Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Similar documents
Impact of indirect evaporative air cooler type on the performance of desiccant systems

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Effect of operating conditions on performance of silica gel-water air-fluidised desiccant cooler

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Heat Recovery Units. Heat Recovery 1

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Experimental study of air evaporative cooling process using microporous membranes

Performance of Heat Recovery Ventilation System with Ground Source Brine Heat Exchanger Pre- Heating System in the Context of nzeb

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Heat pump supplemental heating system for motor vehicles

Basic CFD model of heat pipe

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Performance of an Improved Household Refrigerator/Freezer

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

DEHUMIDIFICATION PERFORMANCE INVESTIGATION OF RUN-AROUND MEMBRANE ENERGY EXCHANGER SYSTEM

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

*Corresponding author;

Modelling the Performance of a Diffusion Absorption Refrigeration System

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

THE EFFECTS OF HUMIDITY, COMPRESSOR OPERATION TIME AND AMBIENT TEMPERATURE ON FROST FORMATION IN AN INDUSTRIAL FRIDGE *

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

EXPERIMENTAL PERFORMANCE ANALYSIS OF SOLAR AIR HEATER WITH THREE DIFFERENT MODIFICATIONS IN ABSORBER PLATE

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

A new method for preventing air-source heat pumps and refrigerators from frosting

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Compression of Fins pipe and simple Heat pipe Using CFD

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

VENTILATION SYSTEM WITH GROUND HEAT EXCHANGER

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

THE EFFECTS OF LEAKAGES IN ROOFS WITH VENTILATED AIR LAYERS - A CFD APPROACH. Zbynek Svoboda

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Induction heating with the ring effect for injection molding plates

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Performance Study of Triple Concentric Pipe Heat Exchanger

THE GATE COACH All Rights Reserved 28, Jia Sarai N.Delhi-16, ,-9998

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Heat Exchanger. The purpose may be either to remove heat from a fluid or to add heat to a fluid.

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Heat transfer and heating rate of food stuffs in commercial shop ovens

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Numerical study of heat pipe application in heat recovery systems

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Measurement of internal pressure and thermal performance in a closed-loop oscillating heat-pipe with check valves (CLOHP/CV)

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

Energy Efficiency of Air-to-Air Mini Heat Pump

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Heat pump and energy recovery systems

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

To investigate the surface properties for increasing efficiency of solar water heater

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Evaluation study of the performance of dual core energy recovery system for dwellings in the Arctic

Energetic vs. Exergetic Efficiency of Food Drying Via Forced Convection with and without Electrohydrodynamic Enhancement

Press Release. How can the efficiency of the dryer section be increased? Dryer Section All Paper Grades. Heimbach wherever paper is made.

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

R07. Answer any FIVE Questions All Questions carry equal marks *****

Transcription:

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Anna Pacak 1,*, Andrzej Jedlikowski 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of Science and Technology, Faculty of Environmental Engineering, Department of Air Conditioning, Heating, Gas Engineering and Air Protection, ul. Norwida 4/6, -373 Wrocław, Poland Abstract. In this study theoretical analysis of the heat and mass transfer in counter-flow recuperators used for energy recovery in air handling units (AHU) under sub-zero outdoor air temperature operating conditions is presented. The most probable variants of year-round heat exchanger operation performance, which characterized by existence of three active heat and mass transfer zones ( dry, wet, frost ), and effect of the latent heat of water vapour condensation on the realization of these variants was determined. It was established, that the frost tends to take place with increasing temperature effectiveness of the heat exchanger. Two main techniques of the frost prevention (preheating and bypassing the outdoor airflow) were described and analysed. The values of critical outdoor temperatures and outdoor-to-return airflow rate ratio were determined on the base of parametric frosting limits analysis conducted under different inlet return airflow conditions. The comparison of the heat recovery efficiency and additional energy consumption for the air treatment in the AHU is presented. 1 Introduction Nowadays the increased global energy consumption, many legal requirements and environmental protection, resulted in the rational management of energy resources. For this reasons, some actions are used to improve the effectiveness of existing and designed air conditioning and ventilation systems, well-known as the major consumers of electricity and heat [1]. For this reason, running costs of air conditioning system can be significantly reduced by implementing heat recovery. Heat recovery can be simply defined as the collection and re-use of waste heat arising from any technical or physical process that would otherwise be lost. This process can contribute to reduce the overall energy consumption and provide energy for other purposes [2]. The counter-flow heat exchanger can be used to perform this function in heat recovery technology. Unfortunately, counter-flow heat exchangers are very often exposed to freezing when a heat recovery system is used in cold climates. Additionally, the presence of a frost layer in the heat exchanger core decreases significantly the heat recovery system performance. For this reason, frosting limits, freezing processes and different frost-preventing techniques * Corresponding author: anna.pacak07@gmail.com The Authors, published by E Sciences. This is an open access article distributed under the terms of the Creative Commons Attribution License 4.0 (http://creativecommons.org/licenses/by/4.0/).

