seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Similar documents
Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

K.F. Fong *, C.K. Lee, T.T. Chow

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

Recent Advances in Energy, Environment and Economic Development

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Energy Performance of a Desiccant and Evaporative Cooling-assisted Airconditioning System under Various Climatic Conditions in China

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

A study of radiant cooling for a room with daytime application in tropical climate

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

Study on an Air-Side Heating Source Liquid Desiccant Regeneration Model

A STUDY ON THE APPLICABILITY OF THE TIME-DIVISION HOT-WATER SUPPLY HEATING FOR ONDOL - THE RADIANT FLOOR HEATING SYSTEM IN KOREA

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Available online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Energy and Buildings

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India

Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Adsorption refrigeration system using waste heat

COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Preliminary Findings on the Performance of a New Residential Solar Desiccant Air-Conditioner

A New Dedicated Outdoor Air System with Exhaust Air heat recovery

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Global Journal of Engineering Science and Research Management

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

EVALUATION OF A LIQUID DESICCANT AIR CONDITIONING SYSTEM WITH SOLAR THERMAL REGENERATION

EXPERIMENTAL INVESTIGATION OF HYBRID NANOFLUID ON THERMOSYPHON TYPE WICKLESS HEAT PIPE HEAT EXCHANGER THERMAL PERFORMANCE

Liquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements. White Paper

Solar Liquid Desiccant Air- Conditioning

Optimisation of cooling coil performance during operation stage for improved humidity control

Heat pump and energy recovery systems

SOLAR HEATING AND COOLING FOR THE SOLAR CITY GLEISDORF

The Potential for Solar Powered Desiccant Cooling

Performance of solar-assisted hybrid air-conditioning liquid desiccant system in Beirut

DESIGN AND SIMULATION OF A SOLAR ASSISTED DESICCANT-BASED AIR HANDLING UNIT

ANALYSIS OF DESICCANT COOLING SYSTEM

Characterization of Desiccant Wheels with Alternative Materials at Low. Regeneration Temperatures

Desiccant-enhanced evaporative (DEVap) cooler system introduction and its comparison with direct expansion (DX) system

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling

TRNSYS modeling of a novel ceiling panel designed to maintain space humidity in an office building

Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses

INSTITUTE FOR ENVIRONMENTAL RESEARCH & SUSTAINABLE DEVELOPMENT NATIONAL OBSERVATORY OF ATHENS (NOA)

Desiccant Dehumidification in Air Conditioning for a Large Commercial Building

System Modeling of Gas Engine Driven Heat Pump

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Experimental Study on Performance of Double pipe Length on Instantaneous Air Source Heat Pump Water Heater. Yin Shaoyou 1, a

A study of Transient Performance of A Cascade Heat Pump System

A Study on Power Consumption of Household Appliances for Life Conduct Activity of Single Household in University Town

Upward Evacuation Experiment for Estimating Evacuation Speed in Water Disaster

Transcription:

A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,* 1 Department of Architecture and Architectural Engineering, Graduate School of Seoul National University, Seoul 151-744, Republic of Korea 2 Department of Architecture and Architectural Engineering, College of Engineering, Seoul National University, Seoul 151-744, Republic of Korea ABSTRACT In hot and humid regions, cooling load and latent load should be removed together. Recently, liquid desiccant dehumidification is suggested as an efficient method of latent load removal. However, for continuous liquid desiccant dehumidification, liquid desiccant should be regenerated and regeneration heat is required. In this study, radiant panel system is suggested as a cooling method. And a method to utilize the generated heat, during the chilled water making for radiant cooling system, for the regeneration of liquid desiccant is suggested. For the evaluation of the suggested method, the energy demands were simulated and compared. As a result of comparison analysis between the energy demands of the system that uses suggested method and system that uses liquid desiccant dehumidifier and radiant panel separately, 85% of energy demand for regenerating liquid desiccant was reduced and 35% of energy demand for producing chilled water needed in cooling was reduced when using suggested method. Totally 63% of energy demand of the system was reduced. Method to utilize the generated heat, during the chilled water making for radiant cooling system, for the regeneration of liquid desiccant will be very useful at hot and humid region that need cooling and dehumidification. KEYWORDS Desiccant regeneration, Latent load, Liquid desiccant dehumidification, Radiant panel INTRODUCTION Radiant panel systems offer several advantages including a moderate set temperature, thermal comfort, and lower energy use compared with air handling unit (AHU) systems. However, using a radiant panel system risks producing condensation on the panels, and it is difficult to remove this moisture, especially during dominant cooling * Corresponding author email: snukkw@snu.ac.kr 862

