A Guide for Applicants and Lighting Designers

Similar documents
Advanced Lighting For Office

Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

Lighting Control Strategies. to meet code requirements save energy and improve building performance

High Performance Lighting. Terry Egnor Senior Consultant NBI

Reduce lighting energy costs with controls

Applied Lighting Controls

Advances in Non-Residential Lighting Technologies

2017 Commercial & Industrial Program C&I Lighting Prescriptive Rebate Application

LIGHTING CONTROLS

miniz Quick Start Guide

Dissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard & 2013

TITLE 24 ICONOGRAPHY. Iconography System

Design and Commissioning of Lighting Control Systems. Rick Miller, PE, LC, LEED AP RNM Engineering, Inc. October 18, 2012

Dimming Ballast + Controls and CALCTP Bonus. New Product Overview

2017 Lighting Incentive

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2012

WSA120: New Energy Codes and Lighting Controls

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Lighting Design Criteria: Codes and Standards

Lighting Proposal Memo. Lighting Proposal. Angela Nudy Lighting/Electrical Dr. Mistrick Lighting Proposal Memo 1

California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings

ASHRAE October 18, 2013

The Bahen Centre for Information Technology. Meeting Room Lighting Redesign. Introduction. University of Toronto ~ Toronto, Ontario, Canada

CA TITLE 24 QUICK SOLUTIONS GUIDE FOR

Are LED s ready for Prime Time?

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

PSO Business Rebates Retrofit Lighting Technical Requirements

LED Retrofit Lighting Rebate 2017 Rebate Application

13-15, 2001 USING LIGHTING SIMULATION TO ASSESS THE PERFORMANCE OF AND INDIRECT OFFICE LIGHTING SYSTEMS IN DYNAMIC WORKPLACES

NRG SYSTEMS, HINESBURG, VT

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

Code Review TITLE PRESENTED BY POURIA NIKNAM

Lighting Application Guide for K-12 Classrooms

Energy Codes. Connected Lighting simplified by Eaton. design and application guide

ANSI/ASHRAE/IES

Advanced Lighting Control for High Building Performance

Lighting Existing Conditions and Design Criteria Report

Daylighting Control Design and Application Guide

Lord Stirling Community School

ANSI/ASHRAE/IES

Surface Materials. Surface Material Reflectance. Acoustic Ceiling 80% Tile. Painted Gypsum 75% Wall Board. Vinyl Composition 32% Tile

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

Incentive & Measure Specifications

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

Aesthetic, energyefficient. control solutions for hospitality facilities QUICK GUIDE TO LIGHTING CONTROL FOR HOTELS

Gathering Space. Function and Orientation. Space Characteristics Gregory Wolfe 2004 Senior Thesis Lighting / Electrical

Supporting the Requirements of EPAct 2005 Tax Deductions

CL001 >400 Watt lamp basecase, up to 600 Watt replacement fixture $95.00 Fixture

Eligible Prescriptive Measures List:

Indoor Controls. SpaceWise SWZG2. Wireless technology

Pacific Gas and Electric Company Energy Efficiency Rebates for Your Business. Lighting Rebate Catalog Saving energy for a brighter future

PRESCRIPTIVE APPROACH

2018 Lighting New Construction Rebate Instructions. City of Buffalo

LED Retrofit Lighting Rebate 2018 Rebate Application

Related Sections: TBD. Effective Date: January 1, 2016

DALI Dimming Controls

MANDATORY MEASURES MANDATORY LIGHTING CONTROLS (a) Area Controls: Manual controls that control lighting in each area separately

Energy Solutions LED Accelerator Program PRODUCT QUALIFICATION REQUIREMENTS 2015

Jennifer Mers. Rio Hondo Library and Learning Resource Center. Executive Summary. General Building. Lighting/Electrical Option

New LED Product Offerings

F series. echoflex. Slim Line Dimming Controller. Product Overview ER1S-FC

Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ Tel

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG-1-A

Colorado November 1, Take advantage of. LED rebates. and start saving

Good-Better-Best LED Retrofit Guide

Waste not, want not. As part of our efforts to ensure we practice sustainability in our business, we ve printed this brochure on recycled paper.

