GRUNDFOS INSTRUCTIONS. Dedicated Controls. Service instructions

Similar documents
GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

CU 300. Installation and operating instructions GRUNDFOS INSTRUCTIONS

Added password for IP setup page : Password must be in IP format!

THX-DL Data Logger USER & INSTALLATION MANUAL V

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

WebAlert WA500 Series Process Monitor Instruction Manual

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

600 Range Dialer Installation Manual. Version 1.0

User manual. KNXgal. version

SC-F3G User Manual 1.0

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014

Monitoring Solutions

T M. User Manual. MarinaGuard. Ground Fault Monitoring Panel For Marina Shore Power

REMOTE MONITORING AND ALARM SYSTEM

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

Panel Mounted Fault Annunciator Series

Ethernet General Purpose

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Alarm module for leak detection with webserver

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

Lift Station Level Controller

Insulation fault evaluator EDS460-DG

Dryer Controller M720

7 USE THE COMMANDS INTERNET VOICE MESSAGES RECORD VOICE MESSAGE DURATION OF VOICE MESSAGES 64

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

RACK MONITORING SYSTEM - RAMOS Ultra

IRIS Touch 400 & 600 Range Installation Manual. Honeywell Galaxy Range. Version 2.0

PowerLogic ION Setup Meter Configuration Software Configuration Guide

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

INSTALLATION INSTRUCTIONS and BASIC SYSTEM CONFIGURATION

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

Diagnostics and Monitoring System WEB Tool 2. User Manual

Panel Mounted Fault Annunciator Series

EviKontroll Silo. Monitor Your Grain Anytime, Anywhere

Monitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING. Manual

HTC-915-CONT. Heat-Trace Control system

Fratech Multipath-IP

CU 300 GRUNDFOS INSTRUCTIONS. Installation and operating instructions

Instructions for the fan motor control system with integrated wiring terminals SILVER C

User Manual. Dryer Controller M720

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

MANUAL FOR PROFORT GSM/LAN DEVICES Ver MANUAL FOR PROFORT GSM/LAN DEVICES 3

Smart Combiners Installation Guide. For Obvius A89DC-08 sensor modules

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

S F IT 6" / 8"HES. Quick Installation Guide. franklinwater.eu

Dew point set DS 400

INSTALLATION INSTRUCTIONS

Security designed for your lifestyle

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

Operating Guide. ECL Comfort 210 / 296 / 310, application A247 / A Table of Contents

RACK MONITORING SYSTEM RAMOS Ultra

ACTIVE INFRARED BARRIER

SUPREMATouch. Modular Fire & Gas Detection System

Halton SAFE / 7.14 user guide and installation instructions

IP & SMS Alarm Communicator

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Healthy. Atmosphere. for Pigs and Poultry. for a

T4000 Security Communicator

1.7. Insulation fault evaluators EDS460/490 EDS461/491

DELOMATIC 400, DM-400 HYDRO

IndigoVision Alarm Panel. User Guide

SACE PR021/K SIGNALLING UNIT

Remote alarm indicator and test combination MK2430

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

M1000 Alarm Annunciator

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

ModBus DE-1 INSTALLATION AND USER MANUAL

SCAN200E USER S MANUAL

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

P2267 NETWORK INTERFACE

REPEATER FS5200R INSTRUCTION MANUAL

Instruction Manual Model Backup Switch, 1 for 8

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

Corrigo E. Second generation which contains all applications and languages

Operating manual. Condor Modular pump control CPSM

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

PTE0705 Electric Fence Monitor

READ AND SAVE THESE INSTRUCTIONS

Memcom Emergency Telephone

RS485 MODBUS Module 8AI

Process & TeMPerATUre UniversAl input DigiTAl MeTers

INSTALLATION AND OPERATION MANUAL

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

Products no longer available

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

TE809-Ats Instructions Manual

IRIS Touch Firmware Enhancements and Additions from Version to Version

Сontrol panel Contact GSM-9N

Labkotec Ice Detector

NU2 Smart Power Supply (SPS) Manual

SUPREMATouch. Modular Fire & Gas Detection System

Two-Channel Gas Controller

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

CAREL heatersteam Electric Element Steam Humidifiers

Transcription:

GRUNDFOS INSTRUCTIONS Dedicated Controls Service instructions

Contents 1. Symbols used in this document... 3 2. Identification... 3 2.1 Dedicated Controls... 3 2.2 CU 361... 5 2.3 IO 351B... 6 2.4 Separate components... 7 2.5 Control cabinet... 9 2.6 Environmental conditions and connection... 10 2.7 Examples of control variants... 11 2.8 CU 361 control panel... 12 2.9 Menu overview... 12 3. Overview of inputs and outputs of control unit/modules... 14 3.1 Functions of terminals... 14 3.2 CU 361 terminals... 17 3.3 IO 351B terminals... 18 3.4 IO 111 terminals... 20 4. Configuration... 22 4.1 Necessary equipment... 22 4.2 Configuration of Dedicated Controls... 22 5. Documentation supplied with Dedicated Controls... 27 6. PC Tool... 27 6.1 Connection of PC to Dedicated Controls... 27 7. Fieldbus communication module... 28 7.1 SCADA system... 28 7.2 Data communication... 28 7.3 Fitting the CIM module... 34 8. General settings, CU 361... 36 8.1 Display language... 36 9. Fault finding... 36 9.1 Power supply... 36 9.2 External control, data collection, SCADA systems... 36 9.3 Pumps... 36 10. Fault finding tools... 37 10.1 CU 361 display... 37 10.2 System... 39 10.3 Specific pump... 40 10.4 GSM/GPRS... 41 10.5 Float switch status... 42 10.6 Mixer... 43 10.7 Electrical overview... 44 11. Alarms and warnings... 47 11.1 Alarm indicators... 47 11.2 Alarm settings... 48 12. How to trace an alarm... 50 12.1 Menu Status... 50 12.2 Menu Alarm... 50 12.3 Password protection... 51 12.4 R100... 52 13. Fault finding by means of fault codes... 53 13.1 Alarm list (system)... 53 13.2 Alarm list (pump)... 55 13.3 Alarm list (mixer)... 56 13.4 Alarm list (combi alarms)... 56 13.5 Alarm list (IO 111 belongs to a pump)... 56 2 / 60

96817867 1. Symbols used in this document Warning If these safety instructions are not observed, it may result in personal injury! Caution Note If these safety instructions are not observed, it may result in malfunction or damage to the equipment! Notes or instructions that make the job easier and ensure safe operation. 2. Identification This section shows the nameplates, the type keys and the codes that can appear in a variant code. Note As codes can be combined, a code position may contain more than one code (letter). 2.1 Dedicated Controls 2.1.1 Nameplate Type: 1 Model: 2 Serial No: 3 Mains supply: 4 Power consumption: 5 W Fuse: 6 A TAMB: 7 º C VCONTACT MAX. : 8 9 A V ICONTACT MAX. : No. of Fixed speed pumps: 10 Imax Vmax Relay output: 11 12 Order No.: Options: 13 14 15 16 IP 18 Weight: 19 kg 17 20 Made in 21 TM04 3790 5008 Fig. 1 Nameplate, Dedicated Controls Pos. Description Pos. Description 1 Type designation 10 Number of fixed-speed pumps 2 Model 11 I max., relay output 3 Serial number 12 V max., relay output 4 Mains supply 13 Order number 5 Power consumption 14-17 Options 6 Fuse 18 Enclosure class 7 T amb. 19 Weight in kg 8 V contact max. 20 CE-mark 9 I contact max. 21 Country of origin 3 / 60

