Service Step by Step Trouble-Shooting Check-List

Similar documents
Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

C13-Series Engineering Guide

VertiCool Aurora Engineering Guide

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

APPLICATION DATA SHEET

M2 Series Startup Form

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

Series 6, Vertical Floor-Mount Units

M2 Series Startup Form

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

PACKAGE AIR CONDITIONER

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

Liebert InteleCool Warranty Inspection Check Sheet

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Air Cooled Condenser Installation and Operating Instructions

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 6, Vertical Floor-Mount Units

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

VariCool VAV Engineering Guide

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

Liebert DataMate (1-3 Ton) Warranty Inspection Check Sheet

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

RCM Refrigerant Module

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

MACH N-407 Heat Pump Air-Cooled Chiller

SA Series Startup Form

R Series Cooling Modules

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

WineZone Ceiling Mount Ductless Split 15

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Series 11, Ceiling Units

40 RM/RMS Packaged Air-Handling Units

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

Series 11, Ceiling Units

PDF Created with deskpdf PDF Writer - Trial ::

DEALER SERVICE BULLETIN

DESIGN STANDARDS SECTION 15600

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

MODEL URS-1: FACTORY RETROFIT PROGRAM

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

Liebert CRV Warranty Inspection Check Sheet

R Series Cooling Modules

CoolSpot Engineering Guide

A/C-HEATER SYSTEM - MANUAL

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

START UP FORM PACKET

Otherwise, you can continue reading the file on the following pages.

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Advance Release September 2009

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Air Cooled Packaged Systems AIRAH Back to Basics

Installation, Operating & Maintenance Instructions. Horizontal Models: LH & HL

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

SA Series Start up Report

R Series Cooling Manual

Residential Piping and Long Line Guideline

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Installation, Operating & Maintenance Instructions. Air Handler Models: AH & AV

Experienced Worker Assessment Blueprint HVAC - Heating, Ventilation and Air Conditioning

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

NOTE: Special care should be given to those areas where these symbols appear.

Preventative Maintenance Tables

Installation, Operation, and Maintenance Information

50 Hz. Air - Cooled Split System. Air Conditioner with Scroll Compressors R22 / R407C COOLING HEAT PUMP. Products that perform...

Installation, Start-Up and Service Instructions

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

INSTALLATION INSTRUCTIONS

T-Series Air Conditioner T20 Model

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

INSTALLATION INSTRUCTIONS

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

CxA to Answer this Section

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified

Chapter-8 Capacity Control of Refrigeration Systems

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Warm Case Troubleshooting Guide 9/18/2014

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Types SDRA and SDRA-RG RENEWAL PARTS IDENTIFICATION

Liebert Challenger 3000/Liebert Challenger ITR with Liebert icom Control. Operation & Maintenance Manual - 50 & 60Hz

Installation, Start-Up and Service Instructions

Transcription:

WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#: Model#: Service Company: Name: Phone#: Problem Reported: Does Problem occur on other units? MAINTENACE AGREEMENT TERMS Is there a periodic maintenance contract?. How often is the periodic maintenance performed on the units? On what date was the last maintenance performed: PIPING INSTALLATION (Maximum equivalent line is 200 feet) Contact Data Aire Engineering Department before installing equipment on pipe runs exceeding 200 feet. Are the refrigerant pipe lines pitched in the direction of refrigerant flow?. A minimum of ½ slope for every ten feet of horizontal line is required for proper oil return. Are there traps on the vertical riser?. Traps must be installed on the refrigerant hot gas line at the bottom of the riser and every 15-20 feet in height. An inverted trap needs to be installed at the top of the refrigerant hot gas line and at the condenser and should equal the height of the condenser coil. Total height of vertical riser? Number of traps? Total horizontal run? Number of elbows? Total pipe run in equivalent feet? Is the liquid line insulated? Heat gain across the liquid line may cause the refrigerant to flash in the liquid line upstream of the metering device Is there a discharge check valve installed on the discharge line?. The check valve is required to prevent the unit from having a liquid migration on the high side of the system on cold days during the off-cycle. Note: New units should have factory-installed check valves in the unit. Was dry nitrogen flowing through the system during brazing?. Purging is required to eliminate carbon deposit build-up on the inside of the joints. Carbon could contaminate the refrigerant and restrict the metering device. Was silver/phosphorus/copper alloy with 5 to15% silver used for brazing?

REFRIGERANT LINE SET(Maximum equivalent line is 200 feet) Contact Data Aire Engineering Department before installing equipment on pipe runs exceeding 200 feet. Pipe size for the liquid line? Pipe size for the discharge line? Pipe size for the suction line? PRESSURE TEST AND LEAK TEST During leak testing, were the valves in the system open?. All valves need to be open to pressure test the full system. Did the system hold 150 PSIG over 24 hours? Where in the system are you reading vacuum level (microns)?. Read Micron levels as far away from the vacuum pump as possible, in the refrigerant system if possible. During vacuum, were the valves in the system open?. All valves need to be open to eliminate noncontaminants in the refrigeration system. After the triple evacuation, did the system hold 500 microns for at least half an hour? If not, inspect for leaks and repeat vacuum procedure. ELECTRICAL Is there any visual signs of arcing? Were copper conductors used? What is the total length of the copper conductors supplied to the unit? Size of gauge? How is the unit grounded? Is it grounded per applicable code regulations and guidelines? Are all the factory and field supplied electrical connections tight?. Does the electrical supply corresponds with rating on the unit s nameplate? What is the test voltage: A-B: A-C: B-C: Was the crankcase heater energized 12hrs before start-up?