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

Code Compliance Commercial Application Guide

Time Warner Center at Columbus Circle, the home of Related s offices. Credit: Green Light New York

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Lighting Controls. Energy-Saving Solutions For Efficient Buildings

Overview. The Reading Room

Center for Health Research and Rural Advocacy

Thesis Proposal. Brian Regan The Virginia Historical Society Building West Wing Addition RICHMOND, VIRGINIA

Duke Tower Main Entrance Lobby Overview

Oregon Non-Residential Building Energy Code

COMMERCIAL LIGHTING DESIGN GUIDE

Lindsey Beane. Executive Summary

2018 Lighting Retrofit Rebate Instructions. City of Arlington

2018 Business Lighting Rebate Application

INSPECTION REQUIREMENTS: ENERGY CODE LIGHTING & ELECTRICAL NON-RESIDENTIAL

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 26 ELECTRICAL

Lighting Depth: Courtyard Franklin Care Center, Franklin Lakes, NJ

Technical Report One

IECC. nlight Applications Guide.

The AstroPower Headquarters Newark, Delaware

INDUSTRIAL & WAREHOUSE LIGHTING Application Guide

InvestSmart Business Energy Upgrades Lighting Equipment Catalog 01/01/2018

Equipment Efficiency Guide

2017 Lighting New Construction Rebate Instructions. City of Brownton

C ontrolsystems Themostadv ingenious a n cedsensor-basedcontrols.now integratedintoourmostpopularfixtures.

Advances in Lighting Controls and the Impact of ASHRAE Requirements. Rich Rattray, LC OSRAM SYLVANIA

Applied Lighting Controls

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM

Lighting Existing Conditions and Design Criteria Report

SECTION LIGHTING CONTROL DEVICES EATON S LIGHTING SYSTEMS (FORMERLY COOPER CONTROLS) VACANCY/OCCUPANCY SENSORS

Schematic Design Proposal Presentation

HARRY RANSOM HUMANITIES RESEARCH CENTER

Lighting Rebates Rebate Application

Transcription:

Sustainable Office Design Program: A Guide for Applicants and Lighting Designers Inside this Guide: Introduction... 2 Organize Your Space... 3 Select Lighting Solutions... 4 Select Controls... 5 Open Offices... 6 Private Offices... 7 Meeting Rooms... 8 Reception Areas... 9 Action Plan...10 Enroll Today...11 Energize Connecticut programs funded by a charge on customer energy bills.

Introduction Benefits to Building Owners Higher energy and operational savings Contributes to LEED and ENERGY STAR certification Shows leadership in sustainability goals Higher tenant productivity and satisfaction Higher building occupancy and rental rates $1/sf incentive* Benefits to Lighting Designers The Sustainable Office Design Lighting Program offers incentives to building owners and lighting designers for well-planned, innovative and controls-rich lighting installations. Sustainable Office Design-qualifying lighting designs use sophisticated lighting fixtures and controls and follow an efficient, and space-optimized lighting plan. Sustainable Office Design is different than other programs because it does not dictate specific products or technologies. Lighting designs must meet a target performance level, but the program does not dictate the means of doing so. This guide outlines best practices for creating lighting solutions that emphasize efficiency and comfort and that qualify for financial incentives through the Energize Connecticut initiative. Helps prevent value engineering of efficient lighting and control systems Supports creativity in design Allows for flexibility in product options Provides competitive advantage Financial incentive up to 20 percent of total incentive amount What to Expect Step 1: Organize your area by space types. Step 2: Select fixtures and layouts that deliver appropriate lighting and meet the lighting power density guidelines. Step 3: Select controls that meet minimum performance requirements. Step 4: Compare design with requirements and complete an application form. * Capped at $200,000 per project. 2

