Can painted glass felt or glass fibre cloth be used as vapour barrier?

Similar documents
Moisture permeability of some porous materials

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

On the Architectural Engineering Competences in Architectural Design MSc in Engineering with Specialization in Architecture Kirkegaard, Poul Henning

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Hygrothermal evaluation of a museum storage building based on actual measurements and simulations

Maximum Obtainable Efficiency For Engines And Refrigerators Based On The Stirling Cycle

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Feasible Working Domains Decision Support for Heat Pump Projects

Modeling of a regenerative indirect evaporative cooler for a desiccant cooling system

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Delivering the Comfort and Performance Your Customers Demand

Characterization of a hygro-regulated Wall Base Ventilation System for Treatment of Rising Damp in Historical Buildings

HYGROTHERMAL PERFORMANCE BENEFITS OF THE CELLULOSE FIBRE THERMAL INSULATION STRUCTURES

High efficient heat pump system using storage tanks to increase COP by means of the ISEC concept - Part 1: Model validation

EVAPORATION NEEDS ENERGY

An interdisciplinary approach to identify adaptation strategies that enhance flood resilience and urban liveability

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

Households' energy use - which is the more important: efficient technologies or user practices? Gram-Hanssen, Kirsten

Air and operative temperature measurements in a plus-energy house under different heating strategies

Cooling load calculations of radiant and all-air systems for commercial buildings

Continuous Strip Reduction Test Simulating Tribological Conditions in Ironing

Functionality Inspection of Interconnected Fire Protection Systems

Impact of Air Distribution on Heat Transfer during Night-Time Ventilation

Thermal Environment Evaluation in Commercial Kitchens of United States

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

Comparison of radiant and convective cooling of office room: effect of workstation layout

Modelling of Split Condenser Heat Pump with Limited Set of Plate Heat Exchanger Dimensions

Energy and Exergy Performances of Air-Based vs. Water-Based Heating and Cooling Systems: A Case Study of a Single-Family House

2. References EN 13829:2001. Thermal performance of buildings. Determination of air permeability of buildings. Fan pressurization method.

Villa Bagatelle Technical Report

TRANSMISSIVITY BEHAVIOR OF SHREDDED SCRAP TIRE DRAINAGE LAYER IN LANDFILL COVER SYSTEM *

Behaviour of an Intumescing System Subjected to Different Heating Conditions. Johansson, Nils; Van Hees, Patrick; Jansson, Robert; Sjöström, Johan

ASSOCIATION POUR LA CERTIFICATION DES MATERIAUX ISOLANTS

Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials

Solar Sustainable Heating, Cooling and Ventilation of a Net Zero Energy House

PART I - MODELING DRYING OF THREE-DIMENSIONAL PULP MOLDED STRUCTURES - EXPERIMENTAL PROGRAM

A new test procedure to measure the soil-water characteristic curves using a small-scale centrifuge

Performance of Geosynthetics in the Filtration of High Water Content Waste Material

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Influence of Compressor Control Strategy on Energy Efficiency and Product Temperature for Professional Counter Cabinets

TEST REPORT No PS/OO3/07

Design, Construction and Testing of Simple Solar Maize Dryer

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

PERFORMANCE OF GEOSYNTHETICS IN THE FILTRATION OF HIGH WATER CONTENT WASTE MATERIAL

Performance Evaluation of Mini-Mesh Fabric

Diffuse Ceiling Ventilation Zhang, Chen; Yu, Tao; Heiselberg, Per Kvols; Pomianowski, Michal Zbigniew; Nielsen, Peter Vilhelm

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Aalborg Universitet. Responsive City Lighting Skouboe, Esben Bala; Andersen, Hans Jørgen; Jensen, Ole B. Publication date: 2013

The Laboratory is qualified to update standards identifying the test procedures.

The Laboratory is qualified to update standards identifying the test procedures.