have been extensively studied in recent years. Nasr et al. [3] analysed two heat exchangers: with a permeable membrane and impermeable membrane under frosting conditions. Wang et al. [4] described a partial bypass technique. The authors concluded that this action facilitates the heat transfer augmentation. Freund et al. [5] considered a preheated air strategy to change the air temperature and prevent frost formation on the coil. Besides, the authors compared the performance of five frost control strategies used for improve energy recovery in ventilation systems. Nasr et al. [6] studied the performance of two cross-flow heat exchangers under different operating conditions. They presented the values of frosting limit and defrosting time ratio. Moreover the authors evaluated the effects of two defrosting methods on energy consumption of ventilation in three cold cities. They concluded, that the air preheating method performs better than the outdoor air bypassing method for frost prevention. Nevertheless, the problem of frost formation occurrence inside the counter-flow heat exchangers is still not solved and the most popular frost control techniques based on the outdoor air preheating or adjusting the outdoor-to-return airflow rate ratio are still facing challenges under extreme outdoor air temperature conditions. 2 Theoretical analysis In order to analyse the counter-flow heat exchanger performance it is necessary to establish the most probable variants of its year-round operating conditions. The most often analysed variant is the dry variant of heat exchange performance. In this case, the surfaces of both heat exchanger channels are dry. Such conditions occur usually in the summer. Although the dry heat transfer conditions always occur in the outdoor air channel, the processes in the exhaust air channel may run differently [1]. For instance, there is a possibility of combined sensible and latent heat transfer on the surface of the return air channel, especially under the cold climate conditions. It means that a part of the plate surface is wet due to water vapour condensation in the form of water film. In this case the latent heat of the water vapour condensation can be additionally recovered. That is why heat recovery effectiveness is higher comparing to the dry mode. On the other hand, water vapour condensation in the form of the frost layer, which can be observed under sub-zero ambient air temperature conditions, reduces the heat exchanger efficiency and increases the pressure drop on the return airflow side, because the passage may be blocked by frost. In this regard, a detailed analysis of coupled heat and mass transfer inside the counter-flow plate heat exchanger under frosting operating conditions was performed on the base of the original -NTU model [7]. Parametric numerical analyses were conducted to investigate heat and mass transfer in the counter-flow plate heat exchanger under sub-zero outdoor air temperature operating conditions. Three active heat and mass transfer areas were established in a counter-flow plate heat exchanger (see Fig. 1). The detail analysis of these particular heat and mass transfer zones creation revealed the most probable variants of year-round operating conditions of the counter-flow heat exchanger. The implementation of the particular variant of heat and mass transfer inside the return airflow channel of the counter-flow plate heat exchanger depends upon the relations of the temperatures in two decisive zones on the return airflow channel surface (in the cold zone and in the hot zone ) and the value of the inlet return airflow dew point temperature (see Fig. 1). In order to illustrate and explain clearly the processes occurring inside the heat exchanger channels, the numerical simulations were carried out under conditions with constant inlet outdoor and return airflows temperatures (t 1i= -20 C, t = 20 C) and variable inlet return airflow relative humidity (RH = (10 90)%). The results of these numerical investigations are presented in Figs. 2(a) and (b). 2