Step 1 - Organize Your Space Organize the leased area into commonly used office space types before selecting lighting fixtures and controls. Assign specific lighting design patterns to common spaces, such as open offices areas, private offices, meeting and conference rooms, reception areas, and other spaces found within the typical business office. Total office space must be at least 7,500 sf or larger, up to 200,000 sf. Open office space must occupy more than 40 percent of the floor area of a Sustainable Office Design-qualifying installation. Both interior open offices and day-lit open offices (perimeter exposure or below skylights) plans qualify. Large (greater than 300 sf) private offices offer control options that differ from the typical small office. Each size range has its own recommended lighting design patterns and lighting control requirements. SPACE USE LEGEND Conference or Training Copy/Mail Room Corridors Employee Break Room Open Office Open Office - DL Zone Private Office Reception/Lobby Storage The six space types that make up the majority of space use in the modern office offer the greatest energy-saving opportunities. Open Office Daylit Zone Open Office Corridors Private Offices <300sf Conference or Training >300sf Conference and Training Rooms <300sf 3

Step 2 - Select Lighting Solutions Select lighting fixtures and layouts that deliver appropriate lighting levels and quality to the space while meeting the lighting power density (LPD) target for that space type. Advances in lighting technology make low-lighting power density designs possible. Private offices placed on the perimeter should have daylight dimming capability Solid State Lighting, using LEDs as a light source, is now found in almost every fixture type from every major manufacturer. Solid State Lighting creates visible light with reduced heat generation and less energy dissipation than fluorescent lighting. Lighting with full dimming capability has a low incremental cost. > Areas within 15 ft. of windows should have daylighting controls. > Recessed luminaires are most appropriate for open plan spaces with ceilings 8 4 or lower, since they do not illuminate the ceilings and have a greater potential for high angle glare. Suspended luminaires provide better quality for open plan ceiling heights above 8 4. > Suspended linear fixtures are available with both high-efficiency fluorescent and LED sources. DESIGN LIGHTING FOR EACH SPACE TYPE AT OR BELOW THE FOLLOWING LPD GUIDELINES Space Type LPD (W/sf) Foot-candles (horizontal) Notes Open Offices 0.6 30-50 fc Shared workspace with open desks or less than 48 high cubical partitions; maximum 2,500 sf per control area Private Offices 0.7 30-50 fc Private, enclosed office with one primary occupant Small Meeting Rooms 0.9 20-55 fc Work room with area <300 sf Conference Rooms 1.1 20-55 fc Work room with area >300 sf and multipurpose lighting Corridors 0.5 10-20 fc Lobbies and Reception Areas 1.0 5-20 fc Copy, File and Work Rooms 0.7 20-50 fc Foot-candle illumination levels based on information gathered from the IES The Lighting Handbook 10 th Edition 4

Steps 3 & 4 - Select Controls Select control components and technologies that meet the minimum performance requirements for each space type. OFFICE SPACE TYPE Open Office Open Office Daylit Zone Private Offices (<300sf) Large Private Offices (>300sf) Conference and Training Rooms (<300sf) Conference and Training Rooms (>300sf) Corridors Copy, File and Work Rooms Reception Areas, Lobbies and Waiting Rooms Store Rooms Employee Break Rooms SOD CONTROL CATEGORY * A B C D E F G H K O P * Notes on space-specific guidelines, and an explanation of what each control category consists of, will follow on later pages. Digital control products operating on wireless networks extend room-lighting controls to the desktop and conference table. Pair space types with controls Match a lighting control category to each assigned space, such as open offices areas, private offices, meeting and conference rooms, and other spaces found in a typical business office. Use the best control technologies In order to take advantage of Lighting Controls, sensors are used. They can be placed in the space, or they can be purchased along with the fixture and on each one. Individual fixtures can be tuned initially upon installation, and they can be controlled going forward. Fixtures and sensors can be meshed together as a platform either wired or wireless. These three key approaches will impact how easy integration of additional control strategies is for the future of your space. Digital lighting controls enable remote programming, provide for energy reporting and diagnostics, and allow for easy integration of additional control strategies in the future. Occupancy sensors automatically turn off lights in an unoccupied space. Auto on/off activated, wall-mounted occupancy sensors with dual relays provide control of two lighting circuits or two lighting levels. Compare the as-designed lighting power density and as-designed number of control points with Sustainable Office Design lighting incentive requirements. If satisfied, complete an application form. 5

