Fire Safety Management System in Modern High-rise Buildings - Hong Kong Perspective

Similar documents
SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG

ASSESSING FIRE SAFETY PROVISIONS FOR SATISFYING GREEN OR SUSTAINABLE BUILDING DESIGN CRITERIA: PRELIMINARY SUGGESTIONS

A Fire Safety Ranking System for Karaoke Establishments in Hong Kong

RESEARCH ON THE MAIN CRITERIA OF DECISION-MAKING FACTORS THAT AFFECT CONSUMERS' PURCHASE OF RESIDENTIAL FIRE ALARMS

ASPECTS OF FIRE SAFETY IN ULTRA HIGHRISE BUILDINGS

The Development of Fire Risk Assessment Method for Heritage Building

Comment on Hawker Stall Fires

Evacuation Hazards in Crowded Subway Stations

FIRE RISK ASSESSMENT

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Fire Risk Analysis and Optimization of Fire Prevention Management for Green Building Design and High Rise Buildings: the Hong Kong Experience

On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

A SURVEY OF OCCUPANT RESPONSE TOWARDS AN AUDIBLE FIRE ALARM

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

NOTTINGHAM CITY HOMES

Fire Safety Policy Date: 0

June 2017 (Updated 18 January 2018) Fire Safety Policy. Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION

Fire Safety Strategy

FIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017

Reported Fires in High-Rise Structures in Selected Occupancies with and without Automatic Extinguishing Systems by Extent of Smoke Damage

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

A Brief on Performance- Based Design for Building Fire Safety

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

St Edward s Oxford FIRE SAFETY POLICY

Fire Safety. A TUC guide for trade union activists

Community Development and Recreation Committee

Fire Safety Management Audit Specification August 2017

SHOULD SMOKE MANAGEMENT SYSTEM BE PROVIDED IN KARAOKE ESTABLISHMENTS?

Secretary of State determination under article 36 of the Fire Safety Order

Management Standard: Fire Safety

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

Quantifying Fire Risk for Telecommunications Network Integrity

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011

Fire Risk Assessment 2017

FIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS

RRC SAMPLE MATERIAL MANAGING FIRE SAFETY LEARNING OUTCOMES

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

How design fires can be used in fire hazard analysis

Fire Risk Management Policy. UK September 2017

ISLE OF WIGHT FIRE & RESCUE SERVICE

- CONSTRUCTION FIRE SAFETY STANDARDS

Dan Gray, Property Director. Date: November 2017 Review Due Date: November 2020

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article

Ch. 569 FIRE AND SAFETY SERVICES 28 CHAPTER 569. FIRE AND SAFETY SERVICES GENERAL PROVISIONS INTERNAL DISASTER PLAN EVACUATION DRILLS

The Social Accountability International (SAI) Fire Safety Checklist

SURVEY ON THE FIRE SAFETY REQUIREMENTS IN KARAOKE ESTABLISHMENTS

Fire Risk Assessment

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

AMBASSADOR HOUSE. A guide on. Fire Safety in Purpose Built Blocks of Flats

Local Rules: Fire Safety

Unit 2 Fire Safety (Zone 2)

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex:

FIRE SAFETY POLICY. Executive Management Team. Health, Safety and Fire Steering Group.

CTBUH Technical Paper

Case Study for Performance-Based Design in Hong Kong

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

FIRE SAFETY AND PREVENTION POLICY

Fire safety policy. Contents. This policy was approved by the Trustees on 3 September 2015 and will be reviewed not later than every 3 years.

PREMISES FIRE SAFETY LOGBOOK

Dangerous Assumptions

Fire Hazard Analysis of Technical Area 53 Building 1

FIRE PROTECTION PROGRAM

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted

Fire Enforcement Report

5 Key Stages to Risk Assessment

Fire Safety Policy. Document Author: Director of Estates, Fleet & Facilities Management

The Science Behind Water Mist Protection of Typical Building Hazards

Millfield Schools Fire Risk Prevention Policy

FIRE PREVENTION STRATEGY FOR BUILDINGS IN CONSTRUCTION. Fire Department, Taipei City Government, Taipei, Taiwan, ROC 2

High Rise Buildings with Combustible Exterior Wall Assemblies: Fire Risk Assessment Tool

Thomasville fire rescue

SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

Smoke Control Requirements for New Railway Infrastructure. Ir Peter Law

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:

A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO)

A Study on Improvement of Fire Protection Systems based on Failure Characteristics accodrding to Yearly Variation in Old Commercial Buildings

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)

Canadian Wood Council Fire and Safety Risks Posed by Wood Frame Residential Construction Professor / Fire Chief Len Garis July 15, 2015