2.1.2 Type key Example DCD 318 400 3 23 DOL -IGM Number of pumps DC: 1 pump DCD: 2 pumps Type number Supply voltage, frequency 230: 230 V, 50 Hz 400: 400 V, 50 Hz Number of phases 1 = single-phase 3 = three-phase Maximum current per pump [A] 5: 1-5 A (230 V and 3 x 415 V DOL) 12: 5-12 A (230 V DOL) 23: 12-23 A (3 x 415 V DOL) 20: 20 A (3 x 415 V SD/SS) 30: 30 A (3 x 415 V SD/SS) 59: 59 A (3 x 415 V SD/SS) 85: 85 A (3 x 415 V SD/SS) Run/starting capacitor [µf] (only 12 A operating current) [ ] = without capacitor 30 = run capacitor 30/150 = 30 µf run capacitor and 150 µf starting capacitor Starting method DOL (Direct On Line): Direct-on-line starting SD: Star-delta starting SS: Soft starter Setup S: Standard I: IO 111 (both pumps) G: GSM module and battery backup M: Mixer/flush valve IG: IO 111, GSM module and battery backup IM: IO 111 and mixer/flush valve GM: GSM module, battery backup and mixer/flush valve IGM: IO 111, GSM module, battery backup and mixer/flush valve 4 / 60

2.2 CU 361 2.2.1 Nameplate The CU 361 can be identified by means of the nameplate on the back. See fig. 2. 1 2 3 Type CU 361 Serial No. 0536 Product No. 96787482 - VO1 P.c. 0811 UN 100-240 Vac 50/60Hz - Max. 22W Made in Thailand! 30 XP OPEN TYPE PROCESS CONTROL EQUIPMENT 96161750 4 5 TM04 0453 0608 Fig. 2 CU 361 nameplate Pos. Description 1 Type designation 2 Product number and version number 3 Serial number 4 Production code (year, week) 5 Rated voltage, frequency and power 2.2.2 Type key Code Description CU 3 6 1 CU Control unit 36 Controller series 1 Model number The CU 361 has a label for backup battery. See fig. 3. Battery powered TM04 2367 2408 Fig. 3 Label for backup battery Warning Remove the battery before starting work on the CU 361. TM00 5827 3408 12V dc 0V 12V 96801950 Fig. 4 Protective earth terminal 5 / 60

2.3 IO 351B 2.3.1 Nameplate 1 2 Type Product No. IO 351B 96161730 - VO1 Serial No. P.c. 96161750 3 4 UN Made in Denmark 100-240 Vac 50/60Hz - max. 9W! 30 XP OPEN TYPE PROCESS CONTROL EQUIPMENT 5 TM03 1017 2205 Fig. 5 Nameplate, IO 351B Pos. Description 1 Type designation 2 Product number and version number Permissible supply voltage, frequency and 3 maximum power consumption 4 Production code (year, week) 5 Serial number 2.3.2 Type key Code Description IO 3 5 1 B IO Input/output module 35 Controller series 1 Model number B For pumps with fixed-speed and pumps controlled by external frequency converters or as input/output module 6 / 60

2.4 Separate components Component Description Functions CU 361 IO 351B GrA 6588 The CU 361 is the 'brains' of the Dedicated Controls system and is mounted in the front of the control cabinet. The CU 361 can control and monitor one or two Grundfos wastewater pumps. The pumps can drain a pit using built-in draining algorithms. The algorithms are based on a water level measured by float switches or an analog level sensor. CU 361 inputs and outputs: GENIbus communication (RS-485) 3 analog inputs for connection to sensors with current (0-20 ma/ 4-20 ma) or voltage (0-10 V) 3 digital inputs 2 digital relay outputs, 240 VAC, 2 A Connection to battery backup (UPS) (optional) Ethernet connection (VNC) Connection to fieldbus CIM modules (CIM = Communication Interface Module): CIM 200 (Modbus via RS-485) CIM 250 (Modbus and SMS via GSM/GPRS) CIM 270 (GRM) (GRM = Grundfos Remote Management). Product number 96787482 IO 111 TM03 2110 3705 TM03 0819 0505 The IO 351B is a general I/O module. The IO 351B communicates with the CU 361 via GENIbus. Via the IO 351B inputs and outputs, the CU 361 controls the pumps according to the built-in algorithms. The IO 111 is a protection module for a Grundfos wastewater pump. The IO 111 has inputs for digital and analog pump sensors and can stop the pump if a sensor indicates a pump fault. The IO 111 is connected to the CU 361 and allows the monitoring of several sensors. IO 351B inputs and outputs: GENIbus communication (RS-485) 2 analog inputs for connection to sensors with current (0-20 ma/ 4-20 ma) or voltage (0-10 V) 9 digital inputs 7 digital outputs, 240 VAC, 2 A 4 PTC inputs. IO 111 inputs and outputs: 1 digital input for moisture in motor 1 digital input for water-in-oil detection 1 digital input for high motor temperature 1 analog input for insulation resistance 1 analog input for stator temperature 1 digital output for alarm relay 1 digital output for warning 1 digital output for moisture-inmotor alarm 1 digital output for stator temperature alarm 1 digital output for insulation resistance alarm. 96161730 96575362 7 / 60

Component Description Functions Product number CIM 200 GrA 6120 The CIM 200 is a Grundfos communication interface module used for the fieldbus protocol Modbus RTU. The CIM 200 is to be fitted in the CU 361 control unit. The CIM 200 is used to communicate with a Modbus RTU network. The CIM 200 module has terminals for the Modbus connection. DIP switches are used to set parity and line termination. Two hexadecimal rotary switches are used to set the Modbus address. Two LEDs are used to indicate the actual status of the CIM 200. One LED is used for internal communication, and the other is used to indicate Modbus communication status. 96824796 CIM 250 TM04 4029 0609 The CIM 250 is a Grundfos communication interface module used for GSM/GPRS communication. The CIM 250 is to be fitted in the CU 361 control unit. The CIM 250 is used to communicate via a GSM network. The CIM 250 module has a SIM-card slot and an SMA connection to the GSM antenna. The CIM 250 also has an internal backup battery. Two LEDs are used to indicate the actual status of the CIM 250. One LED is used for internal communication, and the other is used to indicate GSM/GPRS communication status. 96824795 CIM 270 TM04 4029 0609 The CIM 270 is a Grundfos communication interface module used in Grundfos Remote Management. The CIM 270 is to be fitted in the CU 361 control unit. The CIM 270 establishes communication between the CU 361 control unit and the Grundfos Remote Management system, thereby allowing the CU 361 to be monitored and controlled remotely. The CIM 270 uses GSM/ GPRS communication. The CIM 270 module has a SIM-card slot and an SMA connection to the GSM antenna. The CIM 270 also has an internal backup battery. Two LEDs are used to indicate the actual status of the CIM 270. One LED is used for internal communication, and the other is used to indicate GSM/GPRS communication status. 96898815 8 / 60

2.5 Control cabinet Cabinet Description Functions Control cabinet GrA 6270 The control cabinet is delivered with all necessary components, including battery backup. Different types of control cabinets are available, depending on functions and network. The control cabinet is designed for installation in a control cabinet for outdoor use. Note: The main switch and backup fuses have to be installed externally. Digital input Energy measurement* Volume measurement* Motor protection, pump 1 Motor protection, pump 2 Relay resetting External fault Common phase error Alarm relay resetting Contactor feedback, pump 1 Contactor feedback, pump 2 Contactor feedback, mixer Auto/On/Off, pump 1 On/Off, pump 1 Auto/On/Off, pump 2 On/Off, pump 2 Float switch 1 Float switch 2 Float switch 3 Float switch 4 Float switch 5 Too high motor temperature** Moisture in motor** PTC, pump 1 Klixon, pump 1 PTC, pump 2 Klixon, pump 2. Analog input Pressure sensor* Ultrasonic sensor* Flow rate* Motor current, pump 1* Motor current, pump 2* Water in oil, pump 1* or ** Water in oil, pump 2* or ** User-defined sensor 1* User-defined sensor 2* User-defined sensor 3* Insulation resistance** Stator temperature** Digital output Pump 1, start Pump 2, start Mixer, start User-defined relay High-level alarm Urgent alarms All alarms All alarms and warnings User-defined alarms Alarm relay** Warning** Moisture-in-motor alarm** Stator temperature alarm** Insulation resistance alarm** Communication SMS and Modbus GSM/GPRS*** Modbus-wired**** * External sensor required ** Only via the IO 111 *** Via the CIM 250 GSM module **** Via the CIM 200 Modbus module 9 / 60