One-Side Clear Active Barrier Packaging for Moisture Sensitive Medical Devices:

Operation and maintenance service provision in uncertain times the case of the FLSmidth Group during the Arab Spring

Performance of Chilled Beam with Radial Swirl Jet and Diffuse Ceiling Air Supply in Heating Mode

THE EFFECTS OF LEAKAGES IN ROOFS WITH VENTILATED AIR LAYERS - A CFD APPROACH. Zbynek Svoboda

Proposed ASTM Standard Method

PASSIVE HYGROTHERMAL CONTROL OF A MUSEUM STORAGE BUILDING. Jørgen Erik Christensen 1 and Hans Janssen 2

LABORATORY STUDY ON THE CONSOLIDATION SETTLEMENT OF CLAY-FILLED GEOTEXTILE TUBE AND BAGS

HOT or COLD. Condensation Happens. Chill Out! Boost Productivity. Keeping Up to Standard AS SEEN IN. August 2004

State of the Art of HVAC Technology in Europe and America

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

BS EN ISO : 2010

Woolmark Specification

STS Directory Accreditation number: STS 0021

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Diffuse Ceiling Ventilation Zhang, Chen; Yu, Tao; Heiselberg, Per Kvols; Pomianowski, Michal Zbigniew; Nielsen, Peter Vilhelm

1. Introduction. Abstract. Keywords: Liquid limit, plastic limit, fall cone, undrained shear strength, water content.

Aalborg Universitet. The physical impoverishment and decay of Danish villages causes and consequences Møller, Jørgen

Principles of Cold Insulation

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps

EFFECT OF CENTRAL PILE IN INCREASING THE BEARING CAPACITY OF BORED PILE GROUPS

CR5-9 A-FGJ-A-E-HQQE 1x220/240 50HZ

Effect of harvesting time and moisture on mechanical properties of garlic (Allium sativum L.) skin

Connect North and South Korean Separated Families Higher Comfort Lower Energy

Analysis of Energy Consumption for Biomass Drying Process

Evaluation of the Development of Capillary Barriers at the Interface between Fine-grained Soils and Nonwoven Geotextiles

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

DESIGN, FABRICATION & PERFORMANCE ANALYSIS OF SOLAR AIR HEATER

EFFECTS OF AIR VELOCITY AND CLOTHING COMBINATION ON HEATING EFFICIENCY OF AN ELECTRICALLY HEATED VEST (EHV): A PILOT STUDY

Thermal Comfort with Convective and Radiant Cooling Systems

Distribution systems in apartment buildings

Comprehensive Material Characterizations for a Pavement Embankment Installed with Wicking Fabric

Alphasense Application Note AAN 106 HUMIDITY EXTREMES: DRYING OUT AND WATER ABSORPTION

BS EN ISO : 2010

Heat Exchanger- Lockheed Martin

BS EN ISO : 2010

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

CR A-F-A-E-HQQE 3x400/ HZ

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

ASSOCIATION POUR LA CERTIFICATION DES MATERIAUX ISOLANTS

Low-noise fans are not a product of chance

COOLING SYSTEMS FOR CONTINOUS GALVANIZING LINE Miroslav Raudensky a, Milan Hnizdil a, Jaroslav Horsky a, FrédéricMarmonier b

Transmissivity of a Nonwoven Polypropylene Geotextile Under Suction

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Exercise 8: Soil Compaction. CE337, Section 006, Team 3. Experimental data acquired on April 16, 2015 by:

Transcription:

Downloaded from orbit.dtu.dk on: Oct 22, 2018 Can painted glass felt or glass fibre cloth be used as vapour barrier? El-Khattam, Amira; Andersen, Mie Them; Hansen, Kurt Kielsgaard; Møller, Eva B. Published in: Proceedings of the 10th Nordic Symposium on Building Physics: Nsb 2014 Publication date: 2014 Link back to DTU Orbit Citation (APA): El-Khattam, A., Andersen, M. T., Hansen, K. K., & Møller, E. B. (2014). Can painted glass felt or glass fibre cloth be used as vapour barrier? In J. Arfvidsson, L-E. Harderup, A. Kumlin, & B. Rosencrantz (Eds.), Proceedings of the 10th Nordic Symposium on Building Physics: Nsb 2014 (pp. 1030-1036). [128] Lund University. General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. Users may download and print one copy of any publication from the public portal for the purpose of private study or research. You may not further distribute the material or use it for any profit-making activity or commercial gain You may freely distribute the URL identifying the publication in the public portal If you believe that this document breaches copyright please contact us providing details, and we will remove access to the work immediately and investigate your claim.