Cladding Screening Test Result

Maintenance of Fire Systems

Safety Manual: Emergency Response

Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry

West Yorkshire Fire & Rescue Authority. Fire Protection Policy

Fire Safety Checklist

Fire Safety Plan (FSP) Review Checklist 1

Yunyong P. Utiskul, Ph.D., P.E., CFEI

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

Residential Fire Injury and Death Rates in British Columbia

Fire Safety Plan (FSP) Review Checklist 1

Transcription:

November 02-04, 2009,Tainan,Taiwan Fire Safety Management System in Modern High-rise Buildings - Hong Kong Perspective Lau Kwai-Wing 1 Wan-Ki Chow 2 ABSTRACT The erection of 7627 blocks of high-rise building within the territory of 1092 km² makes Hong Kong popular and famous for it s Concrete Jungle in the world. It has long been a question of life safety and property protection in fire situations of these buildings. Bitter experience learnt from the major building fires in the past twelve years together with the result of a territory-wide building survey within the period are discussed in this paper. In addition, the fabulous, complex and innovative building designs using fire engineering approach to meet with these building features are other great challenges to building fire safety. To secure the overall fire safety in these buildings, a total fire safety concept by employment of the fire safety management system, combined use of the hardware (active and passive fire protection systems) and software (building management and knowledge base of the management staffs) and a safety audit system to ensure mitigation to the potential risks posed are also introduced and discussed. KEYWORDS High-rise building, fire engineering approach, active and passive fire protection systems, fire safety management system, fire safety audit system 1. PhD Candidate, Research Centre for Fire Engineering, Department of Building Services Engineering The Hong Kong Polytechnic University, Hong Kong, China laufred@ymail.com 2. Chair Professor of Architectural Science and Fire Engineering, Leader of Research Centre for Fire Engineering Head of Department, Department of Building Services Engineering, Area of Strength: Fire Safety Engineering The Hong Kong Polytechnic University, Hong Kong, China 271

1. INTRODUCTION Hong Kong is a Special Administration Region of mainland China. Its territory area is just 1092 km² with a population of seven millions. High-rise building is defined in the Code of Practice for Minimum Fire Service Installation as those structures when building height reach thirty metres [FSI 2005]. The development and the trend to build more high-rise buildings is the only solution to the problem. Because of the trend, controlling authorities and building safety professionals raised great concerns on the safety of people staying in these high-rise buildings, in particular we still have such buildings erected in this concrete jungle for more forty year. Not to say the big fires happened in the past twelve years claimed tens of lives and injuries. Despite a number of follow-up actions have been taken by the controlling authorities including the enactment of laws, it appears that the subsequent good fire safety practices might have been deteriorated as reflected in the increased number of fires at institutional buildings and the housing estates which are generally high-rise [FSD 1998-2007]. It is true that new buildings when we first move-in are considered safe but might not be true years after. To keep these buildings in good and safe condition, maintenance and good management to these buildings are solutions for the purpose. To meet with the objective, implementation of the fire safety management system and monitored by a fire safety audit system will greatly secure the overall safety of the buildings. 2. CONCEPT OF FIRE SAFETY IN BUILDINGS The safety concept is to maintain building fire safety to a reasonably practical standard so as to provide a safe place for the people to live in and protect property in the building. To ensure the purposes can be met, we have to consider the following basic controlling measures: Control ignition of materials - ignition sources - ignitability of the material - combustibles Control fire spread - combustibility - fire propagation - spread of flame Control of fire resistance - building materials - non-structural material fixtures Control illegal building works - removal or addition of building works - alteration of building works Controlling and enforcing follow-up and subsequent actions in the routine maintenance work are properly carried out especially those required by laws. 272

The controlling measures mentioned required a systematic and manageable approach to handle. This involves a management team to manage the defined objectives and execute and monitor the measures. However in defining the objectives, the management has to be well conversant with the fire safety concept or in a more generic representation by the total fire safety concept [Chow 2004]. The principle of the concept involves the following stages: Identification of risks from the building and building environment; Using the passive fire protection and active fire protection systems to mitigate the identified risks; Since these protection systems require physical management actions to follow up and will therefore oversee by the fire safety management system. This concept can be represented by the following figure: Fire Safety Management System Passive Fire Protection System Active Fire Protection System Identified Fire Risks Figure 1: Total fire safety concept diagram 3. MAJOR FIRE SAFETY PROBLEMS AND IRREGULARITIES IN EXISTING BUILDINGS To have a closer look into the issues, I have selected some past major fire incidents and a building survey conducted by Hong Kong Fire Services Department for discussion. 273