2.6 Environmental conditions and connection 2.6.1 Ambient temperature 20 C to +50 C. 2.6.2 Relative air humidity Maximum 95 %. 2.6.3 Mains supply, overload protection, fuses See Grundfos wiring diagrams (technical data) supplied with Dedicated Controls. 10 / 60

2.7 Examples of control variants One pump with two float switches One or two pumps with three float switches One or two pumps with four float switches TM02 8114 4703 TM02 8299 4903 TM02 8300 4903 One or two pumps with five float switches One or two pumps with analog sensor One or two pumps with analog sensor and mixer TM02 8301 4703 TM02 8305 1704 TM04 2955 3408 One or two pumps with analog sensor and safety float switches One or two pumps with analog sensor, safety float switches and mixer TM04 2956 3508 TM04 3700 4908 11 / 60

2.8 CU 361 control panel Pos. Description 1 LCD display 2 Changes to next column in menu structure 1 CU 361 2 3 5 4 6 7 8 9 10 11 3 Changes to help text 4 Goes up in lists 5 Goes down in lists 6 Increases the value of a selected parameter 7 Decreases the value of a selected parameter 8 Goes one display back 13 12 9 Goes back to the Status menu Fig. 6 CU 361 TM04 3593 4708 10 Saves a value 11 Green indicator light (operation) 12 Red indicator light (alarm) 13 Changes the contrast of the display 2.9 Menu overview 1. Status 1.1 System 1.2 Specific pump 1.3 GSM/GPRS 1.4 Float switch status 1.5 Mixer 1.6 Electrical overview 1.6.1 Analog inputs 1.6.2 Digital inputs 1.6.3 Digital outputs 2. Operation 2.1 Overview 2.2 Auto/On/Off pump control 2.3 Start and stop levels 2.4 Resetting alarm relays 3. Alarm 3.1 Current alarms 3.2 Alarm log 12 / 60

4. Settings 4.1 Basic functions 4.1.1 Primary settings 4.1.2 Pit configuration and flow calculation 4.1.3 Pump delays 4.1.4 Float switch functions 4.1.4 Drain function, one pump and two float switches 4.1.4 Drain function, one pump and three float switches 4.1.4 Drain function, one pump and four float switches 4.1.4 Drain function, two pumps and three float switches 4.1.4 Drain function, two pumps and four float switches 4.1.4 Drain function, two pumps and five float switches 4.1.4 Analog sensor with safety float switches 4.1.5 Out of operation 4.2 Advanced functions 4.2.1 Anti-seizing 4.2.2 Daily emptying 4.2.3 Foam draining 4.2.4 Mixer configuration 4.2.5 Adjustment of counters 4.2.6 Resetting alarm log 4.2.7 Duty/standby 4.3 Communication settings 4.3.1 Selecting communication module 4.3.2 Ethernet 4.3.3 GENIbus number 4.3.4 SMS numbers 4.3.5 SMS schedule 4.3.6 SMS heartbeat message 4.3.7 SMS authentication 4.3.8 SIM card settings 4.3.9 SCADA settings 4.3.10 Interlock settings 4.3.11 GPRS settings 4.4 I/O settings 4.4.1 Analog inputs 4.4.2 Digital inputs 4.4.3 Digital outputs 4.4.4 Counter inputs 4.4.5 Alarm relays 4.5 Alarm settings 4.5.1 System alarms 4.5.2 Pump alarms 4.5.3 Mixer alarms 4.5.4 Combi alarms 4.6 General settings, CU 361 4.6.1 Run configuration wizard again 4.6.2 Display language 4.6.3 Units 4.6.4 Date and time 4.6.5 Password 4.6.6 Ethernet 4.6.7 GENIbus number 4.6.8 Software status 13 / 60

3. Overview of inputs and outputs of control unit/modules Unit/ module Digital input Analog input Relay output Communication Extra CU 361 3 3 2 NO/NC GENIbus master (RS-485) Ethernet (VNC) SMS and Modbus GSM/GPRS (via CIM 250) Modbus-wired (via CIM 200) IO 351B 9 + 4 PTC 7 NO GENIbus slave (RS-485) IO 111 3 (dedicated) 2 (dedicated) 5 (dedicated) GENIbus slave (RS-485) Battery backup 12 V input 3.1 Functions of terminals 3.1.1 CU 361 0V 12V TM04 2064 4908 Fig. 7 Back of CU 361 Pos. Description 1 Nameplate 2 Terminals for digital output relays 3 Terminals for analog inputs 4 Service connection 5 Ethernet (RJ45) 6 Voltage indicator 7 Terminals for digital inputs 8 Terminals for backup battery 9 Terminals for CIM module (optional) 10 Cable clamps for GENIbus connections 11 Internal GENIbus connection 12 Terminal for power supply 13 Label for backup battery 14 / 60

3.1.2 IO 351B 5 3C 4B 4A 2 3B 3A 1 TM03 2110 3705 Fig. 8 Terminal groups The module can be divided into these groups: Group 1 Connection of power supply Group 2 Digital outputs 1-3 Digital inputs Group 3A, 3B, 3C Analog inputs and outputs GENIbus Group 4A, 4B Inputs for PTC sensor or thermal switch Group 5 Digital outputs 4-7 3.1.3 Indicator lights on the IO 351B Red Green TM03 1131 1105 Fig. 9 Indicator lights on the IO 351B The IO 351B has a green and a red indicator light. Indicator lights Green Red Description Off. The power supply is interrupted. Flashes slowly (1 Hz). The module is ready for operation, but there is no communication yet. Permanently on. The power supply is on, and the module is starting up. Flashes quickly (5 Hz). The module is ready for operation, and the IO 351B and CU 361 communicate. Flashing The IO 351B and R100 communicate. 15 / 60

GENIbus addresses for IO modules IO module GENIbus address GENIbus number (DIP switch) (R100) IO 351B 41 IO 111, pump 1 40 IO 111, pump 2 41 3.1.4 IO 111 1 2 3 T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 PE 16 D1 D2 D3 D4 D5 D6 D7 D8 A Y B 4 5 15 14 13 12 Reset 6 7 8 11 ON DIP 1 2 3 4 5 6 7 8 9 10 P1 P2 P3 P4 P5 10 Fig. 10 IO 111 module I1 I2 I3 9 TM03 0691 0505 Pos. Description 1 Terminal for alarm relay. 2 Terminal for analog and digital inputs and outputs. 3 Terminal for power supply (24 VAC/24 VDC). Potentiometer for setting the warning limit of stator 4 insulation resistance. 5 Terminal for RS-485 for GENIbus or Modbus. 6 Red indicator light. Alarm in case of too high motor temperature. Indicator lights for stator insulation resistance. Green light = OK. 7 Yellow light = warning. Red light = alarm. 8 Indicator lights for measurement of water in oil. 9 Terminal for measurement of stator insulation resistance. 10 Terminal for connection of pump sensors. 11 DIP switch for configuration. 12 Green indicator light. On when the pump is running. 13 Red indicator light. Alarm in case of moisture in the motor. 14 Button for alarm resetting. 15 Yellow indicator light. Warning in case of pump fault. 16 Terminal for digital outputs. 16 / 60

