighting is switched off and the brightness is not below the brightness threshold. Extension LED lights up during the calibration process. LED lights up when a motion is detected. 4 Operation Switching on the light A 2-wire extension or an installation button, NO contact is connected. o Press extension or installation button. Light is switched on independently of the brightness, with a dimming insert to switch-on brightness. Automatic mode is active. i After manual switch-on the run-on time is at least 2 minutes. i Manual switch-on is not possible. 82563812 18.11.2011 2/8

Dimming light with dimming insert The light can be dimmed using a 2-wire extension. The light remains at the dimmed value until the run-on time has elapsed. o Press 2-wire insert at top or bottom until the desired brightness is reached. i An installation button cannot be used for dimming. Saving a switch-on brightness with dimming insert A 2-wire extension can be used to save any desired switch-on brightness. In the state as supplied the switch-on brightness is set to maximum. The saved switch-on brightness is retained in the event of a power failure. o Set the required brightness. o Press 2-wire extension for longer than 3 seconds over entire surface. Switch-on brightness is saved. For confirmation the lighting switches off briefly and then on again to the saved switch-on brightness. 5 Information for electrically skilled persons 5.1 Fitting and electrical connection DANGER! Electrical shock when live parts are touched. Electrical shocks can be fatal. Before carrying out work on the device or load, disengage all the corresponding circuit breakers. Cover up live parts in the working environment. Selecting the installation location Figure 2: Sensor window and detection area The motion detector has a detection area of 360 (Figure 2). The diameter of the detection area depends on the installation height and the direction of motions of persons in the detection area (Figure 3). At an installation height of 3 m the maximum diameter on the floor is approx. 12 to 20 m. 82563812 18.11.2011 3/8

Figure 3: Detection area dependent on the direction of movement i Note direction of motion (Figure 3). Motions that are transverse to the motion detector (Drawing B) can be detected better than motions towards or away from the motion detector (Drawing A). o Select a vibration-free installation location. Vibrations can lead to unwanted switching. o Avoid interference sources in the detection area. Interference sources, e.g. heaters, ventilation, air conditioners, and cooling light bulbs can lead to unwanted switching. i If necessary, the detection area can be limited using the push-on top (see Limiting the detection area). i At an installation height of greater than 3 m the detection area increases, while at the same time the detection sensitivity decreases. Installing the motion detector cover o Align the motion detector so that the brightness sensor is on the side away from the windows. This reduces the effects of scattered light. o Connect flush-mounted insert properly and mount in accordance with the orientation of the motion detector (see instructions for flush-mounted insert). i Use a surface-mounted housing for surface installation. i Use a wind-tight connector socket for cavity wall mounting. o Attach the motion detector cover to the flush-mounted insert. Expanding the detection area To expand the detection area, connect a 3-wire extension insert with motion detector cover. The motion detector of the main unit also evaluates motion signals of the extension and, if necessary, switches the lighting on. o Connect extensions (see instructions for 3-wire extension insert). i The sensitivity of motion detectors on extensions can be set individually. The brightness threshold and run-on time are only set and evaluated on the main device. i Do not connect any main units in parallel. 82563812 18.11.2011 4/8

5.2 Commissioning Testing the detection area Figure 4: Test setting The motion detector is fitted and connected. o Pull off push-on cover (10) o Pull off decor ring (9). o Set sens adjuster (3) to max(figure 4). o Set time adjuster (4) to test. o Set lux adjuster (5) to 3 for brightness-independent switching. o Switch on mains voltage. The motion detector carries out a brief calibration process. The LED display behind the lens lights up during the calibration process. After that test mode is active and the lighting is switched on for approx. 1 second. As long as motions are detected, switch-on will take place again after a lockout time of approx. 3 seconds. In test operation the motion detector operates independently of the brightness. o Leave the detection area and observe the switching behaviour. If the motion detector switches on, then sources of interference must be hidden (see Limiting the detection area). o Measure the detection area. If the detection area is too large, limit the detection area (see Limiting the detection area). If the detection area is too small, expand the detection area using an extension. o Make the operating settings for the run-on time, brightness threshold and sensitivity in order to establish readiness for operation. o Attach decor ring (9). 82563812 18.11.2011 5/8