Table 1. Major fires in the past 12 years Month/Year Nov./1996 Jan./1997 April/1997 May/2007 Aug./2008 (*) (**) (#) Type of Building Commercial 15-storey Commercial 20-storey Residential 20-storey Injuries/ Fatalities Major irregularities/problem identified 80/41 (*) Replacement of metal lift doors by wooden partition during maintenance work in lift lobbies; Unsatisfactory building management 13/17 Non-functioning of the sprinkler system; Wedged-open of lobby protection doors; Unsatisfactory building management 37/9 Storage of plastic foam containers and commercial commodity; Wedged-open/defective smoke lobby doors; Unsatisfactory building management 6/1 (*) Sprinkler system failed to work Industrial 23 -storey Composite Major irregularities include (#) : 15-storey 55/4 (**) Wedged- open lobby protection doors; Sub-standard smoke lobby door; Large amount of combustions used in the Karaoke Box Including one fire fighter Two fire-fighters The irregularities were based on the information from the media and my personal judgment. A death inquest will be convened in the coming months. 4. TERRITORY-WIDE BUILDING SURVEY ON FIRE SAFETY [FSD 1998] Subsequent to the major fire incidents in 1996 and 1997 (Table 1), Fire Services Department conducted a territory-wide fire safety survey with a view to improve the fire safety in the community by analyzing the survey results and formulated a package of administrative and legislative measures. During the survey, a total of 27148 nos. of pre-1987 building were inspected. Survey data collected were analyzed by giving a Fire Safety Index which was composed of Fire Services Installation (FSI) Index on the provision and maintenance of the FSIs and Fire Safety Management (FSM) Index on the condition of the fire safety management in the buildings. The inspection result was summarized in the following diagram and tables. 274

8791 8791 Unsatisfactory FSI but with satisfactory management 10361 10361 Unsatisfactory FSI and Management 497 497 Unsatisfactory Management but with satisfactory FSI 19152 10858 Unsatisfactory FSI Unsatisfactory FSM Figure 2: Diagram showing the distribution on the unsatisfactory surveyed buildings Table 2. Buildings required improvement Buildings requiring rectification of FSI defects 1,984 7% Buildings requiring upgrading of FSI 19,152 70% Buildings requiring improvements to fire safety management 10,858 39% Buildings requiring improvements to both FSI and FSM 10,361 38% Table 3. Statistics on Fire Hazards Reported by the Survey Team Industrial Commercial Domestic Institutions Composite Others Total Floating obstruction 124 109 215 23 2,091 2 2,564 Locked roof/ground exit Defective/ Missing smoke stop door Metal gate erected across means of escape 61 88 411 32 1,950 6 2,548 254 116 170 24 1,988 4 2,556 54 7 156 0 658 0 875 Defective FSI 270 71 228 27 1,381 7 1,984 Total 763 391 1,180 106 8,068 19 10,527 Fire Hazard Abatement Notices issued 1449 275

From the given details on existing buildings, either from the major fire incidents or the building survey, we can summarize the irregularities into three major categories, i.e. failure in active fire protection systems (e.g. defective sprinkler, detection system etc.), failure in passive fire protection system (e.g. removal of protected lobbies, defective lobby doors etc.) and unsatisfactory fire safety management system (e.g. wedge open of lobby doors, floating obstruction in common area, locked exits etc.) in the buildings. 5. IMPROVEMENT OF THE TOTAL FIRE SAFETY CONCEPT MODEL Since the early nineties, Buildings Department and Fire Services Departments of Hong Kong accepted the application of the performance-based building designs due to complex nature, innovative, or special building feature of the nowadays buildings provided that the application of fire engineering design as an alternative to the prescriptive provisions providing this approach, have to observe the following fire safety concerns raised by the Director of Fire Services [FSI 2005]: The design will not provide inferior safety standard to the prescriptive requirements; The methodology for application of the fire engineering approach should outline a structured fire engineering principle(s) to the assessment of total building fire safety effectiveness; and To achieve the pre-identified design objective(s) having taken into consideration of the objectives of fire service installations and equipment for the protection of life and property of the people within the buildings and the firefighting personnel in the event of emergency situations. Buildings Department has included relevant requirements in the building codes on Means of Escape, Means of Access and Fire Resistance since 1996 to reflect the necessary equivalent standard in the application of the performance-based design to new buildings [FRC 1996, MOE 1996, MOA 2004]. Fire Safety Management System for high-rise buildings Maintenance on existing provisions of fire protection systems - Including the annual inspections as required by laws - Code-complied designs - Performance-based designs - others Routine inspection on existing provisions - Active fire protection system - Passive fire protection systems - Building fire safety management - others Staff training - Familiarization of the emergency procedure - Staff duty and responsibility - Appropriate use of first-aid fire fighting equipments 276