3.2 CU 361 terminals Pos. Terminal Designation Data Diagram 1 2 L N PE A1 Y1 B1 Connection to phase conductor Connection to neutral conductor Connection to protective earth RS-485 A RS-485 GND RS-485 B Functional earth 1 x 100-240 VAC ± 10 %, 50/60 Hz GENIbus (Fix the screen with a cable clamp.) CU 361 L N CU 361 A1 Y1 B1 L N PE IO 351B A Y B 3 Connection to external fieldbus, see installation and operating instructions for the CIM module. 4 5 0 V +12 VDC 10 DI1 11 GND 12 DI2 13 GND 14 DI3 Connection to battery Backup battery Digital input 10 11 12 13 All terminals (except mains terminals) must only be connected to voltages not exceeding 16 V rms and 22.6 V peak or 35 VDC. 14 Ethernet RJ45 6 External computing devices connected to the Ethernet connection must comply with the standards IEC 60950 and UL 60950. 7 GENIbus Service connection 8 9 47 +24 V 50 +24 V 51 AI1 Supply to sensor. Short-circuit-protected 30 ma. Supply to sensor. Short-circuit-protected 30 ma. Input for analog signal, 0-20/4-20 ma or 0-10 V 53 +24 V Supply to sensor. Short-circuit-protected 30 ma. 54 AI2 Input for analog signal, 57 AI3 0-20/4-20 ma or 0-10 V 58 GND* All terminals (except mains terminals) must only be connected to voltages not exceeding 16 V rms and 22.6 V peak or 35 VDC. 70 Relay 1 C 71 Relay 1 NO 72 Relay 1 NC 73 Relay 2 C 74 Relay 2 NO 47 50 51 53 54 57 58 70 71 72 73 74 1 2 3 75 Relay 2 NC 75 * GND is isolated from other earth connections. 17 / 60

3.3 IO 351B terminals Group Terminal Designation Data Diagram 1 L L N N Connection to phase conductor Connection to neutral conductor 1 x 100-240 VAC ± 10 %, 50/60 Hz IO 351B L N L N Connection to protective earth PE 2 76 DO1, 2, 3 C 76 DO1, 2, 3 C 77 DO1 NO 79 DO2 NO 81 DO3 NO Relay contact, NO Maximum load: 240 VAC, 2 A Minimum load: 5 VDC, 10 ma IO 351B 76 76 77 79 81 3A 3A 3C 10 DI1 12 DI2 Digital input 14 DI3 15 GND All terminals (except mains supply terminals) must only be connected to voltages of maximum 16 V rms and 22.6 V peak or 35 VDC. Fit jumpers instead of the external stops for which the controller is designed. 53 +24 V Supply to sensor. Max. 50 ma. 55 GND 57 AI1 Input for analog signal, 60 AI2 0/4-20 ma or 0-10 V All terminals (except mains supply terminals) must only be connected to voltages of maximum 16 V rms and 22.6 V peak or 35 VDC. A A Y Y B B RS-485 A RS-485 A RS-485 GND* RS-485 GND* RS-485 B RS-485 B GENIbus (internal) (Fix the screen with a cable clamp.) IO 351B 10 12 14 15 IO 351B 53 55 A Y B 57 60 IO 351B CU 361 A1 Y1 B1 Functional earth 30 PTC 1 32 PTC 2 Input for PTC sensor or thermal switch 34 PTC 3 4A 35 GND, PTC Fit jumpers if no PTC sensor or thermal switch is connected. All terminals (except mains supply terminals) must only be connected to voltages of maximum 16 V rms and 22.6 V peak or 35 VDC. * GND is isolated from other earth connections. IO 351B 30 32 34 35 18 / 60

Group Terminal Designation Data Diagram 3B 4B 5 16 DI4 Digital input 17 GND 18 AO4 Analog output, 0-10 V 20 DI5 Digital input 21 GND 22 AO5 Analog output, 0-10 V 24 DI6 Digital input 25 GND 26 AO6 Analog output 42 DI7 44 DI8 Digital input 46 DI9 47 GND Fit jumpers instead of the external stops for which the controller is designed. 36 PTC 4 38 PTC 5 Input for PTC sensor or thermal switch 40 PTC 6 41 GND, PTC Fit jumpers if no PTC sensor or thermal switch is connected. All terminals (except mains supply terminals) must only be connected to voltages of maximum 16 V rms and 22.6 V peak or 35 VDC. 82 DO4 NO 83 DO4 C 83 DO4 C 84 DO5 NO 85 DO5 C 85 DO5 C 86 DO6 NO 87 DO6 C 87 DO6 C 88 DO7 NO 89 DO7 C Relay contact IO 351B 16 17 18 20 21 22 23 24 25 26 42 44 46 47 IO 351B 36 38 40 41 IO 351B 82 83 83 84 85 85 86 87 87 88 89 19 / 60

3.4 IO 111 terminals 1 2 3 T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 PE 16 D1 D2 D3 D4 D5 D6 D7 D8 A Y B 4 5 15 14 13 12 Reset 6 7 8 11 ON DIP 1 2 3 4 5 6 7 8 9 10 P1 P2 P3 P4 P5 10 Fig. 11 IO 111 module I1 I2 I3 9 TM03 0691 0505 Pos. Terminal Description Data Function Diagram 1 2 3 5 9 T1 T2 G1 A1 G2 A2 Terminal for alarm relay Terminal for alarm relay GND for analog output 1 Terminal for analog output 1 GND for analog output 2 Terminal for analog output 2 Max. 250 VAC Max. 250 VAC 1) 0 V 2) 0 V 1) 15 VDC 2) 24 VDC, max. 100 ma 1) 0 V 2) 0 V 1) 15 VDC 2) 24 VDC, rated 1 ma All alarms trip the alarm relay. The alarm relay is closed during normal operation. In case of alarm or if the IO 111 is not connected to the power supply, the relay opens and breaks the connection between T1 and T2. Analog output 1 has two functions set via DIP switch 7. See section Analog outputs. 1) 4-20 ma for content of water in oil. Load resistance: Max. 250 Ω. 2) Pulse output for content of water in oil and stator insulation resistance. Analog output 2 has two indications set via DIP switch 6. See section Analog outputs. 1) 4-20 ma for stator winding temperature. Load resistance: Max. 250 Ω. There is no 4-20 ma signal in PTC installations. 2) Pt1000 emulator for stator winding temperature. K1 K2 GND connection Terminal for conductor for contactor status 0 V Digital input Feedback from motor contactor whether the pump is running or not. The input must be short-circuited when the pump is running. The signal is used by the IO 111 for filtering of measuring signals and for analysis during fault indication. R1 R2 GND connection Terminal for resetting 0 V Digital input For resetting of alarms, see installation and operating instructions for the IO 111. The input must be short-circuited when alarms are reset. PE Earth Earth GND for power supply + Plus for power supply 0 VDC 24 VAC ± 10 % 24 VAC ± 10 % 24 VDC ± 10 % A RS-485 A Bus input Y RS-485 GND 0 V B RS-485 B Bus input I1 Earth Earth I2 Not connected I3 Terminal for measurement of stator insulation resistance CAT II 600 V Power supply to the IO 111. RS-485 communication connection (9600 baud). The insulation resistance between stator windings and earth is measured. The measurement is only correct when the motor is stopped. Measurement voltage: 10 VDC. 1) 2) 1) 2) A1 G1 A2 G2 A Y B L1 L2 L3 I3 I1 A1 G1 T2 T1 A2 G2 K2 K1 R2 R1 + R R 20 / 60