Full paper no: 128 Can painted glass felt or glass fibre cloth be used as vapour barrier? Amira El-Khattam, M.Sc. 1 Mie Them Andersen, M.Sc. 2 Kurt Kielsgaard Hansen, Associate Professor Ph.D. 3 Eva B. Møller, Senior Researcher Ph.D. 4 1 ALECTIA A/S, Denmark 2 MOE A/S, Denmark 3 Technical University of Denmark, Denmark 4 Danish Building Research Institute, Aalborg University Copenhagen, Denmark KEYWORDS: Acrylic paint, silicate paint, glass felt, glass fibre cloth, water vapour permeability, water vapour resistance SUMMARY: In most Nordic homes the interior surfaces of walls and ceilings have some kind of surface treatment for aesthetical reasons. The treatments can for example be glass felt or glass fibre cloth which are painted afterwards. To evaluate the hygrothermal performance of walls and ceilings it is essential to know how much influence a surface treatment has on the water vapour transport. Traditionally, there has been most focus on paints that affect the permeability as little as possible. However, sometimes water vapour resistance is desirable. Especially, this is relevant in existing buildings with a ventilated attic where the ceiling may be air tight but has no vapour barrier; post-insulation of the attic may cause the need for a vapour barrier. Placing a vapour barrier above the ceiling can be tiresome and it is difficult to ensure tightness. A simpler way is to paint a vapour barrier directly on the ceiling e.g. as an ordinary paint. This paper presents the results of an investigation of the water vapour resistance of surface treatments which are commonly used in-door. The water vapour resistance was measured by the cup method. Aerated concrete was investigated with and without various surface treatments. The surface treatments were glass felt or glass fibre cloth with different types of paints or just paint. The paint types were acrylic paint and silicate paint. The results show that the paint type has high influence on the water vapour resistance while the underlay i.e. glass felt or glass fibre cloth has very little impact. The measured water vapour resistance for specimens with acrylic paint was the highest, these were measured to be up to approximately 3 10 9 Pa m 2 s/kg which is considerably less than 50 10 9 Pa m 2 s/kg as recommended for a vapour barrier. Therefore, two layers of ordinary acrylic paint on glass felt or glass fibre cloth cannot be used instead of a vapour barrier. 1. Introduction In most Nordic homes the interior walls and ceilings have some kind of surface treatment for aesthetical reasons. Surface treatment will to some extent affect the moisture transport and reduce the moisture transport by diffusion compared to untreated surfaces. How much the diffusion will be reduced depends on the water vapour resistance of the surface treatment. In some cases it is desirable to achieve a high water vapour resistance, e.g. if a vapour barrier is needed but difficult to install. Existing buildings with a ventilated attic where the ceiling may be air tight but has no vapour barrier is Full papers - NSB 2014 page 1030