- To be familiarized with the fire protection systems - General knowledge in fire safety - Regular fire drills with staff and occupants - Identification of fire hazards - others Emergency actions - Emergency procedure to be followed, including call to the emergency departments, fighting the fire if consider safe - Inform and assist the occupants to evacuate immediately - Assist the fire fighters in emergency situation - others Other activities In view of the new building designs and the known common irregularities in building and building management, it is therefore in need of a new fire safety concept with an audit system to secure the effectiveness in executing/enforcing the fire safety management system. The structure of the new system on total fire safety concept is modified as below: Fire Safety Audit System Fire Safety Management System Passive Fire Protection System Active Fire Protection System Performance-based Design Identified Fire Risks Figure 3: Modified Total Fire Safety Concept diagram 6. THE FIRE SAFETY AUDIT SYSTEM The audit system is a system used to monitor and ensure the effective operation of the established fire safety management system. It offers a practical way to identify the potential hazards due to inadequate maintenance, inspection on fire service installations and unsatisfactory fire safety management. The priority/weight of the basic event in the fire safety managment system indicates its severity and impact of the event on life safety and property damaged. A team of fire experts, professionals might be required to define/decide the acceptable ranking of each event. Some decision making models such as analytical hierarchy process (AHP), Delphi etc. can be adopted to evaluate the priority according to the judgements from the experts based on variant factors including type of building occupancy, provision of fire service installations, characteristic of occupants etc. To evaluate the inadequacy or deficiency of the fire safety management system, physical inspection or validation test of the sub-system can be used to give the score of each event. The approach 277

provides a quantitative model to evaluate the performance of exsiting fire safety managment system and decide the remedial action to be taken for improvement. It seems to be a complicated system in achieving the goal because of the involvement of different profesionals in drawing up the decision at the beginning. However, once the decision has been made, it is just a matter of simple calculation with individual inspection result. In fact, there are some tools (computer software) in the market can help. The structure of the audit system is shown as below. Fire Safety Audit System Objective: Ensure the effectiveness of the fire safety management system Expert Panel/Team Evaluate the performance of fire safety management system Maintenance Inspection Staff Training Emergency Actions Others Estimate the fire safety level Identify the defects/deficiencies Propose risk mitigation measures Figure 4: Diagram of Fire Safety Audit System 7. THE ANALYTICAL HIERARCHY PROCESS (AHP) [Saaty 2000] The analytic hierarchy process (AHP) was developed by Professor Thomas L. Saaty in 1970s. The AHP provides a comprehensive framework for structuring a complex system and quantifying its elements. It is best suited for multi-criteria decision-making problems that yield priorities for decision alternatives. The process to establish such a fire safety audit system is briefly described as follows: Step 1: Set the fire safety level as the top objective of the fire safety audit system; Step 2: Breaking down the system into a hierarchy of decision categories and independent decision elements (attributes); Step 3: Seeking expertise advice to make pairwise comparisons of the decision elements and determine the importance and impact of each element on the fire safety level; Step 4: Synthesize the comparisons to get the local priorities of the elements with respect to each category/top objective (Local priority); Step 5: Determine whether the input data satisfies a Consistency Test. If it is not satisfactory, return to Step 3 and repeat the pairwise comparisons process; and 278

Step 6: Summarize the results to produce the overall priority of each decision elements (Total priority). After deriving the overall priority of the decision elements, site inspection and validation test can be conducted to evaluate the performance and functions of existing provision of the subsystem as defined in the fire safety audit system. Its performance can be indicated in the numerical score for a given range (i.e. 1~100 indicates the performance/function from worst to best). Finally, the fire safety level of the building can be evaluated as follows: Fire Safety Level (L) Local Priority Total Priority 1) Maintenance on existing provision of fire prevention system R 1 Maintenance on Sprinkler System k 11 R 1 k 11 Maintenance on Detection System k 12 R 1 k 12 Maintenance on Smoke Extraction System k 13 R 1 k 13 Others k 1m1 R 1 k 1m1 2) Inspection on existing provision of fire prevention system R 2 Inspection on escape route k 21 R 2 k 21 Inspection on building layout k 22 R 2 k 22 Inspection on building occupants k 23 R 2 k 23 Others k 2m2 R 2 k 2m2 3) Staff training R 3 Staff duty and responsibility k 31 R 3 k 31 Appropriate use of fire extinguishing k 32 R 3 k 32 equipments Familiar with the fire prevention system k 33 R 3 k 33 Others k 3m3 R 3 k 3m3 4) Emergency actions R 4 Identify the fire hazards and fire causes; k 41 R 4 k 41 Inform the occupants to evacuate k 42 R 4 k 42 immediately Assist the fire fighters k 43 R 4 k 43 Others k 4m4 R 4 k 4m4 Fire safety level (L) of the building can be estimated as: L N m t t 1 s 1 Where R t is the local priority of the t -th category; k ts is the local priority of the s -th item in the t -th category; x ts is the score of the s -th item in the t -th category, it is obtained from physical inspections according to check list/s prepared in the fire safety management system; N is the total number of categories in the fire safety audit system; m is the total number of the items in the t -th category; t R k t ts x ts 279