Pos. Terminal Description Data Function Diagram 10 16 P1 P2 P3 P4 P5 D1 D2 D3 D4 D5 D6 D7 Terminal for sensors in the pump Terminal for power supply to sensors in the pump Terminal for sensors in the pump Terminal for power supply to sensors in the pump Terminal for sensors in the pump Terminal for alarm in case of too high stator temperature GND for alarm in case of too high stator temperature Terminal for alarm in case of moisture in the motor GND for alarm in case of moisture in the motor Terminal for alarm in case of insulation fault GND for alarm in case of insulation fault Terminal for warning Sensor input 15 V Sensor input 15 V Sensor input Digital output 24 VDC min. 10 kω 0 V Digital output 24 VDC min. 10 kω 0 V Digital output 24 VDC min. 10 kω 0 V D8 GND for warning 0 V Digital output 24 VDC min. 10 kω Thermal switch or PTC sensor according to DIN 44081 and 44082. P1 to P5 are used for the connection of sensors in the pump. All sensors in contact with phase voltage must be doubleinsulated according to EN 61010-1. Alarm in case of too high temperature in the stator windings. The output is closed during normal operation. If an alarm occurs, the connection is broken between D1 and D2. Alarm in case of moisture in the motor part of the pump. The output is closed during normal operation. If an alarm occurs, the connection is broken between D3 and D4. Alarm in case of too low insulation value between stator windings and earth. The output is closed during normal operation. If an alarm occurs, the connection is broken between D5 and D6. Warning. The output is closed during normal operation. If a warning occurs, the connection is broken between D7 and D8. The following warnings can occur: communication warning configuration warning too much water in oil stator insulation resistance below warning limit. See also section 8. Indication in the installation and operating instructions for the IO 111 and section 3.1.3 Indicator lights on the IO 351B. P1..P5 D1 D2 D3 D4 D5 D6 D7 D8 21 / 60

4. Configuration 4.1 Necessary equipment The following equipment is needed: R100, SW version 14, Nov. 01, 2005 or later PC Tools PC Tool Link adapter. 4.2 Configuration of Dedicated Controls The configuration consists of three steps: Setting the GENIbus number in the IO 351B module, if installed. See section 4.2.1 Setting the GENIbus number in IO 351B modules, if installed. Configuration of the CU 361 control unit. Use the configuration wizard or the PC Tool WW Controls supplied on CD-ROM. See section 6. PC Tool. Configuration of the IO 111 module, if installed. Use the PC Tool Water Utility, DIP switches in section 4.2.3 or see the installation and operating instructions for the IO 111. 4.2.1 Setting the GENIbus number in IO 351B modules, if installed This module must have a GENIbus number according to the following table: Module number GENIbus number A01 (IO 351B) 41 To assign a GENIbus number to the IO 351B module, proceed as follows: 1. Switch on the power supply to the Dedicated Controls. 2. Switch on the R100 and point it at the IR window of the first IO 351B to establish connection. Note If there are more than one IO 351B module, move close to the IR window to make sure that the R100 only communicates with one module at a time. Fig. 12 IR window of the IO 351B 3. Go to the first display "Number, IO 351" in the INSTALLATION menu with the R100. See fig. 13. Set the number of the module according to the above table. TM04 3788 5008 TM03 9972 4707 Fig. 13 Menu INSTALLATION, "Number, IO 351" 4. Send the number to the module by pressing [OK] on the R100. 4.2.2 Configuration of the IO 111, if installed See section 4.2.3 IO 111 settings. 22 / 60

4.2.3 IO 111 settings Potentiometer The warning limit for stator insulation resistance is set by means of a potentiometer (pos. 4). See fig. 10. The limit can be set between 10 and 1 MΩ. Note The alarm limit is 1 MΩ. 1 MΩ 10 MΩ TM03 3415 0306 Fig. 14 Potentiometer DIP switches The IO 111 must be configured for the pump connected by means of the DIP switches (pos. 11). See fig. 10. ON DIP 1 2 3 4 5 6 7 8 9 10 TM03 0678 0505 Fig. 15 DIP switch A configuration alarm will be given if the configuration does not correspond to the pump connected. if the configuration fault is of safety-related importance. See section 8. Indication, point 6, in the installation and operating instructions for the IO 111. A configuration warning will be given if the configuration fault is of function-related importance. See section 8. Indication, point 15, in the installation and operating instructions for the IO 111 and section 3.1.3 Indicator lights on the IO 351B. Switch 9 is not used. Pump variant The IO 111 must be set to the actual pump. In the pump type designation, there is an A or D. Example 1, internal wiring: SE - 1 80 80 40 A Ex 4 5 1D Example 2, external wiring: SE2.90.250.2250.4.S.496.Ex.S.5.13.C.Q.S These letters (A and D in the examples) can be found on the pump nameplate and refer to the setting of DIP switches 1 and 2. Note The SM 111 cannot be used together with Dedicated Controls. The signals from the SM 111 will not be monitored. Pump variant ON DIP 1 2 3 4 5 6 7 8 9 10 Description Variant A Variant D ON 1 2 ON 1 2 Installation without SM 111. Sensors are connected directly to the IO 111. Installation without SM 111. All sensors are hardwired out of the pump. The IO 111 can be used for indication of water in oil and as PTC relay. 23 / 60

Address for bus communication The IO 111 can communicate with control systems via a bus connection. In connection with bus communication, the IO 111 is slave. As a control system must be able to identify the slave units with which it communicates, the IO 111 modules must have unique addresses. Addresses between 40 and 46 are set by means of the switches 3, 4 and 5. See table. If the DIP switches are set to bus configuration, the address of the IO 111 module is set from the control system via bus. The address can be selected between 32 and 231. As standard, the address is set to 231. Address ON DIP 1 2 3 4 5 6 7 8 9 10 Description 40 Pump 1 3 4 5 41 Pump 2 3 4 5 42 Pump 3 3 4 5 43 Pump 4 3 4 5 44 Pump 5 3 4 5 45 Pump 6 3 4 5 46 Pump 7 3 4 5 Bus configuration 3 4 5 The address of the IO 111 is set from the control system via the bus connection. Default address: 231. 24 / 60

Analog outputs The analog outputs of the IO 111 can be set to various types of output signal. Analog output Analog output 2: G2 and A2 (pos. 2) Analog output 2: G2 and A2 (pos. 2) Analog output 1: G1 and A1 (pos. 2) Analog output 1: G1 and A1 (pos. 2) ON DIP 1 2 3 4 5 6 7 8 9 10 6 6 7 7 Description Motor temperature 4-20 ma, 0-180 C 0 ma = no sensor Motor temperature Pt1000 emulator 1000-1685 Ω, 0-180 C Water in oil 4-20 ma, 0-20 % 0 ma = water-in-oil sensor not fitted 3.5 ma = alarm, air in oil chamber 22 ma = warning, water content far outside the measuring range Water in oil Pulse output: 0-20 % Maximum connection: 24 V, 100 ma Status of output transistor Off On Pulse A Pulse B Time Pulse A, water in oil: 0.5-3.66 s = 0-20 % 10 s = water content far outside the measuring range Pulse B, insulation resistance: 0.5 s = 0 MΩ 10.5 s = 20 MΩ Bus protocol By setting the bus protocol, the type of bus connection is chosen. GENIbus is a Grundfos standard protocol for Grundfos products. The Modbus protocol is used for communication between the IO 111 and a control unit from another supplier. Bus protocol ON DIP 1 2 3 4 5 6 7 8 9 10 Description GENIbus Modbus 8 8 Grundfos standard protocol for communication between Grundfos products See www.grundfos.com, WebCAPS, Literature, Accessories, Accessories, electrical and Operating the IO 111 via Modbus, document number 96623373. 25 / 60

ATEX/IECEx protection ATEX/IECEx protection can be activated/deactivated by means of DIP switch 10. ATEX/IECEx protection ON DIP 1 2 3 4 5 6 7 8 9 10 Description Deactivated Activated 10 10 Activation of ATEX/IECEx protection enables additional alarms: Main bearing temperature to high. Default alarm temperature: 140 C (installation with SM 111). Support bearing temperature to high. Default alarm temperature: 140 C (installation with SM 111). Missing signal from bearing sensor (installation with SM 111). Missing signal from water-in-oil sensor Communication alarm (installation with SM 111). 4.2.4 CU 361 and IO 351 installation and operating instructions See WinCAPS or WebCAPS > Service > Dedicated Controls > CU 361 or IO 351 > Installation and operating instructions. 26 / 60