an example of this; post-insulation of the attic may cause the need for a vapour barrier. However, placing a vapour barrier above the ceiling can be tiresome and it is difficult to ensure tightness. A simpler way is to paint a vapour barrier directly on the ceiling e.g. as an ordinary paint. In the present study aerated concrete was investigated with various surface treatments. The surface treatments were glass felt and glass fibre cloth which were painted with two different types of paints, acrylic paint and silicate paint, respectively. For comparison results without glass felt or glass fibre cloth are also presented. To investigate the water vapour resistance for the surface treatments the cup method was used. 2. Theory The vapour resistance is determined by the cup method according to EN ISO 12572 (2001). It is known that the water vapour resistance is depending on the type of paint, as silicate paint is generally described as an open paint opposed to acrylic paint (Brandt, 2013). The hypothesis of this paper is, that the water vapour resistance can be increased if the paint layer is supplemented with a layer of glass felt or glass fibre cloth, as these surface treatments are expected to absorb more paint than surfaces without this extra layer. In this way common surface treatments may act as vapour barriers. 3. Materials Aerated concrete with dry density 535 ± 15 kg/m ᶾ was used as base material as this material has a high water vapour permeability. The materials for the surface treatments have been chosen because they are commonly used as surface treatments of walls and ceilings in Denmark, and are expected to have different water vapour permeability. Seven test specimen series were fabricated: 1. Aerated concrete with no surface treatment (pure aerated concrete) 2. Aerated concrete with two layers of acrylic paint (three series) a. Putty and acrylic paint b. Putty, glass felt and acrylic paint c. Putty, glass fibre cloth and acrylic paint 3. Aerated concrete with two layers of silicate paint (three series) a. Putty and silicate paint b. Putty, glass felt and silicate paint c. Putty, glass fibre cloth silicate paint For the series with surface treatment a thin layer of putty was applied on one side of the aerated concrete, this was used to level out and fill the coarse pores in the surface. The layer thickness is less than 0.5 mm. On the putty one layer of liquid prime was applied; the liquid prime had a viscosity as water. After this either paint or one of the two kinds of glass fibre and paint was applied. The liquid prime and paint was applied with a roller. The two kind of glass fibre are called glass felt and glass fibre cloth, which has different structures. They are both made of the same inorganic material; small fibres of glass. However, the differences in the two are the structure; one has a glass fibre mat with a smooth surface where the other is woven glass fibre. The two different structures are shown in FIG 1. Full papers - NSB 2014 page 1031

FIG 1 A sketch of the structures of the glass fibre cloth (left) and glass felt (right) which are used in the experiments. It is seen that the structure for glass fibre cloth is rougher compared to glass felt. The two types of painting were acrylic paint and silicate paint. Acrylic paint consists of i.a. acrylic polymers and water. When the paint dries out the polymers will glue together and establish a layer of polymers. The silicate paint is a natural mineral product, where the binding agent is silicate. 4. Methods The experiment was divided into preparation of the specimens and measurements of the water vapour resistance of the seven series. 4.1 Preparation of the specimens with surface treatments Aerated concrete was used as underlay for the surface treatments. Six different surface treatments were investigated. The constitutions of the specimens are listed in the paragraph of Materials. When the surface treatments were applied to the aerated concrete slab the surface area of the slab was 600 mm x 400 mm to obtain an evenly distributed surface. After the surface treatments the specimen were drilled out of the slab. All the specimens had a diameter of 80 mm and a thickness of 24 mm. Four specimens of each surface treatment and eight specimens without surface treatment (pure aerated concrete) were tested. The pure aerated concrete specimens were tested to be used as references. Afterwards, all the specimens were placed in a ring of plexi glass. The height of the plexi glass ring was 25 mm and had an outer diameter of 100 mm and inner diameter of 93 mm. To achieve that the volume between the plexi glass ring and the specimen was completely sealed epoxy was used. Furthermore, all the specimens were painted with two layers of epoxy on the vertical perimeter surface to make sure that it was only the surface treated area that would be examined. The specimens which were used for the cup experiment is shown at FIG 2. Full papers - NSB 2014 page 1032