cold zone X 2 1.0 0.8 0.6 0.4 0.2 0.0 frost area transient area wet area Fig. 1. Variants of heat and mass transfer zones. dry area 0.0 0.2 0.4 0.6 0.8 1.0 X 1 hot zone a) b) F, F % 100 90 80 70 60 30 20 10 0 F=f(RHF ) t 1i = 20 C, t =+20 C, RH =(10...90)%, =0. 10 20 26.14 30 60 70 80 90 RH, % F, F % 100 90 80 70 60 30 20 10 0 F=f(RHF ) t 1i = 20 C, t =+20 C, RH =(10...90)%, =0.85 10 20 26.14 30 60 70 80 90 RH, % condensation area frost area wet area dry area Fig. 2. The percentage distribution of the heat and mass transfer areas inside the counter-flow plate heat exchanger channels determined for the inlet outdoor airflow temperature t1i = -20 C expressed as a function of the return air relative humidity (at the temperature effectiveness: a) η = 0., b) η = 0.85). The data presented in Figs. 2(a) and (b) confirm clearly the obvious fact, that a higher value of the inlet return airflow relative humidity results in a larger area of the plate surface on which water vapour condensation takes place. A dry zone at the entrance region dominates at low values of the return airflow relative humidity, but increasing the relative humidity RH reduces the dimension of this dry zone and at the values of RH > (53 90)% this zone disappears. It can be also seen, that in the case of the sub-zero inlet return airflow dew point temperature t 0 C, which corresponds to the relative humidity RH 26.15%, the water vapour condensation may occur only in the form of the frost layer and increasing the inlet relative humidity RH under such conditions reduces dry zone at the expense of increasing the frost zone. In the case of the above-zero dew point temperature of the return air t 0 C the water vapour condensation may be observed both in the form of the water film and in the form of the frost layer. It should be noted, that the frost zone reaches maximum at the value of inlet return airflow dew point temperature equalled to t 0 C (RH = 26.14%). At first sight, it could be surprising, that the dimension of the frost zone decreases with the increasing the inlet relative humidity of the return air higher 3

than 26.14%. The reason for this phenomenon can be explained by the analysis of the interfacial heat and mass transfer in the return airflow channel. The latent heat of water vapour condensation in the form of liquid film increases the local plate temperature in the return air channel. In turn, a higher value of the local plate temperature leads to a smaller air side temperature gradient at the gas-liquid interface and thus a lower value of the local sensible heat flux and, as a consequence, a smaller temperature drop of the return air in its flow direction. That is why the local plate temperature at the exit region of return airflow channel increases with increasing RH and thus a frost formation occurs on the more remote exit region of the plate surface in the return air channel [7]. So, an increase of inlet relative humidity of the return air in the range of value from 10% to 90% leads to an increase of the total water vapour condensation zone due to natural reduction of the dry zone. Increasing the inlet relative humidity of the return air under such conditions causes a decrease of the frost zone at the exit region due to preliminary expansion of the wet zone, although the total area of condensation is increasing. Moreover, it should be noted, that increasing the inlet relative humidity of the return in the range of RH = 10 90% causes an increase of the temperature effectiveness ε due to additional latent heat recovery at the expanse of the condensation zone expansion [7]. It can be seen in Fig. 2(a), that in the case of the minimum temperature effectiveness (ε = 0.) frost-free operation is observed only at the values of the return air relative humidity in the following ranges RH 10% and RH 70% but at maximum temperature effectiveness (ε = 0.85, see Fig. 2(b)) frost-free operation is completely impossible under analysed range of the return air relative humidity variations. The reason of such heat exchanger performance behaviour is that a higher temperature effectiveness results in a higher risk of frost formation at the expense of the temperature decrease of the outlet return airflow and plate surface in the cold zone (below water freezing point temperature). It should be noted, that the largest frost area occurs under conditions corresponding to the range of the return air relative humidity RH = 20 %. Unfortunately, this range corresponds to the normal (recommended) indoor air conditions in winter season. 3 Frost prevention methods There are two typical methods of frosting protection for counter-flow plate heat exchangers: preheating of intake (outdoor) air and bypassing the outdoor airflow. Preheating of ambient air is usually realized in electrical air heater to the safe values of the inlet outdoor air temperature (called as threshold temperature) defined as minimum intake air temperature at which the local temperature of the plate in the cold zone is above 0 C. In this case there is no any frost area on the heat exchanger s surface. The values of these temperatures are presented in Table 1. In the case of bypassing, the ratio of the outdoor airflow to exhausted airflow is reduced to the level at which frost layer is not observed on the plate surface of the return airflow channel. Threshold values of the outdoor airflow to returned ratio are presented in the Tab. 2 for different values of outdoor air temperature. 4