5. Documentation supplied with Dedicated Controls The following documentation is supplied with the Dedicated Controls control cabinet. Instructions Safety instructions for Dedicated Controls (printed multilingual version) Installation and operating instructions for Dedicated Controls (monolingual version on CD-ROM) Supplement to installation and operating instructions for Dedicated Controls (printed version) Installation and operating instructions for the CU 361 (multilingual version) Installation and operating instructions for the IO 351 (multilingual version). Other documentation on control cabinet Electrical wiring diagrams List of supplied components (parts list) and description of cable colours and dimensions as well as sizes of backup fuses Control cabinet layout. 6. PC Tool For information about PC Tool, open the help function in the software. 6.1 Connection of PC to Dedicated Controls For the physical connection between the PC and Dedicated Controls, a Grundfos PC Tool Link is used. This converts the RS-485 used by Dedicated Controls to USB used by the PC. The PC Tool Link also provides a galvanic separation between Dedicated Controls and the PC. 70 DO1, C 71 DO1, NO 72 DO1, NC 73 DO2, C 74 DO2, NO 75 DO2, NC USB cable PC Tool Link TTL cable 50 +24V 51 AI 1 53 +24V 54 AI 2 57 AI 3 58 GND DI 1 GND DI 2 GND DI 3 RS485, A RS485, GND RS485, B RS485, A RS485, GND RS485, B 10 11 12 13 14 BYA A1 Y1 B1 Line Neutral PE L N Service plug Fig. 16 Connection of PC to Dedicated Controls using the PC Tool Link 27 / 60

7. Fieldbus communication module 7.1 SCADA system See the installation and operating instructions for Dedicated Controls to set up communication to SCADA systems. See also section 7.2 Data communication or menu 4.3 in the CU 361. Grundfos does not supply SCADA systems. If it seems as if the SCADA system is faulty, we recommend you to contact the supplier. Note The SCADA system integrator can order a functional profile from Grundfos. 7.1.1 Communication The communication takes place via a Modbus module or a GSM/GPRS module. See section 7.2 Data communication. 7.2 Data communication The CU 361 must have a CIM module (CIM = Communication Interface Module) fitted to be able to transfer data to the SCADA system or to a mobile phone. Various CIM modules are available, depending on the type of network. The CIM module can be fitted directly in the CU 361. See section 7.3 Fitting the CIM module. For configuration of the CIM module, see the installation and operating instructions and the functional profile on the CD-ROM supplied with the module. The user must select the type of communication module fitted before a network connection can be established. The following CIM modules can be fitted in the CU 361: CIM 200 (Modbus via RS-485) CIM 250 (Modbus and SMS via GSM/GPRS) CIM 270 (GRM) (GRM = Grundfos Remote Management). Display_4.3 Fig. 17 Example, selection of CIM module and communication 28 / 60

7.2.1 Modbus network CIM 200 (Modbus via RS-485) The CIM 200 module transfers data to/from the CU 361 and the local Modbus network. See fig. 18. SCADA Modbus network CU 361 (CIM 200 built-in) TM04 3221 3908 Fig. 18 Example, CIM 200 CIM 250 (Modbus and SMS via GSM/GPRS) The CIM 250 transfers data to/from the CU 361 and a GSM/GPRS network. See fig. 19. The CIM 250 can send/receive SMS messages to/from one or more mobile phones. The CIM 250 can also send data to a remote SCADA system. Note A series of system parameters must be set before SMS messaging can be used. SCADA GSM antenna Mobile phone CU 361 (CIM 250 built-in) TM04 3697 4908 Fig. 19 Example, CIM 250 29 / 60

7.2.2 CIM 270 (GRM) The CIM 270 module is used to link with Grundfos Remote Management. GRM server GRM WebAccess GSM antenna Mobile phone CU 361 (CIM 270 built-in) TM04 3698 4908 Fig. 20 Example, CIM 270 7.2.3 Ethernet Ethernet is the most widely used standard for local networks (LAN). The standardisation of this technology has created some of the easiest and cheapest ways of creating communication between electrical units, for instance between computers or between computers and control units. The web server of the CU 361 makes it possible to connect a computer to the CU 361 via an Ethernet connection (Ethernet crossover cable). The user interface can thus be exported from the CU 361 to a computer so that the CU 361 and consequently the Dedicated Controls system can be remotely monitored and controlled. See figs 21 and 22. Note Grundfos recommends that the system administrator is contacted to arrange security protection for the CU 361 connection. In order to use the web server, the user must know the IP address of the CU 361. All network units must have a unique IP address to communicate with each other. The IP address of the CU 361 from factory is 192.168.0.102. Alternatively to the factory-set IP address, it is possible to use a dynamic assignment of IP address. This is possible by activating a DHCP (Dynamic Host Configuration Protocol) either directly in the CU 361 or via the web server. Ethernet crossover cable CU 361 TM04 3218 3908 Fig. 21 Example, Ethernet connection 30 / 60

PC with access to the CU 361 via the internet Ethernet cable for internet connection CU 361 TM04 3699 4908 Fig. 22 Example, internet connection Dynamic assignment of an IP address for the CU 361 requires a DHCP server in the network. The DHCP server assigns a number of IP addresses to the electrical units and makes sure that two units do not receive the same IP address. A standard internet browser is used for connection to the web server of the CU 361. If the user wants to use the factory-set IP address, no changes are required in the menu display. Open the internet browser, and enter the IP address of the CU 361. Now open the browser, and enter the CU 361 "Host name" (Default: CU361) instead of the IP address. The internet browser will try to connect to the CU 361. The host name can be read in the display, but can only be changed using a PC tool or via a web browser. Note DHCP requires a host name. This is the first menu display seen when the CU 361 connects. TM03 2048 3505 Fig. 23 Connecting to the CU 361 Factory setting Username: admin Password: admin When username and password have been entered, a Java Runtime Environment application starts up in the CU 361, provided that it has been installed on the computer in question. If this is not the case, but the computer is connected to the internet, then use the link on the screen to download and install the Java Runtime Environment application. 31 / 60

Fig. 24 Display with link to JavaScript application The Java Runtime Environment application transfers the CU 361 user interface (including display and panel functions) onto the computer screen. The CU 361 can now be controlled from the PC. Fig. 25 Network setting Change of network setting When the connection to the web server of the CU 361 has been established, it is possible to change the network setting. TM03 2050 3505 TM03 3204 3908 TM03 2049 3505 Fig. 26 Change of network setting 1. Click the icon "Network admin". 2. Enter the changes. 3. Click [Submit] to enable the changes. 32 / 60

Change of password TM03 2051 3505 Fig. 27 Change of password 1. Click the icon "Change password". 2. Enter the new password. 3. Click [Submit] to enable the new password. 7.2.4 GENIbus By installing an external GENIbus module (CIM 050), it is possible to connect a CU 361 to an external network. The connection can be established via a gateway. For more information, contact Grundfos. 33 / 60

7.3 Fitting the CIM module The CIM module must be fitted by authorised personnel. Warning Switch off the power supply to the CU 361 before fitting the CIM module. Warning Electrostatic discharge (ESD) must be avoided when fitting the CIM module, for instance by wearing an antistatic wrist strap as shown in fig. 30. Fit the CIM module as follows: 1. Remove the screw in the back cover of the CU 361. See fig. 28. Fig. 28 Removing the screw holding the back cover 2. Remove the cover. Place the cover on a plane surface, and push out the marked knockout using a screwdriver or a similar tool. See fig. 29. TM04 2403 2508 TM04 2402 2508 Fig. 29 Opening the back cover and removing the knockout 34 / 60

