PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS

Similar documents
U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Performance Investigation of Joule Thomson Refrigeration System with Environment Friendly Refrigerant Mixtures

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

η second law = Second law efficiency

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Chapter 11 REFRIGERATION CYCLES

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Thermodynamics I. Refrigeration and Heat Pump Cycles

DEEPAK PALIWAL, S.P.S.RAJPUT

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Transcritical CO2 Bottle Cooler Development

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Chapter 11 REFRIGERATION CYCLES

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Week 9. Refrigeration Cycles I. GENESYS Laboratory

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

PERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Thermodynamics II Chapter 5 Refrigeration

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

CH2351 Chemical Engineering Thermodynamics II Unit V Refrigeration. Dr. M. Subramanian

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

HFCs or the Old Refrigerants - what is the best Choice?

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

CHAPTER 1 INTRODUCTION

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

Chapter 10. Refrigeration and Heat Pump Systems

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

REFRIGERATION AND AIR CONDITIONING

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Refrigerator and Heat Pump Objectives

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Design of LPG Refrigeration System

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

A study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114

REFRIGERATION AND AIR CONDITIONING

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression Refrigeration System

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Experimental investigation on the performance of air conditioner using R32 Refrigerant

Chapter 11 REFRIGERATION CYCLES. Department of Mechanical Engineering

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

A STUDY OF TWO STAGE CASCADE REFRIGERATION

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

CHAPTER 1 INTRODUCTION

Available online at ScienceDirect. Physics Procedia 67 (2015 )

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

Chapter 10 Lyes KADEM [Thermodynamics II] 2007

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

R134a Refrigerant in Vapour Compression Cycle: A Review Paper

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

Chapter 9. Refrigeration and Liquefaction

S.A. Klein and G.F. Nellis Cambridge University Press, 2011 = 90 F. compressor. condenser. 5 evaporator 1. evap

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Homework Chapter2. Homework Chapter3

Volume 2, Issue 1 (2014) ISSN International Journal of Advance Research and Innovation

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Oyelami S., Bolaji B. O.

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

VCR SYSTEM USING R-600a/ POE OIL/MINERAL OIL/NANO-SiO 2 AS WORKING FLUID: AN EXPERIMENTAL INVESTIGATION

The natural solution for domestic refrigeration

Modeling And Testing Of R23/R134a Mixed Refrigerant System With Water Cooled Separator For Low Temperature Refrigeration

Volume 1, Issue 2 (2013) ISSN International Journal of Advance Research and Innovation

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Transcription:

RIO 3 - World Climate & Energy Event, 1-5 December 23, Rio de Janeiro, Brazil 275 PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS G. Venkatarathnam, V. Ravindranatha Reddy, S. Srinivasa Murthy * Refrigeration & Airconditioning Laboratory Department of Mechanical Engineering Indian Institute of Technology Madras Chennai 636, India Abstract - This paper presents the development and testing of a multistage mixed refrigerant cascade refrigerator for achieving very low temperatures. The main advantage with these systems is the use of natural fluids such as nitrogen, argon, helium, neon, and hydrocarbon fluids such as methane, ethane, propane, butanes and pentane, which, unlike the HFCs and their mixtures, are environment friendly. The system cools down to 1 K in about 6 minutes. A load of 7 Watts could be met at 1 K. Introduction Single stage refrigeration systems can be used for meeting refrigeration loads down to -4 C. Two stage systems are needed for applications operating at temperatures below -4 C and down to -75 C. Three or more stages are needed for temperatures below -1 C. Ozone depleting substances such as CFC13/CFC12 and CFC14/CFC13/CFC12 were widely used in two and three stage cascade systems. However, after the Montreal Protocol ban on the ozone depleting substances, CFC13 has now been replaced by HFC23 and CFC12 by HCFC22 or HFC134a. Under the Kyoto Protocol on Green House gases, HFCs have been included. Hence, there has been a quest for alternate environment friendly fluids / mixtures for obtaining very low temperatures. Refrigeration systems known as Auto Refrigerant Cascade (ARC) or Mixed Refrigerant Cascade (MRC) which can reach temperatures as low as -2 C are under development in many parts of the world. The MRC systems were studied extensively in the former Soviet Union (Alexeev et al, 2; Boiarskii et al, 1998) and were also patented in the United States by Missimer (1972, 1973). The use of a single compressor in a MRC cycle compared to multiple compressors in traditional cascade cycles results in reduction of cost and complexity. The efficiency of the MRC cycle can be as high as the traditional cascade cycles because of the low exergy efficiency of the small compressors, typically between 3 to 45%, depending on the construction (reciprocating or rotary) and working pressures. Figure 1 shows the schematic of a single stage MRC refrigerator. In this cycle a mixture of refrigerants is compressed from state point 1 to state point 2. The heat of compression is rejected in the after-cooler (state point 3). Then the refrigerant and the lubricating oil are separated, before the high pressure refrigerant is introduced into the cryostat (state point 4). The high pressure refrigerant is condensed and sub-cooled using the low pressure refrigerant * Corresponding Author: Phone: +91 44 22578524; FAX: +91 44 2257545; email: ssmurthy@iitm.ac.in