Table 1. The threshold values of the outdoor air temperature for return air temperature equal to t = 20 C and different temperature effectiveness of the counter-flow plate heat exchanger used for energy recovery from exhaust air (without bypassing G1/G2 = 1.0) [7]. Return air parameters relative humidity, RH, % dew point temperature, t, C Outdoor air parameters the threshold values of outdoor air temperature ttrshld, C, for different temperature effectiveness of counter-flow plate heat exchanger = 0. = 0.60 = 0.70 = 0.80 10-12.5-23.3-20.6-18.2-16.1 20-3.6-11.5-9.5-7.7-6.2 26.14 0.0-6.6-4.9-3.5-2.2 30 +1.9-7.6-5.8-4.3-3.0 +6.0-10.0-8.1-6.5-5.0 +9.3-12.5-10.5-8.7-7.1 60 +12.0-15.0-12.8-10.9-9.2 70 +14.4-17.5-15.1-13.1-11.2 80 +16.4-20.0-17.5-15.3-13.3 90 +18.3-22.5-19.9-17.5-15.4 Table 2. The threshold values of the outdoor airflow to returned ratio (G1/G2) at different values of outdoor air temperature for return air temperature equal to t = 20 C and different heat recovery efficiency of the counter-flow plate heat exchanger [7]. Return air parameters relative humidity, RH, % 60 Threshold values of Outdoor air temperature, o C the outdoor airflow to returned ratio (G1/G2) t1i t1i t1i t1i 1.00-10.0 0. -8.1 0.60-6.5 0.70-5.0 0.80 0.80-11.2 0.47-9.3 0.55-7.7 0.63-6.4 0.71 0.60-12.8 0.42-11.0 0.48-9.4 0.53-8.1 0.58 0. -16.6 0.34-13.9 0.37-11.6 0. -9.6 0.43 0.20-22.2 0.20-18.0 0.21-14.3 0.22-10.7 0.23 0.05-28.5 0.06-23.1 0.06-18.2 0.06-13.3 0.06 1.00-12.5 0. -10.5 0.60-8.7 0.70-7.1 0.80 0.80-13.8 0.46-11.8 0.55-10.1 0.63-8.7 0.70 0.60-15.7 0.41-13.8 0.47-12.0 0.53-10.7 0.57 0. -19.8 0.33-17.0 0.36-14.5 0.39-12.3 0.42 0.20-26.5 0.19-21.9 0.20-17.7 0.21-13.7 0.22 0.05-36.9 0.05-29.7 0.06-23.2 0.06-16.6 0.06 1.00-15.0 0. -12.8 0.60-10.9 0.70-9.2 0.80 0.80-16.4 0.46-14.3 0.54-12.4 0.62-10.9 0.70 0.60-18.5 0.41-16.4 0.47-14.6 0.52-13.1 0.56 0. -23.0 0.33-20.0 0.36-17.4 0.39-15.1 0.42 0.20-32.2 0.19-26.7 0.20-21.6 0.21-16.7 0.22 0.05-45.2 0.05-36.3 0.05-28.2 0.06-19.8 0.06 Temperature effectiveness and heat recovery efficiency for the purpose of frost protection analysis were defined as follows: 5

Temperature effectiveness of heat exchanger: t t t t 1o 1i 1i (1) Heat recovery efficiency: t t G c t t G c 1o 1i 1 p1 1i 2 p2 (2) From the above results, one can see that the values of heat recovery efficiency and threshold ratio of the outdoor airflow to exhausted drop with decreasing of the ambient air temperature. 4 Heat recovery efficiency analysis The comparison of the heat recovery efficiency and energy demand for the air treatment in the AHU with counter-flow plate heat exchanger under two examined frosting control strategies is presented in Fig. 3. a) b) Outdoor airflow Counter-flow heat exchanger Return airflow Outdoor airflow Face damper Bypass damper Return airflow Electric air heater Heating coil (electric) Counter-flow heat exchanger Heating coil (electric) Exhaust airflow Q, kw 45 35 30 25 20 15 10 5 0 0.60 Q=f(RH ) t 1i = 20 C, t =+20 C, RH =(10 90)% Supply airflow 0.60 0.60 0.62 0.60 0.66 0.69 0.73 0.76 0.80 10 20 26.14 30 60 70 80 90RH, % heating coil heat recovery unit electric air heater 45 35 30 25 20 15 10 Exhaust airflow Q, kw 5 0 Q=f(RH ) t 1i = 20 C, t =+20 C, RH =(10 90)% Supply airflow 0.60 0.60 0. 0.41 0.32 0.09 0.07 0.17 0.00 0.00 10 20 26.14 30 60 70 80 90RH, % heating coil heat recovery unit electric air heater Fig. 3. The comparison of the heat recovery and additional energy consumption for the air treatment in AHU with counter-flow plate heat exchanger expressed as a function of the return air relative humidity under different frosting control methods: (a) preheating (b) bypass damper system. The energy demand for the air treatment in the AHU was calculated for the value of the volumetric airflow rate equalled to 1 m/s. As one can see in Fig. 3, the performance of the heat exchanger equipped with the bypass dampers is characterized by very low heat recovery efficiency. In this regard, the AHU with the heat exchanger equipped with the bypass dampers needs to provide significantly more total power for the air treatment than in the case of the preheating. 6