3. Fit the CIM module. See fig. 30. TM03 2227 3905 Fig. 30 Fitting the CIM module 4. Place the labels supplied with the CIM module on the back cover. See fig. 31. CIM 250 GSM Type: CIM 250 Kit Funct. module - Geni/RS485Op Prod. No. 96824795 P. C. 0538 Version V01 Serial No. 9854 TM04 2586 2708 Fig. 31 Placing the new labels on the back cover 5. Refit the back cover to the CU 361, and secure it with the mounting screw. See fig. 32. TM04 2587 2708 Fig. 32 Refitting the back cover 35 / 60

8. General settings, CU 361 8.1 Display language In this menu, the CU 361 display language is selected. In connection with service, it is easy to change over to the service language, using the function "Change language to the service language (English)". Path: Settings>General settings, CU 361> Description Other functions related to CU 361 Display language. Display_4.6 9. Fault finding 9.1 Power supply See the system wiring diagram and system documentation. 9.2 External control, data collection, SCADA systems See the system wiring diagram and system documentation. 9.3 Pumps See the documentation for the connected pump(s). For example via WinCAPS, WebCAPS or service instructions for the connected Grundfos pump(s). 36 / 60

10. Fault finding tools 10.1 CU 361 display 10.1.1 Status The first status display is shown below. This display appears when the Dedicated Controls is switched on, and it appears when the buttons of the control panel have not been touched for 15 minutes. The status display is the main opening display of the CU 361. Note If the buttons on the control panel have not been activated for 15 minutes, the CU 361 automatically reverts to this display. An alarm is shown as an alarm bell next to the unit that caused the alarm. When the system registers an alarm or warning, the following will happen: An alarm bell is shown on the right of the upper status line. The red indicator light on the control panel lights up. "Current alarms" appear as the first line below the pit graphics. The alarm relay operates. The indication is maintained as long as the system has an active alarm. An alarm is active until it has been reset, either automatically or manually via "Current alarms" in the status display. An alarm cannot be reset until the fault causing the alarm has been corrected. Example: An overtemperature alarm cannot be reset until the pump has cooled. Note The display shown below should be considered as an example. Path: Status> Description Options: Current alarms See current alarms. The line is only active if there is one or more active alarms. System See operating parameters for the system. Pump 1 See operating parameters for pump 1. Pump 2 See operating parameters for pump 2. The hand symbol indicates that the pump is manually controlled, i.e. the pump can only be started and stopped manually. Float switches See current positions and status of the float switches. Mixer See mixer status. Electrical overview See actual values for analog and digital inputs as well as digital outputs. Note: Float switches and mixer will only appear if they are installed in the system. 4 11 6 7 1 8 2 9 3 10 5 Display_1 37 / 60

Key to display Pos. Description 1 Lowest start level: If the water level rises above this level, the first pump will start. 2 Lowest stop level: If the water level falls below this level, both pumps will stop. 3 The display shows that pump 1 is started. The bottom is a dotted/broken line. 4 The actual flow is measured by a flowmeter or with the help of level measurements and pit data. See installation and operating instructions for Dedicated Controls. Alarm bell: The alarm bell is visible as long as there are active alarms. The red indicator light on the control panel 5 has the same function. 6 The broken line moves up to symbolise flow. The line appears when one or both pumps are running. 7 Shows the water level as falling or rising. 8 This value and the wavy line show the current water level in the pit. 9 Mixer: The propeller rotates if the mixer is operating. 10 The display shows that pump 2 is stopped. The bottom is a thick, unbroken line. 11 Pressure sensor symbol: The sensor is shown at the bottom of the pit and represents a standard pressure sensor. 38 / 60

10.2 System This display shows the actual operating parameters of the system. Note The display shown below should be considered as an example. Path: Status>System> Description The display shows an operating overview of the system. Operating hours Parallel-operation time Overflow time Overflow volume Number of overflows Total volume Energy Specific energy GSM/GPRS. Display_1.1 Description of operating parameters Operating parameter Operating hours Parallel-operation time Overflow time Overflow volume Number of overflows Total volume Energy Specific energy GSM/GPRS Function Total number of system operating hours. The accumulated time in which more than one pump has been in operation. Overflow duration. The estimated overflow volume, based on the latest flow calculation. The number of registered overflows. The accumulated volume of liquid removed. Note: Requires a flowmeter (analog or pulse measurement), or the volume is calculated using an analog sensor if the pit dimensions are known. For more pit configuration details, see installation and operating instructions for Dedicated Controls. Total amount of energy in kwh. Shows the specific energy, indicating the efficiency of the pump to convert the electrical energy (measured in kwh) to pumped volumes (measured in m 3 ). The specific energy is indicated in kwh/m 3. To be able to make a satisfactory average measurement, the measuring interval is one hour. Note: Requires an energy meter (pulse input or analog input). GSM/GPRS modem status: Ready Invalid PIN code Invalid PUK code Invalid service centre Insert SIM card SIM card defective Invalid SIM card SIM busy. 39 / 60

10.3 Specific pump This display shows the actual operating parameters of pump 1. Many parameters will show a value only if the relevant sensors and modules are fitted. Note Note If two pumps are installed in the pit, a display for pump 2 will appear. The display shown below should be considered as an example. Path: Status>Pump 1> Display_1.2 Description The display shows an operating overview of pump 1. Status Controlled by Operation Operating hours Latest runtime Time since service Time for service Number of starts Number of starts/hour Average flow Latest flow Number of flow measurements Average current Latest current Start level Stop level. Description of operating parameters Operating parameters Status Controlled by Operation Operating hours Latest runtime Time since service Time for service Number of starts Number of starts/hour Average flow Latest flow Number of flow measurements Average current Latest current Start level Stop level Function Shows if a pump is started or stopped. CU 361 (system), manually by switch (Auto/On/Off) or via SCADA. Shows how the system is being controlled, automatically or manually. Number of hours the pump has been in operation (can be changed if another pump is installed). The pump's latest operating period. The time elapsed since the pump was last serviced (can be reset by Grundfos Service). Time until the next service is due. Number of pump starts since the pump was installed/connected (can be changed if another pump is installed). Number of pump starts in the last hour. Requires an analog level sensor or flow sensor. See installation and operating instructions for Dedicated Controls. The calculated/measured flow of the last pump that was running. Requires an analog level sensor. See installation and operating instructions for Dedicated Controls. The actual average current consumption. 0 A when the pump stops. The current value when the pump stopped. The value updates when the pump is running. Requires a current sensor/ammeter. Requires an analog level sensor (not shown with alternating operation). Requires an analog level sensor. 40 / 60

10.4 GSM/GPRS This display shows the status of the GSM modem. Note This display is only shown if a modem has been configured in the system. The display can be used to check the antenna conditions and for fault finding. SIM card status Shows the SIM card status message sent to the system. Signal strength A graph shows the actual signal strength. If the signal strength is unknown, " " is displayed. If there is no signal, "No signal" is displayed. GPRS state Shows the GPRS network state. Statistics Displays the number of sent and received SMS messages and the amount (kb) of sent and received GPRS data. GPRS network The current network IP address. Note The display shown below should be considered as an example. Path: Status>System>GSM/GPRS> Description The display shows the status of the GSM modem. GSM/GPRS SIM card status Signal strength GPRS state. Display_1.1.1 Statistics SMS messages sent SMS messages received GPRS data sent GPRS data received Outgoing calls Incoming calls. GPRS network IP address. 41 / 60