Open Offices Use a lighting power density target of 0.6 W/sf for open offices. Lighting in open office spaces should maximize daylight, provide adequate lighting for user tasks and collaboration, and increase sensitivity of control to personal preferences, while maximizing quality and minimizing energy consumption. D B A. Indirect/direct suspended fixtures or high-efficiency recessed fixtures provide the ambient illumination in work areas. C A B. Fixtures specified with continuous dimming down to 10 percent or lower of full output are used for daylight harvesting. These fixtures are capable of reducing electric light in response to the availability of natural light and are controlled by photosensors. Open offices have a target average horizontal lighting level of 30-35 foot-candles (fc), with 45-75 fc on the work surfaces. C. Fixtures in hallways provide ambient lighting in circulation zones. D. Task lights supplement the ambient lighting for any employee who simply desires more light. SOD lighting plans go beyond 2012 IECC standards Use Control Category A in interior open offices Use Control Category B in daylit open offices Keep office cubicle partitions no higher than 48 inches to allow for greater efficiency and more comfortable light levels. Lighting in daylit zones controlled separately from general lighting, with stepped or continuous dimming to minimum 35 percentreduction. Automated shut-off from time clock or building management control after hours. Occupancy sensors not required. Dual technology-zoned Automated shut-off time clock or building management Dual Technology Zoned Photosensors for 0-10 VDC electronic dimming in daylit zones to minimum 20 percent. Automated shut-off from time Products Major manufacturers provide design guidance for the use of automated controls, including line voltage, low voltage, and wired and wireless digital controls. Integrated digital control systems take advantage of new digital (LED) lighting and networked-ready lighting products. Conventional lighting can be controlled with stand-alone sensors (with necessary control packs). Examples include, but are not limited to, SensorSwitch CM-ADC-DZ series with CM-ADC series photosensors, Wattstopper DT-300/DT-305 series with LightSaver LS-301 series photosensors, and Cooper OAC-DT-1000-MV series with Greengate DLC-PD-DIM series photosensors. 6

Private Offices Use an lighting power density target of 0.7 W/sf for private offices. Private office lighting needs to balance the brightness of the room surfaces as well as provide multi-level illumination. This variation accommodates personal needs and increases energy savings. Vacancy sensors are a minimum control strategy. Private offices with high ceilings and windows can use suspended indirect/direct luminaires that illuminate the ceilings and walls as well as the desk area, providing a visually balanced and comfortable workplace. Adjustable desk lights can be used to supplement illumination for tasks and give users personal control and increased satisfaction. A SOD lighting plans go beyond 2012 IECC standards Use Control Category C in small private offices Use Control Category D in larger daylit offices A. Indirect/direct suspended or recessed fixtures are used for ambient lighting. Lighting in daylit zones controlled separately from general lighting, with stepped or continuous dimming to minimum 35 percent reduction. Automated shut-off from time clock or building management control after hours. Occupancy sensors not required. Dual technology-zoned Automated shut-off from time Dual technology-zoned Photosensors for 0-10 VDC electronic dimming in daylit zones to minimum 20 percent. Automated shut-off from time B. Wall washers and down-lights for secondary-use areas provide accent lighting in larger offices. Private offices have a target average horizontal lighting level of 30-35 fc, with 45-75 fc on the work surfaces. Daylighting Although locating private offices on the interior and open-plan offices at the building perimeter is a better strategy for daylight harvesting controls, daylighting controls should still be considered for private offices with perimeter windows. B A Products Integrated digital control systems offer the most flexibility and can take advantage of new digital (LED) lighting and network-ready lighting products. More conventional lighting can be controlled with stand-alone sensors (with necessary control packs). Examples include, but are not limited to, SensorSwitch WSD-PDT-2P series, Wattstopper DW-200 series, Cooper ONW-D-1001-DMV series and 0-10 VDC electronic dimming wallbox control (if dimmable fixtures used). 7