Limiting the detection area Figure 5: Push-on cover The push-on cover can be used to limit the detection area, e.g. in order to mask out interference sources. Cover size Complete push-on cover Area I cut out Areas I + II cut out without push-on cover Detection area on the floor Ø approx 4.5 m Ø approx 7.5 m Ø approx 12 m Ø approx. 20m All data are applicable for an installation height of 3 m and a direction of motion transverse to the motion detector. o Pull off push-on cover o Using scissors, cut out push-on cover along the marked lines as required. o Push on push-on cover Set follow-up time Then the lighting remains switched on for the length of the run-on time. Each detected movement restarts the run-on time again. The run-on time is set in a range from approx. 10 seconds to 30 minutes. o Pull off decor ring. o Turn the time adjuster (4) to the required position (Figure 4). o Attach decor ring. Setting test mode / short-time operation The motion detector can be set to short-time mode, e.g. to use it to control acoustic signal generators. If motion is detected, the motion detector switches on, depending on the brightness, for 1 second. If motions are still detected, switch-on will take place again after a lockout time of approx. 3 seconds. o Pull off decor ring. o Set time adjuster (4) to test(figure 4). o Turn sens adjuster (3) slightly in the min direction, because at maximum sensitivity unwanted switching may occur. 82563812 18.11.2011 6/8

o Attach decor ring. i To make the short-time operation independent of brightness, turn lux adjuster (5) to 3. Setting the brightness threshold Only when the brightness drops below the threshold will the light be switched on when there is motion in the detection area. The brightness threshold is infinitely adjustable in a range from approx. 0 to 80 lux and day operation. In so doing, the symbol stands for brightnessindependent switching and the symbol for switching in case of darkness. o Pull off decor ring. o Turn the lux adjuster (5) to the required position (Figure 4). i Should the motion detector no longer react to detected movements in Night mode, 2 setting, turn the adjuster back somewhat towards 3. o Attach decor ring. Setting the sensitivity The motion detector possess automatic adjustment to the ambient conditions. Normally, the adjuster sens should be set to maximum sensitivity. o Pull off decor ring. o Set the sensitivity using the adjuster sens (3). i If there are unwanted switching operations, reduce the sensitivity. o Attach decor ring. 6 Appendix 6.1 Technical data Ambient temperature +5... +35 C Protection rating IP 20 Brightness setting approx. 0... 80 lx (and day operation) run-on time approx. 10 s... 30 min Lockout time approx. 2 s Follow-up time (test) approx. 1 s Lockout time (test) approx. 3 s Size of detection area at an installation height of 3 m cross walking range Ø approx. 20 m walk to walking range Ø approx. 12 m Detection angle 360 6.2 Troubleshooting Light does not switch on, LED lights up upon detection Cause: The ambient brightness is greater than the set brightness threshold. Increase the brightness threshold using the lux adjuster (5). Light does not switch on, LED does not light up Cause 1: Detection area is limited by push-on cover. Remove or adjust push-on cover. Cause 2: Sensitivity is set too low. Turn sens adjuster (3) in max direction. Light switches on, although no-one is in the detection area. Cause: Interference sources in the detection area, e.g. heating, ventilation, cooling light bulbs. Reduce the detection area with push-on cover or reduce the sensitivity with the sens adjuster (3). 82563812 18.11.2011 7/8

Light switches off briefly and then on again immediately, light oscillation Cause 1: Interference sources in the detection area, e.g. heating, ventilation, cooling light bulbs. Reduce the detection area with push-on cover or reduce the sensitivity with the sens adjuster (3). Cause 2: Installation error, main devices connected in parallel to expand the detection area. Use extensions to expand the detection area. 6.3 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade. Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company/electrical specialist trade). They will forward the devices to the Gira Service Center. Gira Giersiepen GmbH & Co. KG Elektro-Installations- Systeme Industriegebiet Mermbach Dahlienstraße 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel +49(0)21 95-602-0 Fax +49(0)21 95-602-191 www.gira.de info@gira.de 82563812 18.11.2011 8/8