FIG 2 Specimens to the cup tests. Left: Specimen, which has just been painted with epoxy on the vertical perimeter surface sides. Middle: Specimen placed in a plexi glass ring with epoxy between the specimen and the plexi glass ring. Right: Specimens ready for the cup test. 4.2 The cup tests The cup test has been performed according to the European standard EN ISO 12572 (2001) Hygrothermal performance of building materials and products Determination of water vapour transmission properties. This investigation contained only wet cup tests. The cup equipment that was used is more detailed described in West and Hansen (1988). The principle for the cup test is that the specimen is sealed to the top of a cup containing a saturated aqueous solution of Potassium Nitrate (KNO 3 ). The air space between the saturated aqueous solution and the bottom side of the specimen is 6-8 mm, and has a relative humidity of 94 % RH. A net was placed upon the glass cup to avoid the salt solution reached the specimen during handling of the cup. To ensure the sealing between cup and specimen as well as specimen and lid rubber packings were used beneath and above the specimen. A section of the cup used is shown in FIG 3. The cup is placed in a test chamber where the relative humidity and the temperature of the air are controlled to 50 % RH, 23 C. Between the chamber air and the air inside the cup a water vapour pressure gradient will give a one-dimensional stationary moisture transport through the specimen. By weighing the cup periodically the weight decrease was determined. The weighing was continued until five successive determinations of change in mass per weighing interval for each specimen were constant within ± 5 % of the mean values for the specimen. The weight change was afterwards used for calculation of the water vapour resistance. The standard prescribes that the water vapour resistance should be determined as an average of the water vapour resistance of five specimens of this size. However, eight specimens of aerated concrete without surface treatment were used, while four specimens were used for each of the surface treatments. Full papers - NSB 2014 page 1033

FIG 3 The aluminium cup which was used to the test specimens. Inside the aluminium cup was a glass cup placed were the salt solution (KNO 3 ) was located. The cup was placed in a climate chamber at 50 % RH and 23 C. 5. Results The water vapour permeability p for pure aerated concrete was measured to be 26.6 10-12 kg/(pa m s). The measured water vapour resistance Z p for the specimens are shown in FIG 4. Water vapour resistance Zp [(Pa m 2 s)/kg] 3,0E+09 2,0E+09 1,0E+09 0,0E+00 1,02E+09 2,62E+09 1,94E+09 2,53E+09 1,11E+09 1,17E+09 1,37E+09 1. Aerated concrete with no surface treatment 2.a. Aerated concrete, putty and two layers of acrylic paint 2.b. Aerated concrete, putty, glass felt and two layers of acrylic paint 2.c. Aerated concrete, putty, glass fibre cloth and two layers of acrylic paint 3.a. Aerated concrete, putty and two layers of silicate paint 3.b. Aerated concrete, putty, glass felt and two layers of silicate paint 3.c. Aerated concrete, putty, glass fibre cloth and two layers of silicate paint FIG 4 The water vapour resistance, Z p, with standard deviation for the aerated concrete and the different surface treatment. The vapour resistance and its deviation are calculated from four specimens with same surface treatment and have been tested equally. However, for pure aerated concrete the vapour resistance and its deviation are calculated from eight specimens. Full papers - NSB 2014 page 1034

6. Discussion The water vapour permeability and water vapour resistance factor for the pure aerated concrete were found to be 23.6 10-12 kg/(pa m s) and 8.30, respectively. The water vapour resistance factor is compared with values from IEA Annex XIV (1991), Gottfredsen and Nielsen (2006) and information from the manufacturer of the aerated concrete slabs. The comparison is shown in FIG 5. 10 Water vapour resistance factor μ 8 6 4 2 8,30 3,75 2,79 5,86 0 Pure aerated concrete IEA - Annex XIV (1991) Gottfredsen and Nielsen (2006) Manufacturer s information FIG 5 Pure aerated concrete. The water vapour resistance with standard deviation for the cup test compared with Gottfredsen and Nielsen, (2006), IEA Annex XIV, (1991) and information from the manufacturer of the pure aerated concrete. The manufacturer does not state the standard deviation. If the measured water vapour resistance factor is compared with information from the manufacturer there is a factor 1.4 in difference which is lower than compared with IEA Annex XIV (1991) and Gottfredsen and Nielsen (2006). Here is a factor of 2.21 and 2.97 in difference. That means that the recovered water vapour resistance factor is bigger than in the literature. It is important to mention that the water vapour resistance factor is calculated from eight samples, whereas EN ISO 12572 (2001) prescribes that five samples is sufficient. Additionally, the recovered standard deviation is low. FIG 4 show the water vapour resistance for the different aerated concrete specimens with surface treatment compared to the one without surface treatment. The water vapour resistance is calculated from four specimens that are tested concurrently. It was expected that the surface treatments would have a blocking effect. However, the water vapour resistance in the specimens with silicate paint were not significantly affected; the specimens with only silicate paint have almost the same water vapour resistance as aerated concrete without surface treatment. It is seen that by using acrylic paint it is possible to get a higher water vapour resistance than when using silicate paint. This was expected as Brandt (2013) characterises silicate paint as more open to water vapour than acrylic paint. Additionally, FIG 4 show paint combined with glass fibre cloth or glass felt has no significant influence on the water vapour resistance, regardless of the paint type. Therefore, glass felt or glass fibre cloths are not able to absorb more paint than surfaces without this extra layer. Two layers of acrylic paint enhances the water vapour resistance of the aerated concrete by 1-1.6 10 9 Pa m 2 s/kg. This should be compared to 50 10 9 Pa m 2 s/kg, which by Brandt (2013) is considered to be the lower limit for the water vapour resistance of a vapour barrier. Therefore, two layers of ordinary acrylic paint on glass felt or glass fibre cloth cannot be used instead of a vapour barrier. Full papers - NSB 2014 page 1035