276 G. Venkatarathnam, V.R. Reddy, S.S. Murthy: Performance of very low temperature refrigeration leaving the evaporator in a counter current heat exchanger (state point 5). The sub-cooled refrigerant is expanded from state point 5 to state point 6, and is evaporated in the evaporator to state point 7. With appropriate mixtures, the refrigeration temperature can be varied from 245 K to as low as 7 K with a working pressure less than 2 bar. The theoretical exergy efficiency (COP/COP Carnot ) of these refrigerators ranges from 2 to 4% depending on the refrigeration temperatures and mixtures used. The practical exergy efficiency of refrigerators operating at 8 to 1 K varies typically between 2 to 7%. At the Refrigeration & Airconditioning Laboratory of Indian Institute of Technology Madras, MRC refrigerators have been studied by the authors theoretically for the last 1 years and prototypes have been built and tested since 1998. Different types of heat exchangers have been fabricated, and the systems have been tested with different compressors and mixtures. In this paper, the results obtained on a MRC system with phase separators using nitrogenhydrocarbon mixtures are presented. Figure 1: Schematic of the single stage MRC refrigerator Performance of the Multi-Stage MRC Cycle One of the problems with the single stage cycle shown in Fig. 1 is the possibility of carry over of the compressor lubricating oil, which can freeze in the expansion capillary tubes. In order to avoid the freezing, a phase separator cycle (Fig. 2), also known as the multistage cycle is under development in our laboratory. In this cycle (Fig. 2), a phase separator is employed to remove some of the high boiling point components such as butanes and pentanes and the lubricating oil carried over from the compressor from reaching low temperatures where they may freeze. In the phase separators, the liquid consists mostly of the high boiling point components, and the vapour phase preferably does not contain any high boiling components. The liquid is expanded to a lower pressure, mixed with the low pressure refrigerant returning from the evaporator at an intermediate temperature and returned to the compressor. The expanded liquid also provides the necessary cooling to cool and condense the vapour stream leaving the phase separator. The use of phase separator also allows balancing the refrigeration needed to cool the high pressure refrigerant at different temperatures. When no liquid phase is

RIO 3 - World Climate & Energy Event, 1-5 December 23, Rio de Janeiro, Brazil 277 present, the phase separator simply acts as a bypass valve to decrease the flow rate through the heat exchangers. Compressor Aftercooler HX-1 Phase separator HX-2 Evaporator Figure 2 : Schematic of the multistage MRC refrigerator Test Setup In the MRC refrigerator test rig, a rotary piston R22 compressor of 3.8 m 3 /hr capacity has been used. Capillary tubes are employed for expanding the refrigerant at room temperature as well as at low temperature. A coiled heat exchanger of 6.5 metres total lentgh was used. A vacuum level of less than 1-4 mbar was maintained in the cryostat. Ten layers of aluminized mylar separated by paper spacers was applied as insulation. A conventional commercial oil separator used in R22 systems was employed. The test rig is extensively instrumented for measurement of temperatures, pressures, flow rates, etc. Results and Discussion The system was charged with the following mixture:n2/ch4/c2h6/c3h8/i-c4h1: 36/14/7/22/21 mol%. Figure 3 shows the cool down curve of the multistage refrigeration system shown in Fig.2. It can be seen that a temperature of 1 K can be reached in about 56 minutes. The cool down time compares well with the 4-45 minutes required in the single stage cycle tested by the authors (Venkatarathnam et al, 23). Figure 4 shows the heat load and exergy efficiency of the refrigerator with the mixture at different evaporator outlet temperatures. The exergy efficiency of a refrigerator is the ratio of the minimum work required with a reversible (Carnot) refrigerator and the actual work required to meet the same heat load, and is given by η ex T Q a 1 W rev T = = (1) W W In the above expression Q is the refrigeration load, T a is the ambient temperature, T is the refrigeration temperature and W is the compressor power. The exergy efficiency is termed as