Meeting Rooms and Conference Rooms Use an lighting power density target of 0.9 to 1.1 W/sf for meeting and conference rooms. A Flexibility, glare control and visual comfort are high priorities for interior meeting and conference environments. B A. Indirect/direct suspended luminaires, used for ambient lighting and dimmable, down to 1 percent of full output for audio/visual purposes. B. Wallwasher, recessed above the ceiling with reflector and shield, oriented toward the walls to spread the light uniformly. SOD lighting plans go beyond 2012 IECC standards Lighting in daylit zones controlled separately from general lighting, with stepped or continuous dimming to minimum 35 percentreduction. Automated shut-off from time clock or building management control after hours. Occupancy sensors not required. Use Control Category E in interior small meeting rooms Dual technology-zoned Automated shut-off from time Use Control Category F in larger conference rooms Dual technology-zoned Photosensors for 0-10 VDC electronic dimming in daylit zones to minimum 20 percent. Automated shut-off from time Products Integrated digital control systems offer the most flexibility and can take advantage of new digital (LED) lighting and network-ready lighting products. More conventional lighting can be controlled with stand-alone sensors (with necessary control packs). Examples include, but are not limited to, Sensor Switch CM-10, Wattstopper CI-305, Cooper VAC-P series, with low-voltage switch, Manufacturer s guidelines and literature should be checked before final specification of products. 8

Reception Areas and General Circulation Lighting in general circulation areas should be comfortable and pleasing while avoiding excessively high illumination levels and glare. Lighting should also contribute to wayfinding. A. Recessed high-efficiency linear architectural troffers along cross corridors. B. Recessed high-efficiency architectural troffers over primary work surfaces. C. Recessed LED wall washers and down-lights at areas of interest and for general ambient lighting. SOD Lighting Plans go beyond 2012 IECC Lighting in daylit zones controlled separately from general lighting, with stepped or continuous dimming to minimum 35 percentreduction. Automated shut off from time clock or building management control after hours. Occupancy sensors not required. Use Control Category G in circulation Dual Technology Zoned Automated shut off from time Use Control Category K in Reception Areas Dual Technology Zoned Photosensors for 0-10 VDC electronic dimming in daylit zones to minimum 20 percent. Automated shut off from time Products Integrated digital control systems offer the most flexibility and can take advantage of new digital (LED) lighting and network ready lighting products. More conventional lighting can be controlled with stand-alone sensors (with necessary control packs). Examples include, but are not limited, to Sensor Switch CM-10, Wattstopper CI-305 and Cooper VAC-P series (with low-voltage switch). Manufacturer s guidelines and literature should be checked before final specification of products. 9

Action Plan Step 1: Make Sure Your Project is Eligible Contact your utility representative before purchasing the equipment. Equipment should be new and should be installed in a commercial office building within either Eversource or The United Illuminating Company service territory. Confirm space receiving new lighting exceeds 7,500 sf in total area up to 200,000 sf. Confirm Open Plan Office component exceeds 40 percent of total tenant area. Confirm that Open Office Cubicle Partition heights are no higher than 48 inches. Confirm that installed lighting power density does not exceed program limits of 0.675 W/sf. Confirm that the number of control points meets program requirements of less than an average of 290 sf per control point. Step 2: Submit a Completed Application Form Review the terms and conditions governing the program, then submit a completed application: > Eversource customers, contact Jordan Schellens, jordan.schellens@eversource.com > United Illuminating customers, contact Glen Eigo, glen.eigo@uinet.com Once pre-approved, a pre-approval incentive letter will be issued. Step 3: Request Post-Installation Verification If there is a change in equipment, submit updated application materials. At the post-installation verification, sign the post-installation customer acknowledgment section. 10