The results show that the specimens that were surface treated with glass felt and acrylic paint have a high standard deviation. This could indicate that glass felt makes the distribution of acrylic paint more uneven. A possible explanation could be that the fibres in the glass felt makes it harder for the paint to be evenly distributed so the paint may not cover everywhere even though two layers are applied. As silicate paint has no effect on the water vapour resistance an uneven distribution of silicate paint would not be noticeable. To test the theory of uneven distribution of paint on glass felt more specimens should have been tested. First of all five specimens should have been used for each surface treatment; this would in general have decreased the standard deviation. Additionally, tests could have been made on specimens with more than two layers of paint. If the theory of uneven distribution is true, more layers of paint would have reduced the unevenness. It would also be interesting to see if e.g. four layers of paint would have doubled the water vapour resistance compared to two layers. As water vapour resistance of each layer can be added this should theoretically be true. However, the treated surface may not absorb as much paint as the untreated surface. In this test it could have been determined by simply weighing the samples after applying each layer of paint. 7. Conclusions In the present study it was tested how different surface treatments change the water vapour resistance of aerated concrete. Aerated concrete without surface treatment was compared to aerated concrete with a thin layer of putty and different paint types, silicate paint and acrylic paint, respectively, with and without an underlay of glass felt or glass fibre cloth. The results were: The used aerated concrete has lower water vapour permeability than usually reported in the literature and by the manufacturer The water vapour resistance is not changed if silicate paint in two layers is used Acrylic paint in two layers enhances the water vapour resistance by 1-1.6 10 9 (Pa s m)/kg Glass fibre cloth or glass felt as an underlay tissue for the paint has no significant effect on the average water vapour resistance Glass felt as an underlay for acrylic paint has higher standard deviation than the other surface treatments. Maybe the glass felt makes the distribution of the paint more uneven. As a result it must be concluded that glass fibre cloth or glass felt does not absorb more paint than putty without this layer. It might only enhance the unevenness of the distribution of the paint. As two layers of the paint with the highest water vapour resistance (acrylic paint) is about 20 times more open to water vapour than what is recommended for a vapour barrier, two layers of ordinary acrylic paint, with or without glass fibre cloth or glass felt cannot be used as a vapour barrier. References Brandt, E. (2013): Moisture in buildings, SBi-guideline 224, 2. edition, Statens Byggeforskningsinstitut, Aalborg Universitet, Copenhagen (in Danish) EN ISO 12572 (2001): Hygrothermal performance of building materials and products Determination of water vapour transmission properties. Gottfredsen, F. R., Nielsen, A. (2006). Construction Materials: Basic Properties. Polyteknisk Forlag (in Danish). IEA Annex XIV (1991): International Energy Agency Energy Conservation in Building and Community Systems. IEA Annex XIV: Condensation and Energy. Volume 3: Catalogue of Material Proporties. West, G. P, Hansen, K. K. (1988): Cup equipment for measurement of water vapour transfer, Technical report 179/88. Building Materials Laboratory, Technical University of Denmark (in Danish). Full papers - NSB 2014 page 1036