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former study performed by Niu et al. (2002), the energy-saving potential of a chilled ceiling combined with desiccant cooling was investigated. A desiccant wheel was used in the study. The study found that a desiccant wheel can solve the problem of latent load removal, and heat exchange between intake air and exhaust air can recover some heat in order to reduce energy demand. Liquid desiccant dehumidification is one of the dehumidification methods used nowadays. Because it needs a relatively low temperature to regenerate the liquid desiccant then solid desiccant, a liquid desiccant dehumidifier has the potential to be suitably adapted to the buildings. A liquid desiccant dehumidifier is usually divided into dehumidification unit and regeneration unit. The process of dehumidifying air by the desiccant occurs in the dehumidification unit. The process of dehydrating the desiccant occurs in the regeneration unit. Regeneration heat is needed for this process. In a former study performed by Zhang et al. (2012), the methods for heat-pump-driven liquid desiccant dehumidification systems (HPLD) were introduced and analyzed by the optimization method. In the study, hot heat needed in regeneration and cool heat needed in dehumidification are used in the heat pump. By using the heat pump instead of the heater and chiller, the energy demand of the liquid desiccant dehumidifier for regenerating the liquid desiccant is decreased. When using a radiant panel in dominant cooling seasons, the hot heat in the returned chilled water is removed. In a former study conducted by Shin et al. (2012), hot heat from the returned chilled water was used to make domestic hot water. In this study, a liquid desiccant dehumidifier was used, and the hot heat from the returned chilled water was supplied as the regeneration heat for the liquid desiccant dehumidifier. In this study, a method to reduce the energy use of liquid desiccant dehumidifiers with a radiant panel system (RPLD) is suggested, and the applicability of the method is evaluated by analyzing the energy use of the method using the system. RESEARCH METHODS To suggest a method to reduce the energy demand of the RPLD, the load-removing processes of the RPLD and the system construction need to be understood. To evaluate the applicability of the method to reduce energy for RPLD, the system s total energy use should be known. Then, the energy demand of the RPLD using suggested method and the energy demand of the RPLD without using this method should be compared. 863

Load-removing processes of RPLD The load-removing process of the RPLD can be divided into three subprocesses: (1) the dehumidification process; (2) the regeneration process; and (3) the cooling process. The dehumidification process and regeneration process are the processes to remove the latent load and the cooling process is the process to remove cooling load. The dehumidification process includes the dehumidification unit of the liquid desiccant dehumidifier. During this process, inside air that should be treated will be passed through the scattered desiccant drops, and the moisture in the air will be absorbed by the desiccant. During this process, the lower the temperature of the desiccant, the higher the moisture removal rate (ASHRAE 2012). To decrease the temperature of the desiccant, cool heat is needed, and producing this cool heat demands energy. The regeneration process includes the regeneration unit of the liquid desiccant dehumidifier; this is the process that regenerates the desiccant, which is continuously used in the dehumidification process. The outside air (or exhaust air) will pass through the diluted desiccant and dehydrate the desiccant. To dehydrate the desiccant, regeneration heat is needed. This regeneration heat also demands energy to be produced. The cooling process occurs in the radiant panel. During this process, the radiant panel removes the cooling load in the zone with the chilled water. Energy is also needed to produce the chilled water. Method for reducing energy use of RPLD The RPLD consists of a radiant panel, a liquid desiccant dehumidifier, and an auxiliary heater. The radiant panel removes the cooling load, and the liquid desiccant dehumidifier removes the latent load. The auxiliary heater supplies the regeneration heat, which is needed to dehydrate the desiccant so that the desiccant can be used again. Figure 1 shows the construction and operating method (Method 1) of the RPLD and the energy use in each process. Method 2 reduces the energy demand of RPLD by using the method that supplies the regeneration heat with the generated heat during the chilled water making for radiant cooling system. In this system which uses Method 2, the regeneration process and cooling process are combined. Regeneration heat is supplied as hot water (approximately 45 55 C). Heat pump is used for cooling the returned chilled water from cooling process and remained generated heat, during the chilled water making for radiant cooling system, is supplied to regeneration heat medium. Supplying regeneration heat uses lower energy with this method then with auxiliary heater. 864