10.5 Float switch status This display shows the current positions and functions of the float switches. The display can be used for function testing and fault finding. "Off" means that the float switch is hanging downwards. "On" means that the float switch is kept up by the water. Note The display shown below should be considered as an example. Path: Status>Float switch status> Description The display shows the current positions and functions of the float switches. Float switch 4: High level. Float switch 3: Pump 2 starts. Float switch 2: Pump 1 starts, and both pumps stop. Float switch 1: Dry running. Display_1.4 42 / 60

10.6 Mixer This display shows the status of the mixer and the mixer counters. The display can be used for fault finding and service. Note Note This display will only appear if a mixer is installed. The display shown below should be considered as an example. Path: Status>Mixer> Description The display shows the status of the mixer and the mixer counters. Status Operating hours Time since service Time for service Number of starts Number of starts/hour. Display_1.5 43 / 60

10.7 Electrical overview This display shows an overview of the various inputs and outputs. Note The display shown below should be considered as an example. Path: Status>Electrical overview> Description The display shows an overview of the various inputs and outputs. Electrical overview Select submenu: Analog inputs Digital inputs Digital outputs. Display_1.6 44 / 60

10.7.1 Analog inputs This display shows the status of the individual analog inputs. Note The display shown below should be considered as an example. Path: Status>Electrical overview>analog inputs> Description Analog input AI1 (CU 361) [51]: The AI1 analog input on the CU 361 (designated terminal 51) is set up as a current input. The measured value of 14.9 ma corresponds to a level and a pressure of 3.40 m. Display_1.6.1 45 / 60

10.7.2 Digital inputs This display shows the status of the individual digital inputs. Note The display shown below should be considered as an example. Path: Status>Electrical overview>digital inputs> Description Digital input DI2 (IO 351-41) [12]: The DI2 digital input on the IO 351 (designated terminal 12) is linked to the function "Contactor feedback, pump 1", and the contact is closed. Display_1.6.2 46 / 60

10.7.3 Digital outputs This display shows the status of the individual digital outputs. Note The display shown below should be considered as an example. Path: Status>Electrical overview>digital outputs> Description Digital output DO1 (CU 361) [71]: The DO1 digital output on the CU 361 (designated terminal 71) is linked to the function "High-level alarm", and the alarm is active. Display_1.6.3 11. Alarms and warnings 11.1 Alarm indicators Dedicated Controls systems feature the following alarm indicators: Red indicator light on the CU 361. The indicator light will be on when an alarm or a warning is active or until the alarm or warning has been reset. The display of the CU 361. The alarm relay in the CU 361. Alarms and warnings are divided into System alarms Pump alarms Mixer alarms Combi alarms. 47 / 60

11.2 Alarm settings Alarms can only be indicated if the desired alarms have been enabled. See section "Alarm settings" in the installation and operating instructions for Dedicated Controls. All fault sources are either of the analog or digital fault type. 11.2.1 Analog fault configuration Analog faults are activated if the currently measured value is outside a set limit. An analog fault can be registered as a warning or as an alarm. Alarm delay An alarm delay is typically used when a measuring signal is unstable. The signal from surface water waves may generate a high water level for a short period. An alarm delay allows time for the unstable signal to pass, e.g. for the water level to steady. User-defined alarm relay A warning or alarm can be coupled to a relay output. Alarm resetting Select the alarm resetting as manual or automatic. All warnings will be reset automatically. Action, warning and alarm (High level) Set SMS messaging schedules for the service manager in the following periods: Work, Off, Sleep. Schedule periods serve practical purposes, e.g. to avoid sending SMS messages about minor faults to the service manager in the middle of the night. The service manager will receive the SMS messages when he/she has returned to work. Warning or alarm callback to the SCADA system is also selected in this display. Note The display shown below should be considered as an example. Path: Settings>Alarm settings>system alarms>high level> Description Make the required settings. Alarm delay Warning Enabled Limit User-defined alarm relay. Alarm Enabled Limit User-defined alarm relay. Manual resetting Automatic resetting. Display_4.5.1.2 Action, warning and alarm Enable SMS, work Enable SMS, off Enable SMS, sleep SCADA callback. 48 / 60

11.2.2 Digital fault configuration Digital faults are activated in case of a faulty system condition. A digital fault can be registered as a warning or as an alarm. Alarm delay An alarm delay is typically used when a measuring signal is unstable. The signal from surface water waves may generate a high water level for at short period. An alarm delay allows time for the unstable signal to pass, e.g. for the water level to steady. User-defined alarm relay A warning or alarm can be coupled to a relay output. Alarm resetting Select the alarm resetting as manual or automatic. All warnings will be reset automatically. Action, warning and alarm (Battery backup (UPS)) Set SMS messaging schedules for the service manager in the following periods: Work, Off, Sleep. Schedule periods serve practical purposes, e.g. to avoid sending SMS messages about minor faults to the service manager in the middle of the night. The service manager will receive the SMS messages when he/she has returned to work. Warning or alarm callback to the SCADA system is also selected in this display. Note The display shown below should be considered as an example. Path: Settings>Alarm settings>system alarms>battery backup (UPS)> Description Make the required settings. Alarm delay Disabled Warning Alarm. Alarm User-defined alarm relay Manual resetting Automatic resetting. Display_4.5.1.14 Action, warning and alarm Enable SMS, work Enable SMS, off Enable SMS, sleep SCADA callback. 49 / 60

12. How to trace an alarm 12.1 Menu Status See installation and operating instructions for Dedicated Controls, section 13. Status. 1. If an alarm occurs, "Current alarms" will be displayed as the first line in the Status menu. 2. Select "Current alarms", and press [ok] on the CU 361. 12.2 Menu Alarm The display shows the last 24 alarms with date and time of occurrence. 12.2.1 Current alarms This display shows all active system alarms. An alarm can only be reset when it is no longer active. An alarm can be reset when a date/time is given to the right of "Disappeared at". Press [ok] to reset the marked alarm. See section 12.2.2 Alarm log. Symbol Description Alarm Warning This menu shows the following: Warnings caused by faults that still exist. Warnings caused by faults that have disappeared, but the warning requires manual resetting. Alarms caused by faults that still exist. Alarms caused by faults that have disappeared, but the alarm requires manual resetting. All warnings and alarms with automatic resetting are automatically removed from the menu when the fault has been corrected. Alarms requiring manual resetting are reset in this display by pressing [ok]. For every warning or alarm, the following is shown: Whether it is a warning or an alarm. Where the fault occurred: System, Pump 1, Pump 2, etc. What the cause of the fault is, and the alarm code in brackets, e.g. High level (191). When the fault occurred: Date and time. When the fault disappeared: Date and time. If the fault still exists, date and time are shown as --...--. The latest warning/alarm is shown at the top of the display. Note The display shown below should be considered as an example. Path: Alarm>Alarm status>current alarms> Description The display shows two active alarms. Display_3.1 50 / 60

12.2.2 Alarm log The alarm log can store up to 24 warnings and alarms. For every warning or alarm, the following is shown: Whether it is a warning or an alarm. Where the fault occurred: System, Pump 1, Pump 2, etc. In the case of an input-related fault, the input will appear. What the cause of the fault is, and the alarm code in brackets, e.g. warning: Conflicting levels (204), etc. When the fault occurred: Date and time. When the fault disappeared: Date and time. If the fault still exists, date and time are shown as --...--. The latest warning/alarm is shown at the top of the display. Note The display shown below should be considered as an example. Path: Alarm>Alarm status>alarm log> Description The display shows one warning and three alarms, two of which are still active. To reset alarms, see section 12.2.1 Current alarms. Note: An alarm cannot be reset until the fault has been corrected. Display_3.2 12.3 Password protection A password can be set in order to prevent unintentional change of settings. There are two different passwords: password for menu Settings password for menu Operation. 12.3.1 Service password If a customer-set password is not available for the Grundfos service engineer, the Dedicated Controls system can be unlocked by using the Grundfos service code "6814". Please protect this code, and prevent access by unauthorised persons. 51 / 60