To sum it up, it can be said that the performance of preheating technique is more efficient than and bypass dampers method of frosting protection. 5 Conclusions In this study a theoretical analysis of the heat and mass transfer in the counter-flow plate heat exchanger used for energy recovery in AHU under sub-zero outdoor air temperature operating conditions was presented. Two main techniques of the frost prevention (preheating and bypassing the outdoor airflow) were described and analysed on the base of the modified ε-ntu model. Unique aspects of the most probable variants of year-round heat exchanger operation performance, characterized by existence of three active heat and mass transfer areas ( dry, wet, frost ), were revealed. The results of the conducted investigations are summarized as follows: The formation and variability of different active heat and mass transfer zones strongly depends on the inlet return air relative humidity and inlet outdoor airflow temperature. The values of critical outdoor air temperatures and outdoor-to-return airflow rate ratio for frost-free operating conditions were determined at different inlet return airflow parameters (see Tab. 1 and 2). Inlet return airflow dew point temperature plays crucial role in the frosting limit. The most unfavourable operating conditions at sub-zero outdoor air temperature occur at the value of inlet return air dew point temperature t 2 i 0 C. In the case of inlet return air temperature t 2 i 20 C such conditions correspond to the relative humidity RH 26. 14%. Unfortunately, this air relative humidity corresponds to recommended indoor air conditions in winter season. The frost tends to take place with increasing temperature effectiveness ε (heat recovery efficiency ) of the heat exchanger. The obtained results may help to reduce the costs of the supply air treatment in AHU and increase the period of time when heat recovery units are effectively operated. However, more research is needed to find the best frost protection method, which allows for maximum heat recovery from return air. The conference participation was financed from the statutory funds of Faculty of Environmental Engineering, Wrocław University of Science and Technology from the project 01/0066/16. Nomenclature cp specific heat capacity, J/(kg K); F heat or heat and mass transfer surface area, m 2 ; Fo total surface area, m 2 ; F F F o 100% heat or heat and mass transfer surface area relates to total surface area, %; G moist air mass flow rate, kg/s; t temperature, C; L X channel of heat 1 exchanger in X1 direction, m; L X channel length of heat exchanger in X2 direction, m; Q heating 2 capacity, kw; X1 Cartesian coordinate in X1 direction (along outdoor airflow direction), m; X1 X1 LX 1 relative X1 coordinate, dimensionless; X2 Cartesian coordinate in opposite to X1 direction, m (along return airflow direction); X2 X2 LX relative X2 coordinate, dimensionless; 2 α convective heat transfer coefficient, W/(m 2 K); temperature effectiveness of heat exchanger, dimensionless; heat recovery efficiency, dimensionless. 7

Subscripts:1 outdoor airflow; 2 return airflow; referenced to dew point temperature; i inlet; o outlet; trshld threshold value of outdoor air temperature. NTU F Gc Number of Transfer Units; Acronyms: AHU Air Handling Unit; p RH Relative Humidity, %. References 1. S. Anisimov, A. Jedlikowski, M. Skrzycki, Proceedings of the Xth International Scientific Conference Quality of Indoor Air and Environment, 302 308, Volgograd-Budapest May 13-20.2012, 2. CARBON TRUST, Published in the United Kingdom, August 2011, accessed August 21, 2013: http://www.carbontrust.com/resources/guides/energy efficiency/heatrecovery, http://www.carbontrust.com/media/31715/ctg057_heat_recovery.pdf 3. M.R. Nasr, F. Fathieh, D. Kadylak, R. Huizing, R.W. Besant, C.J. Simonson, Exp. Thermal Fluid Sci. 77, 100 115 (2016) 4. C.-C. Wang, K.-Y. Chen, J.-S. Liaw, C.-Y. Tseng, Int. J. Heat Mass Transf. 55, 5367 5372 (2012) 5. S. Freund, S.A. Klein, D.T. Reindl, HVAC&R Res. J. 9, 493 8 (2003) 6. M.R. Nasr, M. Kassai, G. Ge, C.J. Simonson, Appl. Energy 151, 32 (2015) 7. A. Jedlikowski, S. Anisimov, J. Danielewicz, M. Karpuk, D. Pandelidis, Int. J. Heat Mass Transf. 108, 585 613 (2017) 8