Figure 1. Schematic diagram of Method 1 Figure 2. Schematic diagram of Method 2 Methods 1 and 2 are almost the same, except that regeneration heat needed in the regeneration process is produced by the auxiliary heater in Method 1 and by heat pump in Method 2 (Table 1). Therefore, only the regeneration processes which have difference between two methods should be compared. 865

Table 1. Energy use of Methods 1 and 2 Method 1 Method 2 Dehumidification process Regeneration process Energy demand for producing chilled water used for chilling the desiccant to raise the efficiency of desiccant dehumidification (E D ) Energy demand to generate heat for liquid desiccant regenerating with auxiliary heating device (E R,1 ) Energy demand to generate heat for liquid desiccant regenerating with heat pump (E R,2 ) Cooling process Energy demand to produce chilled water by chiller (E C ) Comparative study To evaluate the applicability of Method 2, a comparative analysis should be performed. Because the dehumidification processes are same, the energy demands at dehumidification process of Methods 1 and 2 are same. Therefore, just the energy demands of Methods 1 and 2 at regeneration process and cooling process which is changed as the regeneration process is changeed should be compared. For a precise comparison, both methods should be simulated in the same condition. If they are in the same condition, the loads occurring in the zone are also the same. To evaluate the applicability, the energy demand of both methods should be calculated. In order to calculate this demand, the cooling loads and latent loads of the zone should be simulated. The conditions and loads are simulated by TRNSYS 17 (Klein et al. 2010). The simulation input data in this case are described in Table 2. Table 2. Simulation input data Location Seoul, Republic of Korea Period Three months (June 1 August 31) Area 72.9 m 2 U-value of North window: 1.4 W/m 2 K wall/window East/west/south/north wall: 0.254 W/m 2 K Ceiling (radiant cooling): 0.179 W/m 2 K Floor: 0.266 W/m 2 K Set temperature 26 C Set relative humidity 40% Schedule Monday Friday: workday (8:00 18:00: 100%/other: 0%) Saturday Sunday: weekend (0:00 24:00: 0%) Heat gain from people (sensible): 65 W/person Heat gain from people (latent): 55 W/person Heat gain from equipment: 230 W/each Heat gain from lighting: 5 W/m 2 866

The data from the former study performed by Zhang et al. (2012) were used in the calculations. The data include the temperature and humidity of the desiccant during each process and the coefficient of performance (COP) of the heat pump at each temperature of the heat sources. The ratio between the removed latent load and the regeneration heat was derived from the data. The regeneration heat was calculated using the ratio and the latent load from the simulation. After this calculation, the energy demand in the heat pump was calculated. Returned regeneration heat medium was used as the high temperature heat source for the heat pump, and the chilled water return from the radiant panel was used as the low temperature heat source for the heat pump. The heat pump COP that is suitable for the suggested method for the RPLD was selected. These data are described in Table 3. Table 3. Input data for energy demand calculation Input data Value Regeneration heat medium (high temperature heat source) ( C) 42.6 Chilled water return (low temperature heat source) ( C) 15.4 Ratio of regeneration heat to removed latent load 1.2 COP of heat pump 5.68 COP of chiller 3 RESULTS AND DISCUSSION The simulation data are shown in Figure 3. The figure shows the cooling load, latent load, and energy demand of the chiller to remove cooling load in Method 1; the energy demand of the chiller to remove latent load in Method 1; the energy demand of the auxiliary heater to remove latent load in Method 1; the energy demand of the chiller to remove cooling load in Method 2; the energy demand of the chiller to remove latent load in Method 2; and the energy demand of the heat pump to remove latent load in Method 2. The data were analyzed over 1 week for 3 months. The simulation shows that the cooling load is larger than the latent load every week in this case. It means that it is possible to supply regeneration heat with the generated heat, during the chilled water making for radiant cooling system. The energy demand of the chiller to remove latent load in Methods 1 and 2 are same. Method 1 uses the chiller to remove the hot heat in the returned chilled water and an auxiliary heater to supply regeneration heat. However, Method 2 uses the generated heat, during the chilled water making for radiant cooling system as regeneration heat. After operating heat pump, if more chilling is needed for chilled water, air source heat pump used in Method 1 is used. The results (Figure 3) show that the energy demand of Method 2 is lower than the energy demand of Method 1 overall. Table 4 shows the loads and energy demand of each process over 3 months. The 867