8. CONCLUSION The total fire safety concept allows the building management to exercise their duties and responsibilities in a more systematic and effective manner. The application of an audit system is just another management tool with a view to secure the safety to both people and properties in nowadays complex, innovative, and tall buildings. The success in meeting the ultimate fire safety objectives relies on the joint efforts of the stakeholders, developers, building professionals and the government bodies. Finally, I think we would agree that new buildings with legal occupation permit would be very safe for us to live-in, yet human factors are the main considerations in fulfilling and maintaining the overall safety of the building as well as this fire safety concept. 9. REFERENCES Apple Daily, April 8, 1997. BS 7974. 2001. Application of Fire Safety Engineering Principles to the Design of Buildings - Code of Practice, British Standards Institution, United Kingdom Buildings Department 1996. Code of Practice for Fire Resisting Construction. Hong Kong. Buildings Department 1996. Code of Practice for the Provision of Means of Escape in Case of Fire. Hong Kong. Buildings Department 2004. Code of Practice for Means of Access for Firefighting and Rescue. Hong Kong. Chow, W. K. 1998. Numerical studies on recent large high-rise building fire. ASCE Journal of Architectural Engineering, Vol. 4, No. 2, pp. 65-74. Chow, W. K. 2000. A fire safety ranking system for old highrise buildings. Research Rep., The Hong Kong Polytechnic University, Hong Kong, China. Chow, W. K. 2002. Proposed fire safety ranking system EB-FSRS for existing high-rise nonresidential buildings in Hong Kong. ASCE Journal of Architectural Engineering, Vol. 8, No. 4, pp. 116-124. Chow, W. K. 2004. Fire Safety in Ultra Highrise Buildings. Safety Bimonthly (An Quan), Vol. 25, No. 3, pp. 7-11. Fire Services Department 2005. Codes of Practice for Minimum Fire Service Installations and Equipment and Inspection and Testing of Installations and Equipment. Fire Services Department 1998. Report on Territory-wide Building Survey on Fire Safety 1998. Hong Kong. Fire Services Department 1998-2007. Fire Services Department Annual Report. Hong Kong. Hong Kong Standard, November 21, 1996. http://www.emprois.com (Retrieved on 15/12/2008). http://en.wikipedia.org/wiki/geography_of_hong_kong (Retrieved on 15/12/2008). http://en.wikipedia.org/wiki/analytic_hierarchy_process (Retrieved on 15/12/2008) Lo, S. M. 1999. A fire safety assessment system for existing buildings. Fire Technology., Vol. 35, No. 2, pp. 131 152. Malhotra, H. L. 1987. Fire safety in buildings. Building Research Establishment Report, Department of the Environment, Building Research Establishment, Fire Research Station, Borehamwood, Herts, WD6 2BL, UK. NFPA and SFPE 2000. SFPE engineering guide to performance-based fire protection analysis and design of buildings. National Fire Protection Association, Quincy, Mass., Society of Fire Protection Engineering, Bethesda, Md, USA. 280

National Fire Protection Association (NFPA) 1995. NFPA-550 Guide to the fire safety concepts tree. National Fire Protection Association, Quincy, Mass, USA. National Fire Protection Association (NFPA) 2006. NFPA-101 Life safety code. National Fire Protection Association, Quincy, Mass, USA. Oriental Daily, January 25, 1997. Oriental Daily, May 24, 2007. Rasbash, D. J. 1996. Fire safety objectives for buildings. Fire Technology. Vol. 32, No. 4, pp. 348-350. Sing Tao Daily, Aug.11, 2008. South China Morning Post, Aug.11, 2008. Saaty, Thomas L. 2000. Fundamental of Decision Making and Priority Theory. RWS Publications. Watts, J. M., Jr. 1995. Fire risk ranking. SFPE handbook of fire prevention engineering, P. J. DiNenno et al., eds., National Fire Protection Association, Quincy, Mass., 5-12-5-26. 281