AIR FLOW Are the filters installed and clean? Is the ductwork connected and sealed to prevent air loss?. If the ducts are warmer than the air traveling through them there will be a transfer of heat. If there is any duct leakage latent heat (moisture) and sensible heat will be added as well. Are all raised floor tiles and discharge grills (perforated panels) installed and adjusted for optimum air movement? Height of raised floor? Do the units share supply or return ducts?. If yes, are mechanical back draft dampers or AirSeal being utilized?. When the unit is in standby or in the off cycle, is the return air warmer than the saturated evaporator coil temp?. If the return air is colder than the evaporator coil temp (saturation) than the superheated refrigerant can condense in the evaporator coil. This can then flow down and accumulate into the compressor, wash out the oil, and result in damaging the compressor because of a flooded start. INSIDE UNIT Are the units in the conditioned space? What are the clearances around the unit? Front inches Back inches Right side inches Left side inches Does the unit have vibration isolators? CONDENSER Is the condenser free of obstruction? What is the clearance above and around the condenser? What is the ambient temperature? F Does it have a fan speed control? Does it have a flooded system? CONDENSER COIL Is the condenser coil clean? Is there any visual oil stains?

CONDENSER FAN MOTOR (WITH POWER OFF) Do the motor blades spin freely? Is there any damages on the blades? Motor HP: F.L.A.: Voltage: CONDENSER FAN MOTOR (WITH POWER ON) Is there any vibration? Are there any abnormal noises? Entering Air: F Leaving Air: F Microfarads readings on the capacitor? Running Amps: Rotation: Clockwise Counter Clockwise Distribution of Air: Up down Fan Starting Pressure: R.P.M.: Voltage: WATER COOLED CONDENSER What is the design water temperature for the coil? Actual water loop temp? What is the design water flow for the coil? Actual water flow? What is the design water pressure drop across the coil? Actual water pressure drop? What is the design water temperature drop across the coil? Actual water temp drop across the coil? INSIDE BLOWER MOTOR (WITH POWER OFF) Are the drive and driven blower pulleys aligned? Are the set screws on the pulleys tight? Are the walls of the pulley smooth and free of debris? Is motor base secure? Is the belt tension good? Record pulley and belt sizes. Are the blower wheel clean and clear of debris? Does the blower wheel spin freely?

INSIDE BLOWER MOTOR (WITH POWER OFF) Are the wheel bearings lubricated? Is there any damages on the blades? Motor KW: Name Plate Voltage: Name Plate F.L.A: STANDING PRESSURES (WITH POWER Off TO THE COMPRESSOR) Discharge Pressure: PSI Suction Pressure: PSI Suction Saturated temp: F Return air Temp: F Return air temp needs to be higher than evaporator temp (Saturation) to prevent the superheated gas to condense in the evaporator and prevent from compressor failure. Liquid line pressure: PSI Is the crankcase heater on?. (Note: A crankcase heater's sole purpose is to prevent refrigerant migration and mixing with crankcase oil when the unit is off, and to prevent condensation of refrigerant in the crankcase of a compressor. The crankcase heater keeps refrigerant at a temperature higher than the coldest part of the system). INSIDE BLOWER MOTOR (WITH POWER ON) Is there any vibration? Are there any abnormal noises? Operating Amps: L1 L2 L3 Discharge air temperature?. Return air temperature?. Return air temp needs to be above design room temp before starting compressor. If the return air temp is not above design room temp please turn unit off and create a heat load to prevent compressor failure. (Note: Heat load is required to get heated air across the evaporator coil to boil liquid refrigerant into a superheated gas and prevent liquid from entering the compressor). Return relative humidity?. Delta-T across the evaporator?. What is the total external static pressure?. Total external static pressure should not go over.9 wg How has the airflow been adjusted to achieve design airflow?. Airflow needs to be adjusted before starting up the compressor. If air flow is not adjusted it can result in damaging the compressor.