278 G. Venkatarathnam, V.R. Reddy, S.S. Murthy: Performance of very low temperature refrigeration the external exergy efficiency when T is the temperature of the load, and internal exergy efficiency when T is the temperature of the refrigerant leaving the evaporator. The evaporator 4 35 Temperature (K)/ Pressure (psi) 3 25 2 15 1 Temperature at capillary entry Temperature at capillary exit Compressor discharge pressure 5 Compressor suction pressure 1 2 3 4 5 6 7 8 9 1 Time (minutes) Figure 3: Cool down characteristic of the refrigerator with a mixture of nitrogen, methane, ethane, propane and iso-butane 25 3 2 Exergy efficiency (y2 axis) 2.5 Heat load (Watts) 15 1 Heat load (y1 axis) 2 1.5 1 Internal exergy efficiency (%) 5.5 9 95 1 15 11 115 12 125 13 135 Temperature (K) Figure 4 : Heat load characteristics and internal exergy efficiency with a nitrogen, methane, ethane, propane, iso-butane mixture

RIO 3 - World Climate & Energy Event, 1-5 December 23, Rio de Janeiro, Brazil 279 used in this work has not been optimized for the system. Hence we have chosen to present the results in terms of internal exergy efficiency. With the present mixture, a load of 7 Watts could be met at a temperature of 1 K, and a maximum load of 2 Watts at 13 K. A maximum internal exergy efficiency of 2.5% could be achieved at about 11 K. Figure 5 shows the heat load and internal exergy variation with a mixture of nitrogen, methane, ethane, iso-butane and n-pentane. A maximum exergy efficiency of 4.1% could be obtained with this mixture and a heat load of 3 Watts could be met at a refrigerant temperature of 122 K. The higher refrigerating temperature obtained in this mixture is due to the higher evaporating pressure applied. With an appropriate throttle and evaporator, it is possible to improve the capacity and exergy efficiency with the n-pentane based mixture even further. The results presented above are the preliminary results obtained with the system, and there s much scope for improvement in the refrigeration capacity as well as the exergy efficiency by matching the components of the system, and using an optimized mixture. This work is under progress. 35 4.5 3 4 Heat load (Watts) 25 2 15 1 5 Exergy efficiency (y2 axis) Heat load (y1 axis) 3.5 3 2.5 2 1.5 1.5 Internal exergy efficiency (%) 11 112 114 116 118 12 122 124 Temperature (K) Figure 5: Heat load characteristics and internal exergy efficiency with a nitrogen, methane, ethane, iso-butane, n-pentane mixture Conclusions A multistage mixed refrigerant cascade refrigerator has been built and tested. The main advantage with these systems is the use of environment friendly natural fluids such as nitrogen, argon, helium, neon, and hydrocarbon fluids such as methane, ethane, propane, butanes and pentane. The system cools down to 1 K in about 6 minutes. A load of 7 Watts could be met at 1 K.

28 G. Venkatarathnam, V.R. Reddy, S.S. Murthy: Performance of very low temperature refrigeration References Alexeev, A., Thiel, A., Haberstroh, Ch., and Quack, H., 2, Study of behavior in the heat exchanger of a mixed gas Joule-Thomson cooler, Advances in Cryogenic Engineering, 45, 37-315 Boiarskii, M., Brodyanskii, V.M., Longsworth, R.C., 1998, Retrospective of mixedrefrigerant technology and modern status of cryocoolers based on one-stage, oil-lubricated compressors, Advances in Cryogenic Engineering, 43, 171-178 Missimer, D. J., 1972, U.S. Patent 3,698,22 Missimer, D. J., 1973, U.S. Patent 3,768,273 Venkatarathnam, G., Senthil Kumar, P., Srinivasa Murthy, S., 23, Performance of a throttle cycle refrigerator with nitrogen hydrocarbon and argon hydrocarbon mixtures, International Cryogenic Engineering Conference, Sept. 22-26, 23, Anchorage, USA