Enroll Today The Sustainable Office Design program offers building owners a predictable $1/sf incentive, up to $200,000, for improving the performance and energy efficiency of their lighting systems. Sustainable Office Design also provides lighting designers with a way to give their clients improved savings by moving beyond simple prescriptive lamp and ballast approaches to system-based, integrated design solutions. The simplified qualification and application process leverages documentation common to commercial tenant fit-out construction processes. Program Requirements All projects qualifying for this program must: Be a code-dependent office fit-out project or extensive/substantial renovation project that consists of the installation of new fixtures throughout the building or renovated spaces. Provide maintained lighting levels in accordance with the recommendations of the Illuminating Engineering Society of North America s (IESNA) 10th Edition Handbook or supporting Design Guides. Provide high-quality lighting achieving appropriate levels of glare control, color rendering, lighting uniformity and other lighting-quality parameters. Meet all requirements as specified in this application document. LED products should meet or exceed ENERGY STAR or Design Lights Consortium (DLC) technical requirements. Those that are not ENERGY STAR or DLC-rated should be discussed with your utility representative. Projects must meet current state and local code requirements. Only lighting designers who have obtained LC, CLEP or CLD certification, or who are current members of IALD, are eligible. The lighting designer must design, engineer or install and not benefit solely from the sale of the lighting. Contact Us Eversource Customers: Jordan Schellens, jordan.schellens@eversource.com UI Customers: Glen Eigo, glen.eigo@uinet.com Visit EnergizeCT.com to download your Sustainable Office Design application. Development of the SOD Lighting Program has been supported by the work of Waypoint Building Group and Weller & Michal Architects. Frequently Asked Questions 1. How is the rebate calculated? Qualifying projects receive an incentive of $1/sf of controlled and conditioned interior spaces, capped at $200,000. 100 percent of the incentive will be paid after project occupancy. 2. What are the basic project qualifications? The project must be at least 7,500 sf with a maximum of 200,000 sf. At least one lighting control point must be provided, on average, for every 290 sf of space. The project must achieve a lighting power density of not greater than 0.675 W/SF. 3. When calculating the 7,500 SF threshold, can this include connecting corridors and common areas if they are included in a lighting upgrade? The Sustainable Office Design lighting incentive applies only to individual tenant spaces. Common areas, building lobbies and corridors between discrete tenants cannot be used as part of the qualifying square footage, nor is that square footage eligible for the SOD incentive. 4. How is the minimum square footage verified? It is verified by examination of a signed COMcheck report. 5. Does qualifying for these incentives make me eligible for other lighting incentives? Projects that are eligible for this incentive program are not eligible for other prescriptive lighting incentives that support ballasts, occupancy sensors, photocells and time clocks. 6. Are exterior lighting projects eligible for this program? No, exterior lighting systems are not eligible for this program. Qualifying projects must be in controlled and conditioned interior spaces. Please contact your utility representative for other program opportunities for exterior lighting and HVAC. 7. Are LED lighting technologies eligible for this program? Yes, as long as the LED fixtures meet or exceed ENERGY STAR or DLC technical requirements and are installed in conjunction with the program s qualifications. Other LED products should be discussed with your utility representative before use. 8. Where can I find a list of approved products? There is no requirement that specific products be used. A list of recommended products can be found at the program webpage. Please note: Eversource and The United Illuminating Company do not endorse any particular manufacturers and encourages our customers to meet with different representatives to determine which system best meets their needs. Manufacturer guidelines and literature should be consulted before choosing a product. 11

Energize Connecticut programs funded by a charge on customer energy bills. C0069