COMPRESSOR - (Note- When checking operating conditions allow the unit to run for 10 minutes before recording any readings. This will allow the refrigeration to stabilize, the coil to get wet, and the room conditions to stabilize). Ambient Temperature: F Refrigerant Type: # of pounds/oz. Compressor oil Level (sight-glass) before start-up % Compressor oil condition during the first 7 minutes of start-up Clear Foam Discharge pressure leaving the compressor: PSI. = Discharge Saturation Temp? F Discharge line Temp leaving the compressor: F Liquid Line Pressure before it enters the metering device PSIG = Liquid Saturation Temp? F Liquid Line Temperature before it enters the metering device F Sub-cooling F Suction Pressure: PSIG, Suction line temperature: F Superheat: F Delta-T across liquid line filter dryer F Hot Gas Bypass? Y/N. What s the superheat on the Hot Gas Bypass adjusted too? F Crankcase Temperature F Return Air Temperature F Return air temp needs to be above design set point. If the return air temp is lower than design room temp or the same as the discharge air temp please turn unit off and create a heat load to prevent compressor failure. If you cannot get a heat load consult with engineering. A heater and hot gas by pass might be needed. (Note: Heat load is required to get heated air across the evaporator coil to boil liquid refrigerant into a superheated gas and prevent liquid from entering the compressor). Supply Air Temperature F Delta-T across evaporator coil F If you have low delta-t across the evaporator than it is not absorbing any heat and liquid could be flooding the compressor. Return relative humidity?. If the return temp is at 68 F or below and the relative humidity at 40% or below, compressor damage can result. Return Air Humidity % VFD Operating Amps: L1 L2 L3 Fixed Speed Compressor Operating Amps: L1 L2 L3 Discharge pressure entering the condenser? PSI = Discharge Saturation Temp? F Discharge line Temp entering the condenser? F Liquid pressure leaving the condenser? PSI = Liquid Saturation Temp? F Liquid line temp leaving the condenser? F What is the liquid line temperature drop on the liquid line leaving the condenser to the entering of the metering device? (Answer only if the condenser sits below the evaporator coil) A good way to check for flash gas is to compare the temperature of the liquid line exiting the condenser and the liquid line temperature entering the metering device. A huge temperature drop can indicate the presence of flash gas. What is the saturated temperature drop on the discharge line from the inside unit to the condenser unit? Design pipe size for a pressure drop equivalent to a 2 F saturation temperature drop. What is the saturated temperature drop on the liquid line from the inside unit to the condenser unit? Design pipe size for a pressure drop equivalent to a 2 F saturation temperature drop. Are there any vibrations? Is there any abnormal noises? Compressor Unloader: Yes or No Discharge Pressure (unloaded) PSIG Suction Temperature (unloaded) F Amps (unloaded) L1 L2 L3 Liquid Line Sight glass Color? What color is the EEV sight glass?

Receiver sight glass refrigerant level % Was oil added to the system?. If yes, how many ounces? Oz. Does the crankcase heater turn on when the compressor shuts off?. (Note: A crankcase heater's sole purpose is to prevent refrigerant migration and mixing with crankcase oil when the unit is off, and to prevent condensation of refrigerant in the crankcase of a compressor. The crankcase heater keeps refrigerant at a temperature higher than the coldest part of the system). Run Cycle (How long does the unit stay on vs. off cycle) EVAPOPRATOR COIL Is the evaporator coil clean? Is there any visual oil stains? Is the drain pan clean? Does the water on the drain pan drain freely?. If the water does not drain quickly enough, it can cause high humidity issues and water damage. EEV VALVE SETTINGS Regulations: A Superheat Set point: F Valve position at start-up: % Valve opened in stand-by: Valve position in stand-by: % Start-up delay after defrost: Min Pre-position Time s PID Proport. Gain PID Integral Time s PID Derivative Time = s Low SH Protect Threshold: F Low SH Protect integral time: s MOP protection threshold: F MOP protection integral time: F Liquid level Percentage: % Regulations: B Superheat Set point: F Valve position at start-up: % Valve opened in stand-by: Valve position in stand-by: % Start-up delay after defrost: Min Pre-position Time s PID Proport. Gain PID Integral Time s PID Derivative Time = s Low SH Protect Threshold: F Low SH Protect integral time: s MOP protection threshold: F MOP protection integral time: F Liquid level Percentage: %

TXV Is the sensing bulb located on the horizontal suction line leaving the evaporator coil? Is the sensing bulb secured to the suction line? Does the sensing bulb sit in the correct angel of the suction line? Does the super heat change to a change in sensing bulb temperature? Is the sensing bulb insulated? Can the superheat be set by adjusting the stem? CHILLED WATER: Water in Temp: Water out Temp: Delta T: HUMIDIFIER Is the humidifier cylinder clean? Does the humidifier operate? Steam Generator: Yes or No Operating Amps: L1 L2 L3 RE-HEAT COILS Type: Electric Hot Water Hot Gas Steam (For Electric Reheat) Operating Amps: L1 L2 L3 Do the re-heat coils operate? MENU B SETPOINT: Temp Set point: F Temp Dead Band: F Stage to Stage: F

EC FAN SETTINGS CW Mode: CW Speed: DX Mode: DX Speed: ALARM HISTORY Alarm Description Date Time ZONE MASTER Is the zone master control being utilized? How many units are being controlled by the zone master? Number of units that are ON at the same time? When are they schedule to rotate (Schedule)?