energy demand of the RPLD in the regeneration process decreased approximately by 85% when using Method 2. The energy demand in the cooling process (E C ) also decreased by approximately 35% using this method in this case. Overall, energy demand was reduced by 63% over 3 months. Figure 3. Zone loads and energy demand of Methods 1 and 2 Table 4. Sum of loads and energy demand over 3 months Energy demand Method 1 Method 2 Load Air source Auxiliary Air source Air source Heat Air source Chiller heater Chiller Chiller pump Chiller (dehumidification (regeneration (cooling (dehumidification (regeneration (cooling process) process) process) process) process) process) Cooling load 3,753,370 1,251,123 824,973 273,173 Latent load 1,293,021 86,201 1,551,625 86,201 Total 5,046,391 2,888,950 1,129,822 Note: Units are in kj. CONCLUSIONS AND IMPLICATIONS In this study, the applicability of a liquid desiccant dehumidifier with a radiant panel system was evaluated with a method for reducing the energy demand of an RPLD. For evaluation, the load-removing processes and construction of an RPLD were analyzed, and the standard and suggested methods for RPLD were compared. The conclusions of this study are as follows: 868

(1) The method to reduce the energy demand of the RPLD uses a heat pump instead of an auxiliary heater to replace the regeneration heat supply with the generated heat during the chilled water making for radiant cooling system. (2) When using the suggested method (Method 2), energy demand is reduced during two of three processes of liquid desiccant dehumidification. In the regeneration process, instead of supplying regeneration heat by a heater (Method 1), the generated heat, during the chilled water making for radiant cooling system, is supplied (Method 2). The energy demand in the regeneration process decreased by 85%. In the cooling process, hot heat in the chilled water return after cooling the zone is removed by an air source chiller (Method 1). However, when using Method 2, 35% of hot heat in returned chilled water is removed by the using additional water-to-water heat pump for regeneration heat supply. Energy demand can be reduced by 35% in the cooling process. Overall, when using Method 2, energy demand of the RPLD can be reduced by approximately 63%. (3) This study shows that by using the suggested method for an RPLD, the latent load problem when using a radiant panel can be solved. This method can also reduce energy demand in the regeneration and cooling process. These results will be useful for buildings in regions with hot, humid climates. ACKNOWLEDGMENTS This work was supported by a grant from the National Research Foundation of Korea (NRF) funded by the Korean government (MEST) (No. 2014-050381). REFERENCES ASHRAE. 2012. Handbook HVAC Systems and Equipment. S24. Desiccant dehumidification and pressure drying equipment. Luo Y., Yang H., Lu L., Qi R. 2014. A review of the mathematical models for predicting the heat and mass transfer process in the liquid desiccant dehumidifier. Renewable and Sustainable Energy Reviews, Vol.31, pp.587-599 Niu J.L., Zhang L.Z., Zuo H.G. 2002. Energy saving potential of chilled-ceiling combined with desiccant cooling in hot and humid climates. Energy and Buildings, Vol.34(5), pp.487-495 Sanjeev Jain, P.K. Bansal. 2007. Performance analysis of liquid desiccant dehumidification systems. International Journal of Refrigeration, Vol.30(5), pp.861-872 Shin D.U., Lee S.J., Joe G.S., Yeo M.S., Kim K.W. 2012. A study on an energy balancing system and control strategy. The Second International Conference on Building Energy and Environment 2012, Zhang T., Liu X., Jiang Y. 2012. Performance optimization of heat pump driven liquid desiccant dehumidification systems. Energy and Buildings, Vol.52, pp.132-144 Zhang L., Hihara E., Saikawa M. 2012. Combination of air-source heat pumps with liquid desiccant dehumidification of air. Energy Conservation and Management, Vol.57, pp.107-116 869